COHASSET, MA March 6, The following is the HVAC outline specifications, which defines the scope of work of the HVAC system.

Similar documents
SECTION AIR COILS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

HVAC PROPOSED SYSTEMS SOUTHBOROUGH PUBLIC SAFTEY BUILDING. September 12, 2017

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

SECTION AIR HANDLING UNIT

DARTMOUTH COLLEGE DESIGN March 15, 2003 & CONSTRUCTION GUIDELINES

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

REFRIGERANT PIPING SYSTEM

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

SECTION (15530) - REFRIGERANT PIPING

SECTION DUCTWORK

DIVISION 15 MECHANICAL

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

Modular Supply Make-Up Air Unit

Ratio Architects, Inc. Section Refrigerant Piping

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW...

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

PROJ. NO SECTION REFRIGERANT PIPING

Direct Fired Heater Model AD Specification

D. Fabrication: Steel or Aluminum with baked enamel off-white finish. B. Type: Square and rectangular, adjustable pattern, multi-louvered diffuser.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

EXHAUST FAN SCHEDULE

SECTION AIR OUTLETS AND INLETS

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services

SECTION HYDRONIC PIPING

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

REFRIGERANT PIPING

SECTION CONVECTION HEATING AND COOLING UNITS

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

PITTSBURG STATE UNIVERSITY. HVAC and BUILDING AUTOMATION SYSTEM STANDARDS

SECTION (15530) - REFRIGERANT PIPING

B. HI Compliance: Design, manufacture, and install pumps in accordance with HI "Hydraulic Institute Standards."

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016

A. ASME Compliance: Fabricate and install hydronic piping in accordance with ASME B31.9 "Building Services Piping.

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

DESIGN GUIDELINES SECTION HVAC

DOCUMENT TABLE OF CONTENTS

GARCIA GALUSKA DESOUSA Consulting Engineers

Union County Vocational - Technical Schools Scotch Plains, New Jersey

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories for each type of product indicated.

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

HYDRONIC SPECIALTIES TACO AC(F)-CA 05/08/2008

HYDRONIC SPECIALTIES TACO AC(F)-PAX 05/15/2008

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

FAARM-Underground Facility. Conceptual Design Review. Mechanical Systems. Dunham Associates, Inc.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

Construction Standards Page

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

DESIGN GUIDELINES SPLIT TYPE AIR TO AIR HEAT PUMPS PAGE 1 of 6

SECTION PLUMBING EQUIPMENT

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating.

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC).

GARCIA GALUSKA DESOUSA Consulting Engineers

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

SECTION DRY-PIPE SPRINKLER SYSTEMS

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING

University of Delaware

SECTION CONVECTION HEATING AND COOLING UNITS

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

1.1 This section applies to air handling units for HVAC Systems.

SECTION HEATING BOILERS

B. Shop Drawings: Detail fabrication of pipe anchors, hangers, special pipe support assemblies, alignment guides, expansion joints and loops,

Indirect Gas-Fired Make-Up Air

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

SECTION FUEL-FIRED, DOMESTIC WATER HEATERS

1. Use air systems in combination with perimeter radiation. Perimeter radiation shall be capable of being operated independent of the air system.

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

SECTION PLUMBING EQUIPMENT

Lee s Summit West High School Boiler #3 Replacement SECTION CONDENSING BOILERS

SECTION DOMESTIC WATER PUMPS

Design and Construction Standards SECTION PLUMBING EQUIPMENT

SECTION AIR COILS

Division 23 - HVAC Switzerland Beallsville K-12. Section HYDRONIC PIPING SECTION HYDRONIC PIPING PART 1 - GENERAL

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SECTION HYDRONIC PIPING AND SPECIALTIES

Direct Gas-Fired Make-Up Air Models DG and DGX

C. Samples for Initial Selection: For units with factory-applied color finishes.

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

HVAC REPAIR/REPLACEMENT 07/18/12 SECTION HVAC - MAJOR EQUIPMENT

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

DIVISION 23 - HVAC HVAC Air Distribution

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

B. Chimney: Primarily vertical shaft enclosing at least one vent for conducting flue gases outdoors.

A. This Section includes air-handling units with coils for indoor installations.

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

Heat Pumps SA SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features:

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals.

WET-PIPE SPRINKLER SYSTEMS

Transcription:

23 00 00 HEATING, VENTILATING & AIR-CONDITIONING The following is the HVAC outline specifications, which defines the scope of work of the HVAC system. PART 1 GENERAL 1.1 CODES A. All work installed under the HVAC Section shall comply with the Town of Cohassett Building Code and all state, county, and federal codes, laws, statutes, and authorities having jurisdiction. 1.2 DESIGN INTENT AND SYSTEM DESCRIPTION A. The work of this Section is shown on the drawings. All work is new and consists of furnishing all materials, equipment, labor, transportation, facilities, and all operations and adjustments required for the complete and operating installation of the Heating, Ventilating and Air Conditioning work and all items incidental thereto, including commissioning and testing. B. Capacities of systems and equipment are indicated in the attached HVAC system narrative and/or as indicated on schematic drawings. PART 2 - PRODUCTS 2.1 GENERAL A. Materials and equipment furnished under this section shall be new, unused, first quality of a manufacturer of established reputation. 2.2 PIPING AND FITTINGS A. Hydronic piping shall be Schedule 40 ASTM A-53, black steel pipe with butt welded ends and fittings on 3" and above and threaded ends and fittings on 2-1/2" and smaller. At the contractor option type "L" copper may be used on all 2-1/2" and smaller. Use of mechanical coupling piping systems, equal to Victaulic is acceptable for piping 2 ½ and larger and the use of Propress or equal piping system is acceptable for piping under 2-1/2 in size. B. Refrigerant Piping: 1. General: Provide piping materials and factory-fabricated piping products of sizes, types, pressure ratings, temperature ratings, and capacities as indicated. Where not indicated, provide proper selection as determined by Installer to comply with installation requirements. Provide materials and products complying with ANSI B31.5 Code for refrigeration piping where applicable, base pressure rating on refrigerant piping system maximum design pressures. Provide sizes and types matching piping and equipment connections; provide fittings of materials which match pipe materials used in refrigerant piping systems. Where more than one type of materials and products are indicated, selection is Installer s option. 2. Material: Provide pipes and pipe fittings in accordance with the following listing: Tube Size 4-1/8 and Smaller: Copper tube; Type ACR, hard-drawn temper; wroughtcopper, solder-joint fittings; brazed joints. 23 00 00 - Page 1 of 7

2.3 VALVES 3. Soldered Joints: Solder joints using silver-lead solder, ASTM B32, Grade 96 TS. 4. Brazed Joints: Braze joints using American Welding Society (AWS) classification BCUO- 4 for brazing filler metal. 5. Piping Specialties: Provide piping specialties complying with Division-23 Hydronic Piping in accordance with the following listing: a. Pipe escutcheons. b. Drip pans. c. Sleeves. d. Sleeve seals. A. All valves shall be bronze, brass, or cast iron as system design requires. Locate all valves so as to isolate all parts of the system and as required for normal system operation. documents provide valves of the following manufacturer: a. Milwaukee b. Stockham c. Nibco 2.4 SYSTEM IDENTIFICATION A. Provide markers on all piping and equipment. Tag all valves in system with corresponding valve lists. 2.5 INSULATION A. All hot water piping shall be insulated with snap-on fiberglass insulation with all service jacket. Fittings shall be insulated with snap on pre-molded covers with loose fill fiberglass insulation. All refrigerant piping shall be insulated with 1 closed cell foam insulation with vapor barrier. B. All AC supply ductwork shall be insulated with 1-1/2" thick fiberglass blanket with a foil vapor barrier. All outside air intake ductwork shall be insulated with 2" rigid fiberglass with foil vapor barrier. 2.6 FIN TUBE RADIATION AND RADIANT HEATING PANELS A. Commercial slope top fin-tube with steel tube and steel fin. Cover shall be 14 ga. with baked enamel factory finish. All units shall be provided with full backplate, damper, end covers, and splice pieces for a complete installation. documents provide fin-tube radiation of the following manufacturer: a. Sterling b. Vulcan c. Ritling 23 00 00 - Page 2 of 7

B. Radiant Heating Panels: 1. Radiant heating panels shall be designed to create natural convection to heat the conditioned space. Units shall be designed for ceiling installation with factory supplied trim. Contractor shall provide all hanger supports. 2. Available Manufacturers: Subject to compliance with requirements, provide radiant heating panels of one of the following: a. TWA b. Sterling c. Rittling d. Or equal 2.7 UNIT HEATERS A. Horizontal or cabinet type with exact location to be determined. All units shall be provided with fan and aquastat control. documents provide unit heaters of the following manufacturer: a. Trane b. Sterling c. Ritling 2.8 HYDRONIC COILS A. General: Provide coils of size and in location indicated, and of capacities and having performance data as scheduled. Certify coil capacities, pressure drops, and selection procedures in accordance with ARI 410. 1. Manufacturer: Subject to compliance with requirements, provide coils of one of the following: a. McQuay Inc. b. Trane (The) Co. c. Greenheck d. Precision Coil 2.9 PUMPS & ACCESSORIES A. Base mounted bronze fitted with high efficiency electric motor. Provide primary and stand-by pump for each system with manual alternator and pilot lights. 1. Available Manufacturers: Subject to compliance with the contract documents provide pumps of the following manufacturer: a. Bell & Gossett b. Taco c. Armstrong 23 00 00 - Page 3 of 7

B. Provide expansion tanks, air separators, end-suction diffusers as manufactured by: 1. Bell & Gossett 2. Taco 3. Armstrong 2.10 BOILERS A. High efficiency gas fired condensing hot water boiler. B. Power burners shall be fully modulating (min 5:1 turndown). C. Provide complete boiler exhaust venting and combustion air intake system. D. Boiler venting shall be provided by Div 22 00 00. E. Provide boiler neutralization tunes and associated piping. Provide all code required boiler safeties and controls. F. Manufacturer: Subject to compliance with the above, provide high efficiency gas fired condensing boiler of one of the following: 1. Viessmann 2. Burderus 3. Lochinvar 2.11 ROOFTOP AIR HANDLING UNITS (HVAC 100% O.A.) A. All units shall be of the draw thru 100% outdoor air design and shall be provided with direct expansion cooling coil, hot water heating coil, energy recovery wheel with VFD, filters (MERV- 13), dampers, and centrifugal supply and return air fan with motor. documents provide rooftop air handling units of the following manufacturer: a. Greenheck b. Aaon c. Innovent/Valent 2.12 AIR HANDLING UNITS (HVAC Recirculation) A. All units shall be of the draw thru type provided with direct expansion cooling coil, filters (MERV- 13), hot water heating, energy recovery wheel with VFD, dampers, and centrifugal supply and return air fan with motor. documents provide air handling units of the following manufacturer: a. Greenheck b. Haakon c. Aaon 23 00 00 - Page 4 of 7

2.13 VARIABLE REFRIGERANT FLOW (VRF) SYSTEM A. The basis of design Heat Recovery Variable Refrigerant Flow system is a three pipe system consisting of a single or multiple outdoor units, multiple indoor units of various types and capacities, multiple zone control boxes, individual or central indoor unit controls with on/off temperature settings, all connected by fully insulated refrigerant lines utilizing factory supplied, fully insulated, branching kits. Indoor units are connected to condensate piping that shall be terminated to the nearest drain point. The system shall be fully capable of simultaneous heating and cooling operation as requested by the individual indoor zones that can consist of single or multiple indoor units. 1. Manufacturer: Subject to compliance with requirements, provide variable refrigerant flow (VRF) system of one of the following: 2.14 DUCTWORK a. Mitsubishi b. LG c. Toshiba/Carrier d. Or Equal A. All ductwork shall be galvanized steel with all seams sealed. Entire ductwork system shall be fabricated and installed per SMACNA LOW PRESSURE DUCT CONSTRUCTION STANDARDS. 2.15 DIFFUSERS REGISTERS GRILLES A. All devices shall be steel welded construction with diffusing vanes and baked enamel finish. documents provide diffusers, registers, and grilles of the following manufacturer: 2.16 EXHAUST FANS a. Tuttle & Bailey (RC) b. Price c. Nailor Industries (vaned) d. Metalaire (IV) A. Roof mounted exhaust fans shall be galvanized steel construction with centrifugal fan and belt drive motor. Each roof unit shall be provided with 18" high pre-fab curb with motor operated damper in curb. Inline roof fans shall be provided as shown on the drawings or as indicated in the narrative. documents provide exhaust fans of the following manufacturer: a. Greenheck b. Cook c. Twin City 23 00 00 - Page 5 of 7

2.17 AUTOMATIC TEMPERATURE CONTROLS A. System shall be a direct digital control and building energy management system to provide complete automatic temperature control and monitoring of newly installed HVAC system. documents provide automatic temperature controls of the following manufacturer: a. Honeywell b. Johnson Controls c. Delta d. Or equal PART 3 - EXECUTION 3.1 WORKMANSHIP AND INSTALLATION METHODS A. All work shall be installed in a first-class manner consistent with the best current practices. 1. All piping shall be installed with slope for proper drainage shall be grouped together, and be parallel to each other. Utilize gang hangers wherever feasible. Group all valves together where feasible. 3.2 CLEANING AND PROTECTION A. Protect all materials and equipment during shipment and installation, and properly handle and store at the job site so as to prevent damage, and upon completion of this work, clean all fixtures and equipment and replace damaged parts. 3.3 SLEEVES AND ESCUTCHEONS A. Furnish and install in masonry walls and floors, galvanized steel sleeves as required. Provide escutcheons where sleeves and pipe penetrations are exposed to view. 3.4 FIRESAFING A. At all sleeved walls and floors provide firesafe caulking, packing, blanket etc., for a completely tight system to prevent the passage of smoke and fire. 3.5 TESTING, ADJUSTING, COMMISIONING AND BALANCING A. Requirements include measurement and establishment of the quantities of the mechanical systems as required to meet specifications and recording and reporting the results. Test, adjust and balance the following mechanical systems: 1. Supply air systems. 2. Return air systems. 3. Exhaust air systems. 4. Outside air systems. 5. Hydronic heating and cooling systems. 6. Verify temperature control system operation. 23 00 00 - Page 6 of 7

B. Report forms shall be those standard forms prepared by the referenced standard for each respective item and system to be tested, adjusted, and balanced. Bind report forms complete with schematic systems diagrams and other data in reinforced, vinyl, three-ring binders. C. An independent testing, adjusting, and balancing agency certified by the AABC or NEBB as a Test and Balance Engineer in those testing and balancing disciplines required for this project. 3.6 OPERATION MANUALS AND MAINTENANCE MANUALS A. Refer to the contracts specifications for a complete outline of all requirements of operations and maintenance data. 3.7 RECORD DRAWINGS AND CONTROL DOCUMENTS A. Refer to the contracts specifications project record documents for a complete description of all requirements of recording as built record documents. END OF SECTION 23 00 00 - Page 7 of 7