Weishaupt dual fuel burners Sizes 30 to 70 Version 1LN (NO X -reduction on gas operation) 1/2003 CA

Similar documents
product Industrial burners Industrial burners sizes 30 to 70 flexible and reliable Information on oil, gas and dual fuel burners

Weishaupt WG10 and WG20 gas burners LN (Low NO x ) version 2/2002 CA

product WM 30 oil, gas and dual fuel version Weishaupt monarch WM30 burners highly efficient and versatile

product WM 20 oil, gas and dual fuel version Weishaupt monarch WM20 burners compact and powerful Information on oil, gas and dual fuel burners

LOW NOx MODULATING GAS BURNERS

RS /E-EV C01 SERIES

RS /E-EV C01 SERIES

RIELLO 40 GS/M SERIES

RL/1 SERIES. One Stage Light Oil Burners FIRING RATES LIGHT OIL RL 34/1 MZ kw

Power Flame Incorporated

Product Information. Model: HG, HL, HLG Burner Sizes: 10, 13, 15, 17, 20, 21, 25 GENERAL DESCRIPTION U.L. STANDARD EQUIPMENT

product Ultra Low NO x emissions WM-G10 ZM-PLN and WM-G20 ZM-PLN monarch burners (290 10,240 MBH) Information on Ultra Low NO x gas burners

R-Series Oil Burners. Riello Burners a world of experience in every burner we sell. Reliable Combustion Solutions

Bryan Flexible Water Tube. Ultra-High Efficiency Condensing Hot Water Boilers. 3,000,000 BTUH Natural Gas Fired

TWO STAGE HEAVY OIL BURNERS

Light oil burners. One stage operation

Distributed By: M&M Control Service, Inc Building Technologies

CODE MODEL TYPE PRESS 60 N 616 T PRESS 60 N 616 T80

Cclearfire HIGH EFFICIENCY, COMPACT CONDENSING BOILER 500-3,300 MBTU

BUDERUS. Superior Equipment by Design. Comfortable. Efficient. Intelligent Heating. BUDERUS. G Cast Iron Commercial Boilers

EOLO MODULATING AND CONDENSING SUSPENDED GAS AIR HEATER HEATING COOLING GREEN ENERGY AIR HEATING TECHNOLOGY AND INNOVATION

Light oil - kerosene burner

Rental Boiler Specifications (Nebraska Boiler)

Engineering Bulletin. Gas Heat. for M-Series and T-Series Climate Changer Air Handlers CLCH-PRB010-EN. March 2004

CCLEARFIRE CONDENSING FIRETUBE BOILER DESIGNED FOR MAXIMUM HYDRONIC SYSTEM EFFICIENCY 500 TO 3,300 MBTU

HCLEARFIRE. High-efficiency, modular steam boiler HP

Light oil / kerosene burner

PROFIRE -E SERIES BURNERS

96% COMMERCIAL INDUSTRIAL HEATER. Condensing Gas Water Heating System. Thermal Efficiency

Bosch Uni 7000F Cast Iron Hot Water Boiler

Oil burners Brûleurs fioul Stookoliebranders

Complete Boiler Management in a Compact, Affordable System

Power Flame Incorporated

VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power

MODEL M5M. High-Efficiency Packaged Watertube Boiler MMBTU

Up to 94.6% Thermal Efficiency HIGH EFFICIENCY COMMERCIAL CONDENSING BOILERS OPERATING CONTROL FEATURING A BUILT-IN CASCADING SEQUENCER

VCLEARFIRE. High-Efficiency, Commercial Steam Boiler Horsepower

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

FXLF-9. High Efficiency Water Heaters and Boilers

Typical Specifications For: ADVANTUS TM DOMESTIC HOT WATER SUPPLY Models AV(W)0500 AV(W)4000

Control Products & Systems OEM

Power Flame Incorporated

Typical Specifications For: ADVANTUS TM DOMESTIC HOT WATER SUPPLY Models AV(W)0500 AV(W)4000

WALL HUNG GAS BOILER FOR C.H. AND PREDISPOSTION FOR INSTANTANEOUS D.H.W. PRODUCTION (with optional kit) MODELS 34,8 kw (depotenziata) 50 C

TS Series. Technical Instructions. Document No. TS-4000 June 25, TS-CE Combustion Enclosures with LMV5. Description

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Cleaver-Brooks Webinars

RIELLO ARRAY. High Efficiency Condensing Boiler MBH.

Instructions for High Altitude Installations Above 4500 FT.

LFL Series Burner Flame Safeguard Control

V-Line. Nozzle-mix line burner

Domestic Hot Water Heaters and Boilers FTIIIC-6

FTIIIC-10. Domestic Hot Water Heaters and Boilers

THE CORPORATION OF THE CITY OF LONDON. POTTERSBURG POLLUTION CONTROL PLANT FILTER BUILDING ODOUR CONTROL Tender No ADDENDUM NO.

RTC. Stainless Steel Condensing Floor Standing Boilers Technical data sheet. High efficiency commercial heating

Forced draught gas burner

Superior. A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler. Outputs 120, 160, 200, 240, 280 kw

Indirect gas-fired air heater

INSTRUCTION MANUAL FOR OIL BURNER MODELS

DOM-5. Domestic Hot Water Heaters & Boilers

Complete burner management in a compact, affordable system

MULTIPLEX SELF RECUPERATIVE gas burner

CONDENSING, MODULATING, HOT WATER SUPPLY, POOL, AND HYDRONIC HEATING BOILERS

Steam Fundamentals. (in heating & processing applications)

LOW NOx, HIGH EFFICIENCY, HOT WATER SUPPLY AND HYDRONIC HEATING BOILERS

CAMUS. two-pass counter flow fire tube commercial boilers. for hydronic heating and hot water supply TURNDOWN RATIO! HYDRONICS LTD. Rev.

MONOBLOCK NG SERIES GAS BURNERS INSTALLATION, OPERATING AND MAINTENANCE MANUAL

Specifications of V-Line burners

Savile Plus. Steam Boiler. Suitable for Pressure Jet burners Oil, gas or dual fuel firing. Outputs kg/h

1 VICTRIX ZEUS Superior kw I features

G215 G315 Cast Iron Residential Boilers

SCC Inc. TS Series. Technical Instructions. Document No. TS 5000 February 12, TS CE Combustion Enclosures with LMV3.

CONDENSING HIGH EFFICIENCY BOILERS

Submittal Data GA Line AYF Series Commercial and Specialty Chiller-Heaters 2 or 4 pipe Gas Fired Absorption Chiller-Heater Cooling and Heating

XTHERM, TYPE WH - MODELS 1005A- 2005A DIVISION COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS

Stainless steel range of condensing boilers. Designed to meet carbon reduction targets. Lifetime service and support. Outputs from 50kW to 660kW

INSTRUCTION MANUAL FOR OIL BURNER MODELS

CI/SfB X. EnviroPak Series GAS FIRED HEATING, VENTILATION AND COOLING UNITS

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

Heating system service plans that provide total peace of mind.

Take Charge of Your Commercial Water Heating with the New Commander Series from Bradford White Bradford White s Commander Series The Commander Series

info The Weishaupt programme Burners Heating systems Solar technology Heat pumps Information on Weishaupt products

Metropolitan. Steam Boiler. Suitable for Pressure Jet or Rotary Cup burners Oil, gas or dual fuel firing. Outputs kg/h

About Carlin. Visit our website, or call us at to learn more about this authentic Made-in-America company.

Model 601CRD Oil Burner

FLX FLEXTUBE. The Widest Range of Hydronic and Steam Watertube Boiler Systems 1,500 to 25,000 MBTU/HR (35-600HP)

Proudly assembled in U.S.A

Proudly assembled in U.S.A

SLP98UHV WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

New Features RIELLO ARRAY. v2.0. High Efficiency Condensing Boiler MBH.

INSTRUCTION MANUAL FOR OIL BURNER MODELS

OPERATING AND MAINTENANCE MANUAL

Parts Available from

199,000 to 4,000,000 Btu/h 150 to 4500 Gallons Storage

Suggested Specifications Prestige Excellence 110

mith Mills 4500A Smith Mills 4500A 4500A-3R OIL, GAS OR COMBINATION GAS/OIL COMMERCIAL BOILER/BURNER CAST IRON

96% AFUE Efficiency CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR

DESCRIPTION, CAPACITIES, SPECIFICATIONS, APPLICATIONS

Each burner shall be equipped with a Micro-Processor Based Burner Management Flame Safeguard and Parallel Positioning Control System.

mith Mills Smith Mills 6500A 6500A-4 OIL OR GAS CAST IRON BOILER/BURNER CAST IRON

Transcription:

Weishaupt dual fuel burners Sizes 30 to 70 Version 1LN (NO X -reduction on gas operation) 1/2003 CA

Description Weishaupt burners of sizes 30 to 70 were specially designed and developed for industrial applications. The Monoblock-Burners are characterized with multiple excellent features such as: Big firing range and wide area of applications Stable air fan performance excellent combustion characteristics Burner casing can be swung opened Easy to install, setup and maintenance Air damper closed off during burner stop Oil pump and electric oil heater is standard for heavy oil burners Typical gas side Low NO x flame pattern Control Control of air and fuel is performed according to the fuel type, burner size and requirement: Two and three stage The oil part of the dual fuel burner has a nozzle head with two or three nozzles. The capacity regulation is achieved by opening or closing the oil solenoid valves 2 and 3 with corresponding changes in air amount. Sliding two stage On sliding two stage regulation, the low fire and high fire points are assigned within the control range. The burner slides depending on heat re quirement between both operating points. There is no sudden increase or decrease of supplied fuel amount. Modulating Modulating burners operate according to the heat requirement at any operating point within the control range. Reduced starting capacity The burner starts at ignition position via separated pilot line. This way only a small amount of gas flows into the combustion chamber. After a certain delay time the burner operates in low fire. Controlled shutdown from low fire Controlled shutdown of the burner is performed only at low fire. Sudden pressure surge in the gas supply line can be avoided. Gas train As standard, Weishaupt gas and dual fuel burners are always equipped with two main gas valves. Gas train can be built according to most applicable North American codes and standards. Digital combustion manager W-FM100 and W-FM200 combustion manager control all essential burner functions, e.g. fuel and air supply and monitor the flame with digital precision. The target is optimization of operating conditions, maximization of economical aspect and minimizing the emissions. Thanks to the digital combustion technology, such optimization is available today at reasonable cost. Expenses for installation and maintenance are even clearly lower than with conventional technologies. For example, a separate remote panel is no longer required for burner control. Furthermore, remote operation, remote diagnostic and remote monitoring of the appliances are now realizable. This increases the safety and comfort for operator. Applications The burners can be used with heat exchanger such as heating boiler, steam boiler, air heater and for certain process applications. Due to the fact that the burner is capable of overcoming high combustion chamber pressure, they are most compatible with modern high performance boilers. Fuels Oil section (#2 oil), viscosity 6mm 2 /s at 68F (20 C) Gas section Natural gas Propane (LPG) Installation location The burners are designed for indoor operation with temperature of 5F ( 15 C) up to 100F (+40 C) and relative humidity of max. 80% Certification The burners are in compliance with most applicable European and North American standards Excellent service Weishaupt has a high density sales and service network all over the world. The customer service is available every day around the clock. Optimum in house training conditions ensure high quality of service personnel. 2

Variants Digital combustion manager (W-FM 100) Electronic ratio controller (RVW) with O 2 trim Mechanical linkage Digital combustion manager (W-FM 100) with modulating controller Electronic ratio controller (RVW) with speed control Digital combustion manager (W-FM 100) with modulating controller and speed control Digital combustion manager (W-FM 200) with modulating controller O2 trim and speed control Capacity regulation Electronic ratio controller (RVW) with O 2 trim and speed control Standard Special version Two stage (ZM) Oil side HF G Sliding two stage (ZM) GHF LF K LF K IP Z ON Ein Aus OFF ON Ein OFF Aus Three stage (TM) Oil side GHF Modulating (ZM) GHF ZW INT LF T ON Ein OFF Aus HF = High Fire INT = Intermediate load LF = Low Fire IP = Ignition Position KLF ZIP ON Ein OFF Aus Burner designation RGL 40/1 B, Vers. ZM-1LN Size Fuel: Light Oil Fuel: Gas Regulating burner Index for mixing head Code for capacity range LowNO x ZM = Gas/Oil: Sliding two stage or modulating GL 40/1 B, Vers. TM-1LN LowNO x ZM =Gas: Sliding two stage or modulating Oil: Two stage TM = Gas: Sliding two stage or modulating Oil: Three stage Index for mixing head Code for capacity range Size Fuel: Light Oil Fuel: Gas 3

The advantages of digital combustion management Control and Display Unit Digital combustion management means optimum combustion figures, continuous repeatability of setting values and ease of use. Weishaupt burners are equipped with electronic ratio controller and digital combustion management to satisfy the requirements of modern combustion technology, which demand a precise and continuously reproducible supply of fuel and combustion air. Only in this way optimal combustion figures can be ensured over extended periods of time. If required, the burners can also be equipped with O 2 trim* and variable speed control. Error free operation via AZL display and control unit Setting and control of the burner functions is achieved using a control and display unit, the AZL, which is equipped with an LCD display. The AZL is connected to the combustion manager via a safety bus system and can be positioned anywhere according to the user s preferences within 325 ft. (100 m) distance from the burner. Flexible communication possibilities The integrated communication interface enables all necessary information and functions to be transmitted to a BMS system. If required, remote operation and remote diagnosis functions, which are accessible via modem, can be installed (e.g. oil/gas change-over, adjustment of setting values). Communication with external systems via BUS If data has to be exchanged between burners and other heating systems with PLC devices, the information can be accessible via ebus or MODBUS communication system. Integration with building management For control and management functions, Weishaupt offers ProGraf NT - a software product that provides a real time solution to meet all requirements. The price advantage of the new technology With improved technology and ease of use, combustion plant is becoming even more economical than ever before. No additional burner controls are required, since this function is already governed by the combustion manager. Fuses and burner motor starter are the only additional items required. Less installation work means less errors: the burners are tested as a complete unit at the factory. If required, the W-FM 100 is available with an integrated modulating controller and variable speed module. No separate equipment is required. The modulating controller and variable speed module are included as standard with the W-FM 200. Commissioning and service work takes less time. The initial presetting of the burner is carried out at the factory. On site, only the site specific operating points have to be adjusted. To facilitate O 2 trim, only an O 2 probe and O 2 module have to be installed and connected with the W-FM 200 via the internal safety BUS. * In conjunction with W-FM 200 combustion manager 4

O 2 probe* O 2 module* Gas butterfly Stepping motors Oil regulator Air damper Frequency converter Impulse sender CAN-Bus W-FM 200 combustion manager CAN-Bus Control and Display Unit ebus/ MODBUS BMS visualization ProGraf NT Example of O 2 trim and speed control with W-FM 200 5

Proven quality in detail Increased safety via shut off assembly with solenoid valve The electromagnetically actuated safety shut off device isolates the oil supply and return on burner models RGL40 to 70 when the burner shuts down. Oil shut off directly at the nozzle ensures a drip free burner shut down. (Burner model RGL30 uses a system without nozzle shut off). Considerable noise reduction due to sound absorbing air inlet By utilizing sound absorbing materials on the fan suction side it has been possible to reduce operational noise considerably. Cut-away of a nozzle shut of assembly Cut-away of the fan housing Emission figures for 1LN version Excellent emission results are achievable depending on the geometry of the combustion chamber, volume load and firing system (3 pass or reverse flame). [ppm] 60 50 Example for Natural Gas operation NO x limit* with medium temperature < 230F (110 C) When stating information relating to guaranteed values, certain conditions for measurement and evaluation must be taken into account, such as combustion chamber loading, test tolerances, temperature, pressure, humidity. The designation 1LN is used on the new Weishaupt Low NO x burner series. 40 30 20 10 0 NO x CO * According to German TA-Luft regulation 6

Burner with integrated Control and Display Unit 7

Dual fuel burner selection Models GL and RGL30, 1LN version [ WC ] Burner model GL30/2-A, vers. ZM-1LN GL30/2-A, vers. TM-1LN RGL30/2-A, vers. ZM-1LN Combustion head G30/2-LN 190x35 MBH Nat. Gas/Propane 1,000 6,400 GPH #2 9 45 5 Combustion head open Combustion head closed 4 3 2 1 0 Nat gas/lpg -1 [MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 [GPH] 0 10 20 30 40 50 Burner model Version GL30/2-A ZM-1LN GL30/2-A TM-1LN The ratings given are based on fuel with low calorific value and an installation altitude of 0 ft. (0 m). Depending on the altitude of the installation, a reduction in capacity of approximately 1% for every 328 ft. (100 m) above sea level should be taken into account. RGL30/2-A ZM-1LN The stated oil throughputs are based on a calorific value of 140,000 BTU/Gal for light oil Voltages and frequencies: As standard, the burners are suitable for three phase alternating current available with various voltages from 208-600V, 60Hz. Different voltages and frequency are available on request. Standard burner motor: Isolation class F, IP 54 protection 8

Dual fuel burner selection Models GL and RGL40, 1LN version [ WC ] Burner model GL40/1-B, vers. TM-1LN Combustion head open RGL40/1-B, vers. ZM-1LN Combustion head G30/2-LN 190x35K Combustion head closed MBH Natural gas 1,530 7,500 Propane 1,530 7,500 GPH #2 11 53 7 6 5 4 3 2 1 0-1 [MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 Nat gas/lpg [GPH] 0 10 20 30 40 50 60 [ WC ] Burner model GL40/2-A, vers. TM-1LN Combustion head open RGL40/2-A, vers. ZM-1LN Combustion head G40/2-LN 217x35K Combustion head closed MBH Natural gas 1,700 10,500 Propane 1,700 10,500 GPH #2 13 75 7 6 5 4 3 2 1 0-1 [MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 Nat gas/lpg [GPH] 0 10 20 30 40 50 60 70 80 Burner model Version GL40/1-B TM-1LN RGL40/1-B ZM-1LN The ratings given are based on fuel with low calorific value and an installation altitude of 0 ft. (0 m). Depending on the altitude of the installation, a reduction in capacity of approximately 1% for every 328 ft. (100 m) above sea level should be taken into account. GL40/2-A RGL40/2-A TM-1LN ZM-1LN The stated oil throughputs are based on a calorific value of 140,000 BTU/Gal for light oil Voltages and frequencies: As standard, the burners are suitable for three phase alternating current available with various voltages from 208-600V, 60Hz. Different voltages and frequency are available on request. Standard burner motor: Isolation class F, IP 54 protection 9

Dual fuel burner selection Model RGL50, 1LN version [ WC] Burner model RGL50/1-B, vers. ZM-1LN Combustion head G40/2-LN 217x35K MBH Natural gas 1,700 11,600 Propane 1,700 11,600 GPH #2 20 82 Combustion head open Combustion head closed [ WC ] Burner model RGL50/2-A, vers. ZM-1LN Combustion head G50/2-LN 260x40 MBH Natural Gas 2,050 16,730 Propane 2,730 16,730 GPH #2 21 120 Combustion head open Combustion head closed 8 7 6 5 4 3 2 1 0 Nat gas/lpg -1 [MBH] 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 8 7 6 5 4 3 2 1 0 Nat gas Propane -1 [MBH] 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 [GPH] 0 10 20 30 40 50 60 70 80 90 [GPH] 0 20 40 60 80 100 120 Burner model Version RGL50/1-B ZM-1LN RGL50/2-A ZM-1LN The ratings given are based on fuel with low calorific value and an installation altitude of 0 ft. (0 m). Depending on the altitude of the installation, a reduction in capacity of approximately 1% for every 328 ft. (100 m) above sea level should be taken into account. The stated oil throughputs are based on a calorific value of 140,000 BTU/Gal for light oil Voltages and frequencies: As standard, the burners are suitable for three phase alternating current available with various voltages from 208-600V, 60Hz. Different voltages and frequency are available on request. Standard burner motor: Isolation class F, IP 54 protection 10

Dual fuel burner selection Model RGL70, 1LN version [ WC] Burner model RGL70/1-B, vers. ZM-1LN Combustion head G70/1-1LN 365x85 MBH Natural gas 2,730 24,915 Propane 3,410 24,915 GPH #2 29 163 Combustion head open Combustion head closed [ WC] Burner model RGL70/2-A, vers. ZM-1LN Combustion head G70/2-1LN 365x85 MBH Natural Gas 3,400 34,130 Propane 4,750 34,130 GPH #2 46 244 Combustion head open Combustion head closed 9 8 7 6 5 4 3 2 1 0-1 [MBH] 0 4,000 8,000 12,000 16,000 20,000 24,000 Nat gas Propane 9 8 7 6 5 4 3 2 1 0-1 [MBH] 0 6,000 12,000 18,000 24,000 30,000 36,000 Nat gas Propane [GPH] 0 20 40 60 80 100 120 140 160 180 [GPH] 0 30 60 90 120 150 180 210 240 270 Burner model Version RGL70/1-B ZM-1LN RGL70/2-A ZM-1LN The ratings given are based on fuel with low calorific value and an installation altitude of 0 ft. (0 m). Depending on the altitude of the installation, a reduction in capacity of approximately 1% for every 328 ft. (100 m) above sea level should be taken into account. The stated oil throughputs are based on a calorific value of 140,000 BTU/Gal for light oil Voltages and frequencies: As standard, the burners are suitable for three phase alternating current available with various voltages from 208-600V, 60Hz. Different voltages and frequency are available on request. Standard burner motor: Isolation class F, IP 54 protection 11

Scope of delivery Description GL30-ZM GL30-TM RGL30 GL40-TM RGL40 RGL70 RGL50 Burner housing, hinged flange, housing cover, Weishaupt burner motor, air regulation housing, fan wheel, combustion head, ignition unit, ignition cable, ignition electrodes, nozzle assembly with oil nozzle(s), combustion manager with control unit, flame sensor, flange gasket, limit switch on hinged flange, fixing bolts W-FM 100 combustion manager Double main gas valves Gas butterfly valve Pilot gas valves Connection piece Air pressure switch Oil pressure switch in return Gas pressure switch Adjustable regulating sleeve in the mixing head Adjustable flame tube in the mixing head Servomotor for fuel/air compound regulation via W-FM 100 Servomotor for air damper Servomotor for gas butterfly Servomotor for oil regulator Oil pump Oil hoses 2 oil solenoid valves, 1 safety valve, two stage nozzle assembly without shut off 2 oil solenoid valves, 1 safety valve, two stage nozzle assembly with solenoid shut offg 3 oil solenoid valves, 1 safety valve, three stage nozzle assembly without shut off 2 solenoid valves in flow and return, nozzle assembly without shut off Electromagnetic clutch 12

Special equipment Description Size 30 Size 40 Size 50 Size 70 Vertically firing burner version standard standard standard standard Air intake flange for connection of an air duct 280 003 47 280 001 68 280 000 92 280 000 13 Combustion head extension by 6 (150 mm), model../1-b 290 008 96 290 009 00 290 010 78 by 12 (300 mm), model../1-b 290 008 97 290 009 01 290 010 79 by 6 (150 mm), model../2-a 290 008 90 290 008 98 290 009 39 290 009 59 by 12 (300 mm), model../2-a 290 008 91 290 008 99 * * W-FM 100 with integrated modulating controller 290 010 60 290 010 60 290 010 60 290 010 60 Burner controller Mechanical linkage with LFL flame safeguard in lieu of W-FM 100 -price reduction- 290 011 02 290 011 02 290 011 02 290 011 02 Mechanical linkage with LGK flame safeguard in lieu of W-FM 100 -price reduction- 290 011 09 290 011 09 290 011 09 290 011 09 Solenoid valve for air pressure switch test for continuous run fan or post purge 290 004 29 290 004 29 290 000 31 290 000 31 * Contact Weishaupt corporation for more detailed information 13

Technical Data Sizes 30 and 40 Description GL30/2-A RGL30/2-A Burner motor Model D112/110-2 D112/110-2 Motor rating HP (kw) 6.7 (5.0) 6.7 (5.0) Full Load Amps (FLA) at 460 V A 8.2 8.2 Speed (60 Hz) rpm 3510 3510 Fan wheel colour / ø red / 248 x 100 red / 248 x 100 Combustion manager Model W-FM100 W-FM100 Ignition unit Model W-ZG02/2 W-ZG02/2 Servomotor Model SQM 45 SQM 45 Integral pump Model J6 TA3 Oil solenoid valve 110V 1/4 20 W Model 121 K 6220 110V 1/8 19 W Model 121 K 2423 55V 1/4 (supply) 20 W Model 121 K 6220 55V 1/8 (return) 20 W Model 121 K 2423 55V 3/8 (supply) 20 W Model 55V 3/8 (return) 20 W Model Oil pressure switch 1-10 bar (return - 5 bar) Model DSA 46 F001 Oil hoses DN / Length 13/40 (1000mm) 20/40 (1000mm) Burner weight lbs (kg) 297 (135) 319 (145) Technical data GL40/1-B RGL40/1-B GL40/2-A RGL40/2-A Burner motor Model D112/140-2 D112/140-2 Motor rating HP (kw) 10.5 (7.8) 10.5 (7.8) Full Load Amps (FLA) at 460 V A 11.5 11.5 Speed (60 Hz) rpm 3450 3450 Fan wheel colour / ø red / 275 x 100 red / 275 x 100 Combustion manager Model W-FM100 W-FM100 Ignition unit Model W-ZG02/2 W-ZG02/2 Servomotor Model SQM 45 SQM 45 Integral pump Model J6➀ TA3 Oil solenoid valve 110V 1/8 19 W Model 121 K 2423 110V 1/4 (safety valve) 20 W Model 121 K 6220 55V 3/8 (supply) 20 W Model 321 H 2322 55V 3/8 (return) 20 W Model 121 G 2320 Oil pressure switch 1-10 bar (return - 5 bar) Type DSA 46 F001 Oil hoses DN / Length 13/40 (1000mm) 20/40 (1000) Burner weight lbs (kg) 352 (160) 352 (160) ➀ Burners > 60 GPH (200 kg/h): oil pump J7 in lieu of J6 (refer to Special Equipment for additional cost) Burners > 72 GPH (250 kg/h): oil pump TA2 in lieu of J6 (refer to Special Equipment for additional cost) 14

Technical Data Sizes 50 and 70 Description RGL50/1-B RGL50/2-A Burner motor Model D132/170-2a D132/170-2 Motor rating HP (kw) 14 (10.5) 20 (15) Full Load Amps (FLA) at 460 V A 17.2 23.2 Speed (60 Hz) rpm 3500 3500 Fan wheel colour / ø red / 330 x 100 red / 330 x 100 Combustion manager Model W-FM100 W-FM100 Ignition unit Model W-ZG02/2 W-ZG02/2 Servomotor Model SQM 45 SQM 45 Integral pump Model TA4C T2C Oil solenoid valve 55V 3/8 (supply) 20 W Model 321 H 2322 321 H 2322 55V 3/8 (return) 20 W Model 121 G 2320 121 G 2320 Oil pressure switch 1-10 bar (return - 5 bar) Model DSA 46 F001 DSA 46 F001 Oil hoses DN / Length 25/51 (1300mm) 25/51 (1300mm) Burner weight lbs (kg) 517 (235) 528 (240) Technical data RGL70/1-B RGL70/2-A Burner motor Model D160/215-2B D160/215-2 Motor rating HP (kw) 25 (19) 29.5 (22) Full Load Amps (FLA) at 460 V A 32.2 36 Speed (60 Hz) rpm 3400 3500 Fan wheel colour / ø green / 530 x 120 green / 530 x 120 Combustion manager Model W-FM100 W-FM 100 Ignition unit Model W-ZG02/2 W-ZG02/2 Servomotor Model SQM 45 SQM 45 Integral pump Model T2C (to 175 GPH)) T2C (to 175 GPH) (to 600 kg/h) (to 600 kg/h) T3C (from 175 GPH) T3C (from 175 GPH) (from 600 kg/h) (from 600 kg/h) Oil solenoid valve 55V 1/2 (supply) 20W Model 321 H 2522 321 H 2522 55V 1/2 (return) 20W Model 121 G 2520 121 G 2520 Oil pressure switch 2 40 bar (flow - 18 bar) Model 1 10 bar (return - 5 bar) Model DSA 46 F 001 DSA 46 F 001 Oil hoses DN/Length 25/51 (1300mm) 25/51 (1300mm) Burner weight lbs (kg) 957 (435) 957 (435) 15

Burner fuel systems Type GL30Z (oil side) 10 13 13a 16a Types GL30T / GL40T (oil side) 10 13 13a 16a Type RGL30 (oil side) 10 12 12 16a 55V 55V 55V P M 55V 13a 13a 13a 12a 14 15 12a Types RGL40 to RGL70 (oil side) 10 11 12 16 Types 30 to 70 (gas side) with double main gas valves and pilot line 6 7 4b 4b 9 55V 55V P M P P 12a 14 15 2 3 4 1 5 8 Legend 1 Isolating cock 2 Main gas pressure regulator 3 Low gas pressure switch 4 Double main gas valves 4b Pilot gas valves 5 High gas pressure switch 6 Isolating valve for pilot gas train 7 Pilot gas pressure regulator 8 Gas butterfly valve 9 Burner 10 Oil pump 11 Oil filter 12 Normally closed oil solenoid valve (55 V, electrically connected in series with 12a) 12a Normally closed oil solenoid valve (55 V, electrically connected in series with 12, fitted against the direction of flow) 12b Normally open bypass oil solenoid valve 13 Normally closed oil solenoid valve 13a Normally closed oil solenoid valve for stages 1, 2 and 3 14 Oil pressure switch in return 15 Oil regulator 16 Nozzle assembly with shut off device (solenoid valve) 16a Nozzle assembly without shut off device 17 Oil preheater 18 Pt100 temperature sensor (to monitor minimum oil temperature) 16

Dimensions Sizes 30 and 40 Size 30/2-A 40/1-B 40/2-A 30/2-A 40/1-B 40/2-A Dimensions in inches (mm) l1 l2 l3 l5 l6 l7 l8 l9 l10 l11 b1 b2 b3 b4 b5 b6 42.6 9.6 10.7 0.3 13.9 11.8 2.3 9.4 4.8 1.3 35.2 14.6 8.2 27.6 16.5 13.0 (1083) (245) (272) (8) (354) (300) (58) (238) (123) (32) (895) (371) (208) (700) (418) ( 330) 44.4 10.6 10.7 0.3 16.3 12.6 2.3 9.4 4.8 1.3 37.4 15.8 9.5 29.7 18.2 13.0 (1128) (270) (272) (8) (414) (320) (58) (238) (123) (32) (950) (401) (242) (755) (462) ( 330) 45.2 10.6 13.1 0.3 16.3 13.4 2.6 10.2 5.2 1.7 37.4 15.8 9.5 29.7 18.2 14.6 (1148) (270) (332) (8) (414) (340) (67) (258) (133) (42) (950) (401) (242) (755) (462) ( 370) h1 h2 h3 h4 h6 d1 d2 d4 d5 d6 d7 d8➀ r1➂ r2 22.5 8.1 16.0 8.1 13.0 11.0 9.8 8.6 M12 14.2 11.2 DN50 38.2 35.0 (572) (207) (407) (207) ( 330) (280) (250) (218) (M12) (360) (285) (DN50) (970) (890) 23.9 8.3 16.6 8.1 13.0 11.0 9.8 8.6 M12 14.2 11.2 DN50 41.3 38.2 (607) (211) (422) (207) ( 330) (280) (250) (218) (M12) (360) (285) (DN50) (1050) (970) 23.9 8.3 16.6 8.9 14.6 12.6 11.4 8.6 M12 15.7 12.8 DN65 41.3 38.2 (607) (211) (422) (227) ( 370) (320) (290) (218) (M12) (400) (325) (DN65) (1050) (970) ➀ Flange connection ➁ Pilot line connection either side ➂ With electromagnetic clutch All measurements are approximate. Weishaupt reserves the right to make alterations in light of future developments. 17

Dimensions Sizes 50 Size 50/1-B 50/2-A 50/1-B 50/2-A Dimensions in inches (mm) l1 l2 l3 l5 l6 l7 l8 l9 l10 l11 b1 b2 b3 b4 b5 b6 47.0 12.4 13.1 0.3 16.6 14.3 2.6 10.2 5.2 1.7 41.7 17.3 10.9 32.3 21.7 14.6 (1195) (315) (332) (8) (422) (363) (67) (258) (133) (42) (1060) (440) (277) (820) (550) ( 370) 49.0 12.4 17.6 0.3 16.6 16.3 2.8 12.1 6.2 2.6 43.3 18.3 10.9 33.9 21.7 16.9 (1245) (315) (447) (8) (422) (413) (72) (308) (158) (65) (1100) (465) (277) (860) (550) ( 430) h1 h2 h3 h4 h6 d1 d2 d4 d5 d6 d7 d8➀ r1➂ r2 28.7 10.4 20.2 8.9 14.6 12.6 11.4 10.2 M12 15.7 12.8 DN65 46.5 39.4 (730) (263) (513) (227) ( 370) (319) (290) (258) (M12) (400) (325) (DN65) (1180) (1000) 28.7 10.4 20.2 10.1 16.9 15.0 13.8 10.2 M16 18.9 15.4 DN80 46.5 40.4 (730) (263) (513) (257) ( 430) (382) (350) (258) (M16) (480) (390) (DN80) (1180) (1025) ➀ Flange connection ➁ Pilot line connection either side ➂ With electromagnetic clutch All measurements are approximate. Weishaupt reserves the right to make alterations in light of future developments. 18

Dimensions Sizes 70 d 5 d 7 d 6 Size 70/1-B 70/2-A 70/1-B 70/2-A Dimensions in inches (mm) l1 l2 l3 l5 l6 l7 l8 l9 l10 l11 b1 b2 b3 b4 b5 b6 64.9 19.0 16.5 0.3 24.2 20.1 3.9 13.7 7.0 3.4 55.5 23.7 13.4 44.3 29.9 20.5 (1648) (483) (419) (8) (614) (510) (100) (348) (178) (87) (1410) (602) (340) (1125) (760) ( 520) 65.7 19.0 17.6 0.3 24.2 20.9 3.9 14.5 7.4 3.4 55.5 23.7 13.4 44.3 29.9 23.6 (1668) (483) (447) (8) (614) (530) (100) (368) (188) (87) (1410) (602) (340) (1125) (760) ( 600) h1 h2 h3 h4 h5 d1 d2 d3 d4 d5 d6 d7 d8➀ r1➂ r2 42.3 16.5 30.5 11.9 20.5 17.0 16.0 12.2 M16 18.5 17.1 DN100 59.1 51.6 (1075) (420) (775) (302) ( 520) (432) (406) (310) (M16) (470) (435) (DN100) (1500) (1310) 42.3 16.5 30.5 12.4 23.6 18.5 18.9 12.2 M16 21.7 19.7 DN100 59.1 51.6 (1075) (420) (775) (315) ( 600) (470) (480) (310) (M16) (550) (500) (DN100) (1500) (1310) ➀ Flange connection ➁ Pilot line connection either side ➂ With electromagnetic clutch All measurements are approximate. Weishaupt reserves the right to make alterations in light of future developments. 19

Product and customer service the complete Weishaupt range Weishaupt Corporation 6280 Danville Road Mississauga, ON L5T 2H7 Ph.: (905) 564 0946, Fax.: (905) 564 0949 www.weishaupt-corp.com Print No. 83203816, August 2003 Printed in Germany. All rights reserved. Regular maintenance reduces heating costs and environmental pollution. Only a properly adjusted burner can save energy and be environmentally friendly. Behind each Weishaupt burner stands the whole Weishaupt customer service organization. The outstanding efforts made in maintenance and service justify the enormous trust placed in Weishaupt s burners, for at Weishaupt product and customer service belong together. Weishaupt customer service is there for you all year round. Whenever you need help, be it the supply of spare parts, technical advice or a site visit. We are there when you need us.