Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Similar documents
Refrigerant Mass and Oil Migration During Start-up Transient

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

Effects of Refrigerant-Lubricant Combinations on the Energy Efficiency of a Convertible Split-System Residential Air-Conditioner

A fair comparison of CO2 and propane used in light commercial applications featuring natural refrigerants

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Low GWP Refrigerants for Air Conditioning Applications

Performance of CO2 Cycles with a Two-Stage Compressor

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Experimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Purdue e-pubs. Purdue University

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Extremely Low Refrigerant Charge Beverage Display Cooler Technology Using Propane

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Sub-Critical Operation of the CO2 Expander/ Compressor

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

Designated vs Non-designated Areas for Condenser Subcooling

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Experimental Study of Two-phase Seperators for Vapor Compression Systems in Household Appliances

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

MAL-DISTRIBUTION MODEL OF HEAT EXCHANGERS IN MICRO CHANNEL EVAPORATOR

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Tribology Characteristics of HFO and HC Refrigerants with Immiscible Oils - Effect of Refrigerant with Unsaturated Bond -

Transcritical CO2 Bottle Cooler Development

Performance Analysis of a Miniature-Scale Vapor Compression System for Electronics Cooling: Bread Board Setup

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Study of R161 Refrigerant for Residential Airconditioning

Two-Phase Evaporation Pressure Drop Experimental Results for Low Refrigerant Mass Flux

Air-Cooled Heat Exchanger Performance for R410A

ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Performance Measurement of R32 Vapor Injection Heat Pump System

Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

R32 Compressor for Air conditioning and Refrigeration applications in China

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

Quantification of Liquid Refrigerant Distribution in Parallel Flow Microchannel Heat Exchanger Using Infrared Thermography

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Mobile Heat Pump Exploration Using R445A and R744

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Mini Vapour Cycle System For High Density Electronic Cooling Applications

INTERNSHIP REPORT 1/3

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Compressor Capacity Control: A New Direction

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

Comparison of Oil Retention in R134a and CO 2 Climate Control Systems

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

Performance Testing of Unitary Split-System Heat Pump with an Energy Recovery Expansion Device

EFFECT OF OIL IN CIRCULATION ON AUTOMOTIVE A/C COMPONENT AND SYSTEM PERFORMANCE XUAN LIU THESIS

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Design Optimization of Variable Geometry Microchannel Heat Exchangers

Development of an Open Drive Scroll Compressor for Transportation Refrigeration

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Investigation of Evaporator Performance with and without Liquid Overfeeding

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences - Scott S. Wujek University of Illinois at Urbana-Champaign Predrag Hrnjak University of Illinois at Urbana-Champaign Follow this and additional works at: http://docs.lib.purdue.edu/iracc Wujek, Scott S. and Hrnjak, Predrag, "Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -" (2006). International Refrigeration and Air Conditioning Conference. Paper 772. http://docs.lib.purdue.edu/iracc/772 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

R164, Page 1 EFFECTS OF OIL ON A TRANSCRITICAL CARBON DIOXIDE AIR CONDITIONING SYSTEM - some experiences - Scott S. Wujek*, Pega S. Hrnjak Air Conditioning and Refrigeration Center University of Illinois Urbana, IL, USA Phone: (217) 337-7706 Email: swujek@uiuc.edu ABSTRACT This paper presents some experience related to oil effects when running a prototype transcritical air conditioning system with R744 as refrigerant. System is described and the effects of oil and oil separator quantified. Experiences with different orientation of the sampling cylinder presented, and are related to miscibility for the PAG oil used. 1. INTRODUCTION There are several reasons why oil is in air conditioning systems but one is buy far the most important: lubrication of the moving parts within the compressor, thus increasing its longevity. In some cases, oil is also used to lubricate valves throughout the system. Oil also helps to seal internal leakages within the compressor; especially for twostage compressor designs. Oil plays a necessary role in lubricating the moving parts of the compressor of a transcritical carbon dioxide air conditioning system, but, as in any other air conditioning system oil is a detriment to other components. In order to study the effects of oil, the oil concentration in the circulating charge must first be measured. Once this has been done, the effect of oil on system components can be studied. Oil increases the pressure drop of the refrigerant due to increased viscosity and due to the oil coating the interior of the pipes, thereby decreasing the effective flow area. Oil also decreases the effectiveness of heat exchangers by forming an insulating layer between the refrigerant and the heat exchanger material. The effect of oil on all of the components has an effect on overall system performance, and can be quantified using capacity and the coefficient of performance. Oil reaches other components by being drug along by the refrigerant as it flows through the system (Cremaschi). Among other candidates for R744 systems is Polyaklylene glycol (PAG) oil which is only miscible with carbon dioxide in certain conditions. When miscible, the oil gets easily carried around, but in regions of immiscibility the oil separates from the refrigerant. Such is the case in the evaporator, where the liquid oil is deposited on the walls of the tube as the refrigerant turns into a vapor. 2. SYSTEM DESCRIPTION The system used in this experiment was a prototype split system air-conditioner which utilized R744 (carbon dioxide) as the refrigerant. The real-life purpose of such a system is for residential cooling. As is common with carbon dioxide air conditioning systems, the system operates in a transcritical cycle in most operating conditions; the high side pressure being greater than the critical pressure of 7480 kpa. Since in the supercritical region pressure and temperature are independent of one another, controlling the high side pressure by opening or closing an expansion valve can be an effective control strategy. Figure 1 shows a P-h diagram of the cycle used in this experiment. For this experiment, the tests were conducted with outdoor and indoor temperatures of 35 C and 25 C, respectively. The indoor environment was dry enough so that no condensation would take place. The combined air flow rate over the gas cooler and intercooler was 0.41 m 3 /s. The air flow rate over the evaporator was 0.15 m 3 /s.

R164, Page 2 13-40 o C -30 o C -20 o C -10 o C -5 o C 0 o C 5 o C 10 o C 15 o C 20 o C 25 o C 31 o C 35 o C 40 o C 45 o C 50 o C 55 o C 60 o C 65 o C 70 o C 80 o C 90 o C 100 o C 110 o C 120 o C 130 o C 140 o C 150 o C 11.5 0.1 kj/kg-k 0.3 kj/kg-k 0.5 kj/kg-k 0.7 kj/kg-k 0.9 kj/kg-k 1.1 kj/kg-k 1.3 kj/kg 10 8.5 P [MPa] 7 5.5 1.5 kj/kg-k 4 2.5 1 x=0.1 x=0.2 x=0.3 x=0.4 x=0.5 x=0.6 0 50 100 150 200 250 300 350 400 450 h [kj/kg] Figure 1. Pressure-enthalpy diagram of employed cycle x=0.7 x=0.8 x=0.9 The compressor was a two-stage rotary piston design which could operate between 40 and 100 Hz. A speed of 70 Hz was used for this experiment. The compressor was filled with 350 ml of 46 cst PAG oil. The gas cooler was comprised of two heat exchangers joined in parallel, as can be seen in Figure 2. Both halves were of these serpentine fin heat exchanger were oriented in a cross-counter-flow orientation with respect to the air. The gas cooler had a fin spacing of seven fins per centimeter and the combined face area was 2900 cm 2. The intercooler was a microchannel design consisting of four slabs mounted in a cross-counter-flow orientation. Both the gas cooler and intercooler tubes utilized microchannel tubes. The suction line heat exchanger was made by sandwiching three microchannel layers together. The high temperature refrigerant flowed through the center layer while the lower temperature refrigerant flowed in the opposite direction in the outer layers. The evaporator was round tube-in-fin, divided up into three sections to allow as much surface area as possible in a small volume. The evaporator can be seen in Figure 2. The 7mm outer diameter tube was organized so as to make two passes. There were seven and a half louvered fins per centimeter. The face are of the evaporator was 1820 cm 2. Two-phase refrigerant entered the top of the accumulator where it was separated by a screen. Vapor, which filled the top of the vessel, exited via the tube which ran up from the bottom. A small hole was located at the bottom of this return pipe in order to return oil to the compressor. An electronic expansion valve was used to for this experiment. The stepper motor in the valve allowed the orifice to be enlarged or shrank in order to control the pressure of the refrigerant as it exited the gas cooler. The high side pressure control strategy for this system was determined empirically as shown earlier by in numerous publications and for this system by O Connor. For some of the tests, a centripetal type oil separator was used. The flow through the separator could be varied by use of a needle valve. The flow was varied in order to maintain a level of oil in a sight glass which was installed between the separator and the needle valve. Schematically, the oil separator was located between the compressor and gas cooler. The oil which was separated flowed through a mass flow meter and back to the suction line of the compressor.

R164, Page 3 Figure 2. Components with schematic of pipe routing (O Connor) 3. EXPERIMENTAL SETUP In order to minimize erroneous measurements affecting system results, three independent energy balances were utilized in this experiment. If there is close agreement between the three energy balances, then the data can be viewed as valid. All tests were conducted at steady state with the prescribed conditions. The first of these balances is the chamber side energy balance. For the experiment, there are two calorimetric chambers which are used to create the indoor and outdoor test conditions. The compressor, gas cooler, intercooler, and suction-line heat exchanger are all located within the outdoor chamber. The evaporator is located in the indoor chamber. Between the two chambers, the accumulator and an electronic expansion valve have been placed. A basic diagram of this test setup can be seen in Figure 3. The chamber is treated as a thermodynamic control volume, where the energy flows through the control volume are measured. The chambers can be forced to maintain a constant temperature by adding and removing heat. Heat is added via PID controlled electric resistance heaters and removed by a R404A refrigerant chiller system. All electric power being used within the chamber is measured by watt transducers. The chamber walls, which are constructed of foam insulation, have Type-T thermocouples attached to the interior and exterior surfaces. The conductivity of the walls has been previously determined. Knowing the conductivity allows the heat transmission to be calculated. Summing all of the energy flows through the chamber walls allows for the calculation of heat exchanger capacity.

R164, Page 4 Figure 3. Diagram of experiment setup The second energy balance is the air side energy balance, by which the change in the air s energy as it flows across the heat exchangers is measured. The air flow is directed through wind tunnels where it first passes through a grid of Type-T thermocouples. Next the air passes through the heat exchanger. Another thermocouple grid is located directly after the heat exchanger. These two grids allow for the calculation of the air s change in specific enthalpy. The mass flow rate of the air is calculated by measuring the differential static pressure across nozzles which are installed further downstream. The throat diameters of the nozzles were selected according to ASHRAE Standard 41.2-1987. Another set of thermocouples is located in the throat of the nozzles. The air flow rate is maintained at the test conditions by use of blowers that are controlled by variable frequency drives. The electric heaters which are used to maintain air temperature are located in a duct downstream of the blower. For the indoor duct, chilled mirror dew point sensors are located before and after the evaporator, which allows the change in the air s moisture content to be calculated. Both wind tunnels were calibrated in order to determine the conductance through the wind tunnel walls. All of these measurements allow the calculation of heat exchanger capacity from only air measurements. The third, and final, energy balance is the refrigerant side energy balance. One coriolis type mass flow meter is located in the high pressure line after the suction line heat exchanger. By this placement, any pressure drop can be seen as a continuation of the pressure drop which is experienced by the throttling in the expansion valve. Another mass flow meter was placed in the intermediate pressure line after the intercooler which allowed the determination of leakages internal to the compressor. Absolute and differential pressure sensors were used to determine the static pressure entering and leaving every major component. Type-T thermocouples were placed in the center of the refrigerant stream before and after each component. The locations for the pressure and temperature measurements are denoted by the dots in Figures 1 and 3. Multiplying the refrigerant mass flow rate by the enthalpy difference across the heat exchangers yields the refrigerant side energy balance. In absence of enthalpy data for the R744 PAG oil mixture, the effects of oil were taken in account in two ways: First by reducing measured flow rate by thefor oil contribution based on concentration measurement, and second by taking into account sensible heat contribution of oil flow. Heat of mixing was not taken in account. Many tests were conducted with this experimental setup mostly by O Connor, besides those tests which yielded the findings presented in this paper. Figure 4 shows the relationship between the chamber, air, and refrigerant energy balances versus the average of the three independent balances for each data point. As can be seen, all three energy measurements for the evaporator were accurate to within 10%, most within 5%. This energy transfer is also known

R164, Page 5 as the cooling capacity. The coefficient of performance (COP), is this value divided by the electrical power supplied to the compressor, which is measured by a watt transducer. Independant energy balance capacity [kw] 3.5 3.4 3.3 3.2 3.1 3 2.9 2.8 2.7 2.6 2.5 +10% +5% Air balance Chamber balance Refrigerant balance 2.5 2.7 2.9 3.1 3.3 3.5-5% -10% Average capacity [kw] Figure 4. Evaporator energy balances A great deal of effort was put into making the best possible measurement of the oil circulation rate (OCR). Some techniques have involved creating capacitance or density correlations (Cremaschi and DeAngelis), but due to time constraints, it was not possible to take enough data points to form a correlation. ASHRAE Standard 41.4-1996 gives a standardized method for measuring OCR for oils which are miscible with the refrigerant. This standard does not apply directly to the R744 with PAG oil because the combination is immiscible in many operating conditions. However, the ASHRAE standard does give some insight as to how a mixture can be sampled in order to determine OCR. In order to measure OCR, an aluminum sample cylinder with ball valves at both ends was used. Before installing the sample cylinder for each test, it was cleaned with acetone and evacuated with a vacuum pump. The cleaned and evacuated sample cylinder was weighed. The sample cylinder was then attached to the system in one of three different orientations. The first orientation, inclined downward flow, can be seen in Figure 5. For this setup, all of valves were positioned so as to force all flow to go through the cylinder. After steady state measurements had been taken, the 3 way valve was turned to bypass the sample cylinder. Immediately, the other three valves were closed. Next, the cylinder was removed and the entire sample cylinder was weighed on an electronic balance. After weighing, the cylinder was oriented vertically, and the upper ball valve was opened slightly in order to allow only the refrigerant to escape through a paper filter of known weight. After the sample cylinder reached atmospheric pressure, the paper filter was removed and weighed, to check to make sure no oil had escaped. A vacuum pump was then attached to the upper valve for fifteen minutes to pull the remaining dissolved refrigerant from the oil and to remove the gasses from the cylinder. The valve was then closed, and the sample cylinder was reweighed. By knowing the weight of the empty cylinder, the cylinder with mixture, and the cylinder with just oil, the OCR could be determined. The quantity of oil removed in the sample cylinder was replaced to the system by adding fresh oil. Besides the inclined downward orientation, other orientations were also tried as presented in Figure 6. The next orientation was similar except the refrigerant oil mixture flowed vertically downward. The third, and final, method was different from the others in that the flow did not pass through the cylinder. Instead, the cylinder with its ball valves positioned vertically above valve 3. Valve 3 was left open, and valve 2 was opened for 3 seconds. Because the mixture in the system was higher in pressure than the evacuated cylinder, the refrigerant oil mixture filled the cylinder. Both valves were then closed and the cylinder removed.

R164, Page 6 Another method of measuring the compressor s OCR was also employed. When the oil separator was installed for some tests, the mass flow of the separated oil could be divided by the total mass flow from the compressor. With this technique, the oil separator is often assumed to be completely effective at separating oil and refrigerant. Figure 5. Inclined downward sample cylinder orientation, with valves (O Connor) Figure 6. Orientations of the sample cylinder with valves

R164, Page 7 4. EXPERIMENTAL RESULTS The technique used to measure OCR had a sizable effect. A table showing the data collected from the three sample cylinder techniques can be seen in Table 1. Since all points were run at the same test condition with the same oil and refrigerant charges, it is believed that the actual OCR did not change; the difference was only from the experimental technique. A plausible explanation for the differences is in immiscible combination of R744 and PAG in the operating regime. As can be seen, the results with flow through the cylinder are close to one another; however there is a large standard deviation for both of these measurements. The upward sample cylinder which was only opened at one end measured a larger OCR, but with a much smaller standard deviation. Since this result gave a far smaller deviation, it is believed that this technique gives the most repeatable results. Therefore, this technique was the only one which was used when the oil separator was installed. All test setups have an unknown offset error. Table 1. Results of varying sample cylinder orientation on determined OCR Experimental Setup Average OCR [%] Standard Deviation Sloped downward flow 3.75 0.72 Vertical downward flow 3.53 0.89 Vertical upward, dead end 5.30 0.33 After placing the oil separator in the system, the vertical upward sampling technique yielded an OCR of 1.51% with a standard deviation of 0.62%. The separator efficiency was found to be 72%. This is the amount of oil which the separator short circuits back to the compressor. Conversely 28% of the oil still went throughout the system. With the oil separator installed it was also possible to approximate the OCR produced by the compressor. The mass flow rate of the saturated oil, which was separated, was found to be 2.51% with a standard deviation of 0.20%. However, if this separation efficiency is taken into account, the OCR of the system without the oil separator would have been 3.5%, which is in line with the data found in Table 1. This technique was the simplest, but requires sample cylinder testing in order to determine the separation efficiency. This efficiency also may change as the difference between the refrigerant and the oil densities changes. This is due to the physics involved within the separator mechanism. Using the energy balances described in the experimental setup, it was possible to measure the effect of reducing the oil circulation rate on the performance of various system components. The approach temperature of the gas cooler, which is the difference between the air temperature entering the gas cooler and the refrigerant temperature leaving the gas cooler was reduced from 1.46 C to 1.10 C. A lower approach temperature is preferred because it means that the gas cooler is allowing the refrigerant exiting the gas cooler to approach the theoretical minimum. A reason for this decrease may be that the oil layer which forms on the walls of the condenser is thinner, causing a smaller thermal resistance, thus allowing more heat transfer. Similarly, the refrigerant pressure drop in both the evaporator and the gas cooler was reduced. In the evaporator the pressure drop was reduced by 23%, from 43 kpa to 33 kpa, by installing the oil separator. In the gas cooler, the pressure drop was reduced from 75 kpa to 62 kpa, or 18%. There are a couple reasons why this may have occurred. Again, a thinner oil film inside the tubes allows less restricted flow of the refrigerant. Secondly, the viscosity of the refrigerant-oil mixture is reduced. A reduced pressure drop is preferred because it reduces the amount of work which must be done by the compressor. Also, a reduced pressure drop is preferred in the gas cooler, because it allows for a greater decrease in refrigerant enthalpy when the approach temperature is constant. The effect of OCR on system performance can be seen by studying the energy balances. The evaporator showed only a 20 W increase in cooling capacity, which is about 1% improvement. There are several reasons why even though the component performance. One is that the oil separator lowers the pressure of the refrigerant in the gas cooler. Also, the oil separator reduces the mass flow through the heat exchangers by about 2%. Finally, the compressor is forced to work harder in order to overcome the pressure drop in the oil separator. This can be seen by a decrease in the coefficient of performance (COP) by 6.4%.

R164, Page 8 CONCLUSION The technique used to determine the oil circulation rate (OCR) had a large impact on results. Using the same sample cylinder but in different orientations affected the measured OCR by as much as 50% at the low OCR found in this experiment. It was found that the most consistent reading was found when the sample cylinder was mounted vertically upward into a dead end. This orientation also gave the largest OCR result. Having the mixture flow through the sample cylinder was shown to be less repeatable and comprised the lower limit. If an oil separator with a known separation efficiency is used, mass flow meters may be utilized in order to show the OCR that would have been present had no mass flow meter been used. Decreasing the oil circulation rate was shown to increase component performance. Pressure drop in the heat exchangers was greatly reduced. The approach temperature in the gas cooler was also reduced substantially. However, oil effects on the system showed little or adverse effects when an oil separator was installed. The cooling capacity of the system increased a hair while the coefficient of performance was slightly worse. Therefore, it is not advantageous to add an external oil separator to the system. However, because measures of component performance generally increased with lower OCR, it would be advantageous to design an oil separator with lower pressure drop, or else produce a compressor with the smallest possible portion of oil allowed to flow through the system. REFERENCES ASHRAE, 1992, ANSI/ASHRAE 41.2-1987 Standard Methods for Laboratory Airflow Measurement, Atlanta, 32. ASHRAE, 1996, ANSI/ASHRAE 41.4-1996 Standard Method for Measurement of Proportion of Lubricant in Liquid Refrigerant, Atlanta, 5. Cremaschi, L., Hwang, Y., and Radermacher, R. 2005, Experimental investigation of oil retention in air conditioning systems, Int. J. of Refrigeration, V 28, p. 1018-1028. DeAngelis, J. and Hrnjak, P. 2005, Experimental Study of System Performance Improvements in Transcritical R744 Systems with Applications to Bottle Coolers, ACRC CR-57, Urbana, IL, 140. O Connor, T. 2005, Experimental Investigation of a Prototype Transcritical R744 Air-Conditioning Split System for a Small Residential Application, University College, Dublin, 176. ACKNOWLEDGEMENTS The authors would like to acknowledge the equipment donations from Sanyo Electric and Modine Manufacturing Companies, as well as other members of the Air Conditioning and Refrigeration Center at the University of Illinois in Urbana-Champaign. A great deal of insight to this experiment was provided by Donal Finn, Stefan Elbel, and Christopher Seeton. A special thanks to Thomas O Connor, for allowing time in his laboratory and providing model templates.