GESTRA Steam Systems NRGS 11-2, NRGS Installation Instructions Level Electrode Types

Similar documents
GESTRA Steam Systems ER 50-1, ER Installation Instructions Level electrode

TRG 5-6x. GESTRA Steam Systems. Installation Instructions

GESTRA Steam Systems BK 15. Installation Instructions Steam Trap BK 15, DN 40-50

GESTRA Steam Systems LRG English. Installation Instructions Conductivity Electrode

GESTRA Steam Systems BK 37 BK 28 BK 29. Installation Instructions Steam Trap BK 37, BK 28, BK 29 BK 37 ASME, BK 28 ASME, BK 29 ASME

Level Electrode NRG NRG Original Installation Instructions English

Level Electrode NRG Original Installation Instructions English

MK 45-1 MK 45-2 MK 45 A-1 MK 45 A-2

NRG NRG NRG NRG

Conductivity Electrode LRG Original Installation Instructions English

Installation & Operating Instructions

TRG 5-53 TRG 5-54 TRG 5-55 TRG 5-57

Temperature Sensor TRG Original Installation Instructions English

MK 45 A. Stainless Steel Design. Installation Instructions Steam Trap MK 45 A

BK 46. Installation Instructions Steam Trap BK 46

GESTRA Steam Systems NRS English. Installation Instructions Level Switch NRS 1-51

SMK 22 SMK SMK SMK 22-82

GESTRA Steam Systems OR Installation Instructions Oil & Turbidity Detector OR 52-7

GESTRA Steam Systems NRS For TWO Electrodes. English. Installation Instructions Level Switch NRS 1-50

GESTRA Steam Systems DK 45. English. Installation Instructions Steam Trap DK 45

GESTRA. GESTRA Steam Systems NRS For ONE Electrode. English. Installation Instructions Level Switch NRS 1-50

GESTRA. GESTRA Steam Systems TRS English. Installation & Operating Instructions Temperature Switch TRS 5-50

BK 45 BK 45-U BK 45-LT BK 46

GESTRA. Program for Universal Connections. The Smart Solutions

Steam Trap BK 45 BK 45-U BK 45-LT BK 46

1592P01. for liquids in piping DN

1592P01. for liquids in piping DN max. DC 48 V, 1 A, 20 W

Flow switch. Operating Manual. English manual page Page 1 of 15 Fax:

LP30 High Integrity Low Level Alarm Probe Installation and Maintenance Instructions

GESTRA Steam Systems OR 52-5 OR English. Installation & Operating Instructions Oil & Turbidity Detector OR 52-5, OR 52-6

opening trap 30 mm Space required for Space required for opening trap 30 mm MK 45-1 with flanged ends (to DIN)

Installation, operating and servicing instructions

LC3000 Level Controller Installation and Maintenance Instructions

! WARNING. Before using product, read and understand instructions.

FSW300 Series Flow Switch

! WARNING. Before using product, read and understand instructions.

! WARNING. Before using product, read and understand instructions.

Mechanical seals external, single or double, to DIN EN 12756

Safety. Operating instructions Ionization pilot burners ZAI, ZMI, ZKIH DANGER. Contents WARNING CAUTION Edition 12.11

Forced draught gas burner

GEM TRAP FITTING & MAINTENANCE INSTRUCTIONS

Installation and maintenance instructions

UV Flame Supervision System

Manual Power relay SR853

Operating Manual MS220KA and MSR220KA

Water level controller and limiter

UFM-T100H US ES CA Power Alarm Test TM

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document

GESTRA Steam Systems OR English. Installation Instructions Oil & Turbidity Detector OR 52-7

1. Description INSTRUCTION FOR BLAST COOLER TYPE COOL 250. Material

Operating Instructions for Limit switch Model: NBK-R NBK-RM NBK-RT NBK-RA

Immersion heaters for ATEX/IECEx hazardous areas or in non-atex version

Model: 1100 Float-Controlled Condensate Trap, PN 25

Flame Safeguards LFE10. Building Technologies HVAC Products

Consignes d installation

Model: 1413 Model: 1418 Float-Controlled Condensate Trap, PN 100

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

USER MANUAL FOR EXPLOSION PROTECTED FLUORESCENT LIGHT FITTING type PSF 218

Model: 1200 Model: 1200-G Model: 1200-N Float-Controlled Condensate Trap, PN 40

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner

Circulation heaters for ATEX/IECEx hazardous areas or in non-atex version

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version

QRA2... QRA10... QRA53... QRA55... Flame Detectors. Siemens Building Technologies HVAC Products

S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions

ISIS SAFETY SYSTEM Installation guide

COMPACT FLAME CONTROLLER CFC 100

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

COMPASS HIGH-EFFICIENCY WET-ROTOR CIRCULATORS

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content

Electronically controlled instantaneous water heater. MCX: 27300, and models. Installation instructions

GENERAL SPECIFICATION ELECTRICAL

CalMag Filter Installation Instructions

QRA10... QRA53... QRA55...

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use!

INSTRUCTION & SERVICE MANUAL

Sensor module. Operating instructions. Sensor module, Type 17-51P2-... Document No P2-7D0001 Version: 17 May 2011/Rev. 0

GESTRA. Product Overview. The optimum components for every application

INSTRUCTION MANUAL MM-615E. Series FS1 High Sensitivity Liquid Flow Switch

1. Description INSTRUCTION FOR AIR BLAST COOLER TYPE COOL 450

SERVICE MANUAL. IPP Cooled incubator with Peltier technology HPP 108 Constant Climate Chamber with humidification

Installation manual extra-low-voltage socket outlets for panel- and surface-mounting

Thermo-Sealer. Manual Heat Sealer. User Manual

Glass and Dishwashers AMX / AUX Series

QVE1901U Flow Switch. Technical Instructions Document No September 20, Description. Features. Application.

VERTICAL COOKING PRECISIO/PRECIJET COMBI OVEN PRECISIO/ PRECIJET OVENS S.A.V. MAINTENANCE AND REPAIR

Titon CME1 Q Plus Mechanical Extract Ventilation Unit

ExDetector IRCO2. ExDetector IRHC. Operating and Installation Instructions. Gas Detection and Warning Systems

Series 47 and 247 Mechanical Water Feeders. Series 47-2 and Combination Mechanical Water Feeder/Low Water Cut-Off ! WARNING

CRU-S Series Stainless Steel Condensate Recovery Unit

Heat Exchanger Block Replacement Instructions

INSTRUCTION MANUAL. DECKMA HAMBURG GmbH. Type OMD-12. Oil-in-Water Monitor

INSTRUCTION MANUAL MM-601REVI. Series FS4-3 General Purpose Liquid Flow Switch

Supplementary Installation and Operating Instructions. Category II2G

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

CENTRIFUGAL FAN IN SCROLL CASING. Helix S-Vent OPERATION MANUAL

Leakage detection sensor

COMMERCIAL GAS AND ELECTRIC STACKED WASHER/ DRYER INSTALLATION INSTRUCTIONS

Frost Units for air temperature monitoring

Transcription:

GESTRA Steam Systems NRGS 11-2 NRGS 16-2 Installation Instructions 810366-01 Level Electrode Types NRGS 11-2, NRGS 16-2

Contents Important Notes Page Usage for the intended purpose...4 Safety note...4 Danger...4 Attention...4 ATEX ( Atmosphère Explosible)...4 Explanatory Notes Scope of supply...4 System description...5 Function...5 Design...5 Technical Data NRGS 11-2, NRGS 16-2... 5, 6 Corrosion resistance...7 Sizing...7 Name/marking...7 Dimensions...8 Design NRGS 11-2, NRGS 16-2...9 Key...11 Functional Elements NRGS 11-2, NRGS 16-2...10 Key...11 Installation NRGS 11-2, NRGS 16-2...12 Table 1...12 Attention...12 Note...12 Tools...12 Example of installation...13 Key...14 2

Contents continued Wiring Page NRGS 11-2, NRGS 16-2...15 Wiring diagram...15 Attention...15 Tools...15 Basic Settings Factiory settings...16 Switch selection fo measuring range...16 Attention...16 Tools...16 Commissioning Warning...17 Wiring check...17 Application of mains voltage...17 Check assignment of switching functions...17 Check low-level alarm...17 Operation Resetting low-level alarm...17 Troubleshooting Fault finding list...18 Annex Declaration of conformity...19 3

Important Notes Usage for the intended purpose Use level electrodes NRGS 11-2 and NRGS 16-2 only for indicating liquid levels. Safety note The equipment must only be installed and commissioned by qualified and competent staff. Retrofitting and maintenance work must only be performed by qualified staff who through adequate training have achieved a recognised level of competence. Danger When loosening the electrode steam or hot water might escape. This presents the danger of severe scalds to the whole body. It is essential not to mount or dismantle the electrode unless the boiler pressure is verified to be 0 bar. The electrode becomes hot during operation. Touching the hot equipment presents the risk of severe burns to hands and arms. All installation and maintenance work must only be performed when the equipment is cold. The terminal strip of the NRGS 11-2, NRGS 16-2 is live during operation. This presents the danger of electric shock. Cut off power supply before fixing or removing the housing cover. Attention The name plate specifies the technical features of the equipment. Note that any piece of equipment without its specific name plate must neither be commissioned nor operated. ATEX ( Atmosphère Explosible) According to the European Directive 94/9/EC the equipment must not be used in potentially explosive areas. Explanatory Notes Scope of supply NRGS 11-2 1 Compact system type NRGS 11-2 1 Joint ring (of stainless steel 1.4301) D 33 x 39 to DIN 7603 1 Installation manual NRGS 16-2 1 Compact system type NRGS 16-2 1 Joint ring (of stainless steel 1.4301) D 33 x 39 to DIN 7603 1 Installation manual 4

Explanatory Notes continued System description The compact system NRGS 11-2, NRGS 16-2 works according to the conductivity measurement principle. With the NRGS 11-2, NRGS 16-2 a maximum of 3 levels can be signalled in conductive liquids: Low level alarm, pump ON, pump OFF with a normally open contact The NRGS 11-2 / NRGS 16-2 has its level switch integrated in the electrode case for the control of all functions. An external switching device is not required. The NRGS 11-2 / NRGS 16-2 has two electrode tips for the detection of low water level. The signalling of the low-level alarm is effected via two separate switching channels. Function The conductivity of the liquid is used to signal the liquid level. Some liquids are conductive, which means that they allow an electric current to flow through them. For the safe functioning of this device a minimum conductivity of the liquid to be measured is required. The conductivity measurement method can detect two conditions: electrode tip submerged or exposed, meaning switchpoint reached or not reached. Before installation, the length of the electrode tip must be cut to the required switching levels, e. g. for max./min. alarm, controlling of a valve or pump. Designs NRGS 11-2: Screwed design 1" BSP, EN ISO 228-1, PN 6. NRGS 16-2: Screwed design 1" BSP, EN ISO 228-1, PN 40. Fig. 1 Technical Data NRGS 11-2, NRGS 16-2 Type approval n TÜV WR/WB 02-392 Max. service pressure NRGS 11-2: 6 bar g at 159 C, NRGS 16-2: 32 bar g at 238 C Connections Screwed 1", EN ISO 228-1 Materials Terminal box Die cast aluminium 3.2161 G AlSi8Cu3 Stem S.S. 1.4571 CrNiMoTi17-12-2 Housing.4571 Flange Forget steel 1.0460 C22.8 Measuring electrodes S.S. 1.4571 CrNiMoTi17-12-2 Electrode insulation PTFE Spacer disc PTFE 5

Technical Data continued NRGS 11-2, NRGS 16-2 continued Lengths supplied 500 mm 1000 mm 1500 mm Mains supply 230 V +/ 10 %, 50/60 Hz 115 V +/ 10 %, 50/60 Hz 24 V +/ 10 %, 50/60 Hz (option) Power consumption 5 VA Fuse Thermal fuse T max = 102 C Sensitivity Range 1: 10 µs/cm Range 2: 0.5 µs/cm Electrode voltage 10 V ss Output 4 volt-free relay contacts for low level alarm, 1 normally open contact (e.g. for pump). Max. contact rating with a switching voltage of 24 V, 115 V and 230 V a. c.: resistive 4 A, inductive 0.75 A at cos ϕ 0.5. Max contact rating with a switching voltage of 24 V d. c.: 4 A. Contact material: silver, hard-gold plated. Indicators and adjustors 2 red LEDs for signalling Low water, 1 green LED for signalling Pump ON, 1 four-pole code switch for changing sensitivity, 1 button TEST for checking low-level alarm 1 button RESET for resetting the low-level alarm Cable entry Cable gland with integral cable clamp M 16 (PG 9) M 20 (PG 16) Protection IP 65 to DIN 40050 Max. admissible ambient temperature 70 C Weight approx. 0.8 kg 6

Technical Data continued Corrosion resistance Provided that the equipment is used for its intended purpose, its safety is not impaired by corrosion. Sizing The body must not be subjected to sharp increases in pressure. Welds and flanges of the electrode are designed to withstand dynamic loading (bending and alternating stress). The dimensional allowances for corrosion reflect the latest state of technology. Name plate / marking Vor Öffnen des Deckels Gerät freischalten! Betriebsanleitung beachten! NRGS 11-2 NRGS 16-2 G 1 1.4571 Pmax Tmax 24 V Before removing cover isolate from power supplies See installation instructions! Avant d'ouvrir le couvercle dèconnecter complètement l'appareil! Voir instructions de montage! 115/230 V 50 / 60 Hz 5VA 0,5 / 10 µs/cm TÜV. WR/WB. 02-392 TEST 6 bar ( 87psi) 159 C (318 F) PN 6 PN 40 32 bar (464psi) 238 C (453 F) Tmax 70 C IP 65 (133 F) 250 V ~ T 2,5 A GB Reg. Design 2 053 113 US Pat. 5 719 342, Design 383 403 GESTRA AG D-28215 Bremen ENTRIEGELN RESET DESENCLENCHER Fig. 1 7

Technical Data continued Dimensions 173 337.5 140 42 1", EN ISO 228-1 500, 1000, 1500 Fig. 1 8

Design NRGS 11-2, NRGS 16-2 D B A C 40 50 14 65-70 1", DIN 228 N 8 N 10 0.5 Fig. 2 Fig. 3 9

Functional Elements NRGS 11-2, NRGS 16-2 GESTRA Steam Systems GESTRA NRGS 16-2 E F G 5 6 1 2 3 4 Fig. 4 ON O 1 2 3 4 N M L N 1 2 3 4 5 6 7 8 9 10 11 13 14 12 H K J I Fig. 5 6 5 6 10

Design / Functional Elements continued Key 1 LED Low-level alarm 2 LED Low-level alarm 3 LED Pump ON 4 Code switch Measuring range 5 Button TEST 6 Button RESET A Thermal insulation, provided on site, = 20 mm (outside of thermal insulation of steam boiler) B Seating surface C Joint ring (of stainless steel 1.4301) D 33 x 39 to DIN ISO 7603 D Electrode thread 1", EN ISO 228-1 E Housing screws M4 F Cable entry PG 9 / PG 11 G Housing cover H Fixing screws for cover plate I Separating segment J Terminal strip K PE connection L Terminal strip Test M Thermal fuse T max 102 C N Plug O Cover plate 11

Installation NRGS 11-2, NRGS 16-2 1. Determine required measuring lengths of electrode tips and enter data in table 1, Fig. 2. 2. Cut electrode tips 1, 2, 3 and 4 accordingly. The electrode tips 1 and 2 (low level limiter) must have the same length. 3. Deburr faces of electrode tips. 4. Strip off 50 mm of PTFE insulation from the ends of electrode tips. 5. Check seating surfaces of threads or flange provided on vessel or boiler standpipe. Fig. 3 6. Place joint ring C onto seating surface B of electrode Fig. 2. Use only joint ring (of stainless steel 1.4301) D 33 x 39 to DIN 7603 supplied with electrode. 7. Apply a light smear of silicone grease (e. g. DOW Corning 111 Compound) to electrode thread D. 8. Screw level electrode into threads or flange provided on vessel or boiler standpipe and tighten with a 41 mm open-end spanner. The torque required is 140 Nm when cold. Table 1 Function Function Electrode tip Length [mm] Low-level alarm 1 Low-level alarm 2 e. g. Pump ON 3 e. g. Pump OFF 4 Enter data here! Attention The seating surfaces of the threads or flange provided on the vessel or boiler standpipe must be accurately machined. Fig. 3 Do not bend electrode tip when mounting. Do not lag electrode body. Note For the approval of the boiler standpipe with connecting flange the relevant local and national regulations must be considered. See four examples of installation on page 13. Tools Open-end spanner 41 mm A. F. Hacksaw Bolt cutter Flat file, medium cut 12

Installation continued Examples of installation DN 50 1" BSP 1 2 DN 50 1" BSP 1 2 4 8 90 10 20 20 Fig. 6 Fig. 7 20 3 5 6 0! 1500 4 8 90 20 10 20 20 3 5 6 0! ¾" BSP 1" BSP 1 2 DN 20 1" BSP 20 1 2 4 9 3 20 20 90 20 DN 100 24.5 24.5 4 3000 10 5 7 8 0 " ME DN 20 20 5 0 Fig. 8 Fig. 9 DN 20 13

Installation continued Key 1 Flange PN 40, DN 50 (2"), DIN 2527 Flange PN 40, DN 100 (4"), DIN 2527 2 For the approval of the boiler standpipe with connecting flange the relevant regulations must be considered. 3 Vent hole 4 High water (HW) 5 Electrode tip = 5 mm 6 Protection tube DN 80 7 Protection tube DN 100 8 Electrode distance 14 mm 9 Electrode distance 40 mm 0 Low water (LW)! Reducer K-88.9 x 3.2 42.4 x 2.6 W to DIN 2616, part 2 " Reducer K-114.3 x 3.6 48.3 x 2.9 W to DIN 2616, part 2 14

Wiring NRGS 11-2, NRGS 16-2 Use multi-core flexible control cable with min. conductor size 1.5 mm² for wiring. 1. Unscrew screws E, remove housing cover G Fig. 4 2. Unscrew union nuts of cable entry F. The electrode terminal can be turned through +/- 180. 3. Loosen plug N with 17 mm open-end spanner but do not remove. Fig. 5 4. Turn electrode terminal into desired direction (+/- 180 ). 5. Tighten plug N slightly. 6. Remove terminal strip J from board. 7. Connect terminal strip according to wiring diagram, connect PE connection K. 8. Plug in terminal strips J. 9. Install cable entry F. 10. Replace housing cover G, fasten screws E and install cable entry. Wiring diagram Alarm 1 2 3 4 NRGS 11-2 NRGS 16-2 ON 115 V 230 V 24 V MIN 1 2 3/4 ON 1 2 3 4 10 µs/cm 0.5 µs/cm 24V Fig. 10 PE 1 2 3 4 5 6 7 8 9 10 11 13 14 12 N L Mains TEST RESET Relays are shown in the power-off position (alarm condition) Attention Fuse supply cables with T 2.5 A. Tools Screwdriver for cross head ( Phillips ) screws, size 1 Screwdriver for slotted screws, size 2.5; completely insulated according to VDE 0680 Open-end spanner 17 mm A. F. 15

Basic Settings Factory setting The compact system is delivered with the following default factory settings: Measuring range 10 µs/cm 2 Switch selection of measuring range The measuring range can be switch selected between 0.5 µs/cm und 10 µs/cm by means of the code switch 4: 1. Unscrew screws E at the electrode terminal, remove cover G, Fig. 4, Fig. 5 2. Undo screws H and remove cover plate O. Code switch 1 4 OFF Measuring range 0.5 µs/cm. Code switch 1 4 ON Measuring range 10 µs/cm. 3. Put cover plate O in place and use screws H to fix it. 4. Replace cover G and fasten screws E. Attention Do not damage the electronic components when setting the code switch. Tools Screwdriver for cross head ( Phillips ) screws, size 1 Screwdriver for slotted screws, size 2.5; completely insulated according to VDE 0680 16

Commissioning Wiring check Warning The terminal strip of the NRGS 11-2, NRGS 16-2 is live during operation. This presents the danger of electric shock. Cut off power supply before removing or replacing housing cover. 1. Check whether the system NRGS 11-2, NRGS 16-2 has been wired according to wiring diagram Fig. 10. 2. Check whether mains supply corresponds to the wiring of the equipment. Application of mains voltage 1. Switch on mains supply and check the correct functioning of the equipment at the corresponding switchpoints. LEDs 1, 2, 3 are provided for visual check of switchpoints. Fig. 5 Remove housing cover G to check LEDs 1, 2, 3. See Fig. 4 and 5 Check assignment of switching functions 1. Check the switching function Low level alarm of the electrode tips 1 and 2. For this test the level in the vessel must fall below the low level mark. The low-level alarm must then be activated by the level switch. 2. Check the switching functions Pump ON and Pump OFF. See table 1. Check low-level alarm The function of the low-level alarm can be simulated by pushing the button TEST 5. Fig. 5 The low-level alarm must then be activated. Operation Resetting low-level alarm You can reset an activated low-level alarm by pushing the RESET button 6. Fig. 5 17

Troubleshooting Fault finding list Level has exceeded switchpoint High Water no function Fault: Mains voltage has not been applied. Remedy: Apply mains voltage. Wire equipment according to the wiring diagram. Fault: The thermal fuse has been triggered. Remedy: In case of defective thermal fuse the mains voltage has not been connected to terminal L: Replace defective thermal fuse (Order No. 051629) The ambient temperature must not exceed 70 C. Fault: The electric conductivity is too low. Remedy: Set code switch 4 to 0.5 µs/cm. Fault: The electrode housing does not have earth connection to the boiler. Remedy: Clean seating surfaces and insert metal joint ring (of stainless steel 1.4301) 33 x 39 to DIN 7603. Do not insulate compact system with hemp or PTFE tape! Fault: Electronic board is defective. Remedy: Replace board, Order No. 391556 (115/230 V a.c.), 391636 (24 V a.c.). Level has fallen below switchpoint Low Water no function Fault: The electrode tips have earth contact. Remedy: Change installation position. Fault: The vent hole in the protection tube does not exist, is obstructed or flooded. Remedy: Check protection tube and, if necessary, provide vent hole. Fault: The isolating valves of the external measuring pot (optional extra) are closed. Remedy: Open isolating valves. Switchpoint has been reached incorrect function Fault: The switching function has not been correctly allocated. Electrode tips have been cut to the wrong size. Remedy: Identify electrode supply wire and reconnect accordingly. If faults occour that are not listed above, please contact our subsidiary or agency in your country. 18

Annex Declaration of conformity We hereby declare that the equipment NRGS 11-2 and NRGS 16-2 conform to the following Euopean guidelines: LV guideline 73/23/eec version 93/68/eec EMC guideline 89/336/eec version 93/68/eec LV standard EN 50178 EMC standard EN 50 081-2, EN 50 082-2 This declaration is no longer valid if modifications are made to the equipment without consultation with us. Bremen, 3 rd January 2005 GESTRA AG Dipl. Ing. Uwe Bledschun Head of the Design Dept. Dipl. Ing. Lars Bohl Quality Assurance Representative 19

GESTRA Agencies all over the world: www.gestra.de España GESTRA ESPAÑOLA S.A. Luis Cabrera, 86-88 E-28002 Madrid Tel. 00 34 91 / 5 15 20 32 Fax 00 34 91 / 4 13 67 47; 5 15 20 36 E-mail: aromero@flowserve.com Polska GESTRA Polonia Spolka z.o.o. Ul. Schuberta 104 PL - 80-172 Gdansk Tel. 00 48 58 / 3 06 10-02 od 10 Fax 00 48 58 / 3 06 33 00 E-mail: gestra@gestra.pl Great Britain Flowserve Flow Control (UK) Ltd. Burrel Road, Haywards Heath West Sussex RH 16 1TL Tel. 00 44 14 44 / 31 44 00 Fax 00 44 14 44 / 31 45 57 E-mail: gestraukinfo@flowserve.com Portugal Flowserve Portuguesa, Lda. Av. Dr. Antunes Guimarães, 1159 Porto 4100-082 Tel. 0 03 51 22 / 6 19 87 70 Fax 0 03 51 22 / 6 10 75 75 E-mail: jtavares@flowserve.com Italia Flowserve S.p.A. Flow Control Division Via Prealpi, 30 l-20032 Cormano (MI) Tel. 00 39 02 / 66 32 51 Fax 00 39 02 / 66 32 55 60 E-mail: infoitaly@flowserve.com USA Flowserve GESTRA U.S. 2341 Ampere Drive Louisville, KY 40299 Tel.: 00 15 02 / 502 267 2205 Fax: 00 15 02 / 502 266 5397 E-mail: dgoodwin@flowserve.com GESTRA AG P. O. Box 10 54 60, D-28054 Bremen Münchener Str. 77, D-28215 Bremen Telephone +49 (0) 421 35 03-0 Fax +49 (0) 421 35 03-393 E-Mail gestra.ag@flowserve.com Internet www.gestra.de 810366-01/406cm 2004 GESTRA AG Bremen Printed in Germany 20