Technical Assignment 3 11/15/04. Executive Summary

Similar documents
Andrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

I. Introduction and Arrangement

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

4. OVERVIEW OF MECHANICAL SYSTEM

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

Technical Assignment 3. Mechanical Systems Existing Conditions Evaluation

SHOE PALACE HUNTINGTON PARK M.200

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

C13-Series Engineering Guide

VertiCool Aurora Engineering Guide

VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Mechanical Systems Existing Conditions Evaluation. Instructor: Dr. Bahnfleth. November 12, Thesis Building Sponsor s: INOVA Fairfax Hospital

Mechanical Technical Report 3. Mechanical Systems Existing Conditions Evaluation

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

VariCool VAV Engineering Guide

ISERIES VERTICAL AHU ENGINEERING SPECIFICATIONS

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

CoolSpot Engineering Guide

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

11/2 ORT THREEE. Virtua Repla. acement Hospi. ital. Voorhees NJ. Justin Prior. Mechanical

EADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option

AIR HANDLER DESIGN WORK SHEET

Appendices. Included in this section are

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

photo by PFC Price Fan Column

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

The Temperature and Relative Humidity Control in Cushing Library

Technical Assignment 3 Mechanical Systems Existing Conditions Evaluation

R7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

HVAC Mandatory Provisions Part II, Page 1

City of Duluth Festival Center 04/25

Architectural Alliance Incorporated MDP CONSULTING ENGINEERS, INC N 11th Street Beaumont, TX 77702

Multi-Path RTU-TYPE 2

DIGI-VAV APPLICATIONS

Dates of Construction Construction Start 2/28/1999 Date of Completion 4/2000 Occupancy 5/2000

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ)

TECHNICAL REPORT III Mechanical Systems Existing Conditions

GARCIA GALUSKA DESOUSA Consulting Engineers

VERTICAL AHU ENGINEERING SPECIFICATIONS BULLETIN

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

Job Name Control Systems Description Date

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

CHAPTER 4. HVAC DELIVERY SYSTEMS

CLIMATAIR PENTHOUSE AIR HANDLING SYSTEMS

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

Vertical Air Handler Unit

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

Technical Assignment #2a. Atlanta, GA Green Building Mechanical

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

7. MECHANICAL SYSTEM DESIGN

DACC Health Sciences Building Air Handler Assessment/Study

Computing Services Center

Architectural Engineering Senior Thesis Mechanical System Redesign

Technical Development Program

TECHNICAL REPORT 3 Mechanical Systems and Existing Conditions Northfield Mental Healthcare Center Northfield, Ohio

Description of All Alternatives Considered-

CONTROLLED CHILLED BEAM PUMP MODULE

Civil Engineering Building

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

Technical Assignment 3

APPLICATION GUIDE BEAMS

HVAC Controls Upgrades: Requirement Details ( )

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

MT. AIRY MIDDLE SCHOOL CARROLL COUNTY PUBLIC SCHOOLS

BULLETIN. Temperature Controls (Chilled Water) Phase III only (3/11/2010)

Now In Production JULY 2008

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Madeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012)

VERTICOOL TECHNICAL DATA MANUAL. Vertical Air/Water Cooled 3-25 Tons

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

Christopher Kelly Technical Report Three

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

Appendix 13. Categories of Cooling and Heating systems

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

MACH N-407 Heat Pump Air-Cooled Chiller

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT. February 29, NO CHANGE: March 8, 2012 / NOT LATER THAN 2:00 PM

EarthWise System Seminar

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

HVAC 101. H V A C S y s t e m s

2 Existing Mechanical System

Linear Floor Heaters

Terminal. Las Vegas, NV. Technical

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

MBNA Career Services Center The Pennsylvania State University University Park Campus

Transcription:

Executive Summary This report is an analysis of the existing systems within the Outreach Innovation Building in University Park, PA. One significant design criteria was a lower than average noise criteria within some spaces of the building such as the radio and television production rooms. The project is currently being constructed and therefore utility billing and energy consumption data is not available. General descriptions and system requirements are given for all air handlers, chilled water control sequence, and heating hot water control sequence. The critique of the system includes mechanical system costs (actual costs were not available, RS Means was used to estimate major equipment only), space requirements, maintainability, and environmental control and indoor air quality. Schedules and schematic diagrams were made using the design documents. Schematics include air handling diagrams, heating hot water diagram, and chilled water diagram. Schedules include all major equipment information. The analysis concluded that the existing systems are adequate in all areas analyzed.

Table of Contents Design Objectives and Requirements 1 Energy Sources and Rates 1 Site Factors 1 Design Conditions 2 System Requirements 3 Chilled Water Temperature Control System 4 Heating Hot Water Temperature Control Sequence 5 Operating History 5 Critique of System 6-7 AHU Diagram 1 8 AHU Diagram 2 9 Heating/Chilled Water Diagrams 10 Equipment Schedules 11-12

Design Objectives and Requirements The design requirements for the are that of a type B building in the International Building Code 2000. The mechanical systems must meet the heating/cooling loads and the ventilation requirements set by the International Building Code 2000. Noise Criteria was also considered due to the multiple television and radio studios throughout the building. An NC of 20 to 25 was designed for such spaces. Duct sizes were increased to reduce the velocity of the supply air and therefore lower the sound pressure level in order to comply with these design standards. Under-floor air distribution was used in open office areas. This enables a floor plan that can easily be changed. Also the large amounts of telecommunication cables can be placed within this raised floor area. Energy Sources and Rates The electricity rates for the were taken from a document about the West Penn Power Company: Rates, Terms, and Conditions Governing Interchange of Electricity with The Pennsylvania State University (Issued Dec 30, 2003). DEMAND CHARGE First 10,000 kilovolt-amperes Additional kilovolt-amperes ENERGY CHARGE All kilowatt-hours All kilowatt-hours $0.91 per kilovolt-ampere $0.90 per kilovolt-ampere $0.00277 per kilowatt-hour $0.01895 per kilowatt-hour (Effective 1-1-04) Site Factors No major site factors influenced the design. The building is being built in a developing region on Penn State University land. 1

Design Conditions Outdoor design conditions Summer 89 F DB, 72 F MWB (0.4%) Winter 5 F DB (99.6%) Indoor design conditions 74 F and 50% relative humidity year round (Design conditions taken from ASHRAE Fundamentals 2001) Design Heating/Cooling Loads SYMBOL HEATING COOLING MBH MBH AHU-1A 55 290.4 AHU-1B 55 290.4 AHU-2A 639.3 768 AHU-2B 639.3 768 AHU-3A 974.7 974.4 AHU-3B 974.7 974.4 B-1 1500 - B-1 1500 - B-1 1500 - CH-1-648 CH-2-2100 CH-3-2100 2

System Requirements AHU-1A, 1B, 2A, 2B General Description Air units are variable air volume units, comprised of the following: mixing box with separate minimum and modulating outdoor dampers, filter section, hot water heating coil, access section, chilled water cooling coil, humidifier, access section, and plenum supply fan. The system return fans are vane axial frequency drives. These units serve production areas on the First Floor. Freezestat shall de-energize the fans whenever the temperature falls below setpoint (36F, adj.). Smoke Detector: The unit shall shut down upon actuation of any smoke detector and initiation by the Fire Alarm System for air unit shutdown. Start Time Optimization: The Building Automation System (BAS) shall automatically calculate the optimum time to start the unit(s) based on space temperature, ambient temperature, and a building heat loss/gain coefficient in order to bring the space temperature to the proper setpoint no more than 15 minutes before scheduled occupancy time. Static Pressure High Limit Sensor: System shall turn off upon actuation of duct static pressure high limit sensor. Fan Tracking: Supply fan air volume shall be controlled with variable frequency drive via static pressure sensors in the supply air ductwork, setpoint 0.75 in/wg, adj. Return fan shall be modulated with variable frequency drive to maintain a fixed CFM differential between supply and return as measured by air measuring devices, equal to minimum outside air and/or building exhaust, plus building pressurization CFM. AHU-3A and 3B These units supply the under-floor air distribution system. General Description similar to AHU-1A, 1B, 2A, 2B above. 3

Chilled Water Temperature Control Sequence General Description The chilled water system is primary-secondary plant, comprised of the following components: air-cooled chillers with evaporator barrel remotely located in mechanical Penthouse, primary chilled water pumps (constant speed) dedicated to each evaporator barrel, and variable speed secondary chilled water pumps that deliver chilled water to terminal cooling coils. To prevent short cycling, each chiller shall run for a minimum of 30 minutes and be off a minimum of 20 minutes. On failure of the lead pump, the lag pump will run and the lead pump will be de-energized. The chiller will shut down and an alarm set off if a refrigerant leak is detected within the mechanical penthouse. The chiller plant shall be enabled to run whenever ambient temperature is greater than 50F. Secondary chilled water pump(s) will be energized any time the chiller(s) is called to run. Pump speed will be modulated to maintain differential pressure sensor setpoint of 25 ft/wg. 4

Heating Hot Water Temperature Control Sequence General Description The heating hot water system is primary-secondary plant, comprised of the following components: gas-fired hot water boilers, primary hot water pumps (constant speed) dedicated to each boiler, and variable speed secondary hot water pumps that deliver heating hot water to terminal heating units (coils, finned tube radiation, radiant ceiling panels, and cabinet unit heaters). To prevent short cycling of the boilers, each boiler shall run for a minimum of 5 minutes and be off a minimum of 1 minute. The boiler plant will run whenever ambient temperature is less than 65 F. Secondary hot water pump(s) will be energized any time the boiler(s) is called to run. Pump speed will be modulated to maintain differential pressure sensor setpoint of 15 ft/wg. Operating History The operating history for the is not available. (Building not complete as of November 15, 2004) 5

Critique of System Mechanical System Cost Actual mechanical system costs were not able to be obtained. Only major mechanical equipment such as air-handling units, chillers, boilers, etc. was taken into account. No piping, ductwork, under-floor air distribution system (including grilles), or labor were taken into consideration for this assignment. Actual bidding documents could not be obtained, therefore RS Means Facilities Construction Cost Data, 17 th Annual Edition was used to estimate the major mechanical equipment cost. Due to the omission of parts of the mechanical system the cost estimation is low compared to the actual value. The following chart is a breakdown of equipment estimated. RS MEANS 2002 Cost Estimation CHILLER SIZE TYPE QUANTITY UNIT PRICE TOTAL COST CH-1 64.8 KW AIR 1 44800 44800 CH-2 217.1 KW AIR 1 108375 108375 CH-3 217.1 KW AIR 1 108375 108375 AIR HANDLING SIZE TYPE QUANTITY UNIT PRICE TOTAL COST AHU-1A&B 10,000 CFM HORIZ. DRAW 2 7975 15950 AHU-2A&B 17,500 CFM HORIZ. DRAW 2 14825 29650 AHU-3A&B 35,000 CFM HORIZ. DRAW 2 28000 56000 HUMIDIFIERS SIZE TYPE QUANTITY UNIT PRICE TOTAL COST H-1 200 LBS/HR 1 7725 7725 H-2 350 LBS/HR 1 11000 11000 H-3 600 LBS/HR 1 16525 16525 FAN SIZE TYPE QUANTITY UNIT PRICE TOTAL COST EF-1 2700 CFM 1 984 984 EF-2 1530 CFM 1 550 550 EF-3 11440 CFM 1 1700 1700 EF-4 150 CFM 1 100 100 CSF-1 275 CFM 1 240 240 PUMP SIZE TYPE QUANTITY UNIT PRICE TOTAL COST P-1A&B 80 GPM INLINE 2 2500 5000 P-2&3 280 GPM END SUCT. 2 2275 4550 P-4A&B 640 GPM END SUCT. 2 3880 7760 P-5,6,7 130 GPM INLINE 3 2700 8100 P-8A&B 320 GPM END SUCT. 2 3000 6000 BOILER SIZE TYPE QUANTITY UNIT PRICE TOTAL COST B-1 1500 MBH 3 18500 55500 TOTAL EQUIP. COST 488884 EQUIP. COST PER FT^2 5.04 6

Space Requirements Floor area for the mechanical equipment including shaft area totals approximately 7,400 sq.ft. This does not include the exterior penthouse space which is approximately 1600 sq.ft. These areas appear to be adequate for the mechanical systems and do not seem to pose any problems such as duct or pipe layout, etc. Maintainability Serviceability of equipment does not appear to be an issue. All major equipment appears to have adequate clearance in order for maintenance and/or replacement of parts. Under-floor air distribution system allows for flexibility of spaces and access to under-floor VAV boxes and equipment. All ceilings allow for access to piping and ductwork where necessary. Environmental Control and Indoor Air Quality The ASHRAE Standard 62-2001 analysis showed that ventilation rates meet the minimum requirements and IAQ is not an issue. Equipment selected is also able to meet the required load, and therefore environmental control is also not an issue. 7

AHU 1A & 1B DIAGRAM (AHU-2A &2B SIMILAR, EXCEPT AS NOTED) COMPONENT LEGEND 1. MIXING BOX 2. PRE- AND FINAL FILTERS 3. HEATING COIL 4. ACCESS SECTION 5. COOLING COIL/ COND. DRAIN PAN 6. HUMIDIFIER 7. ACCESS SECTION 8. SUPPLY FAN (PLENUM TYPE) 9. RETURN FAN (VANE AXIAL TYPE) NOTES 1. MIXED AIR TEMPERATURE SETPOINT - AHU-1A/B = 49.5 F - AHU-2A/B = 51.5 F 2. DISCHARGE TEMPERATURE SETPOINT - AHU-1A/B = 50.5 F - AHU-2A/B = 52.5 F 3. STATIC PRESSURE SENSORS - AHU-1A/B = QTY.1 - AHU-2A/B = QTY.2 8

AHU 3A & 3B DIAGRAM (UNDERFLOOR AIR SYSTEM) COMPONENT LEGEND 1. MIXING BOX 2. PRE- AND FINAL FILTERS 3. HEATING COIL 4. ACCESS SECTION 5. COOLING COIL/ COND. DRAIN PAN 6. RETURN AIR BYPASS SECTION W/ FILTER AND CNTRL. DAMP. 7. HUMIDIFIER 8. ACCESS SECTION 9. SUPPLY FAN (PLENUM TYPE) 10. RETURN FAN (VANE AXIAL TYPE) 9

10

CHILLER SCHEDULE SYMBOL CAPACITY EVAPORATOR CONDENSER COMPRESSOR GENERAL REFRIGERANT (TON) GPM EWT(F) LWT(F) AMB. (F) QTY. FANS TOT. FAN KW TOTAL KW TOT. CH. KW V-Ph-Hz CH-1 54 HCFC-22 86 57 42 95 2 5.6 59.2 64.8 460-3-60 CH-2 175 HCFC-22 280 57 42 95 8 18 199.1 217.1 460-3-60 CH-3 175 HCFC-22 280 57 42 95 8 18 199.1 217.1 460-3-60 BOILER SCHEDULE SYMBOL CAPACITY (MBH) BURNER (GAS) PRESSURE (IN/WG) DESIGN PRESSURE ELECTRICAL DATA INPUT OUTPUT MIN. MAX. (PSIG) AMPS V-Ph-Hz B-1 1500 1275 5 14 160 18.7 120-1-60 B-1 1500 1275 5 14 160 18.7 120-1-61 B-1 1500 1275 5 14 160 18.7 120-1-62 AIR TERMINAL SCHEDULE AIR SEPARATOR SCHEDULE EXPANSION TANK SCHEDULE SYMBOL MIN CFM MAX CFM TYPE MAX SP. (IN/WG) SYMBOL SERVICE SYMBOL SERVICE TYPE AD-1 40 100-0.09 AS-1 HW SYSTEM ET-1 HW SYS. VERTICAL AD-2 100 150-0.1 AS-2 CW SYSTEM ET-2 CHW SYS. VERTICAL AD-3 75 150-0.04 P-4A (4B) SECOND CHW AD-4 150 250-0.05 AD-5 250 380-0.08 AD-6 380 500-0.08 AD-7 425 650-0.09 AD-8 600 725-0.1 AD-9 250 CFM/LF - LINEAR 0.02 AD-10 90 CFM/LF - LINEAR 0.05 AD-11 500 910-0.05 AD-12 800 1100 ROUND CONE 0.02 - - - - - RG/EG-1 50 525 EGGCRATE 0.05 RG/EG-2 500 1285 EGGCRATE 0.05 RG/EG-3 500 2000 EGGCRATE 0.05 RG/EG-4 1000 2800 EGGCRATE 0.02 RG/EG-5 50 440 BAR GRILLE 0.05 RG/EG-6 450 800 BAR GRILLE 0.05 RG/EG-7 800 1570 BAR GRILLE 0.05 RG/EG-8 1900 1900 BAR GRILLE 0.05 AIR HANDLING UNIT SCHEDULE (CONTINUED BELOW) SYMBOL TYPE SUPPLY FAN RETURN FAN COOLING COIL TOTAL CFM TSP (IN/WG) MIN OA CFM MOTOR HP TOTAL CFM TSP (IN/WG) MOTOR HP TOT TONS CFM EAT (DB/WB) LAT (DB/WB) FACE VEL. (FPM) EWT (F) LWT (F) GPM AHU-1A VAV HOR DRAW 10000 4.65 1000 15 10000 1.5 7.5 24.2 10000 73.7/59.1 48.3/48.2 500 42 57 39 AHU-1B VAV HOR DRAW 10000 4.65 1000 15 10000 1.5 7.5 24.2 10000 73.7/59.1 48.3/48.2 500 42 57 39 AHU-2A VAV HOR DRAW 17500 4.65 3350 25 16640 1.5 10 64 17500 82/64.8 50.9/50.5 500 42 57 100 AHU-2B VAV HOR DRAW 17500 4.65 3350 25 16640 1.5 10 64 17500 82/64.8 50.9/50.5 500 42 57 100 AHU-3A VAV HOR DRAW 35000 5.1 4450 60 38000 1.5 25 81.2 35000 82/64.8 52.8/52.2 500 42 57 165 AHU-3B VAV HOR DRAW 35000 5.1 4450 60 38000 1.5 25 81.2 35000 82/64.8 52.8/52.2 500 42 57 165 AIR HANDLING UNIT SCHEDULE (CONTINUED) SYMBOL PREHEAT COIL HUMIDIFIER TOTAL MBH CFM EAT (DB/WB) LAT (DB/WB) FACE VEL (FPM) EWT (F) LWT (F) GPM STEAM LB/HR STM PRES. (PSI) AHU-1A 55 10000 70 75 500 180 160 36 100 5 AHU-1B 55 10000 70 75 500 180 160 36 100 5 AHU-2A 639.3 17500 60 91.5 500 180 160 65 150 5 AHU-2B 639.3 17500 60 91.5 500 180 160 65 150 5 AHU-3A 974.7 35000 65 92 500 180 160 98.5 400 5 AHU-3B 974.7 35000 65 92 500 180 160 98.5 400 5 11

FAN-POWERED TERMINAL BOX SCHEDULE - SERIES FLOW (FPB) SYMBOL PRIMARY AIR (COOLING) FAN DATA (HEATING) HEATING COIL HOT (HOT WATER) MAX CFM MIN CFM SP (IN/WG) SP (IN/WG) HP CFM MBH SP GPM EWT FPB-4 175 40 0.25 0.25 0.08 90 4.3-0.4 180 FPB-5 275 70 0.25 0.25 0.08 140 6.6-0.7 180 FPB-6 400 100 0.25 0.27 0.1 200 9.5 0.02 0.9 180 FPB-8 700 180 0.25 0.28 0.25 350 16.6 0.03 1.7 180 FPB-10 1100 280 0.25 0.32 0.25 550 26 0.07 2.6 180 FPB-12 1600 400 0.25 0.38 0.33 800 37.8 0.13 3.8 180 FPB-14 2100 530 0.25 0.37 0.5 1050 49.7 0.12 5 180 FPB-16 2800 700 0.25 0.36 0.75 1400 66.2 0.11 6.6 180 FAN COIL UNIT SCHEDULE SYMBOL FAN DATA HEATING COIL (HOT WATER) TOTAL CFM MIN OA CFM MOTOR HP&W V-Ph-Hz CFM CAPACITY (MBH) EAT (DB) LAT(DB) GPM EWT (F) FCU-1 350 0 1/16 95W 115-1-60 350 23.6 65 125 1.5 180 FCU-2 350 0 1/8 95W 115-1-60 350 23.6 65 125 1.5 180 FCU-3 540 0 1/8 125W 115-1-60 540 41.9 65 133 3 180 FCU-4 540 0 1/8 125W 115-1-60 540 41.9 65 133 3 180 FAN SCHEDULE SYMBOL CFM SP W.C. HP OR WATTS RPM TIP SPEED V-Ph-Hz EF-1 2700 0.5 1/2 HP 740 3923 208-3-60 EF-2 1530 0.5 1/3 HP 675 3578 120-1-60 EF-3 11440 0.375 3 HP 1750 13744 480-3-60 EF-4 150 0.5 77W 1050-120-1-60 CSF-1 275 0.25 132W 1550-120-1-60 VARIABLE VOLUME BOX SCHEDULE (V V) SYMBOL INLET MAX DESIGN MIN. SP HEATING COIL (HOT WATER) (4) DIA (IN) CFM (1) CFM (2) (IN/WG) (3) CFM MBH (5) EAT (F) SP (IN/WG) (6) GPM (7) EWT (F) WPD (FT/WG) V V-4 4 175 45 0.25 175 6.7 55 0.03 0.7 180 0.14 V V-5 5 275 70 0.25 275 10.6 55 0.08 1.1 180 0.17 V V-6 6 400 100 0.25 400 15.4 55 0.15 1.5 180 0.3 V V-8 8 700 175 0.25 700 27 55 0.3 2.7 180 0.93 V V-10 10 1100 275 0.25 1100 42.4 55 0.52 4.2 180 0.62 V V-12 12 1600 400 0.25 1600 61.6 55 0.65 6.2 180 1.47 V V-14 14 2100 525 0.25 2100 80.9 55 0.72 8.1 180 2.79 V V-16 16 2800 700 0.25 2800 107.8 55 0.92 10.8 180 4.5 HUMIDIFIERS SYMBOL SERVICE TOTAL OUTDOOR AIR HUMIDITY ROOM TEMP MAX STEAM MAX INPUT GAS INLET ELECTRICAL CFM % (F) FLOW (LBS/HR) (MBH) PRES. (INWC) 120-1-60 H-1 AHU 1A&1B 20000 2000 30 74 200 300 7 3 FLA H-2 AHU 2A&2B 35000 6700 30 74 350 600 7 4.5 FLA H-3 AHU 3A&3B 70000 8900 30 74 600 800 7 6 PUMP SCHEDULE SYMBOL SERVICE TYPE PUMP MOTOR GPM HEAD (FT/WG) MHP RPM V-Ph-Hz P-1A (P-1B) PRIM CHW (CH-1) INLINE 80 25 1.5 1750 460-3-60 P-2 (P-3) PRIM CHW (CH-2&3) END SUCT. 280 25 5 1750 460-3-61 P-4A (P-4B) SECOND CHW END SUCT. 640 50 15 1750 460-3-62 P-5 (P-6&7) PRIM HW (B-1,2,3) INLINE 130 20 1.5 1750 460-3-63 P-8A (P-8B) SECOND HW END SUCT. 320 70 10 1750 460-3-64 UNIT HEATER SCHEDULE SYMBOL TYPE HEATING COIL (HOT WATER) MBH GPM EAT (F) EWT (F) WPD (FT/WG) FAN CFM FAN HP V-Ph-Hz UH-1 HORIZ. 13.4 1.5 65 180 0.05 545 1/20 120-1-60 UH-2 HORIZ. 4.2 1 65 180 0.03 280 1/50 120-1-60 12