Heating controller Lago Product brochure GB 10 Edition 02.08 Wall-mounted (Lago Basic 0101/1001 and Lago 0321) Boiler or control panel attachment (Lago 0201R) Simple operation and programming Automatic sensor recognition LCD display to show temperatures, operating conditions and parameters For weather- and room temperature-dependent control, or fixed value control of the flow temperature Demand-related pump control CAN bus for system extension and system integration Various room control module connection facilities Choice of sensor 1 kω PTC or 5 kω NTC
2 Lago Edition 02.08 Boiler controller with direct heating circuit and hot-water function Lago Basic 0101/1001 Boiler module / Mixer module Basic function Control of a fixed flow temperature or a fixed return temperature by controlling a heat generator or mixer. A room thermostat or timer (24 V) can be connected. Hot-water function via sensor or thermostat. Weather- and room temperature-dependent flow temperature control by controlling a heat generator or mixer (time-dependent control available with add-on module). Heating module in a cascade. Performance features Safety temperature limiter test Cooling operating mode (1001 in conjunction with mixer operation) Start-up relief Frost protection function Charging pump relief Circulation pump control (not with fixed value control) Pump blocking protection Mixer blocking protection Delayed pump switch-off Choice of sensor (5 kω NTC <-> 1 kω PTC) The Lago Basic is a basic module, which is suitable for the most diverse applications and is expansible for a more specific application. This controller is suitable for wall mounting. The electrical connection of the controller and the control components is possible via screw terminal blocks in the base. The controller features a demand-related pump circuit for every heating circuit. When connected to an outdoor sensor, the controller calculates a boiler or flow temperature based on the outside temperature, which can then be supplemented by a room control module with time control (see accessories). Control of a fixed flow temperature or a fixed return temperature by controlling a heat generator or mixer is achievable with the Lago Basic. The Lago Basic can also act as part of a cascade control. Here it is feasible to use it as a boiler or heating circuit controller. Display mode In the normal mode Run, the flow temperature of the heat generator or heating circuit is displayed. The following temperatures are given: 1. Outside temperature 2. Hot-water temperature 3. Room temperature Information about outputs Burner ON / Mixer OPENS Feed pump ON / Mixer CLOSES Heat generator pump ON / Heating circuit pump ON Bus communication OK
Lago Edition 02.08 3 Boiler controller in cascade mode Boiler controller with header pump / mixer extension
4 Lago Edition 02.08 Lago 0321 Basic function The unit includes the control for a one-stage heat generator, a process water generator and for a maximum of two heating circuits (one with mixer). Saving functions (demand-related circulation pump control) are also integrated. Alternatively, the pump relay of the direct heating circuit can also be used for the following functions: Circulation pump Return temperature increase Header pump If no heat generator sensor is connected, the unit can be used as a mixer extension. When a heat generator sensor is connected and an address is set (bus ID), the heat generator can be used in a cascade. It is then activated by a system controller. Performance features Safety temperature limiter test Auxiliary relay Choice of sensor (5 kω NTC <-> 1 kω PTC) Choice of controller operating mode Heating program [F1, F2] Heating curve Room sensor influence Outside temperature frost protection Maximum heat generator temperature Minimum heat generator temperature Start-up relief Minimum limit Charging pump relief Parallel pump operation Anti-legionnaire s disease function Maximum flow temperature Minimum flow temperature Mixer dynamic OPEN / CLOSE Multi-functional relay Relay test Display mode In the normal mode Run, the flow temperature of the heat generator or heating circuit is displayed. The following temperatures are given: 1. Outside temperature 2. Hot-water temperature 3. Room temperature Information about outputs Burner ON / Mixer OPENS Feed pump ON / Mixer CLOSES Heat generator pump ON / Heating circuit pump ON Bus communication OK
Lago Edition 02.08 5 Boiler controller with a direct and a mixed heating circuit, and hot-water function Boiler controller with mixed heating circuit, hot-water function and return temperature increase Boiler controller with circulation pump, mixed heating circuit and hot-water function
6 Lago Edition 02.08 Lago 0201R Heating module Basic function Heating module in a cascade with up to 8 heat generators Control of return temperature increase by pump or by mixer (depending on the configuration) Boiler or control panel attachment Rast 5 connection system Operation in a cascade A one-stage heat generator with appropriate boiler pump and return temperature increase via a pump or a mixer A two-stage heat generator with appropriate boiler pump and return temperature increase via a pump or a mixer Two one-stage heat generators with appropriate boiler pump and common return temperature increase via a pump A modulating heat generator with appropriate boiler pump Performance features Safety temperature limiter test Frost protection function (flow sensor frost protection, outdoor sensor frost protection) Temperature monitor function Return temperature increase via pump Return temperature increase via mixer Pump blocking protection Mixer blocking protection Delayed pump switch-off Choice of sensor (5 kω NTC <-> 1 kω PTC)
Lago Edition 02.08 7 Legend A Heat generator with temperature sensor KF and connecting input T1, T2 B Heat generator pump (in the flow circuit if required) C Return sensor VF D Return temperature increase via mixer E Return temperature increase via pump Heat generator controller in cascade mode
8 Lago Edition 02.08 Technical data Supply voltage pursuant to DIN IEC 60038: 230 V AC ± 10% Power consumption: max. 5 VA Switching capacity of the relays: 250 V, 2(2) A Max. current on terminal L1: 6.3 A Enclosure pursuant to DIN EN 60529: IP 40 Safety class pursuant to DIN EN 60730: II, totally insulated Power reserve of the timer: >10 hours Permitted ambient temperature in operation: 0 50 C Storage temperature: -20 60 C Sensor resistance: NTC 5 kω (AF, KF/SPF, VF) Tolerance in Ohm: +/- 1% at 25 C Temperature tolerance: +/- 0.2K at 25 C Sensor resistance: PTC 1010 Ω, (AFS, KFS/ SPFS, VFAS) Tolerance in Ohm: +/- 1% at 25 C Temperature tolerance: +/- 0.3K at 25 C Dimensions (HxWxD): Wall-mounted base for Lago Basic 0101/1001 and Lago 0321: 96x144x67 mm Installation dimensions for Lago 0201R: 96x144x63 mm Accessories A room thermostat or timer (24 V) can be connected. If a room thermostat is connected, the flow temperature can be controlled dependent on the outside temperature, room temperature or time by controlling a heat generator or mixer. Merlin BM Digital operation-control module with CAN bus interface BM8 Digital operation-control module with CAN bus interface Lago FB Digital remote control with CAN bus interface FBR 1 / 2 Remote control with room sensor Lago FB switch Room thermostat (0 24 V switching voltage) Lago FB analogue switch Room thermostat (0 24 V switching voltage) Detailed information on this product Contact www.kromschroeder.com Sales Elster GmbH Postfach 2809 49018 Osnabrück Strotheweg 1 49504 Lotte (Büren) Germany T +49 541 1214-0 F +49 541 1214-370 info@kromschroeder.com www.kromschroeder.com http://docuthek.kromschroeder.com/doclib/main.php?language=1&folderid=311098&by_class=6 We reserve the right to make technical modifications in the interests of progress. Copyright 2013 Elster GmbH All rights reserved.