Off Design Operation of Hybrid Noncondensable Gas Removal Systems for Flash Steam Cycle Geothermal Power Plants

Similar documents
Optimization of Hybrid Noncondensable Gas Removal System for a Flash Steam Geothermal Power Plant

POWERENERGY

OPTIMISE VACUUM TO IMPROVE PLANT PERFORMNCE

Liquid Ring Vacuum Pumps, Compressors and Systems

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

The Condensate Water Systems

Modification of Condenser Nozzle and Cooling Tower Exit Screen to Increase Condenser Performance

LIQUID RING PUMPS FOR THE POWER INDUSTRY

The Performance of Thermocompressors as Related to Paper Machine Dryer Drainage Systems

Understanding Process Vacuum for Process Improvement

MECHANICAL VACUUM BOOSTERS:-

CENTRIFUGAL PUMPS. STATE the purposes of the following centrifugal pump components:

Jet Compressors. Circulate Steam Boost Low-Pressure Steam Compress and Mix Gases in Desired Proportion

Reliable Vacuum Condenser Performance

Economical analysis between Vacuum system with ejectors and VS with liquid ring pump

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Figure 1. Ejector cross-sectional drawing. Figure 2. Precondenser to left of vacuum flasher. pressure.

Vacuum System Troubleshooting Author: Keith Webb, P.E. Application Engineering Manager

Points to be Considered when Purchasing a Steam Jet Vacuum Pump

(Refer Slide Time: 00:00:40 min)

Vacuum Booster for Distillation Process

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Jet Vacuum Systems. GEA Wiegand GmbH

Fig.: macroscopic kinetic energy is an organized form of energy and is much more useful

J. LINES, Graham Corp., Batavia, New York

OIL AND GAS INDUSTRY

1 /35 2 /35 3 /30 Total /100

Benefits Offered by Passive Dehumidification Wheel Speed Control

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

Adding More Fan Power Can Be a Good Thing

Prepared by Technical Team

the NC gases and the partial pressure Pv of the water vapor. Then, (1) Pt = Pnc + Pv Also, M v M nc

Chapter 4 Compressors Overview & System Annual Power Consumption

CHAPTER 3 BASIC STEAM CYCLE

R07. Answer any FIVE Questions All Questions carry equal marks *****

HEAT EXCHANGER FORMULAS & EXAMPLE

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Modern vacuum and overpressure generation for pneumatic conveying

Fan Selection. and Energy Savings

Homework #4 (group) Tuesday, 27 by 4:00 pm 5290 exercises (individual) Tuesday, 27 by 4:00 pm extra credit (individual) Tuesday, 27 by 4:00 pm

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Efficiency of Application the Condensing Heat Utilizers in the Existing Boiler's Unit in Heat Power Station

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

SBS5311 HVACR II Experiment 2: Analysis of the Combined Rankine and Vapour Compression Cycle

Study and Design Considerations of HRSG Evaporators in Fast Start Combined Cycle Plants. Govind Rengarajan, P.E.CEM, Dan Taylor

PERFORMANCE OF A MODEL IN-LINE VORTEX SEPARATOR. Keng-Choon Lee Geothermal Institute, The University of Auckland, Private Bag 92019, Auckland, New

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Jet ejectors for the oil industries. Vacuum solutions for refineries and the petrochemical industries

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek

UNIT 6 STEAM CONDENSERS

Jurnal UMP Social Sciences and Technology Management Vol. 3, Issue. 3,2015

Performance of an Improved Household Refrigerator/Freezer

HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

Evaporation studied on a duplicated vessel, pilot scale evaporator equipped with a heat pump

SIHI LPH-X - Liquid Ring Vacuum Pump One Stage

Efficient Steam System Design

1. Know your process. The following guidelines will help you navigate what can be a challenging and time consuming task.

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

THE PRESSURIZED CONDENSATE RECOVERY SYSTEM:

Single Screw Ammonia Heat Pumps. Harness Your Heat... Don t Reject It

Evaporation is a unit operation that separates a liquid

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

COMPARING PLASTIC STAKING TECHNOLOGIES

Cost, time and water savings gained through optimized tank cleaning

Guidelines for Optimizing Drying and Blow-Off Operations

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

Hot Reservoir Stainless-Methanol Variable Conductance Heat Pipes for Constant Evaporator Temperature in Varying Ambient Conditions

MECHANICAL SCIENCE Module 2 Heat Exchangers

Water Pumps. turbo-hydraulic pumps, positive-displacement pumps.

CERTIFICATION BULLETIN

SERIES 8796 SELF PRIMING PROCESS PUMPS ENGINEERING DATA

Brown Hills College of Engineering & Technology

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

Thermodynamics II Chapter 5 Refrigeration

Use this Construction/HVAC Glossary to answer the questions below.

HFO-1234yf Performance in a Beverage Cooler

SIHI LPH-X - Liquid Ring Vacuum Pump One Stage

MIT Architecture Fall 2008 L. Glicksman 4.42 FINAL Open Book

Chapter 8. Production of Power from Heat

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Evaluation of Sorbents at Elevated Temperatures for Downhole Application

Condenser Water Pump Calculator Guide

Performance investigation of Air-conditioning system using ejector as expansion device

ICONE DRAFT Proceedings of the 16th International Conference on Nuclear Engineering ICONE16 May 11-15, 2008, Orlando, Florida, USA

System Modeling of Gas Engine Driven Heat Pump

MINIMISING THE RISK OF WATER HAMMER AND OTHER PROBLEMS AT THE BEGINNING OF STAGNATION OF SOLAR THERMAL PLANTS- A THEORETICAL APPROACH

Homework Chapter2. Homework Chapter3

USING THE P-T CARD AS A SERVICE TOOL

Don t Turn Active Beams Into Expensive Diffusers

Transcription:

GRC Transactions, Vol. 40, 2016 Off Design Operation of Hybrid Noncondensable Gas Removal Systems for Flash Steam Cycle Geothermal Power Plants Jason Project Engineer, Vooner FloGard Corporation, Charlotte NC, USA jdevinney@vooner.com Keywords Noncondensable gas, NCG Removal System, steam jet air ejector, liquid ring vacuum pump, hybrid vacuum system, off design ABSTRACT The Noncondensable Gas (NCG) Removal System for the condenser of a flash steam geothermal power plant must be able to remove the NCG load at all plant operating conditions. Hybrid vacuum systems, incorporating steam first stage jet air ejectors (SJAE) and second stage liquid ring vacuum pumps (LRVP) have proven to be reliable and efficient in this service. The design basis for the NCG Removal System is determined by the conditions corresponding to the highest expected vapor mass and volumetric load. As SJAEs are substantially constant mass flow devices and LRVPs are positive displacement near constant volumetric flow devices, any variations from the design basis will have different effects on the NCG handling capacity and loading of each stage. Since the SJAE and LRVP operate in series, limitations or excess in capacity of each stage will affect the other. The system must be designed so that the NCG Removal System will operate at expected off design conditions. This paper provides an overview of the operational limits of a typical NCG Removal System at several combinations of off design basis conditions. Introduction Flash cycle geothermal steam includes a component of naturally occurring noncondensable gases typically in the range of 1-12% by weight in the flash steam. Additionally in barometric condenser applications, a significant amount of air is released from the condenser cooling water. The NCG Removal system is designed to compress these gases from the condenser operating Figure 1. Typical NCG removal system. 815

pressure to atmospheric pressure for release. Typically a hybrid system consists of a first stage steam jet air ejector (SJAE) followed by an intercondenser used to minimize the condensable vapor load and finally a liquid ring vacuum pump (LRVP) as shown in Figure 1. The system requires steam to drive the SJAE, cooling water for the intercondenser and LRVP, and electrical power for the LRVP and control system. The actual configuration of hybrid NCG system often consists of multiple parallel partial capacity trains which may be used with a common or separate intercondenser(s). Configuration is based partially on cost, redundancy requirements and user based confidence in expected NCG load. Systems design basis often exceeds % in varying configurations (example 3x50%, 70% + 40%, etc.) Steam Jet Air Ejector Overview A SJAE uses a convergent/divergent nozzle to create a venturi effect. The converging nozzle converts the pressure energy of motive steam to velocity energy. This change creates a low pressure zone inside the ejector that draws in the suction fluid (in this case NCG from the condenser). The diverging nozzle converts the velocity energy back into pressure energy. Figure 2 shows a typical ejector. SJAEs are typically selected to operate at a single design basis compression ratio. At off design compression ratios the suction vapor mass flow rate of the steam jet will vary. Figure 3 shows a typical SJAE mass flow capacity and compression ratio curve. Figure 2. Steam Jet Air Ejector (SJAE). Liquid Ring Vacuum Pump Overview Compression Ratio, :1 8 6 Design 4 2 0 0 2000 4000 6000 8000 00 12000 Suction capacity, Kg/hr Equivalent Dry Air Figure 3. SJAE performance curve. A LRVP uses a rotating impeller with multiple chambers to mechanically compress the suction fluid from the inlet of the pump to the discharge of the pump. Figure 4 shows a cross section of a typical LRVP. The LRVP is a positive displacement device that operates at a near constant (other than efficiency loss at higher compression ratios) volumetric flow. The LRVP volumetric capacity curve is typically published as volumetric flow of dry air at standard conditions, the actual operating conditions must be adjusted back to dry air at standard conditions for selection. LRVP power consumption curves are also published for dry air and must be adjusted for compression ratio and vapor density. Figure 5 shows a typical LRVP suction volumetric flow capacity curve. Figure 4. Liquid Ring Vacuum Pump (LRVP). Intercondenser Overview LRVP Volumetric Capacity 700 600 500 400 300 200 Figure 5. LRVP Capacity Curve. 14000 13000 12000 M 3 /hr of Dry Air At Standard Conditions The intercondenser uses cooling water to reduce the temperature and water vapor flow between the SJAE and the LRVP. The more efficient the intercondenser, the less volumetric capacity is required in the LRVP. 816

In a majority of systems the LRVP inlet manifold is equipped with spray nozzles diverting a portion of the required sealing water to provide a further amount of water vapor condensing before the LRVP inlet. Hybrid System Operation Hybrid NCG removal systems are typically designed around a single point worst load case. The compression load is split between the SJAE stage and the LRVP stage. The interstage pressure determines how the load is split. Splitting of the load can be optimized to greatly reduce parasitic load, this is not addressed in this paper. Figure 6 below shows a P&ID of a typical single train NCG removal system. At the design basis operating condition the flow rate of the first stage and the second stage is balanced to maintain the design intercondenser pressure without any manipulation. At off design conditions the load will not be balanced. The SJAE has a near constant mass flow capacity, while the LRVP has a near constant volumetric flow capacity. As volume of a gas is dependent on the temperature and pressure, the volumetric load will vary for a set mass load. In addition water carryover from the intercondenser to the second stage LRVP is dependent on temperature. The 2 nd stage LRVP will control the interstage pressure by either removing NCG volume at a rate faster or slower than it is added by the SJAE. Removing NCG faster than the first stage supplies will cause the interstage pressure to drop; conversely, removing the NCG slower than the first stage supplies will cause the interstage pressure to rise. In all conditions the system will either stabilize at the off design conditions naturally, with controlled assistance, or cease to operate properly. Operation Figure 6. Typical Hybrid NCG removal system. The following is the minimum information required for the design basis of the hybrid NCG removal system First stage suction pressure (condenser design operating pressure minus the pressure drop in the vapor piping to the first stage ejector) Vapor temperature at the first stage suction NCG gas mass flow rate NCG composition or average molecular weight Mass flow rate of air release from the cooling water and air in-leakage Mass flow of water vapor to saturate the NCG and air at the condenser operating pressure and vapor discharge temperature Motive steam pressure available for the steam jet(s) Plant Net Power 50 mw NCG percent weight content of the motive steam Steam Flow 349,200 kg/hr Cooling water supply temperature Discharge pressure of the NCG removal system A typical 50mW (net) flash cycle geothermal power plant typically requires approximately 349,200 kg/hr of flash steam to the turbine. We will use this value with 3% NCG in the steam and the below design basis as our example. NCG in the motive steam 3% NCG average MW 42 First stage suction pressure 57.50 mbara Vapor Temperature 18.3 C Mass Flow of air neglected Mass Flow of Water Vapor Per HEI saturation formula Cooling Water Temperature 16.7 C 817

Choosing a 264mbara intercondenser pressure this system operates at the design basis as shown in Figure 7 P&ID. Off Design Operation A variety of different of design conditions can occur. Addressed below are various common scenarios. For all of these conditions the following general assumptions are made: 1. The motive steam usage by the SJAE have been estimated Figure 7. Design basis operation. and not rigorously calculated by any SJAE manufacture. 2. Off design SJAE capacities have been estimated and not rigorously calculated by any SJAE manufacturer. 3. Vapor temperature at the condenser exit is a constant 0.9 C above the cooling water temperature. 4. Condenser operating pressure is the vapor pressure at 9.3 C above the cooling water temperature. 5. Intercondenser vapor approach temperature is 2.2 C 6. Changes in heat load to the inter condenser are neglected. Restrictions If the compression ratio of the jets is pushed beyond the operating range the jets will become unstable. The LRVP uses cooling water as a sealing liquid. This water must remain within a margin of safety below the vapor temperature of the LRVP suction. To facilitate this requirement a minimum interstage pressure is determined during the design. A valve is installed between the LRVP vapor discharge and inlet. If the interstage pressure falls below the minimum the recirculation valve will open and supplement the NCG load from the intercondenser, raising the interstage pressure. Minimum interstage pressure has been set at 225mbar. Cooling Water Temperature Exceeds The cooling water provided for the Condenser, the intercondenser and the LRVP are all provided from the same source, when this source temperature varies from design the temperature of water for each will vary the same amount. Condenser vapor temperature and condenser operating pressure need to be set for all conditions. For our theoretical condenser vapor temperature is assumed to be a constant 1.6 C above the cooling water temperature. Condenser Operating Pressure (unless restricted by the NCG removal system) is assumed the vapor pressure at 16.7 C above the cooling water temperature. This method can be used to study off design conditions of a particular plant with collaboration of the condenser and SJAE manufacturers. The SJAE is a mass flow device with a (nearly) constant mass flow for a given compression ratio. As the condenser pressure is increased above design basis by the warmer than design cooling water, the intercondenser pressure can also rise to maintain design SJAE compression ratio. Figure 8 below shows the required LRVP dry air equivalent volumetric flow rate that is required to maintain the design mass flow from the intercondenser at higher than design intercondenser pressures. (This curve is the NCG removal requirement LRVP Capacity Design Basis,16.7 C 22.2 C 25.0 C 19.4 C 27.8 C 30.6 C 33.3 C 700 600 500 400 300 200 Figure 8. Dry air equivalent of volume to be removed from intercondenser & LRVP Capacity. 20000 00 5000 Dry Air, M3/hr 818

to maintain SJAE design basis compression ratio and does not represent any physical operating condition as the interstage pressure is set by the 2 nd stage). Figure 8 also shows the LRVP dry air equivalent capacity curve. At the design point the required volumetric capacity matches the LRVP capacity and the hybrid system will behave in a steady state, removing the design NCG load. Yet, the off design conditions do not lie on the LRVP dry air capacity curve. At conditions of cooling water temperature exceeding the design temperature the volumetric capacity required to be removed from the intercondenser is less than the capacity of the pump. Since the LRVP is a positive displacement device it will remove NCG from the intercondenser faster than it is supplied by the SJAE. This evacuation will cause the pressure in the intercondenser to drop below the interstage pressure that corresponds to the SJAE design compression ratio, until the NCG flow volume meets the pump capacity as shown in Figure 9. The intercondenser pressure (set by the LRVP) is now higher than design, the condenser pressure (set by the cooling water) is also higher than design. For all these cases the compression ratio of the steam driven air ejector is lowered. A typical capacity vs compression ratio SJAE curve is shown previously in Figure 3. As the compression ratio is raised above design the mass flow of the SJAE decrease and as the compression ratio drops below design the mass flow of the SJAE increases. Therefore at these higher than design cooling water temperature conditions the capacity of the SJAE is higher than design, and the SJAE will displace additional water vapor above design bases into the intercondenser. This additional water vapor will add heat of condensation into the intercondenser and raise the discharge water and possibly the gas outlet temperature. For the purpose of this example the possibility of the intercondenser approach temperature changing with the additional water vapor load has been neglected. The result of the higher than design cooling water temperature is that the condenser pressure rises due to cooling water temperature and the intercondenser pressure rises, compression ratio of the jets is lowered from design, the compression ratio of the LRVP is raised from design (however the volumetric load to the pump is smaller than design basis). The NCG removal system does not limit condenser pressure. Once the SJAE reaches the end of its compression range, the system will become unstable. Cooling Water Temperature is Less Than Design Basis With cooling water below the design basis temperature, the volume of NCG required to be removed from the intercondenser surpasses the LRVP capacity, as shown in Figure 10, and the pressure in the intercondenser will rise due to the NCG buildup until the pressure in the intercondenser is high enough for the volumetric requirement to match a point on the LRVP curve. A minimum design interstage pressure will be set during design. Once this minimum pressure is reached volumetric load will be recirculated from the LRVP exhaust to the inlet maintaining minimum suction. After the minimum interstage pressure has been reached, the compression ratio of the SJAE continues to try to increase as the cooling water temperature (and condenser pressure) lowers. Referring again to Figure 3 we see that the capacity of the jets decreases as the compression ratio exceeds design. Condenser pressure is limited to the SJAE design compression ratio and therefore limited by the minimum interstage operating pressure at the design NCG load. Estimated condenser pressure is shown in Figure 11. 700 600 33 C 31 C 500 28 C 400 29 C 32 C 25 C 27 C 24 C 18 C 21 C Design Basis,16.7 C 17 C 19 C 22 C 300 200 20000 00 5000 LRVP Dry Air Capacity Estimated NCG Removal Capacity Requirements (at design jet CR) Figure 9. 2nd Stage Dry Air Equivalent Requirement, LRVP Capacity and Estimated Operating. 400 350 16 C 18 C,16.7 C 13 C 10 C 7 C 13 C 10 C 300 250 200 LRVP Dry Air Capacity Estimated NCG Removal Capacity Requirements (at design jet CR) Estimated Operating Conditions Minimum Design 7 C 25000 20000 00 Figure 10. 2nd Stage Dry Air Equivalent Requirement, LRVP Capacity and Estimated Operating. Condenser Operating Pressure, mbara 125 75 50 5 10 15 20 25 30 35 Cooling Water Temperature, C Figure 11. Expected Condenser Operating Pressure. Dry Air, m3/hr Dry Air, m3/hr 819

Power requirements of the pump may vary slightly at off design conditions. Variation will vary depending on pump model. In this case the higher pump suction pressure the higher the power consumption. Variation in this example is less than +/-5kw. Non Condensable Gas Load is Less Than The non-condensable portion of the steam flow is sometimes significantly reduced below design basis. A SJAE is a mass flow device with a (nearly) constant flow for a given compression ratio. Assuming that the jet is allowed to operate at a fixed compression ratio at the condenser design pressure the required volumetric capacity, in m3/ hr of dry air, that is nessasary for the second stage to remove is shown in Figure 12. (this curve does not represent any physical operating condition as the interstage pressure is set by the 2 nd stage). Since the NCG removal requirement of the SJAE has been reduced but the compression remains the same, the load to the SJAE is lower than design, and the SJAE will displace additional water vapor above design basis into the intercondenser. This additional water vapor will add heat of condensation into the intercondenser and raise the discharge water and possibly the gas outlet temperature. For the purpose of this the possibility of the intercondenser approach temperature changing with the additional water vapor load, has been ignored. With the mass of NCG required to be removed from the intercondenser reduced from the design basis, the volumetric requirement at the design pressure is also reduced. Since, the LRVP is a positive displacement device it will remove vapor from the intercondenser faster than required. This evacuation will cause the pressure in the intercondenser to drop until the required capacity meets the pump capacity, also shown in Figure 12. However, a minimum interstage pressure should be set during the design process to prevent cavitation in the LRVP. When the minimum intercondenser pressure is reached load to the LRVP will be supplemented from the LRVP discharge via a recirculation valve stopping the intercondenser pressure from dropping farther. Depending on the % of original load, the LRVP will operate somewhere between the design and the minimum interstage pressure. As the condenser pressure is set by the cooling water temperature, there is no change in the condenser pressure. Power requirements of the pump may vary slightly at off design conditions. Variation will vary depending on pump model. In this case the minimum suction pressure condition requires proximity +/-2kw from the design basis condition. Non Condensable Gas Load is Greater Than With NCG load above the design basis, the NCG removal system will not be able to remove all of the NCG at the design condenser pressure. The condenser pressure will rise until the NCG removal system can evacuate the required gas. Analysis of off design operation in this case will have to be done with collaboration of the condenser manufacturer. 350 25 C 330 310 22 C 290 97.500% 95.00% 92.50% 90.00% 87.50% 85.00% 80.00% 77.50% 270 250 230 210 190 170 Estimated NCG Removal Capacity Requirements (at design jet CR) Estimated Operating Conditions LRVP Capacity 19 C,16.7 C 13 C 10 C 7 C 16000 14000 13000 12000 10 00 Figure 12. 2nd Stage Dry Air Equivalent Requirement, LRVP Capacity and Estimated Operating. 400 350 300 250 200 LRVP Dry Air Capacity Estimated NCG Removal Capacity Requirements (at design jet CR) 90% NCG Removal Capacity Requirements (at design jet CR) 80% NCG Removal Capacity Requirements (at design jet CR) Figure 13. 2nd stage Dry Air Equivalent Requirement. 24000 19000 14000 9000 4000 Dry Air, M3/hr Dry Air, m3/hr 820

Varying Cooling Water Temperature With Lower Than Design NCG Content Condition The non-condensable portion of the steam flow is reduced below design while temperature of the cooling water provided for the Condenser, LRVP and intercondenser varies. For this example we consider the NCG load reduced to 90% and 80% of design. Assuming that the jet is allowed to operate at a fixed compression ratio the required volumetric capacity, in M 3 of dry hr air, that is nessasary for the second stage to remove is shown in Figure 13. (This curve does not represent any physical operating condition as the interstage pressure is set by the 2 nd stage) This curve is shifted down from the % NCG load condition. At all conditions the NCG load is less than design basis and additional water vapor may be moved by the SJAE to account for the mass flow difference. This additional water vapor will add heat of condensation into the intercondenser and raise the discharge water and possibly the gas outlet temperature. For the purpose of this example the possibility of the intercondenser approach temperature changing with the additional water vapor load, has been ignored. Operating conditions will be similar to the varying cooling water design, however, because of the lower flow rates the temperature that the intercondenser reaches the minimum design pressure is reduced. See Figure 14. Also, due to the decreased NCG mass flow to the SJAE, it is possible for the system to operate at a slightly higher compression ratio than design. Other lower NCG flow rates will be similar. An important observation to make is that the condenser pressure at off design conditions is limited primarily by the condenser cooling water temperature and secondly the compression ratio of the jets. As the required capacity of the SJAE(s) is lowered from the design basis, the compression capacity increases, allowing very slightly lower condenser pressures than possible at design NCG loads, as shown in Figure 15. Figure 16 shows the amount of excess capacity in each compression stage at 80% NCG condition. 400 350 22 C 19 C,16.7 C 300 250 13 C 200 10 C 26000 24000 22000 20000 18000 16000 14000 12000 00 Figure 14. 2nd Stage Dry Air Equivalent Requirement, LRVP Capacity and Estimated Operating. Condenser Operating Pressure, mbara 140.00 130.00 120.00 110.00.00 90.00 80.00 70.00 60.00 50.00 40.00 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 Cooling Water Temperature, C % NCG 90% NCG 80% NCG Figure 15. Expected Condenser Operating Pressure. % of capacity 105% % 95% 90% 85% 80% 75% 0 5 10 15 20 25 30 35 Cooling Water Temperature, C SJAE Figure 16. 80% NCG, NCG capacity required each stage. LRVP Capacity is satisfied by recirculation LRVP SJAE Capacity is satisfied by displacing aditional Water Vapor Dry Air, m3/hr 821

Summary and Conclusions Notes 1. In a system with a properly chosen design basis, the NCG removal system will not limit the condenser pressure until the minimum interstage pressure is reached. 2. The design basis must be the worst case scenario. The system will not operate effectively with higher than design basis NCG flow rate, and the condenser pressure will be limited. 3. Higher than design cooling water temperature with design NCG flow will cause: a) Condenser pressure to rise due to cooling water temperature b) Intercondenser pressure will rise due to cooling water temperature and LRVP volumetric capacity c) SJAE will operate at a lower CR than design and displace additional water vapor and heat load to the intercondenser 4. Lower than design cooling water temperature with design NCG flow will cause: a) Condenser pressure will attempt to drop due to cooling water temperature b) Intercondenser pressure will remain between design and the minimum set pressure, at the minimum pressure vapor will recirculate from the LRVP discharge to the inlet c) Condenser pressure will be limited by the SJAE compression ratio 5. Higher than design NCG content will cause the condenser pressure to rise as it cannot be evacuated at a sufficient rate. 6. Lower than design NCG content will cause a) The intercondenser pressure to be between the design and the minimum pressure. b) Since the condenser pressure is set by the cooling water temperature there is no change. 7. Lower than design NCG flow rate with lower than design cooling water temperature will cause: a) Condenser pressure will attempt to drop due to cooling water temperature b) Intercondenser pressure will remain between design and the minimum set pressure; at the minimum pressure vapor will recirculate from the LRVP discharge to the inlet c) Condenser pressure will be limited by the SJAE compression ratio. However as the NCG flow rate decreases the jet can compress to a higher compression ratio and the condenser pressure lowers. Note 1: The example geothermal power plant design used in this study does not represent a specific power plant, but rather is derived from many power plant designs with conditions averaged and normalized to a design capacity of 50mW net electric generation capacity. Note 2: The example geothermal power plant design is based on 50mW net generating capacity, at the design basis using 97kg/s of geothermal steam with an average molecular weight of 43.5. Condenser operating pressure of.057bara. Cooling water is available at 16.7 C. Discharge pressure of the system is 1.034 bara. While the method of analysis remains the same, any change to any of the design basis parameters will affect the study. 822