30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

Similar documents
30GK. Air-Cooled Liquid Chillers. Nominal cooling capacity kw

30GX - 50 Hz. Air-Cooled Screw Compressor Liquid Chillers GLOBAL CHILLER. Nominal cooling capacity kw

30HXC - 50 HZ. Water-Cooled Screw Compressor Liquid Chillers. Nominal cooling capacity kw

30RH B Nominal cooling capacity kw Nominal heating capacity kw

30GX 50 Hz. Air-Cooled Screw Compressor Liquid Chillers GLOBAL CHILLER. Nominal cooling capacity kw

AQUASNAP JUNIOR 30RHV

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

38RBS Air-Cooled Condensing Units. Nominal cooling capacity: kw. Features. Easy and fast installation

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module. Nominal cooling capacity kw. Easy and fast installation.

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

38RBS Air-Cooled Condensing Units. product selection data. commercial and industrial applications. compact design.

30RB/RQ 039S-160S. Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump Nominal cooling capacity: kw Nominal heating capacity: kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

30RB /30RQ

30XA Air-Cooled Liquid Chillers. Nominal cooling capacity kw

61AF High-Temperature Monobloc Air-to-Water Heat Pumps with Integrated Hydronic Module. Nominal heating capacity kw.

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

30RB /30RQ

30HXC Nominal cooling capacity kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

AQUASNAP AIR CONDITIONING MADE SIMPLE 30RA/30RH AQUASNAP LIQUID CHILLERS HEAT PUMPS

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

AR Ductable Air-Cooled Liquid Chillers Ductable Reversible Air-to-Water Heat Pumps

Unit with optional hydronic module 61WG/30WG. Nominal cooling capacity kw Nominal heating capacity kw

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module PRODUCT SELECTION DATA. Compact design

30RBY/RQY Ductable Air-Cooled Liquid Chillers/ Ductable Air-to-Water Heat Pumps PRO-DIALOG +

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module. Nominal cooling capacity kw. Easy and fast installation.

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

30XAS Air-Cooled Liquid Chillers PRO-DIALOG + Nominal cooling capacity kw. Features and advantages. Very economical operation

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

3 0 H X C A - H P 2

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS

30RB/RQ Air-Cooled Liquid Chillers/Air-to-Water Heat Pumps. product selection data

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY

30GT FLOTRONIC AIR-COOLED CHILLERS

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ

30GN FLOTRONIC II AIR-COOLED CHILLERS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

30HXC-HP Water-to-water Screw Heat Punp. Nominal cooling capacity: 460~1283 kw Nominal heating capacity: 498~1591 kw

30XAS A Air-Cooled Liquid Chillers. Nominal cooling capacity kw 50 Hz. Features and advantages. Very economical operation

30RB A /30RQ

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR

50VZ (40PZ/38VZ) Vertical Air-Cooled Split-System Cooling Units. Nominal cooling capacity kw

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

30RB/RQ Air-Cooled Liquid Chiller Reversible Air-to-Water Heat Pump

30RB /30RQ

30HX GLOBAL CHILLER LIQUID CHILLER IN HARMONY WITH THE ENVIRONMENT

High COP. Water-Cooled Screw Chiller

Большая библиотека технической документации каталоги, инструкции, сервисные мануалы, схемы.

CONDENCIAT CD. Condensing units. Quiet operation Low speed fans All year round operation USE. Cooling capacity : 25 to 165 kw.

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

Advance Split

Aquaflair TRAC-TRAF-TRAH

.2 Section Waste Management and Disposal.

DOLPHIN RADIATOR & COOLING SYSTEMS P.O.Box: 1424,Ph#: , Fax#: ,

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

61WG/30WG/30WGA. Water-Cooled and Condenserless Liquid Chillers Water-Sourced Heat Pumps. product selection data. 30WG optimized for cooling

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module. Nominal cooling capacity kw. Easy and fast installation.

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

EPCE00-10B. Powerful. air cooled. Hydronic systems EUWA*40-200K(A)X

Compact and silent Scroll compressors All-season operation

30RBV/30RQV Inverter Air-Cooled Liquid chillers & Reversible Air to Water Heat Pumps PRODUCT SELECTION DATA INSTALLATION, OPERATION AND

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

CENTRAL SPLIT UNIT UNIC

CIATCOOLER LJA. Chilled water production units USE. Attractive design, Compact and quiet

ERAH MC Ka. Range kw. AIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS FOR OUTDOOR INSTALLATION (Standard line)

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01

CATALOGUES SUMMARY - WCHBZ Pages WCHZ Pages 19-42

30GXN,R AIR-COOLED LIQUID CHILLERS WITH COMFORTLINK CONTROLS 50/60 Hz

30KAV Variable Speed Air-cooled Screw Chiller

LDK LDK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

30RB/RQ Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump 30RB: Nominal cooling capacity: kw 30RQ: Nominal cooling capacity:

30RQV NEW. Nominal cooling capacity kw Nominal heating capacity kw AIR-TO-WATER HEAT PUMPS HEATING. Easy and fast installation

SECTION ROTARY-SCREW WATER CHILLERS

30RB/RQ 039S-160S Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

MAC N-407 Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

LSA LSA A + Air cooled water chillers with axial fans VERSIONS ACCESSORIES

MAC-120HE-03 Air-Cooled Chiller

30AW. Reversible Air to Water Heat Pump PRODUCT SELECTION DATA. Monobloc inverter. Compact, reliable and efficient. More than a Heat Pump

50AZ/UZ Packaged Rooftop Cooling Only Units and Heat Pumps

Air cooled chillers. Air cooled chillers with brushless oil-free compressors. RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw

LSK LSK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

Carrier India. Snapshots of Carrier India manufacturing facility

PYXIS U PYXIS U. rcgroupairconditioning

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

LZT High efficiency air to water heat pumps with E.V.I. compressors

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

Transcription:

Air-Cooled Liquid Chillers Nominal cooling capacity 21-94 kw Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. The 30GH air-cooled liquid chillers are compact and reliable, and ideally suited to residential, commercial and industrial comfort and process applications. They are designed for easy and fast installation, and equipped with Pro-Dialog control or conventional electromechanical control. Features n The compact size facilitates maintenance and permits installation on roofs where space is at a premium. With their low height (maximum 1.2 m) and their attractive paint finish they fulfil most architectural requirements. n Low-noise operation. The revolutionary, low-noise, shrouded axial Flying Bird fan is made of a composite plastic material which is fully recyclable. Together with the substantial reduction of compressor noise transmission (discharge muffler, anti-vibration mountings), this results in a uniform chiller sound spectrum and eliminates intrusive low frequency noises. n The 30GH units offer an excellent coefficient of performance. High-efficiency hermetic or semi-hermetic compressors together with oversized air-cooled condensers and stainless steel plate heat exchangers guarantee superior efficiency levels. n Refrigerant containment - rigorous factory tightness tests and use of temperature or pressure sensors without capillary tubes eliminate the risk of leaks. Shut-off valves permit isolation of the refrigerant charge in the heat exchangers. Maintenance operations become less frequent and more effective. n Simple installation with the Hydroflow option. The chiller is supplied complete with all hydronic components required for correct system operation: chilled water pump, buffer tank, expansion tank, etc. 301

PRO-DIALOG control PRO-DIALOG is an advanced numeric control system that combines complex intelligence with great operating simplicity. PRO-DIALOG ensures intelligent leaving water temperature control and optimises energy requirements. n The PID control algorithm with return water temperature compensation anticipates load variations, guarantees leaving water temperature stability and prevents unnecessary compressor cycling. PRO-DIALOG ensures preventive protection and enhances chiller reliability. n No capillary tubes or pressostats (except as safety device) n PRO-DIALOG monitors all chiller safety parameters including insufficient evaporator water flow. The fault history function and the 80 fault codes facilitate immediate fault location (see Technical Description) PRO-DIALOG offers extended communications capabilities n Clear and easy-to-understand operator interface. The LEDs, numeric displays and touch keys are well-positioned on the schematic chiller diagram. The user immediately knows all operating parameters: pressures, temperatures, operating hours, etc. n The extensive chiller remote control capabilities (wired connection) allow integration into building monitoring systems (see Technical Description) n RS485 series port for connection to the Carrier Comfort Network (CCN) or any other monitoring system (optional communications interface with open protocol allows transfer of almost 50 parameters). Low-noise Flying Bird fan 30GH with Hydroflow module Options and accessories Option Accessory Copper/copper condenser coils (30GH 030-035) Condenser anti-corrosion treatment for rural, urban and industrial applications Condenser anti-corrosion treatment for marine applications Low leaving brine temperatures from 1 C to -10 C Compressor sound enclosure (Note: 30GH 009-013 option includes low-speed fan) Tropicalized control box Oil pressure gauge (30GH 015-035, electromechanical control) High and low pressure manometers Oil pressure safety switch (30GH 015-035) Head pressure control for low outside temperature applications (fan speed variation) 220-3-50 power supply Main power disconnect switch with auxiliary circuit power supply transformer Additional capacity stage (30GH 015-025-030-035) Hydroflow module, including circulating pump, buffer tank, expansion tank RS485 communications interface with open protocol Water flow switch Protection grilles Compressor run-time indicator (electromechanical version) Auxiliary circuit power supply transformer 302

Physical data 30GH 009 013 015 020 025 030 035 Net nominal cooling capacity* kw 21.2 31.6 40.1 52.0 65.0 74.0 93.0 Operating weight kg 265 283 400 460 510 682 725 Refrigerant charge (R-22) kg 6.5 8.0 9.2 11.9 13.3 15.7 16.5 Compressor 1...hermetic, 48.3 r/s 1...semi-hermetic, 4 or 6 cylinders, 24.2 r/s Control type Pro-Dialog or electromechanical Capacity control steps 1 1 2 2 2 2 2 Minimum capacity step % 100 100 66 50 66 66 66 Evaporator Direct-expansion, plate heat exchanger Water volume l 1.9 2.8 3.8 4.7 5.6 6.6 7.5 Number of refrigerant circuits 1 1 1 1 1 1 1 Water connections in Gas thread Outlet-inlet 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 Max. water side operating pressure kpa 1000 1000 1000 1000 1000 1000 1000 Condenser Copper tube, aluminium fins Fans Propeller Low-noise shrouded axial Flying Bird fan Quantity 1 1 1 1 1 2 2 Total air flow l/s 2640 2640 4700 4700 4700 9400 9400 Fan speed** r/s 15.8/12.5 15.8/12.5 12.5 12.5 12.5 12.5 12.5 * Net cooling capacity = gross cooling capacity minus the water pump heat against the internal evaporator pressure drop. Evaporator entering/leaving water temperature 12 C and 7 C. Condenser entering air temperature 35 C. ** The first figure is for the standard fan, the second figure is for the optional low speed fan. Electrical data 30GH 009 013 015 020 025 030 035 Power circuit Nominal power supply V-ph-Hz 400-3-50 Voltage range V 360-440 Auxiliary circuit V-ph-Hz 230-1-50 Auxiliary circuit power input (heaters) W 70 70 110 250 250 250 250 Fan power input kw 0.80 0.80 1.15 1.15 1.15 2.30 2.30 Fans, nominal power supply V-ph-Hz 400-3-50 Nominal unit power input* kw 8.4 13.7 13.6 18.2 24.2 26.9 37.8 Maximum unit power input** kw 10.0 16.8 16.4 22.0 29.0 32.3 46.2 Maximum unit starting current A 83.2 136.7 87.0 107.0 134.0 158.0 213.0 Nominal unit current drawn* A 13.2 22.5 21.1 29.0 39.3 42.1 60.7 Maximum unit current drawn** A 24.7 38.7 34.0 38.9 51.0 60.0 83.0 Notes: * Evaporator entering/leaving water temperature 12 C and 7 C. Condenser entering air temperature 35 C. ** Evaporator entering/leaving water temperature 18 C and 13 C. Condenser entering air temperature 45 C. Currents are given at nominal voltage NOTES: units have a single power connection point. A separate power source (230 V, 1 ph, 50 Hz) that does not exceed the main switch capacity is required to power the compressor crankcase heater circuit. This source must be supplied from a transformer. It must not be supplied from a phase + neutral supply (for ground + neutral systems). The control box includes the following standard features: - Starter and motor protection devices for each compressor and the fan(s) - Control devices Field connections: All connections to the system and the electrical installations must be in full accordance with all applicable codes. The Carrier chillers are designed and built to ensure conformance with local codes. The recommendations of European standard EN 60 204-1 (machine safety - electrical machine components - part 1: general regulations) are specifically taken into account, when designing the electrical equipment. Conformance with EN 60 204 is the best means of ensuring compliance with the Machines Directive and 1.5.1. Generally the recommendations of IEC 364 are accepted as compliance with the requirements of the installation directives. Annex B of EN 60204-1 describes the electrical characteristics used for the operation of the machines. 1. The operating environment for the chillers is specified below: a. Environment* - Environment as classified in IEC 60 721: - outdoor installation* - ambient temperature range: -18 C to +46 C, class 4K3* - altitude: 2000 m* - presence of hard solids, class 4S2 (no significant dust present) - presence of corrosive and polluting substances, class 4C2 (negligible) - vibration and shock, class 4M2 b. Competence of personnel, class BA4* (trained personnel - IEC 364) 2. Power supply frequency variation: ± 2 Hz. 3. The neutral (N) line must not be connected directly to the unit (if necessary use a transformer). 4. Overcurrent protection of the power supply conductors is not provided with the unit. 5. The factory-installed circuit breaker is of type a (EN 60 204-1 5.3.2). NOTE: If particular aspects of an actual installation do not conform to the conditions described above, or if there are other conditions which should be considered, always contact your local Carrier representative. * The protection level required to conform to this class is IP43BW (according to reference document IEC 529). All units are protected to IP44CW and fulfil this protection condition. 303

Dimensions/clearances 30GH A B C D E F G 009-013 1160 1220 1060 1200 1000 1000 1000 015-025 1720 1160 1112 1200 1000 1000 1000 030-035 2060 1370 1231 1200 1000 1000 1000 30GH 009-013 30GH 015-025 Do not obstruct Do not obstruct C C A A E F E F G B D B D G 30GH 030-035 Do not obstruct C A Legend: E F All dimensions are given in mm. Required clearance space for servicing. Power supply Water inlet G Water outlet B Note: Certified dimensional drawings are available on request. D 304

Cooling capacities LWT Condenser entering air temperature C 25 30 35 40 45 CAP COMP UNIT COOL CAP COMP UNIT COOL CAP COMP UNIT COOL CAP COMP UNIT COOL CAP COMP UNIT COOL 30GH ( C) kw kw kw l/s kpa kw kw kw l/s kpa kw kw kw l/s kpa kw kw kw l/s kpa kw kw kw l/s kpa 009 4 21.8 6.6 7.5 1 24 20.5 6.9 7.8 1 22 19.0 7.2 8.1 0.9 19 17.6 7.5 8.6 0.8 17 16.3 7.8 8.6 0.8 14 013 31.9 11 11.9 1.5 22 29.9 11.5 12.4 1.4 20 27.9 12.1 13.0 1.3 17 25.9 12.6 13.9 1.2 15 24.0 13.1 13.9 1.1 13 015 40.7 10.5 11.9 2 26 38.6 11.2 12.5 1.8 24 36.3 11.8 13.1 1.7 21 34.0 12.3 14.2 1.6 19 31.8 12.9 14.2 1.5 17 020 53 14.6 16.1 2.5 31 50.0 15.3 16.7 2.4 27 46.7 16 17.4 2.2 24 43.4 16.6 18.5 2.1 20 40.1 17.2 18.7 1.9 18 025 66 19.8 21.3 3.2 28 62 20.7 22.1 3 25 58 21.5 22.9 2.8 22 55 22.3 24.2 2.6 19 51 22.9 24.4 2.4 17 030 77 20.9 23.6 3.7 30 72 22.2 24.8 3.4 27 67 23.3 25.8 3.2 23 62 24.4 27.8 3 20 57 25.3 28.0 2.7 17 035 95 30 32.9 4.6 36 90 31.7 34.5 4.3 32 85 33.3 36.0 4 29 80 34.8 38.8 3.8 26 74 36.2 39.0 3.5 22 009 5 22.6 6.7 7.6 1.1 26 21.2 7 7.9 1 23 19.8 7.4 8.3 0.9 20 18.3 7.7 8.7 0.9 18 16.9 7.9 8.7 0.8 15 013 33.2 11.2 12.1 1.6 24 31.2 11.8 12.7 1.5 21 29.1 12.4 13.3 1.4 19 27.1 12.9 14.3 1.3 17 25.1 13.4 14.3 1.2 15 015 42.2 10.7 12.1 2 28 40.0 11.4 12.8 1.9 25 37.6 12 13.3 1.8 23 35.3 12.6 14.4 1.7 20 33.0 13.1 14.4 1.6 18 020 55 14.8 16.3 2.6 33 52 15.6 17.0 2.5 29 48.5 16.3 17.7 2.3 25 45.2 17 18.9 2.2 22 41.9 17.6 19.1 2 19 025 68 20.3 21.8 3.3 30 65 21.2 22.7 3.1 26 61 22 23.4 2.9 23 57 22.8 24.8 2.7 21 53 23.5 25.0 2.5 18 030 79 21.2 23.9 3.8 32 75 22.6 25.2 3.6 28 70 23.8 26.4 3.3 25 64 24.9 28.3 3.1 22 59 25.8 28.5 2.8 19 035 98 30.7 33.6 4.7 38 93 32.4 35.2 4.5 34 88 34 36.7 4.2 31 82 35.5 39.6 3.9 27 77 37 39.8 3.7 24 009 6 23.4 6.8 7.7 1.1 28 22.0 7.1 8.0 1.1 25 20.5 7.5 8.4 1 22 19.0 7.8 8.9 0.9 19 17.6 8.1 8.9 0.8 17 013 34.6 11.5 12.4 1.7 26 32.5 12.1 13.0 1.6 23 30.4 12.6 13.5 1.5 20 28.3 13.2 14.6 1.3 18 26.2 13.7 14.6 1.3 16 015 43.7 10.9 12.3 2.1 29 41.4 11.6 13.0 2 27 39.0 12.2 13.6 1.9 24 36.6 12.8 14.7 1.7 22 34.2 13.4 14.7 1.6 19 020 57 15.1 16.6 2.8 36 54 15.9 17.4 2.6 31 51 16.7 18.1 2.4 28 47.1 17.4 19.3 2.2 24 43.7 18 19.5 2.1 21 025 71 20.7 22.3 3.4 32 67 21.7 23.2 3.2 28 63 22.5 23.9 3 25 59 23.3 25.4 2.8 22 55 24 25.6 2.6 19 030 82 21.6 24.3 3.9 34 77 22.9 25.6 3.7 30 72 24.2 26.8 3.4 27 67 25.3 28.8 3.2 23 62 26.3 29.0 2.9 20 035 102 31.3 34.3 4.9 41 97 33.1 36.0 4.6 37 91 34.7 37.5 4.3 33 85 36.3 40.4 4.1 29 80 37.8 40.6 3.8 26 009 7 24.2 6.9 7.8 1.2 29 22.7 7.3 8.2 1.1 26 21.2 7.6 8.5 1 23 19.7 7.9 9.1 0.9 20 18.2 8.2 9.1 0.9 18 013 35.9 11.7 12.7 1.7 28 33.8 12.3 13.2 1.6 25 31.6 12.9 13.8 1.5 22 29.4 13.5 14.9 1.4 19 27.3 14 14.9 1.3 17 015 45.2 11.1 12.5 2.2 31 42.6 11.8 13.2 2 28 40.1 12.4 13.8 1.9 26 37.8 13 14.9 1.8 23 35.4 13.6 14.9 1.7 21 020 59 15.4 17.0 2.9 38 56 16.2 17.7 2.7 34 52 17 18.4 2.5 30 48.8 17.7 19.8 2.3 26 45.3 18.4 20.0 2.2 23 025 73 21.2 22.8 3.5 34 69 22.1 23.6 3.3 30 65 23 24.5 3.1 27 60 23.9 26.0 2.9 24 56 24.6 26.2 2.7 21 030 85 21.9 24.7 4.1 36 80 23.3 26.0 3.8 32 74 24.6 27.2 3.6 28 69 25.8 29.3 3.3 25 64 26.8 29.5 3.1 22 035 105 31.9 34.9 5 43 99 33.7 36.6 4.8 39 93 35.5 38.3 4.5 35 88 37.1 41.3 4.2 31 82 38.6 41.5 3.9 27 009 8 25.1 7 7.9 1.2 31 23.5 7.4 8.3 1.1 28 21.9 7.7 8.6 1.1 25 20.4 8.1 9.3 1 22 18.9 8.4 9.3 0.9 19 013 37.4 12 13.0 1.8 30 35.1 12.6 13.6 1.7 27 32.8 13.2 14.1 1.6 24 30.6 13.8 15.3 1.5 21 28.4 14.4 15.3 1.4 18 015 46.7 11.3 12.7 2.2 33 44.1 12 13.4 2.1 30 41.6 12.6 14.0 2 27 39.0 13.3 15.2 1.9 24 36.6 13.9 15.2 1.8 22 020 61 15.6 17.2 3 41 58 16.5 18.0 2.8 36 54 17.4 18.9 2.6 32 51 18.1 20.2 2.4 28 47.2 18.8 20.4 2.3 24 025 75 21.6 23.2 3.6 36 71 22.6 24.2 3.4 32 67 23.6 25.1 3.2 28 62 24.4 26.6 3 25 58 25.2 26.8 2.8 22 030 88 22.3 25.1 4.2 39 82 23.7 26.5 4 34 77 25 27.7 3.7 30 72 26.3 29.9 3.4 27 66 27.4 30.1 3.2 23 035 108 32.6 35.7 5.2 46 102 34.4 37.4 4.9 41 96 36.2 39.1 4.6 37 91 37.9 42.2 4.4 33 85 39.5 42.4 4.1 29 009 10 26.7 7.2 8.2 1.3 35 25.2 7.6 8.5 1.2 32 23.6 8 8.9 1.1 28 22.0 8.4 9.3 1.1 25 20.3 8.7 9.6 1 22 013 40.4 12.5 13.5 1.9 34 37.9 13.2 14.2 1.8 31 35.5 13.8 14.8 1.7 27 33.2 14.4 15.3 1.6 24 30.9 15 15.9 1.5 21 015 49.8 11.6 13.1 2.4 37 47.1 12.4 13.9 2.3 34 44.5 13.1 14.5 2.1 30 41.8 13.8 15.2 2 27 39.2 14.4 15.8 1.9 25 020 66 16.2 17.9 3.2 47 62 17.2 18.8 3 42 58 18.1 19.6 2.8 37 55 18.9 20.4 2.6 33 51 19.6 21.0 2.5 28 025 80 22.5 24.2 3.9 41 76 23.6 25.2 3.6 36 71 24.6 26.2 3.4 32 67 25.5 27.0 3.2 29 62 26.4 27.9 3 25 030 94 23 26.0 4.5 44 88 24.5 27.3 4.2 39 83 25.9 28.7 4 34 77 27.2 29.9 3.7 30 71 28.4 31.0 3.4 26 035 115 33.9 37.1 5.5 52 109 35.9 39.0 5.2 47 103 37.7 40.7 5 42 97 39.5 42.4 4.7 37 90 41.2 44.0 4.4 33 Legend: CAP kw - Net cooling capacity (gross cooling capacity minus the water pump heat against the internal evaporator pressure drop) COMP kw - Compressor power input UNIT kw - Effective unit power input (power input of the compressors, control circuit and fans plus the power input of the pump against the internal evaporator pressure drop) COOL l/s - Evaporator water flow kpa - Evaporator water pressure drop LWT - Leaving water temperature C - Capacity at Eurovent conditions Full load correction factors for Eurovent laboratory test: Net cooling capacity 1.000 Compressor power input 1.000 Energy efficiency ratio 1.000 Evaporator pressure drop 1.000 Application data: Refrigerant: R-22 Evaporator water entering/leaving temperature difference: 5 K Evaporator fluid: Fresh water Fouling factor: 0.44 x 10-4 (m 2 K)/W Minimum cooler flow rates 30GH Minimum flow, l/s 009 0.3 013 0.5 015 0.7 020 0.8 025 1.0 030 1.2 035 1.3 30GH Operating range Condenser entering air temperature C 50 40 30 20 10 0 45 45 30GH 009 42 43 30GH 013 40 30GH 025 36 33 12 30GH 009-025* 30GH 030-035* 01 13 Glycol Standard 30GH 30GH with low temperature option Water -10-5 0 5 10 15 Evaporator leaving water temperature C * Application down to -18 C with head pressure control option Note : t = 5 K at the evaporator 305

Sound levels 30GH 009 013 015 020 025 030 035 Sound power db(a) 83 83 87 87 87 88 88 Note: According to ISO standard 3744 and Eurovent 8/1. Technical description Air-cooled packaged liquid chillers for outdoor installation, equipped with numerical control or electromechanical control. Quality assurance Designed and manufactured in a factory, accredited to Quality Assurance Standard ISO 9001. Performances are checked by independent laboratories and are Eurovent certified. Chassis and casing Galvanized steel, with polyester-powder paint finish, bakedin electrostatically before assembly, colour light grey (RAL 7035). Compressors 30GH 009-013: Reciprocating, hermetic compressors with 2-pole electric motor cooled by suction gas. Protected by internal thermal safety switch and thermo-magnetic circuit breaker. External crankcase heater. 30GH 015-035: Semi-hermetic reciprocating Carrier compressors, lubricated by oil, using a reversible oil pump. Crankcase heater includes a protection device that stops the compressor in case of a fault. 4-pole electric motor with two windings, part-winding start, cooled by suction gas and protected against abnormal operating conditions by discharge gas thermostat, thermo-magnetic circuit beaker (breaking capacity 22 ka). The compressors are mounted on rubber anti-vibration dampers and equipped with a discharge muffler (30GH 015-035) and suction and discharge service valves. Condensers Aluminium fins mechanically bonded to seamless copper tubes, with built-in subcoolers. Metallic propeller fan (30GH 009-013) or ultra low-noise axial Carrier Flying Bird fan(s) with 15 blades and rotating shroud, made of recyclable composite material. 6-pole (30GH 009-013) or 8-pole, 3- phase motor(s) to IP55, protected by thermo-magnetic circuit breaker. Evaporator Stainless steel, brazed plate heat exchanger. Water connections threaded (MPT). Freeze-up protection down to an outside temperature of -20 C using 19 mm closed-cell polyurethane foam and trace heater. Refrigerant circuits Each circuit includes: compressor, filter drier, combined moisture indicator and sightglass, liquid line shut-off/drain valve (30GH 015-035), thermostatic expansion valve, dualsafety high pressure switch. Control box, power and control wiring Galvanized sheet steel, polyester paint finish, with hinged access doors and removable sun protection shield. Control box contains: circuit breakers and compressor and fan contactors, control circuit transformer, 3-phase power supply terminals, and separate 230 V power supply for heater circuits. Numeric PRO-DIALOG control accessible without opening the control box, offers: n PID control of leaving water temperature with return temperature compensation for control of compressors and fans. n Protection against abnormal operating conditions, compressor faults, high or low refrigerant pressure, low suction temperature, insufficient chilled water flow, evaporator freeze-up. n Communications Digital display of parameters: suction and discharge pressures and temperatures, evaporator entering/leaving water temperatures, compressor operating hours, history of recorded faults, etc. Remote location of controls: start/stop, dual setpoint, setpoint reset, demand limit control, general fault reporting. n Series RS485 port for connection to a building monitoring system. Electromechanical control Multistage thermostat controller. The evaporator entering water temperature is used as a reference. The thermostat is factory-set to control the return water temperature. Delivery All chillers are factory-tested before shipping. Standard packing: wooden skid. Order No. 13029-20, June 1996. Supersedes order No. 13029-76, December 1993 + 13023-20, August 1995. Manufacturer reserves the right to change any product specifications without notice. Manufactured by: Carrier SA, Montluel, France. Printed on Totally Chlorine Free Paper. Printed in the Netherlands. 306