Installation Instructions

Similar documents
Installation Instructions

Installation Instructions

Installation Instructions

Owner s Manual & Installation Instructions

Total Comfort TC Series Air Handler

PCAH SERIES AIR HANDLER

INSTALLATION INSTRUCTIONS

Technical Data Manual Model Nos. and pricing: see Price List

Installation Instructions

CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH CAH

INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER

Operation & Maintenance Manual

Installation Guide. Dehumidification. Fresh Air Ventilation. Compact Size. Energy Efficient. RXID-AW90A Whole House Dehumidifier

ECAH SERIES ECM AIR HANDLER

Easy installation in both new construction and retrofit. ZB90C ZB110C X2 Multi-Speed Ventilation Fan INSTALLATION GUIDE

WMWLB / WMWFM / WTWLB / WTWFM Series Hydronic Heating Unit

Installation & Maintenance Instructions

Owner s Manual Phoenix Aquadry TX 200

Quest Power Electric Heat EHS 31 Pro

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

Owner s Manual Phoenix FireBird

Model 8140 & 8141 Fresh Air Ventilator Installation and Operations Manual

Vertical Stack Fan Coil Units Models: TVA, TVE, TVS

Service Manual ES50LVS / ES90LVS MULTI-SPEED AIR HANDLER. Ecosmartair 105 Haist Avenue, Unit 10 Vaughan, ON L4L 5V ecosmartair.

Installation Instructions

Quest PowerHeat HFC 100 Pro

VENTILATION FAN WITH LED LIGHT AND HEATER MODEL RAD110LED

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

"SWVP - SWHP" COMMERCIAL WATER SOURCE HEAT PUMPS & AIR CONDITIONERS

SECTION AIR HANDLING UNIT

TEMSPEC INC. VERTICAL FAN COIL UNIT MODELS TVA, TVE, TVS

MX Series Indoor Modular Blowers Electric Heat, Hot Water Heat, or No Heat

Healthy Climate Whole-Home Dehumidifier. Nominal Capacity - 70 to 130 pints per day INDOOR AIR QUALITY HCWHD PRODUCT SPECIFICATIONS.

READ AND SAVE THESE INSTRUCTIONS

AIC Brazed Plate Heat Exchanger Operating and Instruction Manual

DBF 4XL Dryer Booster Fans

Section 1 - Safety Information Section 2 - Installation: Wall Mount Hoods Section 3 - Installation: Island Mount Hoods

Quest Power Electric Heat EHS 62 Pro

e Heater/Exhaust Fan/Light User s Guide

JH Series Installation

R Series Cooling Manual

Low Temperature Stainless Steel Panel Series Installation and Commissioning Guide

Total Comfort TC Series Air Handler

SECTION SPECIFICATION FOR HI-VELOCITY FAN COIL SYSTEMS

INSTALLATION INSTRUCTIONS FOR FANLESS MAKE-UP AIR MODEL NER (USA)

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.

Installation Instructions Remote Blowers

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer

Bathroom Exhaust Fan

Viessmann B1HA Boiler Series

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

RSIF Power Venter USA CAN. Product Information. ... Chapters Mechanical Installation. ... Chapter 3. Electrical Installation. ...

Air Bear Accu-Fit TM. Media Air Cleaner READ AND SAVE THESE INSTRUCTIONS UNITS NOT FOR COMMERCIAL USE. TRION

Owner s Manual Refrigerated Compressed Air Dryers Models F-3528, F-3529, F-3530, F-3531 & F-3532

SH, VH & SE Models. SH, VH & SE Series Heat & Energy Recovery Ventilators IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT

MODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM

INSTALLATION AND OPERATION GUIDE

e Bath Fan with Light User s Guide

e Bath Fan with Light User s Guide

READ AND SAVE THESE INSTRUCTIONS READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT DESCRIBED. PROTECT YOURSELF AN

Owner s Manual Refrigerated Compressed Air Dryers Model F-100

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

ULTRA SILENT VENTILATION FAN READ AND SAVE THESE INSTRUCTIONS WARNING CLEANING & MAINTENANCE OPERATION CAUTION!

ENGINEERING SPECIFICATIONS

TWIN-FLOIII HEATER INSPECT THE SHIPMENT IMMEDIATELY WHEN RECEIVED TO DETERMINE IF ANY DAMAGE HAS OCCURRED DURING SHIPMENT.

ENGINEERING SPECIFICATIONS

Advance Release September 2009

HPS Controls Ltd. Series 600 LFI / CFI Series 700 HFS Zone Control Stations. Heating and Radiant Floor Zone Control Stations

Comfort Series Instant Hot Water System

Your Solar Home Inc. SolarSheat Hot Water System. Installation, Operation and Maintenance Manual

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

e Bath Fan with Light User s Guide

Surna 25-Ton Chiller Operating & Maintenance Manual

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

B SERIES ELECTRIC FURNACE

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

VENTILATION FAN WITH LIGHT AND HEATER

MPA Modular Plenum Array Installation, Operation, and Maintenance Manual

COMBUSTION AIR SYSTEM Model: CAS-3

R Series B & T2 Model

Owner s Manual Refrigerated Compressed Air Dryer Model F-50

Service Step by Step Trouble-Shooting Check-List

HUMIDITY SENSING BATH FAN

HB CDA SERIES WITH TEMPERATURE SETBACK

ISERIES VERTICAL AHU ENGINEERING SPECIFICATIONS

HEX390 Heat Exchanger

Electric Duct Heaters

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Chilled Water DOAS Fan Powered Terminal Units

HPS Controls Ltd. Series 100 LTV / CTV Zone Control Stations. Heating and Radiant Floor Zone Control Stations. Installation Instructions

INSTALLATION INSTRUCTIONS FOR MINI MAKE-UP AIR MODEL FER

DIGI3U. Zoning Systems. Installation Guide. That s all we do. Three-Zone, Universal Controller for Gas/Electric or Heat Pump Applications

SAFETY AND INSTALLATION MANUAL MODEL 8100

Safety & Installation Instructions

IMPORTANT INSTRUCTIONS - OPERATING MANUAL

DOLE REFRIGERATING COMPANY 1420 Higgs Road Lewisburg, Tennessee Phone (931)

The Premium Quality Fan Coil Units for Vertical, Horizontal (Left or Right) Application with Direct Expansion, Hydronic or Electric Heat

SKYPAK II, 3 Ton Series, gives you a

Transcription:

Installation Instructions Make Up Air Unit with high efficiency EC motor 45 Cowansview Rd. Cambridge, Ontario N1R 7L2 Phone: 888-781-8151 Fax: 888-670-2544 info@vortexsource.com www.vortexsource.com MUA-1402

Table of Contents TYPICAL APPLICATION... 4 ELECTRICAL WIRING DIAGRAM... 6 PHYSICAL PROPERTIES... 7 INTRODUCTION... 8 HOW IT WORKS... 8 PRODUCT DESCRIPTION... 8 CABINET... 8 HEATING COILS... 8 FAN AND MOTOR... 8 CIRCULATING PUMP... 8 CHECK VALVE... 9 CONNECTING TO A BOILER... 9 EQUIPMENT SIZING AND DESIGN... 9 DUCT LAYOUT... 9 PLUMBING LAYOUT... 10 INSTALLATION... 11 AIR HANDLER MOUNTING... 11 DUCTWORK... 11 PLUMBING... 12 ELECTRICAL... 12 LOW VOLTAGE... 12 CONTROL PROGRAMMING... 13 START-UP PROCEDURES... 13 SERVICE AND MAINTENANCE... 14 TROUBLESHOOTING... 14 DOES NOT COME ON WITH EXHAUST FAN... 14 PUMP DOES NOT RUN... 14 PUMP IS NOISY AT START-UP... 15 INSUFFICIENT OR NO HEAT... 15 HEATING DURING STANDBY MODE OR IN THE SUMMER... 15 MAKE UP AIR UNIT PARTS & ACCESSORY LIST... 16 PRODUCT WARRANTY... 17 2

Important notes For the Installer A Quick Check List Is the purge valve installed on the return line from the air handler upstream from the isolation valve? Is the system filled with anti-freeze? Is the air handler hung and isolated to avoid transmitting vibration through framing and duct work? Or is it installed on a housekeeping pad? Are the isolation valves full-port? Restrictive valves will limit performance. Is the low-voltage interconnect to the exhaust fan complete? Have the packing materials been removed from the blower and the pump? Is there an installation manual for the home owner? Is the unit accessible? Are there clearances for service and component replacement? Is the ductwork sealed? Is the intake insulated to at least R12 (RSI 2.1)? Is the filter cover in place? Is a clean filter in place? Is the supplied filter rack installed? 3

TYPICAL APPLICATION 4

5

ELECTRICAL WIRING DIAGRAM 6

PHYSICAL PROPERTIES Plumbing Amps Maximum Airflow (cfm) MUA700C-EC ½ 4 700 MUA1300C-EC ½ 6 1300 MUA800-EC ¾ 4 800 MUA1400-EC ¾ 6 1400 MUA2000-EC 1 12 2000 Catalogue No. MUA800 MUA700C MUA1400 MUA1300C MUA2000 Cabinet dimensions (in.) w d h Supply air Return air Shipping info. Weight (lb.) Dimensions fan box 14 20 24 12 x16 14 x18 70 15 x23 x27 slab coil 5 23 18 12 x16 14 x18 22 6 x15 x24 fan box 22 25 31.5 20 x20 18 x23 90 23 x25 x35 slab coil 5 25 22 20 x20 18 x23 32 6 x23 x26 fan box with slab 22 25 51 20 x20 18 x23 120 23 x25 x52 coil Minimum Boiler Capacity Required in MBH Outdoor Design Air Temp. MUA800 1 MUA1400 1 MUA700C 2 MUA1300C 2 MUA2000 3-5C 23F 42 74 37 68 102-10C 14F 50 87 44 81 122-15C 5F 58 101 50 94 141-20C -4F 65 114 57 106 161-25C -13F N/R N/R 64 119 180-30C -22F N/R N/R 71 131 200-35C -31F N/R N/R 78 144 219-40C -40F N/R N/R 84 157 239-45C -49F N/R N/R 91 169 258-50C -58F N/R N/R 98 182 277 1. MUA800 and MUA1400 based on 30% glycol and 160F minimum boiler water temperature. 2. MUA700C and MUA1300C based on 50% glycol and 140F minimum boiler water temperature. 3. MUA2000 based on 50% glycol and 160F minimum boiler water temperature. 7

INTRODUCTION Make up air units are designed to replace the air exhausted by a large exhaust fan with fresh air from the outdoors. The outdoor air is heated to room temperature but it is not meant as a heating system.. HOW IT WORKS The exhaust fan should be inter-locked with the make-up air unit so that when the exhaust fan comes on, the make-up air fan also comes on to replace the exhausted air. There are five different air flow volumes that can be selected at the time of installation. The selected air flow should match the exhausted air flow. If the air temperature from outside is below the setpoint (usually room temperature), a pump will come on to circulate hot anti-freeze fluid from a boiler. The pump will normally cycle on and off to try to maintain the proper supply air temperature without overheating. Models 700C and 1300C are designed for cold climates where the outdoor temperature may drop below -20C (-4F). If the first (external coil) has insufficient capacity to heat the air on very cold days, a second internal coil and pump will activate to heat the air. PRODUCT DESCRIPTION Cabinet All cabinets have a tough, durable low maintenance pre-painted finish. Cabinet dimensions are designed to provide maximum installation flexibility. Refer to installation requirements for more details. Heating Coils All heating coils are potable water grade copper suitable for use in plumbing systems. No lead solder is used in any component construction. All coils and internal piping conform to ASTM B68 or ASTM B88 standards. High-density aluminum fins provide maximum heat transfer for small coil surface. Fan and Motor All fans are wide body dynamically balanced for extra quiet operation. Multi-directional sleeve bearing motors allow mounting in any direction for maximum installation flexibility. The blower motor is an energy efficient EC motor Circulating Pump 8

The circulating pump is matched for maximum performance. The external coil is supplied with a field installed external pump. Cold-weather MUA units include an internal coil with factory installed internal pump. Check Valve The check valve is in the pump union at the outlet. Check valves protect against thermal siphoning. Thermal siphoning is flow of fluid through the hydronic circuit while the circulating pump is not operating due to hot fluid rising by natural convection. During summer months this will cause overheating, interfere with air conditioning and waste energy. All systems come supplied with spring loaded, vertical lift check valves. These check-valves have been tested and proven to resist thermal siphoning for installations where the air handler elevation does not exceed the distance above the boiler shown in the table below. Check Valves valve size 1/2 (12mm) 3/4 (20mm) Connecting to a Boiler Maximum elevation 25 feet(8 metres) 50 feet(15 metres) All make up air systems are compatible for use with boilers. Refer to the standard installation drawings. Note: if the anti-freeze solution is not permitted or desired in the boiler, an isolating heat exchanger and possibly an additional pump may be required. Standard drawings are available from Vortex for most boiler applications. EQUIPMENT SIZING AND DESIGN Proper sizing of system components is crucial for proper operation. Steps for sizing and selection: 1) Determine the airflow of the exhaust fan (cfm) 2) Obtain the Winter outdoor design temperature. 3) Select model from specification sheet or physical properties table. 4) Select a boiler of suitable capacity based on the boiler capacity table. 5) Determine duct layout. 6) Determine plumbing layout. Allow for glycol/antifreeze fill/ purge/ isolation from the rest of the hydronic system. Duct Layout Make sure a proper duct design has been completed for the dwelling using HRAI, ASHRAE or other approved design method. For the purposes of duct design, determine air handler mounting/orientation. The air handler may be mounted upflow, downflow or horizontally. The cased slab coil may be 9

mounted on either side of the air handler or bottom or back. Supply Air Plenum Provide a supply air plenum that is the same dimensions as the outlet flanges of the air handler. A length of 36 inches is recommended. Acoustic lining is recommended. A smooth, square-to-round transition may be used in place of the supply air plenum for horizontal installations where there is only one supply main. Plenum takeoffs may be mounted on the end of the plenum or the sides of the plenum, but not both. Spin-in collars or transition takeoffs may be used, but not both. Supply mains Plan duct layout to avoid branch runs in outside walls or attics and to minimize the length of the main duct However, 1 or 2 elbows (main + branches) and a minimum length of 10ft. (3 m) is recommended to reduce noise. Supply mains may be round duct or equivalent rectangular duct. Round duct can be spiral duct, welded or snap lock seams. Rectangular duct must be at least 26 gauge for all dimensions. The aspect ratio for square ducts (wide dimension over short dimension) shall not exceed 2.5 to 1. Supply Branches One or several branches and grilles are acceptable provided the grilles and branches meet the capacity required. Note: Supply air temperatures vary greatly during operation and could be as low as outdoor temperatures for brief periods. Supply grilles can be located almost anywhere with the following recommendations: avoid areas that may blow onto occupants high wall across a ceiling is acceptable close to the exhaust source (eg. Kitchen) or an adjacent low occupancy space such as hall or vestibule. Avoid rooms with doors that could isolate the supply from the exhaust Return/Intake air duct The return air duct should be sized for a total pressure drop of not more than 0.15 w.c. Using conventional sizing methods and installed in accordance with HRAI guidelines or equal. All return (fresh air) duct must be insulated to a minimum of R12 (RSI 2.1). A motorized damper at the intake is acceptable. A 24VAC motor is recommended. Ensure the power rating does not exceed transformer capacity (40VA) or isolate the damper circuit from the air handler.. Plumbing Layout Refer to the plumbing diagrams as a guideline. Any suitable hydronic pipe is acceptable for use with the MUA unit. Do not exceed 150 psi or 180F (82C). The boiler, piping or other components may have more restrictive ratings. 10

Size piping to match MUA unit sizing. Increase one pipe size if distance from boiler exceeds 25ft. or size pipe according to an accepted design method. Include expansion tank, pressure relief valve, pressure gauge and a suitable antifreeze fill system. Some of these may be included in the boiler. Include drains at system low points and manual air vents at high points as required. A temperature gauge near the inlet to the MUA unit is recommended. 15psi is the minimum recommended design pressure for proper pump operation. Higher pressure may be necessary for systems of significant elevation e.g. basement to attic. INSTALLATION The installer must adhere strictly to all local and national code requirements pertaining to the installation of this equipment. Detailed instructions are shipped with all accessory items and should be followed in detail. Air Handler Mounting The air handler can be installed in any direction. Its compact dimensions even allows for installation between joists (some models). The air handler can be floor mounted or hung from straps. Some precautions must be observed for some of the possible mounting positions. For installations where the access door faces up or down, select an air handler with an external pump to avoid the pump being mounted with its shaft vertical. The pump shaft must be mounted horizontally to avoid premature failure. The air handler can be hung by securing straps through any of the existing screw holes in the cabinet. When the existing screw is too short for securing a mounting strap, a longer screw can be used provided care is taken not to damage any internal components. When fastening straps using screws other than those supplied with the cabinet, special care should be taken in the vicinity of the coil to avoid tube puncture. Warning!: Do not put screws into the cabinet directly in front of and behind the coil. 3/4 screws can be safely installed on either side of the coil. The cabinet is designed so that the return air can be located on either side of the cabinet, through the bottom of the cabinet, or from the back. Position the filter rack so that the filter is readily accessible. Install the air handler with the door firmly screwed in place to make sure the cabinet remains square. Provide at least 2 feet (0.75 m) of service clearance in front of the access panel of the air handler. Zero clearance is acceptable on all other faces. For floor installations, a minimum 2 housekeeping pad is recommended. Ductwork General SEAL all joints and seams with metal tape or sealing compound. Ductwork installed in unheated spaces such as 11

attics must be installed between the insulation and the heated space. Provide at least R-12 of insulation above ducts. If cooling is required, the branch and trunk lines must be insulated and sealed with a vapour barrier prior to applying house insulation. Supply Ductwork Supply trunks may be square or round. Volume dampers for each of the main supply trunks must be accessible for balancing. (Near the supply plenum is preferred) Locate outlets at least 6 inches from outside walls or window coverings. Return/Intake Ductwork All return/intake ductwork must be insulated to a minimum of R12 (RSI 2.1) with continuous vapour barrier on the outside. Return air plenum should be the same cross sectional area as the air handler return air opening. In vertical installations, a conventional return air drop and elbow is acceptable. Plumbing Refer to the plumbing diagrams as a guideline as well as the design section. ELECTRICAL Warning! - Make sure unit is properly grounded. Locate air handler on a separate electric circuit, or use the same circuit as the water heater or boiler where permitted. Air handler wiring diagrams are located on the blower or door for easy reference during installation and servicing. Nameplate data is located on the side of the unit. All air handlers operate on 115VAC/1ph/60hz line voltage. All control circuits are 24 VAC. One leg of the 24 VAC is grounded to the chassis. Low voltage Make up air units operate on 24VAC using an internal 40VA transformer To operate, an external switch with no voltage is required between R and the desired fan speed (20/40/60/80/100). A 115VAC isolating relay at the exhaust fan may be required. Refer to its manual. Select the airflow which is equal to or slightly less than the exhaust fan capacity. For example: 600 cfm for MUA 800 : 800 cfm x 60% = 480 cfm; for MUA 700C : 700 cfm x 80% = 560 cfm. Boiler The yellow wires labeled TT on the relay are dry contacts for connection to a boiler or external pump. Contacts are rated for up to 240vac and up to 10Amps. 12

CONTROL PROGRAMMING Control setup can be found on the inside of the air handler door. Display shows actual temperatures To change settings: Hold both arrow keys to change ºF to ºC Press MENU and use up and down arrows SP = Set point dif = differential ASd = anti-short cycle delay SF = sensor failure OFS = offset (not used) Factory Settings 1 st Stage Temperature SP= 70ºF dif= 1ºF ASd= 1 (minute) SF= 0 (off) 2 nd Stage Temperature (cold climate units) SP= 68ºF dif= 1ºF ASd= 1 (minute) SF= 0 (off) START-UP PROCEDURES Do not start the air handler or boiler until ALL air has been purged! 1.Fill the loop with antifreeze solution but do not start the system. 2.Purge all air from the boiler system. Run all pumps with the boiler heating off. If significant air noise is heard, repeat the purging procedure. 3. Purge all air from the make up air unit hydronic loop by closing the isolation valve on the return leg of the loop and open the drain to purge air. Open the return leg isolation valve and then close the drain valve. For cold climate models, purge one coil at a time. 15psi is the minimum recommended pressure. 4. Turn on the power to the air handler and set the room thermostat for heat to energize the fan and pump. If a gurgling sound is present, it should subside within one minute. If noise is still present after one minute, repeat step 3 to purge air as necessary. 5. Start the boiler according to the manufacturer s instructions. Set the design water temperature and wait for the system to shut off. 6.Check pipes for heating to make sure there is flow (warm pipes). 13

SERVICE AND MAINTENANCE Filter The air handler is provided with a highefficiency, pleated filter. This filter should be inspected monthly and replaced as required. Replacement filters are available from Vortex. Duct cleaning If proper filter maintenance is adhered to, duct cleaning will not be required for the life of the equipment. Coils Air conditioning and heating coils should not require cleaning if the filter maintenance schedule is adhered to. If a filter is damaged or collapses from plugging, dust may foul the coils. If this happens, replace the filter and carefully vacuum the heating coil. The fan may need to be removed to gain access to the face of the heating coil. Fan and motor Check fan for dust once a year. If dirty, vacuum to remove dust. Keeping the fan blades clean will reduce noise and improve the capacity and efficiency of the heating system Pump The circulating pump is water lubricated and should require no regular maintenance. The system control may have an optional cycle timer to exercise the pump even during prolonged periods of no heat to avoid seizing from long idle periods. TROUBLESHOOTING Does not come on with exhaust fan First, review How It Works on page 9 for normal operation. Frequent pump cycling is normal. For testing purposes, disconnect the existing external low voltage wires and jumper between R and any speed (20/40/60/80/100). If everything works normally, the problem is the external switch at the exhaust fan or the wiring to the MUA unit. Pump does not run Check control settings. In areas where hard water is present the pump may stick and fail to run. Often, closing the isolation valve on the return leg and opening the drain port so that water flows through the pump can free this. If this method fails to free the pump, removal for cleaning or replacement is 14

necessary. The daily pump exerciser will help prevent pump sticking. Pump is noisy at start-up Air is present in heating loop. If sound has not diminished within 1 minute, purge air in accordance with the Start-Up procedures Insufficient or no heat Plugged air filter or coil. Refer to Maintenance section for filter care and coil cleaning. Air in heating loop; purge system. Inlet and outlet connections to air handler backwards; reverse connections. Supply fluid temperature set too low or not calibrated properly; check temperature. Restrictions in heating loop; remove restrictions, check valve stuck, isolation valves too restrictive, left partially closed after purging or closed valve. Heating during Standby Mode or in the Summer Check control settings Probable cause is thermal siphoning. See check valve description for details; repair or replace check valve. Check elevation of air handler above boiler to see if motorized valve required for positive shut-off. 15

Part No. MAKE UP AIR UNIT PARTS & ACCESSORY LIST Description MUA700C MUA800 UC12163 Hot Water Coil -- 12 x16 S UC12163ASS Coil assembly c/w pump-12x16 S MUA1300C MUA1400 UC18203 Hot Water Coil 20 x18 S UC18203ASS Coil assembly c/w pump-18x20 S UC18304 Hot Water Coil 30 x18 S GUPS15-58RUC Pump-Grundfos c/w check S S GUPS26-99BFC Pump-Grundfos c/w check S TC024 Pump Control 24VAC S S S XPLC004 Vertical lift check valve 1/2 A XPLC006 Vertical lift check valve 3/4 A A XELR024DPDT Pump Relay 24VAC S S S XELR01TIMER Cycle Timer/Pump Exerciser O O O XELT002 Transformer 24VAC, 40 VA S S S XELD002 Door interlock switch S S S XECM03 EC Blower motor -- -1/3 HP S S XECM04 EC Blower motor -- -1/2 HP A XECM06 EC Blower motor -- -3/4 HP S XBLF105T Blower 10x5T DD S XBLF108 Blower 10x8 DD S XBLF128T Blower 12x8T DD S XELH610 Wire Harness - control S S S XELH620 Wire Harness - power S S S PME01 PME02 CPVA04 CPVA06 External pump module, ½ plumbing c/w check valve External pump module, 3/4 plumbing c/w check valve Valve Assembly 1/2 full port sweat ball valves plus hose Valve Assembly ¾ full port sweat ball valves plus hose S=Standard, A=Alternate, O=Option or Accessory O O MUA2000 O O O O O O O 16

PRODUCT WARRANTY This product is warranted by Vortex Source Systems to be free from defects in materials and workmanship that affect product performance under normal use and maintenance within the applicable periods specified below. Replacements furnished will carry only the un-expired portion of the original warranty. Two-Year Parts Vortex Source Systems will provide replacement parts for ANY part that fail within two years of purchase, subject to the terms below. Five-Year Parts Vortex Source systems will provide replacement parts for any heating coils, cabinetry and piping that fail within five years of purchase, subject to the terms below. Terms Reasonable proof of original purchase date must be provided in order to establish the effective date of the warranty, failing which, the effective date will be based on the date of manufacture plus thirty days. The warranty does not cover failure or damages caused by: improper installation or operation accident, abuse or alteration operation of device at temperatures or pressures outside of the rated capacities lime or scale deposits corrosive operating environment equipment moved from original installation location Replacements furnished under this warranty will be F.O.B. Vortex Source Systems product distribution points in the United States and Canada. They will be invoiced at regular prices. The account will be credited the full amount when the defective part is received by Vortex, examined and approved as a valid warranty. Warranty applies to the original purchaser, but may be transferred to another owner provided the equipment is not moved from the original installation site. This warranty does not apply to labour, freight or any other cost associated with the service repair or operation of the product. Vortex shall not be liable for any direct, special, incidental or consequential damages caused by the use, misuse, or inability to use this product. Vortex is under no legal obligations to rectify, including but not limited to, lost profits, downtime, good will, damages to, or replacement of equipment and property Purchaser assumes all risk and liability of loss, damage or injury to purchaser and purchaser s property and to others and their property arising out of the use, misuse or inability to use this product. 17