Metal Cassette Ceiling with BEKA Heating and Cooling Mats

Similar documents
BEKA ceiling heating versus traditional underfloor heating

Zehnder ZIP Radiant Ceiling Panels

Cooling and heating systems. Static cooling ceiling system SKS-5/3 for visible installation

Heating and cooling ceiling systems Suspended ceiling systems. Heating Cooling Fresh Air Clean Air

Cooling Strip Model SPB

Heating and Cooling Panels. Aluline. W a r m l i k e t h e s u n

RADIANT HEATING AND COOLING SYSTEMS Produced by FRENGER SYSTEMEN BV

Heating and cooling ceiling systems Zehnder ZBN Planning document. Heating Cooling Fresh Air Clean Air

Intelligent Temperature Management. ThermaCool - Say goodbye to inefficient temperature peaks. GeoClima Inclusive Technical Package

Chilled Ceiling Elements

Radiant Ceiling. Metawell Klimadecke 1

Static cooling ceiling system SKS-4/3 DS 4094 E /1. Technical Selection

Chilled ceiling panel INDUCOOL-Compact

Heating and cooling ceiling systems Zehnder ZIP Planning document. Heating Cooling Fresh Air Clean Air

Multibox. Flush Individual Room Control for Floor Heating Systems. To be precise.

Decorative radiators Comfortable indoor ventilation Heating and cooling ceiling systems Clean air solutions Zehnder ZBN

ZIP Radiant Heating and Cooling Ceiling Panels. Catalog

Modula Standard Performance

General System Layout Sketch

A new age in HEATING. ROTEX Monopex The natural way to save energy! The complete heating system

Installation of a Brunner fireplace. General Indications

Technical Bulletin. Fire protection requirements for cabling systems MLAR 03/2000 MDBR 12/1998. Date: 08/2006

Flush individual room control for floor heating systems

BTBa. FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation. BTBa

Installation instructions

Installation and Operating Instructions

Application technology, 5th edition. Volume III: Fonterra radiant heating and cooling

Furring Channel Resilient Mount - Direct Fixing. Ceiling Systems. intex.com.au / intex.co.nz. Intex

The new standard. The advanced solar absorber tube. The collector for every budget. Efficient modular installation system

Mounting and Operating Instructions EB 2231 EN

Fan Coil Unit CULTRA

Multibox. Floor Heating Controller Flush individual room control for floor heating systems

Ultraflex Ceiling Grid (UFR)

User Guideline LMD-E 200 LMD-E 200. Hook-On Ceiling Hook-On / Lay-On Type ceiling panels - removable Standard installation.

C o o l i n g a n d h e a t i n g s y s t e m s

FIREPRO FIRESTOPPING AND PENETRATION SEALS PRODUCT GUIDE

Units for suspended ceilings

Technical Concept. Ultraflex Ceiling Grid (UFR) All Types Cleanroom Ceiling Systems

Performance Specifications LSF LIFT-SMOKE-FREE

Mikrotherm. Manual Radiator Valves With presetting

4 1 Heating. wooden floors or renovated floors.

PowerVent. Installation manual (GB) English. Store this document in a safe place UK

Units for suspended cei lings

Krantz. Multifunction exposed ceiling AVACS. Cooling and heating systems

VARICOOL Velum. System description/applications 4 Design and application 5 Planning and dimensioning 7 Technical features 8

TS RD 7761 RD, 7761 RD

According to the following European Regulations which come into force:

Ultrasonic Level Measurement nivopuls FDU 10 S

Multibox 4. Floor Heating Controller Flush individual room control for floor heating systems with supply shut-off

Simply perfect garden watering. With these step-by-step instructions, you can quickly and easily plan your customised Kärcher Rain System.

PRODUCT INFORMATION. Technical description. Hygienic stratification storage tank HSK ÖKO Universal heat center for legionella safe preparation of DHW

1 What is the name of the tool shown in the diagram? Basin wrench Footprint wrench Stilson wrench Torque wrench.

Type 5347 (TR/STL), Type 5348 (TR/ST) and Type 5349 (STM/STL) Double Thermostats

Room heating and cooling for floors, walls and ceilings

LINDOFLAMM thermal engineering.

Self-operated Temperature Regulators Series 43 Temperature Regulators Type 43-1 Type 43-2

CIRCO 6 Solar Circulation Unit

electric floor heating Heating mats Heating cables Temperature controllers

Ceiling office High-performance Radiant Ceiling Systems

CHILLED & HEATED CEILINGS

Instruction manual ASPIMAX 16

Extreme industrial environments Air/water heat exchangers (roof-mounted, wall-mounted) Recooling system

Installation guide PRO7-VAQ E. Before installing read this guide first

Fume extraction system FEC.

Installation guide VAQ E. Before installing read this guide first

Installation and maintenance instructions

Smoke extraction duct of sheet steel

EFFECTIVE FROM 1ST JULY 2012 PRODUCT OVERVIEW PRE-INSULATED PIPING SYSTEM

Innovation + Quality. Product range. Awards:

Data Sheet. >>AMTAX inter 2

SDU A. SDU A Loops. (available in 3, 4, 5 loops) Water Based Systems. Standard Distribution Unit assembled with: A Blank Port (capped)

esfr pendent sprinkler vk510 (k25.2)

General System Layout Sketch

HERZ Differential Pressure Control Valve 4002

General System Layout Sketch

OneZone. Underfloor heating range. For existing properties & new build extensions. Extensions Conservatories Single rooms HEAT PUMPS

Secondary systems used in Europe.

ULTIMATE REVERSE OSMOSIS SYSTEM

electric floor heating Heating mats Heating cables Temperature controllers

European Technical Assessment. ETA-08/0314 of 8 August General Part. Technical Assessment Body issuing the European Technical Assessment:

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA

TECHNICAL DATA. * Refer the Approval Chart on page 120c and Design Criteria on page 120d for culus and FM approval requirements that must be followed.

Operating Instructions

Thermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating

aquatherm black Heating and cooling system for ceiling, wall and other applications aquatherm state of the pipe

Passive fire protection. 6 Passive fire protection. 6.1 Fire compartmentation. Passive fire protection

Service Manual For electronic dual temperature zone wine cellar Includes DWC282 / 283

Hydronic Heating Fan Coils Radiant ceiling systems Water Source Heat Pumps Alumline Radiant Heating and Cooling Ceiling Panels

Ray Magic Quad Metal panels for suspended ceiling

Installation and operation instructions Solar stations SolarBloC midi Premium DN 20 SolarBloC maxi Premium DN 25

2 OZONFILT And Bono Zon Ozone Plants

Zehnder ComfoAir flat 150

Installation guide COMBI E. Before installing read this guide first

HERZ TS-3000 HERZ HERZ Armaturen A-1230 Vienna Richard-Strauss-Straße 22

RACK CONVEYOR DISHWASHER WD-151E - WD-421E. Spare parts manual

FLEXIBLE CORRUGATED TUBE

Constant climate chamber with ICH-compliant illumination

Swegon PACIFIC. Integrated chilled beam PACIFIC CHILLED BEAM KEY FIGURES

PRINETO universal system for plumbing and heating

Instruction Manual. Orayonne. Glass radiation heater

Transcription:

TI-K2 Short Description Metal Cassette Ceiling with BEKA Heating and Cooling Mats 1. General Modern office- and business facilities must be cooled mostly throughout the whole year because of the internal loads coming from office- and computer appliances and because of the high thermal insulation of walls and facades. During the heating period itself the rooms need comparatively little heating. Because of this the utilisation of the energetically low cost BEKA heating- and cooling ceiling is possible. The BEKA heating- and cooling mats are simply laid on top of the panels of the suspended metal cassette ceiling. This way each metal cassette ceiling can be utilised very easily and economically as a heating- and cooling ceiling. This set-up can also be used for renovation. Because of the combined function of the ceiling the investment cost for the building installations can be minimised. 2. Description of the System open cooling and ground water possible. For the generating of heating water the same advantages are true. In connection with solar collector systems and even with standard techniques significant energy savings are achieved, because already with low supply temperatures (below C) it can be heated with respectable heating performances. Supply lines Connecting hoses piping Cassette ceiling with BEKA heating- and cooling mats Further ceiling areas The BEKA heating- and cooling mats are simply laid on top of the metal cassettes. The capillary tubes are positioned directly on the sheet metal or on a thin acoustic fibre. The surface is rapidly cooled-down or heated-up. The reaction time of the ceiling is less than 15 minutes. 3. Cold Water-/ Heating Water Technique The BEKA heating- and cooling mats are tiedup in zones to the piping as a circuit and connected to the heating- or cooling supplier. The connection to a storey distributor is recommended. For the cold-water preparation different techniques and systems can be utilised. The economical advantages of the cooling ceiling exists because the ceiling will provide already high performances with supply temperatures which are only slightly below the room temperature. This makes the utilisation of alternative energy sources such as heat pumps or Connection to Cooling unit or heating source 4. Installation Generally the standard installation guidelines must be obeyed. All materials used in the BEKA heating- and cooling mat system must be non-corrosive. Materials to be used can be: plastics, stainless steel, copper, brass and red brass. Other materials in use could cause sludge and could lead to malfunction of the system. Edition: August 2 BeKa Heiz- und Kühlmatten GmbH, D-13127 Berlin, 1996-9 Copyright: No part of this publication may be reproduced without written permission p.1 TI-K2

5. Regulating Technique The regulating technique secures, first the desired comfort, second the necessary system reliance. The cooling ceiling requires : a room temperature regulation, a dew point guard and regulation of the supply temperature for the cold water. Supply temperatures below 16 C must be avoided because of the danger that the dew point could be reached! For the heating ceiling a room temperature control is required which regulates the volume of heating water in dependence to the desired room temperature. In rooms higher than 3,5 m supply temperatures above C must be avoided because of excessive surface temperatures! 6. Dimensioning of the Installation The BEKA heating- and cooling mats are dimensioned according the dimensions of the metal cassettes. The necessary quantity of mats and the temperature of the cooling water or heating water are determined according to the following layout tables. The supply temperature determined in the water circuit, taken at the side of the cooling unit or heat generator, is regulated with the water temperature before the heat exchanger. 7. Preparation for Installation For the installation of the suspended metal cassette ceiling, the manufacturer s instructions must be followed. The capillary tubes of the BEKA heating- and cooling mats should have good contact to the surface of the metal cassettes, so that the heat transfer is directly lead to the water. If there are additional heat sources in the ceiling cavity (heat radiation from light fixtures and from warm water pipes, etc.) a mineral wool mat can be laid on top of the capillary tubes for energy saving purpose. Sometimes such an installation could be required for the sound insulation of the ceiling. If this requirement is not set forth we recommend to glue the capillary tubes to the surfaces. The BEKA heating- and cooling mats are produced in measurement of the metal cassettes based on the object to avoid any tailoring work at the building site. At the border areas and at areas where ceiling in-builds are planned inactive cassettes will be installed. The BEKA heating- and cooling mats are supplied with quick-action couplings for the connection of supply- and return lines with flexible hoses. Before starting work a ceiling pattern and an installation pattern must be drawn-up. All mats with the dimensions, the direction of installation and the supply lines must be recorded. In the ceiling pattern all areas must be marked which will stay uncovered, i.e. for the installation of partition walls or light fixtures and for other ceiling in-fills. Also the installation positions for the BEKA dew point sensor must be marked at the ceiling pattern. The connection of the polypropylene piping is done by thermal welding. Here the welding directions DVS 27-11 of the Deutschen Verband für Schweisstechnik e.v. must be obeyed. (the ambient temperature must not be below 5 C. The pre-heating, -welding- and setting time must be according to the given regulations.) 8. Tools, Materials For the installation of a metal cassette heating- and cooling ceiling with BEKA capillary tube mats standard tools and materials for ceiling constructions and for the installation of plastic pipes can be used such as: Metal cassettes Suspender profiles and suspenders depending at the type of construction used for the chosen ceiling. Dowels and screws Sheet metal scissors Mineral wool insulating wool (if req.) Scissors to cut plastic piping Hand-held welder with sleeve welding adaptor for plastic welding Plastic fittings For the connection of the supply lines to the cold water circuit a hand-held welder with sleeve welding adaptor and plastic fittings are recommended. Alternatively sealing ring connectors can be used. Edition: August 2 BeKa Heiz- und Kühlmatten GmbH, D-13127 Berlin, 1996-9 Copyright: No part of this publication may be reproduced without written permission p.2 TI K2

9. Installation Steps at the Ceiling The bearing structure is fastened and aligned to the raw ceiling with vernier suspension bars according to manufacturer s recommendations of the chosen ceiling brand. The supply lines are laid into the ceiling cavity and connected to the main supply lines (connections done either by thermal welding or with sealing ring connectors) The flexible connecting hoses are plugged into the quick-action couplings of the supply lines. I. II. The BEKA heating- and cooling mats are laid into the cassettes and if necessary fixed with BEKA adhesive V.K.1. III. Plug the flexible hoses into the quick-action couplings of the BEKA mats. The cassettes with the BEKA mats in it are hooked into the bearing structure and the joints are aligned. If required, place insulating mat on top of it. Pre-test with compressed air at 1 bar for one hour. Main test with water at 1 bar for 4 hours, maintain an idle pressure of 3 bar until the system is taken into operation. insulation Edition: August 2 BeKa Heiz- und Kühlmatten GmbH, D-13127 Berlin, 1996-9 Copyright: No part of this publication may be reproduced without written permission p.3 TI K2

1. Lay-out for Metal Cassette Cooling Ceiling with BEKA Capillary Tube Mats Project: Date : Project consultant: Lay-out valid for 27 C - room temperature and 2 K cooling water spread! Required cooling capacity 1 Cooling load for the room W from calculation of the planning office 2 Planned coverage with mats m 2 maximum possible arrangement derived from the room dimensions 3 Required specific cooling capacity W/m 2 = cooling load / coverage Determination of performance Quick lay-out for ceiling cooling with BEKA mats in metall cassettes Cooling capacity [W/m 2 ] 1 24 23 22 21 19 18 17 16 15 14 13 12 Supply temperature [ C] valid for room temperature 27 C and cooling water spread 2K 6 9 12 16 23 27 31 35 38 42 46 5 Mass flow of cooling water [kg/(m 2 h)] 4 Supply temperature from diagram 1 C 5 Return temperature C 6Water volume per mat kg/m 2 h 7 Water volume per zone l/h Pressure loss determination 8 Length of the connection pipe m 9 Resistance in the pipe from diagram 2 Pa/m 1 Pressure loss in pipe Pa = pipe length * Resistance 11 Pressure loss of the mat Pa with value of line 2 from diagram 1 12 Addition for pressure loss through fittings Pa (recomm: 3% addition to pipe) 13 Addition for heat transfer station Pa (recomm: for zone valves 5 - Pa for mains regulating valves 7-15 Pa for heat exchanger approx. Pa) 14 Total pressure loss Pa If BEKA heat transfer stations are utilised the determination of pressure loss can be omitted. In this case only the quantity of cooling circuits and the total cooling capacity is required for the selection. Pressure loss [Pa/m] Pressure loss [Pa] 9 7 5 3 1 Pressure loss in the pipe x2mm 1 1 2 2 3 3 Mass flow [kg/h] Druckverlust Typ S15 Pressure loss type U 1 25 1 2, m 8m 7m 6m 1 1 1,8 m 5m1,6 m 15 1 1,4 4m m 1,2 m 3m 5 1, m 2m 1m 1 15 25 3 35 1 15 25 3 M assenstrom (kg/m2h) 35 Mass flow[kg/m 2 h] Edition: August o2 BeKa Heiz- und Kühlmatten GmbH, D-13127 Berlin, 1996-9 Copyright: No part of this publication may be reproduced without written permission p.4 TI K2

11. Lay-out for Metal Cassette Ceiling Heating with BEKA Capillary Tube Mats Project : Date Projekt consultant: Lay-out valid for 22 C room temperature and 6K heating water spread! Required Haeting Capacity 1 Heat requirement for the room W from calculation of planning office 2 Planned coverage with mats m 2 maximum possible arrangement derived from room dimensions 3 Required specific heating capacity W/m 2 = heat requirement / coverage Determination of Performance heating capacity [W/m2] Quick lay-out for ceiling heating with BEKA mats in metal cassettes 1 1 1 1 27 29 31 33 35 37 39 41 43 45 Supply temperature [ C] valid for room temperature 27 C and heating water spread 6K 1 3 5 6 8 1 11 13 15 17 Mass flow of the heating water [kg/(m 2 h)] 4 Supply temperature -> from diagram 1 C 5 Return temperature C 6 Water volume per mat area kg/(m 2 h) 7 Water volume per zone l/h Pressure Loss Determination 8 Length of connection pipe m 9 Resistance in the pipe -> from diagram 2 Pa/m 1 Pressure loss in the pipe Pa = pipe length * resistance 11 Pressure loss of the mat Pa -> with value of line 2 from diagram 1 12 Addition for pressure loss through fittings Pa (recomm.: 3% addition to pipe) Addition for heat transfer station Pa (recomm.:for zone valves 5 - Pa 13 for mains regulating valves 7-15 Pa for heat exchanger approx. Pa 14 Total pressure loss Pa If BEKA heat transfer stations are utilised the determination of pressure losses can be omitted. Then only the quantity of heating circuits and the total heating capacity is requird for the selection! Pressure loss (Pa) Pressure loss [Pa/m] 1 1 1 1 Pressure loss in a pipe x2mm 1 1 2 2 3 3 Mass flow [kg/h] Pressure loss type U1 5 1 15 25 Mass flow (kg/(m 2 h)] 2,m 1,6m 12m Edition: August o2 BeKa Heiz- und Kühlmatten GmbH, D-13127 Berlin, 1996-9 Copyright: No part of this publication may be reproduced without written permission p.5 TI K2

12. Technical Data BEKA Capillary tube mats Type K.U1 Type K.UM1 Type K.G1 Material Polypropylene Random-Copolymer Type 3 DIN 78 Geometry Collector pipe x 2 mm Capillary tube 3,35 x,5 mm Capillary tube spacing 1 mm Exchange surface 1,67 m 2 Dimensions Length - mm (in increments of 1 mm) Width 15-1 mm (in increments of 1 mm) Mass,43 kg/m 2 (empty, without collector),82 kg/m 2 (filled, without collector) Water contents,39 l/m 2 Cooling capacity: Depending upon type W/m 2 for metal cassette (DIN 4715) Heating capacity Depending upon type up to 15 W/m 2 Condition of operation: Temperature resistant for endurance run to 45 C Operation pressure 3 to 4 bar Test pressure 1 bar maximum 1 hours Operational area / type of installation : Cooling- and heating ceilings for the installation on top of metal cassettes Connections via quick-action coupling system Type of delivery: The mats are supplied lying flat in cartons or in one-way transport cassettes Edition: August o2 BeKa Heiz- und Kühlmatten GmbH, D-13127 Berlin, 1996-9 Copyright: No part of this publication may be reproduced without written permission p.6 TI K2