Ventilation Technical Data Outdoor air processing unit, ventilation and air processing EEDEN13-205 FXMQ-MF
TABLE OF CONTENTS FXMQ-MF 1 Features............................................................. 2 2 Specifications....................................................... 3 Technical Specifications............................................. 3 Electrical Specifications.............................................. 3 3 Safety device settings............................................. 5 4 Options.............................................................. 6 Coli ng/ Heati ng CapacityTables 7 DimensionalDr awings 10 DimensionalDr awingswi thaccessories 12 5 Capacity tables..................................................... 7 6 Dimensional drawings............................................ 10 7 Centre of gravity................................................... 14 8 Piping diagrams................................................... 15 Wir ingdiagrams-singlephase 16 SoundPressur espectr um 17 9 Wiring diagrams................................................... 16 10 Sound data......................................................... 17 11 Fan characteristics................................................ 18 12 Operation range................................................... 20 Ventilation FXMQ-MF 1
t t i ai an l r i F or t o - do n dt e nu IF 1 Features r U M Q M X VO 100% fresh air intake possible Ideal solution for shops, restaurants or offices requiring maximum floor space for furniture, decorations and fittings Operation range: -5 C to 43 C Up to 225Pa external static pressure allows extensive ductwork runs and flexible application: ideal for use in large areas Drain pump kit available as accessory 1 2 Ventilation FXMQ-MF
2 Specifications 2-1 Technical Specifications FXMQ125MF FXMQ200MF FXMQ250MF Cooling capacity Nom. kw 14.0 (1) 22.4 (1) 28.0 (1) Heating capacity Nom. kw 8.9 (2) 13.9 (2) 17.4 (2) Connection ratio Outdoor units with only ventilati on units connect ed Ventilation units when combin ed with VRV indoor units Standard Accessories : Clamps; Standard Accessories : Screws; Standard Accessories : Sealing pads; Standard Accessories : Installation and operation manual; Standard Accessories : Connection pipes; Minimu m Maximu m Maximu m % 50 % 100 % 30 Casing Material Galvanised steel Dimensions Unit Height mm 470 Width mm 744 1,380 Depth mm 1,100 Weight Unit kg 86 123 Heat exchanger Rows Quantity 3 Stages Quantity 26 Fin pitch mm 2.0 Face area m² 0.28 0.65 Fan Type Sirocco fan External static pressure - 50Hz High Pa 185 225 205 Fan motor Model D13/4G2DA1 Output 50 Hz W 380 Drive Direct drive Operation range On coil temperature Cooling Max. CDB 43 (13) Heating Min. CDB -5 Refrigerant Control Electronic expansion valve Type R-410A Piping connections Liquid Type Flare connection OD mm 9.52 Gas Type Flare connection Braze connection OD mm 15.9 19.1 22.2 Drain PS1B Safety devices Item 01 Thermal potector for fan motor, fuse 3 2 2-2 Electrical Specifications FXMQ125MF FXMQ200MF FXMQ250MF Power supply Phase 1~ Frequency Hz 50 Voltage V 220-240 Voltage range Min. % -10 Max. % 10 Current Minimum circuit amps (MCA) A 1.9 3.3 3.8 Maximum fuse amps (MFA) A 15 Fan motor rated output kw 0.380 Full load amps (FLA) Fan motor A 1.5 2.6 3.0 Ventilation FXMQ-MF 3
2 Specifications Notes 2 (1) Cooling: outdoor temp.: 33 CDB, 28 CWB (68%RH), discharge set temperature: 18 CDB, equivalent piping length 7.5m (horizontal) (2) Heating: outdoor temp. 0 CDB, -2.9 CWB (50%RH); discharge set temp. 25 CDB; equivalent piping length: 7.5m (horizontal) (3) Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (4) The air filter is not a standard accessory, but please mount it in the duct system of the suction side. Select its colorimetric method (gravity method) 50% or more. (5) When connected to VRV water-cooled outdoor units a mix of ventilation units and VRV indoor units is not possible (6) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (7) Maximum allowable voltage range variation between phases is 2%. (8) MCA/MFA: MCA = 1.25 x FLA (9) MFA 4 x FLA (10) Next lower standard fuse rating minimum 15A (11) Select wire size based on the value of MCA (12) Instead of a fuse, use a circuit breaker (13) 45% Relative humidity 4 Ventilation FXMQ-MF
3 Safety device settings 3 3 Ventilation FXMQ-MF 5
4 Options 4 6 Ventilation FXMQ-MF
5 Capacity tables 5-1 Cooling/Heating Capacity Tables 3 5 Ventilation FXMQ-MF 7
5 Capacity tables 5-1 Cooling/Heating Capacity Tables 5 8 Ventilation FXMQ-MF
5 Capacity tables 5-1 Cooling/Heating Capacity Tables 3 5 Ventilation FXMQ-MF 9
6 Dimensional drawings 6-1 Dimensional Drawings 6 NOTES 10 Ventilation FXMQ-MF
6 Dimensional drawings 6-1 Dimensional Drawings FXMQ200,250MF Piping size (field supply) 3 32 - ø 4.7 hole (All around) Inspection hole 600 or more 650 or more 11x100=1100 (Service space) Discharge side A View 3x100=300 1148 1100 or more (Service space) 1296 1380 Approx. 150 Suction side (Note 2) B 470 250 360 330 3x100=3 32 - ø7 hole (All around) 250 250 360 330 200 16 - M5 hole (All around) 360 330 200 11x100=1100 1200 1230 A View 580 5x200=1000 1230 61 B View ( For FXMQ200MFV1) 1004 245 60 25 30 296 390 Indoor unit Gas side Liquid side FXMQ200MFV1 ø 19.1 attached piping ø 9.5 FXMQ250MFV1 ø 22.2 attached piping ø 9.5 Nr Name Description 1 Liquid pipe connection Flare connection 2 Gas pipe connection Attendant piping connection 3 Drain pipe connection PS1B Internal thread Major dia. ø 33.349, Minor dia. ø 30.391 4 Control box 5 Ground terminal M5 (Inside control box) 6 Name plate Note 1 7 Power supply wiring connection 8 Transmission wiring connection 9 Hanger bracket M10 10 Discharge companion flange 11 Water supply port 12 Attached piping Brazing NOTES 1 Location of unit's name plates: Control box surface. 2 Mount the air filter at the suction side. (Select its colorimethod (gravity method) 50% or more). 6 613 760 1100 50 16 - M5 hole (All around) 5x200=1000 1230 B View ( For FXMQ250MFV1) 3D045128A Ventilation FXMQ-MF 11
6 Dimensional drawings 6-2 Dimensional Drawings with Accessories FXMQ125MF 6 685 650 or more (Service space) 1148 5x100=500 744 Approx. 300 20 - ø4.7 hole (All around) 690 or more (Service space) 250 360 330 3x100=300 20 - ø7 hole (All around) 300 or less 5x100=500 600 630 A View (0~250) 222 222~472 Nr Name Description 1 VRV D.P. Unit C. duct type 2 Filter chamber 3 High-efficiency filter 4 Long-life replacement filter 5 Drain pump kit Built-in 6 Drain pipe connection VP25 (O.D. ø 32, I.D. ø 25) (drain pump kit) 7 Water supply port 8 Drain hose Attached to drain pump kit Inspection hole 600 or more 1100 529 285 79 744 16 - ø8 hole (All around) A 222 3x100=300 456 200 330 360 8 5x100=500 564 594 223 3D046155 12 Ventilation FXMQ-MF
6 Dimensional drawings 6-2 Dimensional Drawings with Accessories FXMQ200-250MF 3 1296 1148 32 - ø4.7 hole (All around) 11x100=1100 1380 250 360 330 3x100=300 32 - ø7 hole (All around) 11x100=1100 1200 1230 A View 300 or less (0~250) Nr Name Description 1 VRV D.P. Unit C. duct type 2 Filter chamber 3 High-efficiency filter 4 Long-life replacement filter 5 Drain pump kit Built-in 6 Drain pipe connection VP25 (O.D. ø 32, I.D. ø 25) (drain pump kit) 7 Water supply port 8 Drain hose Attached to drain pump kit 6 650 or more (Service space) Approx. 300 222 222~472 690 or more (Service space) 1100 529 Inspection hole 600 or more 285 79 1380 16 - ø8 hole (All around) A 222 3x100=300 456 200 330 360 8 5x200=1000 1200 1230 233 3D046154 Ventilation FXMQ-MF 13
7 Centre of gravity 7 14 Ventilation FXMQ-MF
8 Piping diagrams 3 8 Ventilation FXMQ-MF 15
9 Wiring diagrams 9-1 Wiring Diagrams - Single Phase 9 16 Ventilation FXMQ-MF
10 Sound data 10-1 Sound Pressure Spectrum FXMQ200MF 3 Octave band sound pressure level db(0db=0.0002μbar) Approximate threshold hearing for continuous noise 10 Octave band center frequency (Hz) 4D046272 NOTES 1 Over All (db): (B, G, N is already rectified) Scale 220V 240V 2 Operating conditons: Power source: 220-240V 50Hz Standard condition A 47 48 External static Pressure: 225Pa (220V), 275Pa (240V) : 220 Hz : 240 Hz 3 Measuring place: Anechoic chamber 4 Location of microphone Discharge Duct Suction Duct 2m 1,5m 1m FXMQ250MF Octave band sound pressure level db(0db=0.0002μbar) Approximate threshold hearing for continuous noise Octave band center frequency (Hz) 4D046273 NOTES 1 Over All (db): (B, G, N is already rectified) Scale 220V 240V 2 Operating conditons: Power source: 220-240V 50Hz Standard condition A 47 48 External static Pressure: 205Pa (220V), 255Pa (240V) : 220 Hz : 240 Hz 3 Measuring place: Anechoic chamber 4 Location of microphone Discharge Duct Suction Duct 2m 1,5m 1m Ventilation FXMQ-MF 17
11 Fan characteristics 11 18 Ventilation FXMQ-MF
11 Fan characteristics FXMQ200MF 3 220V-50Hz 240V-50Hz (mmh 2 O) (Pa) (mmh 2 O) (Pa) 11 External static pressure Lower limit of ESP (standard ESP) External static pressure Lower limit of ESP (standard ESP) Air flow (m 3 /min) Air flow (m 3 /min) 3D046266 Ventilation FXMQ-MF 19
12 Operation range NOTES 12 20 Ventilation FXMQ-MF
12 Operation range 3 NOTES 12 FXMQ250MF NOTES 1. 2. 3. 4. 3D046313A Ventilation FXMQ-MF 21
These products are not within the scope of the Eurovent certification program The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V. BARCODE Daikin products are distributed by: Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende EEDEN13-205 07/13 Copyright Daikin The present publication supersedes EEDEN12-205