II112918-SL Installation Guide VOLTEX IMS64-2 Dual output indoor flush mount PIR motion detector IMS64-2
TECHNICAL DATA Rated voltage: 220V-240V~ 50/60Hz Load: Load 1( /T1) for Lighting Incandescent: Max. 1200W Halogen: Max. 850W Fluorescent or LED: Max. 300W Load 2(T2A,T2B) for HVAC (Dry contact, not controlled by Lux setting): Max. 3A (normally open contacts) 12-250VAC or 5-30VDC Environmental Protection: Sensor IP23 from below, when installed Operating Temperature: -20 C ~ 45 C PACKAGE CONTENTS Power box x 1 Lens shield x 1 Plastic plug x 2 Detector x 1 Wood screw x 2 Instruction manual x 1
PRODUCT DESCRIPTION Features This series is for ceiling flush mount with spring clips. A red LED indicator is equipped for indication of Test function and IR setting. Dimension Detector Power Box Ø76.00 62.0 130.80 35.60 41.0 58.5 59.80 OPERATION AND FUNCTION Detection Range: Approx. Ø7m/360 at height of 2.5m H 2.5m approx.ø2m approx.ø7m Time Adjustment: Time 1 (for Load 1) with 7 steps adjustable: 30s-1m-5m-10m-20m-30m-TEST (FIG.1) Time 2 (for Load 2) with 7 steps adjustable: 10s-1m-5m-10m-20m-30m-60m (FIG.2) The sensor LED indicator will flash 3 times every time the VR knob is adjusted and the desired step is successfully selected.
Lux Adjustment: With 7 steps adjustable (for Load 1 only): 10-100-300-500-1000-2000 lux- (Day Mode) (FIG.3) Load 2 is independent and not controlled by Lux setting. The sensor LED indicator will flash 3 times every time the VR knob is adjusted and the desired step is successfully selected. Sens Adjustment: (For Time 1 & Time 2): approx. 25% ~ 100% (FIG.4) Adjust sensitivity to suit the location and avoid false triggering for T1 for T1&T2 FIG. 1 FIG. 2 FIG. 3 FIG. 4 Test Function Under Test mode the load will switch on for 3 sec to each detection, and switch off for 2 sec before next detection. Under Test mode the Lux setting is deactivated. Day Mode Function Under Day Mode the sensor can operate regardless of brightness level. INSTALLATION AND WIRING Please disconnect power completely and read the entire instruction manual carefully before installation. Installation and assembly of electrical equipment must be carried out by qualified electricians. Contact a qualified electrician in the event of fault or break down. A circuit breaker (250VAC, 10A) type C according to EN60898-1 of load 1 ( / T1) must be installed in the fixed wiring for protection. A circuit breaker (250VAC, 6A) type C according to EN60898-1 of load 2 (T2A,T2B) must be installed in the fixed wiring for protection. If using power tools, ensure that they are set to a low torque setting.
Wiring T2AT 2B N L /T1 Load Load Power Supply N 220-240V~ L 8mm FIG.5 Knockouts for Power Cable Entry There are several layers of knockout at the cable entry where can be trimmed according to the size of power cable to be connected. The existing cable entry is suitable for cable size Ø2.5~4mm. Trim the lower knockouts gradually by layer to reach the ideal space for cable size Ø5~10mm. If more space is required, please also trim upper knockout gradually by layer to reach the space up to Ø15mm. E D A B C
Suitable Cable Size Ø2.5~4mm Ø5~6mm Ø7~8mm Ø11~12mm Ø13~14mm Ø15~15.5mm Knockout Layer Existing cable entry Trim layer A Trim layer A+B Trim layer A+B+C Trim layer A+B+C+D Trim layer A+B+C+D+E Installation Procedure 1. To install the detector, please drill a hole with diameter of 64~68mm on ceiling board and keep the power cable outside. Please strip off 6-8mm of cable sheathing for wiring (FIG.6). 2. Please refer to illustration of FIG.5 for correct wiring. 3. Insert the power module into the ceiling first, raise the two spring clips, and insert the detector into the drilled hole on ceiling (FIG.7). 4. Detection range can be extended with additional slave sensors. 5. Restore the power supply. =64~68 Drill a hole with =64~68mm on the ceiling Power box 6-8mm 30-35mm FIG. 6 FIG. 7
Walk Test It takes about 60 sec for sensor to warm up after power is supplied. The purpose of walk test is to check and adjust the detection coverage at the installation of sensor. Set Time VR knob to Test, and then conduct the walk test. Pay attention to the walking direction in the walk test. The sensor is more sensitive to movement across the detection range and less sensitive to movement directly towards it. The load will switch ON for 3 sec for each movement detected, and switch OFF for 2 sec before next trigger. Set the Time VR knob to the desired setting after walk test. When using IR remote control to enter Test mode, it will exit Test mode after 10 min. The sensor LED indicator will stay ON during the warm up period. For remote controllable models, the sensor LED indicator will blink during the warm up period if the sensor has previously been programmed via remote control.. Usage of Lens Shield Undesired detection areas can be shielded off by fixing the enclosed lens shield onto the lens. Trim the lens shield with scissors either horizontally or vertically until the desired detection area is obtained. TROUBLE SHOOTING 1. Unit will not function at all/lights won t turn on - Check wiring to make sure that you have correct AC power at the unit. - Check the wiring from the unit to the source of power to make sure you have wired the unit correctly. - Check the ambient light control to see if it was set at your desired level. 2. Detector clicks but does not work - Check if lamps are broken. - Check if lamps are tight in lampholders. 3. Lights go on and off quickly - Ensure light and heat are not being reflected onto the detector. Check for white or reflective surfaces that may be causing the problem.
- Note the detector is more sensitive in cold weather. - Make sure the sensor is not installed close to air-conditioner. - Make sure the Time setting is not set to Test Mode position. 4. Lights stay on - Light bulb sockets may be wired directly to the power source -Recheck the wiring diagram. - Adjust time to minimum, and ensure unit is firmly fixed to a solid object with no moving branches etc. in field of view. - Ensure detector is not being activated by stray moving heat sources such as heating outlets. - Fit the lens shield to eliminate triggering outside detection field. - Reduce the sensitivity level. 5. Detector goes on under windy and rainy conditions - Adverse weather conditions and temperature changes can result in unwanted activations. - This can be minimized by mounting in a protected location. 6. Maintenance and repair - Do not attempt to repair as this could invalidate warranty or result in personal injury. - Clean detector lens and outside casing with damp cloth. Voltex Electrical Australia www.voltexelectrical.com.au P: 1300 722 275 E: sales@voltexelectrical.com.au New Zealand www.voltexelectrical.co.nz P: 0800 55 66 33 E: sales@voltexelectrical.co.nz