BETA REV series kw. General High energy efficiency, personalised chillers and heat pumps with scroll compressors for indoor installations.

Similar documents
TETRIS 2 series. 84 to 913 kw

Zeta Rev HE FC kw

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

Tetris W Rev kw

BETA ECHOS. Air/water cooled chillers and heat pumps kw. General BETA ECHOS is a range of chillers and ductable air-water heat pumps.

Tetris 2 FC series kw

ZETA REV HP XT kw

Zeta Rev HEi FC kw

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Water chillers water/water type SIGMA Technical information manual

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

Omicron Rev S kw

Blue Box Epsilon Echos +

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

LZT High efficiency air to water heat pumps with E.V.I. compressors

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES

LZA High efficiency air to water heat pumps with HP compressor

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR

Omega Sky. Indoor water-condensed liquid Chiller kw. Technical information manual

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

LSA LSA A + Air cooled water chillers with axial fans VERSIONS ACCESSORIES

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

CRIMSON & CRIMSON MAX

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 385 kw. Scroll Compressors SCAEY-FC DE 98

Большая библиотека технической документации каталоги, инструкции, сервисные мануалы, схемы.

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

LDK LDK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

ERAH MC Ka. Range kw. AIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS FOR OUTDOOR INSTALLATION (Standard line)

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS

Air cooled chillers. Air cooled chillers with brushless oil-free compressors. RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

PRODUCT GUIDE

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw. Scroll Compressors SCAEY-FC DE 98

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata

Aquaflair TRAC-TRAF-TRAH

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw

PYXIS U PYXIS U. rcgroupairconditioning

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB

LSK LSK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

pyxis u pyxis ua NEW rcgroupairconditioning

Air Cooled Chillers & Heat Pumps WinPACK HE-A

LZT High efficiency air to water heat pumps with E.V.I. compressors

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB

Galletti Water chillers and heat pumps catalogue

pyxis pyxisa NEW rcgroupairconditioning

KELVIN Clim F497. Kelvin air conditioning

kw COOLING kw HEATING

black Thermal power (A7:W45) kw Cooling power (A35;W7) kw

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS

Air cooled industrial chillers

FHE FHE. Dehumidifiers for radiant cooling systems with heat recovery. Versions

unico pf unico pf rcgroupairconditioning

1

RTA TECHNICAL MANUAL AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION O L S E A F RA N

LZT LZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSION ACCESSORIES

pyxis cla pyxis cla A-CLASS NEW rcgroupairconditioning

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw

21,8 222 kw COOLING 25,2 236 kw HEATING

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).


pyxis hp "u" pyxis hp "u" IDEA NEW rcgroupairconditioning

Ultimate energy saving technology

BRH. Climaveneta Technical Bulletin. Water-cooled liquid chillers ,5-35,1 kw. Versatile High efficiency Maximum silent-running

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

WZT High Efficiency Air to Water Split System Heat Pumps With E.V.I. Compressors

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ

NECS-N. Climaveneta Technical Bulletin. Reversible unit, air source for outdoor installation. 0202T T kw

44,9 202,0 kw. technicalcatalogue

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

EQSL TECHNICAL CATALOGUE AIR COOLED WATER CHILLER UNITS AXIAL FANS. Models: 300 V2 F V2 F16. Cooling capacity: 299 to 1310 KW

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01

O L R E RGA ST RA N AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION TECHNICAL MANUAL

ELFOEnergy Duct Inverter

RMA AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

NECS-N. Climaveneta Technical Bulletin. Reversible unit, air source for outdoor installation. 0202T T kw

H4T R410A. refrigerant

NEXT EVO DXR410A NEXT EVO DX NEW SOFTWARE. rcgroupairconditioning

LER kw. Indoor motor-driven evaporating units. Motor-driven evaporating units LER PLUS

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

Modular Air-cooled Chillers

GLIDER EVO FREE GLIDER EVO FREE GLYCOL FREECOOLING. rcgroupairconditioning

WZH Ground source heat pumps

GLIDER EVO GLIDER EVO. rcgroupairconditioning

Transcription:

series 40 240 kw General High energy efficiency, personalised chillers and heat pumps with scroll compressors for indoor installations. Configurations HP: heat pump SLN: Super Low Noise LE: condensing unit LE/HP: reversible condensing unit RFA: setup with AC radial fans RFE: setup with EC radial fans DS: Desuperheater DC: Heat exchange condenser Pump and integrated buffer tank available as option Strengths Unit with Night Shift function Advanced control always available as option Multilogic Integrated hydraulic modules also with a buffer tank. Three types of pumps: standard, oversize and for high percentages of glycol (e.g. up to 50%). Availability of pumps with inverter on user side. Setup with AC or EC radial fans

2

SPECIFICATIONS Water chiller unit with hermetic scroll compressors, air heat rejection with centrifugal fans and user-side plate heat exchanger. Refrigerant fluid: R410A STRUCTURE The structure of the unit is made of galvanized sheet-iron coated with polyester powder RAL 7035/5017 at 180 C, which makes it highly resistant to weather conditions. The structure is a load-bearing frame, with removable panelling lined with sound absorbing expanded polyurethane matting. All screws and bolts are stainless steel. COMPRESSORS The compressors are hermetic orbiting spiral scroll compressors connected in tandem. They are provided with oil level sight glass, internal Klixon thermal overload protection or external Kriwan module (depending on the model) and oil equalisation line. The compressors are enclosed in a dedicated technical compartment, which can be accessed by removing the panelling that allows maintenance operations to be carried out even with units running. All the compressors are fitted as standard with crankcase heater. SOURCE-SIDE HEAT EXCHANGER For the cooling only units, the exchangers are made with microchannel aluminium coils. For /HP units, finned pack coils with copper tubes and aluminium fins are used. These also have a special circuit for keeping the lower part of the coil free of ice by circulation of gas at high temperature. Thanks to continuous research in the field of metal alloys and to sophisticated production methods, microchannel coils are made using specific aluminium alloys for the tubes and for the fins. This allows the effects of galvanic corrosion to be drastically reduced to always ensure protection of the tubes that confine the refrigerant. Tubes and fins are also subjected to SilFLUX coating processes (or equivalent) or have zinc added to further increase their corrosion resistance. If the unit has to be installed in an environment with a particularly aggressive atmosphere, e-coated microchannel coils are available as an option. This option is strongly recommended for applications in coastal or highly industrialized areas. The use of microchannel coils compared to conventional copper/aluminium coils reduces the total weight of the unit by about 10% and gives a reduction in refrigerant charge of at least 30%. To protect the exchangers from corrosion and ensure optimal operation of the unit, we advise following the recommendations given in the user, installation and maintenance manual for cleaning the coils. For installations within a kilometre of the coast, the use of Cu/ Al coils with anti-corrosion treatment is strongly recommended for cooling only units too. The exchanger is protected by a metal mesh. The /HP units are fitted as standard with condensate collection tank placed under the coil. The tank has one or more connections to which the customer must connect with pipes of suitable diameter, to direct the condensate from defrost cycles to a drain. FANS The standard fans are statically and dynamically balanced dual suction centrifugal fans with forward-curved blades, with belt and pulley transmission, connected to three-phase 4-pole electric motors. The fan includes a safety guard in conformity with standard UNI EN 294. Alternatively, the unit can be requested with /RFA or /RFE option that uses radial fans with backward-curved blades with directly coupled motor. All units have vertical exhaustion as standard and, for the basic unit, the available pressure is 50Pa. Horizontal exhaustion and higher pressures are available as accessories. USER-SIDE HEAT EXCHANGER The exchanger is a braze-welded stainless steel plate heat exchanger, insulated with a shroud of closed-cell insulating material. For dual circuit models, the unit uses two exchangers already manifolded inside the unit and therefore with a single hydraulic connection. The exchanger is also equipped with thermostat-controlled anti-freeze heater to protect it from ice formation when the unit is not running. REFRIGERANT CIRCUIT Each refrigerant circuit of the basic unit (cooling only) comprises: valve on the liquid line charging valves liquid sight glass replaceable solid cartridge dehydrator filter (except for sizes 3.2, 4.2 and 5.2 where the filter is a weld-on filter) thermostatic expansion valve with pressure equalization high and low pressure switches The pipes of the circuit and the exchanger are insulated with extruded closed-cell expanded elastomer. As an accessory, all the units can be fitted with an electronic expansion valve that allows machine stability to be reached more quickly and better superheating control than the mechanical expansion valve, to maximize the use of the evaporator in all load conditions. ELECTRICAL CONTROL PANEL The electrical control panel is made in a painted galvanized sheet-iron box with forced ventilation and IP54 protection rating. 3

The electrical control panel of the basic unit comprises: main disconnect switch automatic circuit breakers for compressors with fixed calibration fuses for the fans and auxiliary circuits thermal magnetic circuit breakers for the pumps (if present) contactors for the compressors, fans and pumps (if present) phase monitor potential free general alarm contacts single potential free operating contacts for compressors, fans and pumps (if present) microprocessor control with display accessible from the outside All the electrical cables inside the panel are numbered and the terminal board dedicated to the customer s connections is coloured blue so that it can be quickly identified in the panel. The power supply to the unit is 400V/3~/50Hz for all models. CONTROL Thermoregulation of the unit controls water temperature at the inlet to the user-side heat exchanger. Outlet water temperature control is available as an option. As standard, the unit uses a parametric controller that allows the following functions: freeze protection compressor timings automatic rotation of compressor starting sequence management of capacity reduction due to high pressure limit display of alarms recording of log of last 100 alarms - in addition to the alarm, it shows the date, time and type of operation of the unit when the alarm occurs an RS485 serial port with Modbus protocol clock board sliding defrost management digital input for remote ON/OFF digital input for remote Summer/Winter selection digital input for remote selection of double set point display of hours of operation of all the compressors display of starts per hour of the compressors position a compressor or a circuit to OFF from button display the time left to the start of the next defrost cycle The control has a 6-button interface with a display that can display 2 quantities and 20 icons at the same time, so as to see the unit s operating state at a glance. The Advanced controller accessory is available as an option and adds the following to the above-listed functions: recording of all the variables and parameters of the unit with sampling for 15 seconds - this allows a log to be kept with FIFO logic that covers about 20 days, depending on the size of machine an Ethernet serial port with TCP/IP protocol and Modbus over IP an integrated WEB server with display pages and management of preloaded pages Both types of control have a display that allows the following to be shown: water inlet and outlet temperatures set temperature and differential set points description of the alarms (only for the advanced control) hour meter of operation and number of start-ups of the unit, the compressors and the pumps (if present) high and low pressure values condensing and evaporating temperatures (only for the advanced control) external air temperature superheating at compressor suction (only for the advanced control) For further details on available functions and on displayed information, you can refer to the specific documentation of the control. By default, the serial connections present as standard are enabled only for reading from BMS. CONTROLS AND SAFETY DEVICES chilled water temperature probe antifreeze probe at outlet of each user-side heat exchanger high pressure switch (with manual reset) low pressure safety device (with manual reset managed by the control) high pressure safety valve protection against compressor overtemperature protection against fan overtemperature water flow sensor already installed and wired that, depending on the version and size of machine, will be a differential water pressure switch or a paddle flow switch. TESTING All the units are factory-tested and supplied complete with oil and refrigerant. VERSIONS Alongside the basic version, there are other versions that differ in efficiency and noise levels.. SLN: super low noise unit The SLN version unit uses a soundproofed compressor compartment and oversize coils compared to the standard efficiency unit that allows a reduction in the air flow rate. The speed reduction of the fans is such that, under nominal operating conditions, the air flow rate and noise level are lower than those of the basic version of the unit. LE: motocondensing unit Compared to the basic unit, the LE version is without user-side heat exchanger and thermostatic expansion valve (to be posi- 4

tioned on the remote evaporator). The unit is supplied with: standard solenoid valve on the liquid line pressurised refrigerant circuit charged with nitrogen (therefore without refrigerant charge) weld-on refrigerant connections closed with copper plugs LE/HP: reversible motocondensing unit Compared to the HP version, the LE/HP version is without user-side heat exchanger and thermostatic expansion valve for operation in air conditioning mode (to be positioned on the remote evaporator). The solenoid valve on the liquid line is supplied as standard. The unit is supplied with: standard solenoid valve on the liquid line pressurised refrigerant circuit charged with nitrogen (therefore without refrigerant charge) weld-on refrigerant connections closed with copper plugs OPTIONS /RFA: set-up with AC radial fans Units with this option are made using radial fans with backward-curved blades, without scroll. The 4-pole electric motor is directly coupled and controlled by a phase cutting speed adjuster. With this type of fan, the use of belts and pulleys that need greater maintenance is avoided. For some sizes, this option requires the addition of an exhaust plenum placed above the machine. Plenum and fans are fixed with screws and can therefore be disassembled on site to make it easier to pass through doorways. Refer to the specific dimensional drawings for further details. All units have vertical exhaustion as standard and, for the basic unit, the available pressure is 50Pa. /RFE: set-up with EC radial fans Units with this option are made using radial fans with backward-curved blades, without scroll. The directly coupled electric motor is an EC (Electronically Commutated) motor. In addition to higher efficiency given by there being no rubbing parts or shearing of magnetic fields, this type of fan allows self-adaptation to the head losses of the aeraulic ducting, even when these change over time because of the fouling of filters and channels. The correct speed of the fans is identified according to the condensing control that is standard for units with this option. With this type of fan, the use of belts and pulleys that need greater maintenance is avoided. For some sizes, this option requires the addition of an exhaust plenum placed above the machine. Plenum and fans are fixed with screws and can therefore be disassembled on site to make it easier to pass through doorways. Refer to the specific dimensional drawings for further details. All units have vertical exhaustion as standard and, for the basic unit, the available pressure is 50Pa. For some sizes, this option requires the addition of an exhaust plenum placed above the machine. Plenum and fans are fixed with screws and can therefore be disassembled on site to make it easier to pass through doorways. Refer to the specific dimensional drawings for further details. /HP: reversible heat pump In addition to the basic set-up, HP units comprise (for each refrigerant circuit): 4-way reversing valve fluid accumulator second thermostatic expansion valve. For defrost management, the control of the unit uses a sliding intervention threshold, depending on the pressures inside the unit and the external air temperature. By putting together all this information, the control can identify the presence of ice on the coil and activates the defrosting sequence only when necessary, so as to maximize the energy efficiency of the unit. Summer/winter switching can be done from the control keypad, digital input or BMS (requires write enabling of the advanced controller). /DC: unit with recovery condenser In addition to the basic set-up, the /DC units comprise: a recovery condenser for recovering 100% of the condensation heat on each refrigerant circuit. The exchanger is a braze-welded plate heat exchanger. For dual circuit units, the exchangers are to be manifolded outside the unit (by the customer). temperature probe at the inlet of each recovery exchanger. For dual circuit units, the probe is supplied with the unit and is to be positioned on the exchanger inlet manifold (by the customer). liquid receiver for each refrigerant circuit with system for emptying the refrigerant from the condensing coil potential free contact in the electrical control panel for activation of recovery. When required by the system, through the closing of a contact, the control automatically manages activation of recovery. Recovery management is carried out through a control on the temperature of the return water. The control also automatically manages safety deactivation of recovery if the condensing pressure becomes too high, and changes to using the condensing coils. This option is not available for /HP units /DS: unit with desuperheater In addition to the basic set-up, /DS units comprise (for each refrigerant circuit) an exchanger for condensation heat recovery of up to 20% (depending on size, version and operating conditions), placed in series with the condensing coil. The exchanger is a braze-welded plate heat exchanger. For dual circuit units, the exchangers are to be manifolded outside the unit (by the customer). To maximize the use of the accessory and optimize machine 5

operation, combination with the speed adjuster of the fans or with the EC fans is recommended. This option is also available for /HP units, but in this case, in the installation, it must have provision for shutting off the recovery water circuit during operation in heat pump mode to avoid taking power from the user-side heat exchanger. /LN: low noise unit In the unit with /LN option, the technical compartment that houses the compressors is fully soundproofed with sound absorbing material and soundproofing material. /HAT: unit for high external air temperatures The unit fitted with this accessory adopts an electrical control panel made using specific components to withstand high temperatures, special cables and oversize protection parts. The accessory enables the unit to work with external air temperatures of over 46 C as indicated in the section on operating limits. Units with hydraulic module All units can be fitted with hydraulic module in various configurations: /1P: hydraulic module with one pump /2P: hydraulic module with two pumps /1PS: hydraulic module with one pump and buffer tank /2PS: hydraulic module with two pumps and buffer tank All the above-mentioned modules have pumps with standard discharge head. The following are also available: modules /1PM, /2PM, /1PMS and /2PMS that have pumps with increased available discharge head modules /1PG, /2PG, /1PGS and /2PGS that have pumps suitable for operating with glycol up to 50% Hydraulic modules with one pump have: one pump a gate valve on the delivery side of the pump an expansion vessel Hydraulic modules with two pumps have: two pumps a check valve on the delivery side of each pump a gate valve on the outlet of the delivery manifold an expansion vessel In the version with 2 pumps, these are always with one on standby while the other is working. Switching over between the pumps is automatic and is done by time (to balance the hours of operation of each one) or in the event of failure. Hydraulic modules with tank also have: a gate valve at the inlet of the pump or the suction manifold a tank with drain valve and air valve Refer to the table of configurations that are not possible to check for availability of specific set-ups. 6

7

DESCRIPTION OF ACCESSORIES CODE Accessory Operation and advantages RG TEMP SERR MAFR RIC RUB DVS VS VTE BK RPR Condensing control with fan speed adjuster Condensing control by steps Condensing control with modulating damper Pressure gauges Liquid receivers. Compressor suction and delivery valves Double safety valve Liquid line solenoid valve Electronic expansion valve Brine Kit Refrigerant leak detector REFRIGERANT CIRCUIT ACCESSORIES This accessory is applicable only to units with the /RFA option. The control manages the speed of the fans through a phase cutting speed adjuster, in order to optimize the operating conditions and efficiency of the unit. By checking the condensing pressure, the control adjusts the speed of the fans in order to overcome the aeraulic head losses and so ensures achievement of the correct air flow rate to the source-side heat exchanger. Control is dynamic and therefore a function of the real operating conditions of the unit and of the level of fouling of filters and channels. For HP units, the control also carries out evaporating control when the unit is working in heat pump mode. For units with the /RFE option, this functionality is supplied as standard. With this accessory, the condensing pressure of the unit is controlled through the stepped switching off of the fans. There are two steps for units with 2 fans and three steps for units with 3 or 4 fans. This accessory consists of installing a modulating damper installed on the exhaust outlet. This is operated by a servo motor controlled by the control to change the air flow rate depending on the condensing pressure. The operating pressures of each circuit of the unit can be displayed on the control by accessing the relevant screens. Also, the machine can be fitted with pressure gauges (two for each circuit) installed in a clearly visible position. These allow reading in real time of the working pressures of the refrigerant gas on the low pressure side and on the high pressure side of each refrigerant circuit. The adoption of this accessory always guarantees correct feeding of the expansion valve even when the unit is subjected to wide external air temperature ranges. This accessory is standard on DC and HP units. The valves situated on the suction and delivery manifolds of the compressors allow the tandem or the trio to be isolated from the rest of the refrigerant circuit, so making the maintenance operations quicker and less invasive. With this accessory, instead of each individual safety valve per circuit, there is a "candelabrum" with two safety valves and a diverter valve for choosing the valve in operation. This allows the safety valves to be replaced without having to drain the machine and without having to stop it. This accessory prevents refrigerant migration that could damage the compressor on starting. Standard on HP units. The use of this accessory is particularly advisable on units that have to work in conditions of very variable heat load, large differences in external air temperatures or frequent operating mode change, as in the case of combined management of air conditioning, heating and hot water production. The use of an electronic expansion valve allows you to: maximize heat exchange at the user-side heat exchanger minimize the response times of the refrigerant circuit to variations in the load and in the operating conditions optimize superheating control Application of this accessory is mandatory if the unit has to produce water with temperature lower than +3 (if the unit is provided with double set point or variable set point, the lower set point is considered). The accessory consists of adopting an increased insulation and a suitable sizing and calibration of some components. This accessory obligatorily requires insertion of the condensing control. With this accessory, a refrigerant leak detector is placed inside the compressor compartment. If the unit is fitted with the standard control (parametric), detection of a refrigerant leak causes the closing of a potential free contact shown in the terminal board and the activation of sound and visual signalling on the machine. If the unit is fitted with the advanced control, detection of a refrigerant leak is managed by the control through a specific alarm and display of a specific icon on the display of the control. This alarm does not stop the unit. 8

CODE Accessory Operation and advantages RPP EO EO Refrigerant leak detector with automatic pump down Centrifugal fans with available pressure of Pa Horizontal exhaust for units with centrifugal fans Horizontal exhaust for units with radial fans With this accessory, a refrigerant leak detector is placed inside the compressor compartment. Detection of a refrigerant leak is managed by the control through a specific alarm and display of a specific icon on the display of the control. The alarm also starts the procedure of machine stopping with pump down, confining all the refrigerant in the coils. This accessory is available only in combination with the advanced control. FAN ACCESSORIES Depending on the available pressure required at the fan outlet, a different diameter of the pulleys is identified. In this case, the pulleys are variable diameter pulleys so as to be able to adjust the available pressure of ±30Pa. With this accessory, the scroll is fitted differently to the standard one, so that the air throw is horizontal instead of vertical. When this accessory is present, exhaustion is always on the opposite side to the coil. With this accessory, the exhaust air delivery outlet is on the opposite side to the coil instead of on the cover. For some sizes, the application of this accessory requires the addition of an exhaust plenum that increases the height of the standard unit (refer to the specific dimensional drawing). 9

CODE Accessory Operation and advantages IVPO Soundproofed pump compartment ACCESSORI CIRCUITO IDRAULICO With this accessory, the motor and the impeller of the pumps are enclosed in a compartment that is fully soundproofed with sound absorbing material and soundproofing material. IPU Inverter for pump on user side This accessory requires the following to be supplied: inverter for controlling the pumps of the hydraulic module motor-driven modulating bypass valve (supplied with it) pressure transducers dedicated controller for management of the inverter and of the bypass valve, provided with display P 2 This accessory can be offered as an alternative to the conventional layout that has a constant flow pump on the primary circuit (P1) and a variable flow pump on the secondary circuit (P2). P 1 Circuit braker This layout shows the use of the hydraulic uncoupling pipe (circuit breaker) between primary and secondary circuit that is sized at 100% of the flow rate: if the users require only a percentage of the nominal capacity, the uncoupling pipe recirculates the excess flow rate with consequent waste of pumping energy. In the solution with the Inverter for pump on user side accessory, there is a single variable flow pumping unit (P1), already integrated in the chiller, which feeds both the primary and secondary circuits. Instead of a simple separation pipe, a bypass valve (VBP) is inserted and this guarantees that the minimum water flow rate to the evaporator is maintained even when demand from the users is well below nominal demand. This system also allows the separation pipe and the bypass valve to be sized for a much lower water flow rate than the nominal flow rate, to therefore obtain a net reduction in energy losses due to water recirculation. The benefits obtained with the use of this accessory are therefore: insertion of a single set of pumps in the system, with consequent reduction in investment and pumping costs reduction in the space necessary inside the technical compartment of the building simplification of the hydraulic circuit greater pumping energy efficiency 22% Also, by assessing the ESEER level of the unit, also counting the absorption of the integrated pump as well as the absorption of the compressors and fans, it can be seen that there is a gradual increase in efficiency as the degree of capacity reduction of the system is increased, with a consequent increase in ESEER up to 11%. improvement 2% 5% 11% 11% EER 100% EER 75% EER 50% EER 25% ESEER To understand more clearly how the accessory works, we refer to the following layout: Δp 1 Δp 2 V BP P 1 V FW The whole system is controlled by a dedicated controller (provided with its display) that, through pressure transducers, detects the head losses on the evaporator ( p1) and the head losses on the system side ( p2). When all the users are in operation, the pump of the unit works at the nominal flow rate. The decrease in heat load of the system causes the shut-off valves of the users to close, with a consequent increase in head losses on the system side because of the increase in flow rate in the lines left open. The control therefore detects the variation of p2 and, by also assessing the water outlet temperature from the exchanger (varied with respect to the decrease in head), implements a procedure of adjustment of the speed of the pump P1 in order to return the head losses to nominal conditions. 10

CODE Accessory Operation and advantages IPU Inverter for pump on user side Again considering the water outlet temperature and the variation of p1, the control checks that at the exchanger there is always the minimum flow rate necessary to ensure correct heat exchange. If the flow rate required by the system is too low to have the correct flow rate at the exchanger, the control modulates the bypass valve VBP until the correct operating conditions for both the system and the exchanger are restored. To ensure correct operation of this system in all conditions, it is necessary to assess the volumes of water present in the system and their position: when the system has most of the shut-off valves closed and therefore with heat load near zero, even if the machine is working in conditions of maximum capacity reduction, conditions that trigger the antifreeze alarm could occur. To avoid this problem, it is necessary to have a thermal wheel minimum in the section between the exchanger of the unit and the bypass valve (represented in the figure with the VFW tank). The required volume can be determined with the following formula: Where V FW is the volume of the thermal wheel minimum expressed in l P 0 is the total refrigeration capacity of the machine expressed in kw s min is the minimum capacity reduction step expressed in % k is a coefficient equal to 14.3 l/kw The water content of the exchanger, the buffer tank of the hydraulic module (if present) and the pipes between bypass and exchanger, can contribute to the determination of the thermal wheel minimum. If the accessory is combined with a cold only unit connected to a system in which an ethylene glycol mixture is used, the thermal wheel minimum can be reduced according to the following table: Glycol concentration 0 to 10% 10 to 20% 20 to 30% N of compressors 1 0% -56% -77% 2 0% -58% -82% 3 0% -60% -84% 4 0% -62% -86% RA VSIW FLUS Anti-freeze heater Water-side safety valve Flow switch (instead of the water differential flow switch) The thermal wheel minimum also allows correct operation of the unit in heat pump mode, but in this case, the presence of glycol does not allow its volume to be reduced. As indicated in the user, installation and maintenance manual, to guarantee correct operation of the unit and avoid excessive fluctuations on the temperatures, it is always necessary to ensure the presence of a minimum volume of water in the system. The thermal wheel minimum is a part of it, but while V_FW must obligatorily be positioned as shown in the figure, the remaining minimum volume can be distributed in the system. We strongly recommend the use of three-way valves on the users that are furthest away from the machine and a calibration gate valve that connects the final part of the backbones of the system, in order to guarantee a minimum flow of water to the system in any condition. The system is calibrated at the factory to work on a plant that, under nominal conditions, must work with a thermal gradient of 5 C on the water. For different values, please contact our sales department. When this accessory is present, even the minimum water outlet temperature is limited: in chiller operating mode, the minimum settable set point is 7 C, while in heat pump operating mode, the minimum set point is 40 C. If outlet temperatures lower than these limits are required, please contact our sales department. In addition to the anti-freeze heater already present as standard on the user-side heat exchanger, with this accessory, anti-freeze heaters are also inserted on the pumps and in the tank (depending on the configuration of the machine) to prevent damage to the hydraulic components due to ice formation during periods when the machine is stopped. Based on normal operating conditions and the percentage of glycol in the system, an appropriate antifreeze alarm temperature is set in the control. When a temperature that is 1 C higher than the antifreeze alarm threshold is detected at the outlet from the exchanger, the pump (if present) and the antifreeze heaters are switched on. If the temperature of the outgoing water reaches the antifreeze alarm threshold, the compressors are stopped, keeping the heaters and the pumps active, and the general alarm contact of the machine is activated. With this accessory, a safety valve is inserted in the hydraulic circuit of the unit: when the calibration pressure is reached, the valve opens and, by discharging (to be routed by the customer), prevents the system pressure from reaching limits that are dangerous for the components present in the system. The valves have positive action, that is, performance is guaranteed even if the diaphragm deteriorates or breaks. As an alternative to the differential pressure switch (standard flow sensor), it is possible to request the paddle flow switch as accessory. This detects when there is no water flow to the user-side exchanger and sends a signal to the control of the unit that will stop the compressors to prevent damage to the exchangers. The flow switch is supplied with the unit (installation by the customer) and replaces the water differential pressure switch (standard). 11

CODE Accessory Operation and advantages CA PBA GLO FM2 FM6 FM0 LIID RIF COTW SETD SETV Advanced control BACnet protocol over IP (Ethernet) Lon Gateway Multilogic function for Master unit for managing up to 2 Slaves Multilogic function for Master unit for managing up to 6 Slaves Multilogic function for Slave unit Limitation of the current absorbed by digital input Power factor correction to cosφ 0.9 Outgoing water temperature control Double set point from digital input Variable set point with remote signal (0-1V, 0-10V, 4-20mA) ACCESSORI ELETTRICI Compared to the parametric control fitted as standard, the advanced control adds the following functionalities recording of all the variables and parameters of the unit with sampling for 15 seconds - this allows a log to be kept with FIFO logic that covers about 20 days, depending on the size of machine an Ethernet serial port with TCP/IP protocol and Modbus over IP an integrated WEB server with display pages and management of preloaded pages The control is set for using the BACnet protocol (instead of Modbus) on the Ethernet port. By default, the programming gives read-only access to the control of the unit. Enabling of read/write access should be requested when ordering. With this accessory, a RS485/Lon gateway is installed inside the electrical control panel. By default, the programming gives read-only access to the control of the unit. Enabling of read/write access should be requested when ordering. With this accessory, the unit is programmed as master of a system of machines in Multilogic network (for further details, refer to the control manual). Also, a network gateway with 4 ports is installed in the electrical control panel of the unit to allow the unit to be connected to an external LAN network and up to 2 slave units to be managed. With this accessory, the unit is programmed as master of a system of machines in Multilogic network (for further details, refer to the control manual). Also, a network gateway with 8 ports is installed in the electrical control panel of the unit to allow the unit to be connected to an external LAN network and up to 6 slave units to be managed. With this accessory, the unit is programmed as slave of a system of machines in Multilogic network (for further details, refer to the control manual). When this accessory is requested, a digital input is prepared in the terminal board to activate the forced capacity reduction of the unit to a set fixed level. This accessory is useful when there is a need to necessarily limit the power absorbed by the unit as regards particular conditions. With this accessory, an electrical control panel, containing power factor correction condensers to bring the cosφ of the unit to being greater than 0.9, is supplied with the unit. The condensers should be connected (by the customer) to the electrical control panel of the unit in the specially prepared terminal board. Besides reducing the absorbed reactive power, the use of this accessory also allows the maximum absorbed current to be lowered. When this accessory is requested, the unit is set to use the water outlet temperature (instead of the inlet temperature) as reference for thermoregulation. This system requires the management of a neutral zone to the control; the lower the number of compressors of the unit, the wider this zone will be. For units fitted with this accessory, it is possible to preset two different operating set points and manage the change from one to the other through a digital signal. The set point temperatures must be specified when ordering. For units fitted with this accessory, the set point can be varied continuously between two preset values, a maximum and a minimum, depending on an external signal that can be of the 0-1V, 0-10V or 4-20mA type. For units fitted with this accessory, the set point of the unit is set so that it can vary between two values, a maximum and a minimum, depending on the external air temperature. The compensation ramp and the maximum and minimum values of the set point can be changed by the user. Unless otherwise specified in the order, the control will be set to implement a negative compensation logic according to the temperatures shown in the following diagrams: Negative compensation SET POINT 2 17/12 C Positive compensation SET POINT 2 17/12 C CSP Set point compensation depending on external air temperature Chiller SET POINT 1 12/7 C 25 C 35 C External air temperature SET POINT 1 12/7 C 25 C 35 C External air temperature Heat pump SET POINT 2 40/45 C SET POINT 1 35/40 C 0 C 15 C External air temperature SET POINT 2 40/45 C SET POINT 1 35/40 C 0 C 15 C External air temperature 12

CODE Accessory Operation and advantages RE1P RE2P TERM TERM Relay for management of 1 external pump Relay for management of 2 external pumps Remote-controlled user terminal Remote-controlled user terminal (unit with advanced control) This accessory can be requested for units without pumps and allows a pump outside the machine to be controlled. This accessory can be requested for units without pumps and allows two pumps outside the machine to be controlled with a running/stand-by logic by implementing a rotation on the hours of operation. This accessory consists of a replica of the control that can be remotely operated up to 150m, from which it is possible to work completely on the configuration of the unit and display all its parameters on the display. This terminal is suitable for insertion in an ordinary electrical enclosure box (box 503) and does not need an external power supply unit because it takes its power directly from the control of the unit. The terminal is also fitted with an NTC temperature probe and can therefore work as a room thermostat (for LE or LE/HP units combined with air handling units). The parameters are accessed by entering passwords that enable the various modification levels. This accessory allows the terminal normally situated on the machine to be replicated on a support situated at a distance. It is particularly suitable when the unit is placed in an area that is not easily accessible. The accessory is supplied with the unit and is to be installed by the customer at a maximum distance of 120m from the unit. RMMT IA ARU NSS SQE Maximum and minimum voltage relay Automatic circuit breakers Stopping of the unit due to temperatures below the operating limit Night Shift System Heater for electrical control panel This accessory constantly monitors the voltage value and the unit's power supply phase sequence. If the supply voltage does not fall within the set parameters or there is a phase reversal, an alarm is generated that stops the machine to prevent damage to its main parts. With this accessory, automatic circuit breakers are installed for the protection of auxiliary loads and fans. Also, this accessory uses automatic circuit breakers with adjustable thermal overload protection to protect the compressors. With this accessory, it is possible to set the unit so that the controller switches off the compressors when the unit is operating in heat pump mode and the external air temperature falls below a minimum set limit: this will prevent the unit from going into low pressure alarm, so avoiding having to manually restart the machine. At the same time, the control will enable a digital output that can be used for activating an auxiliary heat source. When the external air temperature returns above the set threshold temperature, the unit will automatically resume operation without it being necessary to do anything. For units equipped with integrated pump, the pump will always be kept running so as to prevent ice formation and ensure correct reading of the temperature and antifreeze safety probes at all times. The stopping temperature must be set based on the set point temperature and in accordance with what is allowed by the operating limits of the machine. With the default programming, the limit that considers a production of outgoing water at 45 C is set, therefore -7 C for standard units and -10 C for /HE and /SLN units. The same function can be used to set an external air temperature below which to use an alternative heat source because it is more efficient or economically more advantageous. This accessory is applied to high efficiency /LN version units with speed adjuster or to SLN units. In the day time band, which is normally the one with the highest heat load, priority is given to efficiency and therefore the machine works with a fan control curve that maximises the EER. In this time band, therefore, the unit is a high efficiency low noise machine (equivalent to HE/LN) In the night time band, priority goes to keeping down the noise of the machine and therefore the control implements a reduction of the air flow rate using a specific speed adjuster control curve. So in this time band, the unit is a super low noise machine (equivalent to SLN). The time bands can be set from the control depending on installation requirements. Electric heaters are positioned inside the electrical control panel and these prevent the formation of ice or condensation inside it. 13

CODE Accessory Operation and advantages OTHER ACCESSORIES AG Rubber anti-vibration mounts These allow you to reduce the vibrations transmitted from the unit to the surface it is standing on. Accessory supplied with the unit. AM MCHE Spring anti-vibration mounts E-coated microchannel coil These allow you to reduce the vibrations transmitted from the unit to the surface it is standing on. Accessory supplied with the unit. The e-coated microchannel coils are treated by immersion of the whole exchanger in an emulsion of organic resins, solvents, ionic stabilisers and deionised water. This is all subjected to a suitable electric field that causes the formation of a solid, uniform deposit on the exchanger. The function of this deposit will be to protect the aluminium from corrosion without penalising its thermophysical properties. The choice of whether or not to treat the exchanger should be made with regard to the environment in which the unit is to be installed and through observation of other structures and machinery with exposed metal surfaces present in the destination environment. The cross observation criterion is the most valid method of selection currently available without having to carry out preliminary tests or measurements with instruments. The identified reference environments are: marine coastal industrial urban with a high housing density rural Please note that in cases where different conditions co-exist, even for short periods, the choice must be suitable for preserving the exchanger in the harsher environmental conditions and not in conditions between the worst and best situation. Particular attention must be given to cases where an environment that is not particularly aggressive becomes aggressive as a consequence of a local and/or temporal concomitant cause such as, for example, due to the presence of a heating flue outlet or an industrial kitchen or a solvent extraction fan in a small craft business. Protective treatment of the exchanger is strongly recommended if at least one of the points below is verified: there are obvious signs of corrosion of the exposed metal surfaces in the installation area the distance from the coast is less than 20 km the prevailing winds come from the sea towards the unit the environment is industrial with a significant concentration of pollutants the environment is urban with a high population density the environment is rural with the presence of organic discharges and effluents. For installations within a kilometre of the coast, the use of Cu/Al coils with anti-corrosion treatment is strongly recommended for cooling only units too. This accessory is not available for HP version units. RAAL Cu/Al coils This accessory uses finned pack coils with copper tubes and aluminium fins instead of microchannel coils. ALPR Pre-painted aluminium coil This accessory uses finned pack coils with copper tubes and aluminium fins pre-painted with an anti-corrosion treatment. This accessory is available only for HP version units. 14

CODE Accessory Operation and advantages ANTC PREA SLIT GABB RETE VASC RAV FW Coil treated with anticorrosion paints Partially assembled construction Special pallet/skid for container shipment Packaging in wooden crate Coil protection mesh Coil protection mesh with metal filter Condensation collection tank for HP units Anti-freeze heater for condensation collection tank Water filter The treatment is applied exclusively to finned pack coils with copper tubes and aluminium fins and consists of aluminium passivation and coating with a polyurethane base; a double layer of paint, of which the first passivates the aluminium and acts as primer and the second is a polyurethane based surface coating. The product has high resistance to corrosion and all environmental conditions. The choice of whether or not to treat the exchanger should be made with regard to the environment in which the unit is to be installed and through observation of other structures and machinery with exposed metal surfaces present in the destination environment. The cross observation criterion is the most valid method of selection currently available without having to carry out preliminary tests or measurements with instruments. The identified reference environments are: marine coastal industrial urban with a high housing density rural Please note that in cases where different conditions co-exist, even for short periods, the choice must be suitable for preserving the exchanger in the harsher environmental conditions and not in conditions between the worst and best situation. Particular attention must be given to cases where an environment that is not particularly aggressive becomes aggressive as a consequence of a local and/or temporal concomitant cause such as, for example, due to the presence of a heating flue outlet or an industrial kitchen or a solvent extraction fan in a small craft business. Protective treatment of the exchanger is strongly recommended if at least one of the points below is verified: there are obvious signs of corrosion of the exposed metal surfaces in the installation area the distance from the coast is less than 20 km the prevailing winds come from the sea towards the unit the environment is industrial with a significant concentration of pollutants the environment is urban with a high population density the environment is rural with the presence of organic discharges and effluents. For chiller units, this accessory also includes the Cu/Al coil accessory. The unit is delivered so that it can be disassembled easily on site if this makes the installation operations easier. A unit requested with this option is supplied: screwed instead of riveted with plugged and not welded pipes without refrigerant charge untested covered by the warranty only if reassembled and screwed together by personnel authorized by the factory The unit is placed on a skid that makes the container loading and unloading operations easier. The accessory is mandatory if shipping by container is required The unit is enclosed in a treated and ISPM 15 marked wooden crate. This accessory is strongly advised for shipping by container. Safety mesh that protects people from accidentally touching the coil. Safety mesh, which protects people from accidentally touching the coil, combined with an aluminium filter to protect the coil from leaves and hail. This accessory cannot be combined with HP units. This accessory can be combined with HP units in order to collect the condensation that forms after each coil defrost cycle. The tank is made of stainless steel and is placed under the source-side heat exchanger, at a suitable distance. On the opposite sides of the tank, there are some 1 close nipples to allow the customer to connect a pipe to it for draining out the water so as not to cause harm or damage to people or objects. A heating cable, glued to the bottom, can be combined with the condensation collection tank to prevent ice formation at the base of the coil or near the outlets. The heater is controlled by a thermostat and is activated depending on the external air temperature. To protect the elements of the hydraulic circuit (in particular, the exchangers), there are Y filters that can stop and settle the particles that are normally present in the water flow and would otherwise settle in the more delicate parts of the hydraulic circuit and damage its heat exchange capacity. Installation of the water filter is mandatory even when it is not supplied as an accessory. Accessory supplied with the unit. 15

TECHNICAL SPECIFICATIONS - Unit Size Cooling (A35; W7) Refrigeration capacity Absorbed power EER ESEER Eurovent efficiency class /HP Cooling (A35; W7) Refrigeration capacity Absorbed power EER ESEER Eurovent efficiency class Heating (A7; W45) Heating capacity Absorbed power COP Eurovent efficiency class Compressors Quantity/Refrigerant circuits Minimum capacity reduction step Refrigerant charge (CH) Refrigerant charge (HP) Fans Quantity Air flow rate Available pressure rated/maximum User-side heat exchanger Quantity Water flow rate Head losses Water flow rate /HP Head losses /HP Hydraulic module Volume of the buffer tank Volume of the expansion vessel Pump model (STD) Available discharge head (1P) Available discharge head (2P) Pump model (OVS) Available discharge head (1PM) Available discharge head (2PM) Pump model (GLY) Available discharge head (1PG) Available discharge head (2PG) Noise levels Sound power level (-) Sound pressure level (-) Sound power level (LN) Sound pressure level (LN) Basic dimensions Length Depth Height 3.2 4.2 5.2 6.2 7.2 8.2 9.2 10.2 12.2 (1) kw 40 45 53 60 67 81 93 102 116 (1) kw 16 19 22 22 26 28 33 38 45 (1) 2,47 2,36 2,44 2,73 2,61 2,88 2,84 2,70 2,56 3,84 3,94 3,96 4,08 4,03 4,20 4,25 4,09 3,89 E E E C D C C D D (1) kw 40 45 52 59 66 80 90 98 114 (1) kw 17 19 21 22 26 29 34 40 46 (1) 2,40 2,30 2,46 2,64 2,55 2,79 2,67 2,48 2,45 3,79 3,91 3,97 4,01 3,99 4,20 4,25 4,02 3,83 E F E D D C D E E (2) kw 42 47 55 63 70 84 95 104 122 (2) kw 16 18 20 21 23 28 31 35 43 (2) 2,62 2,59 2,83 3,01 3,03 3,01 3,02 2,98 2,83 D E C B B B B C C n /n 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 % 50% 50% 50% 50% 50% 50% 43% 50% 44% (5) kg 4 4 4 6 6 9 9 9 10 (6) kg 11 12 12 17 18 23 26 26 26 n 1 1 1 2 2 3 3 3 3 m 3 /h 17.000 17.000 15.000 19.000 19.000 28.500 28.500 28.500 36.000 Pa 50 / 250 50 / 250 50 / 250 50 / 250 50 / 250 50 / 250 50 / 250 50 / 250 50 / 250 1 1 1 1 1 1 1 1 1 (1) m 3 /h 7,0 7,8 9,2 10,3 11,5 14,0 16,0 17,6 20,1 (1) kpa 38 33 33 42 22 33 28 34 34 (1) m 3 /h 6,9 7,7 9,0 10,1 11,4 13,8 15,6 16,9 19,7 (2) m 3 /h 7,2 8,1 9,5 10,8 12,0 14,3 16,2 17,8 20,8 (1) kpa 35 31 32 40 21 31 26 30 32 (2) kpa 41 35 38 47 25 36 30 36 38 l 165 165 165 200 200 450 450 450 450 l 5 5 5 18 18 18 18 18 18 P2 P2 P3 P4 P4 P5 P7 P7 P9 (1) kpa 145 135 162 133 148 168 177 165 172 (1) kpa 137 125 149 117 128 136 162 147 149 P1 P6 P6 P6 P6 P8 P8 P8 P11 (1) kpa 255 237 233 218 232 322 320 298 295 (1) kpa 247 227 221 202 212 291 305 280 271 P15 P15 P16 P16 P16 P17 P17 P18 P18 (1) kpa 120 124 168 150 174 153 153 158 146 (1) kpa 105 105 143 138 158 146 143 146 132 (3) db(a) 91 91 91 90 91 92 92 92 94 (4) db(a) 75 75 75 73 74 74 74 74 76 (3) db(a) 89 89 89 88 89 90 90 90 92 (4) db(a) 73 73 73 71 72 72 72 72 74 (7) mm 1.750 1.750 1.750 2.200 2.200 3.200 3.200 3.200 3.200 mm 1.000 1.000 1.000 1.000 1.000 1.100 1.100 1.100 1.100 mm 1.400 1.400 1.400 1.740 1.740 1.740 1.740 1.740 1.880 1. External air temperature 35 C; user-side heat exchanger inlet-outlet water temperature 12-7 C. Values compliant with standard EN 14511 2. External air temperature 7 C DB, 6 C WB; user-side heat exchanger inlet-outlet water temperature 40-45 C. Values compliant with standard EN 14511 3. Sound power levels calculated according to ISO 3744 4. Sound pressure levels measured at a distance of 1 metre from the unit in free field and directivity factor Q=4 5. The reading refers to the basic unit with microchannel coils 6. The reading refers to the basic unit with Cu/Al coils 7. The reading refers to the unit without pumps, tank or recovery Refer to the specific dimensional drawing if the unit is configured 16