SENSIT HXG-2. Instruction Manual For use with combustible gases Gas Leak Detector

Similar documents
LS1. Operator Manual. Kane International Ltd

Instruction Manual MSI Sensit HXG

Model GD Instruction Manual. Combustible Gas Leak Detector. reedinstruments. www. com

SENSIT HXG-2d Combustible Gas Detector

SENSIT HXG-2d. SENSIT TECHNOLOGIES 851 Transport Drive Valparaiso, IN Phone: (219) Fax: (219)

II 2 G. SENSIT HXG-2d. Ex ib IIB T3 IP20. Suitable for combustible gases such as Methane, Butane, Propane and Natural Gas MADE IN USA

SENSIT HXG-2d Combustible Gas Detector INSTRUCTION MANUAL Read and understand Instructions before use. PENDING Ex. II3G Ex ic llb T3 IP20

CD100A COMBUSTIBLE GAS DETECTOR

INSTRUCTION MANUAL CD Fax: (503)

Combustible Gas Leak Detector Instruction Manual

99 Washington Street Melrose, MA Phone Toll Free Visit us at

LD910. User Manual. Combustible Gas Leak Detector. Detects all Hydrocarbon and other Combustible Gases. Made in U.S.A. MSHA Approved Intrinsic Safety

GAS-Mate. Combustible Gas Leak Detector

REFRIGERANT LEAK DETECTOR OPERATIONS MANUAL LD-170

Combustible Gas Leak Detector Instruction Manual

INSTRUCTION MANUAL GAS LEAK DETECTOR CD200

SENSIT PROPANE GAS. 4Gas Leak Detectors 4Hazardous Gas Monitors 4Calibration Stations 4Data Management 4Pipe Locators ENERGY INDUSTRIES

NGD8800 USER S MANUAL

SENSIT FIRE SERVICE. 4Hazardous Gas Monitors 4Gas Leak Detectors 4Calibration Stations 4Data Management EMERGENCY RESPONSE

6-1 Installing Batteries 6-2 Automatic Circuit/Reset Feature 6-3 Feature Sensitivity Adjustment

Single Gas Monitor 777

PRODUCT GUIDE. Gas Leak Detectors Gas Monitors Pipe & Joint Locators Calibration Stations Data Management MUNICIPAL SERVICES

RK/ RK Combustible Gas Detector Operator s Manual

RK Multi Point Detector Operator s Manual

Confined Space Monitoring. Leak Investigation. Functions 4. Bar Hole Sampling. Line Purge Testing. Actual Size GX-2012

Model C Electronic Nose Accelerant and Gas Detector Operation and Maintenance

Macurco Single-Gas XL Series Monitor, CM-1XL Carbon Monoxide (CO), HS-1XL Hydrogen Sulfide (H2S) User Instructions

SENSIT MUNICIPAL. 4Gas Leak Detectors 4Hazardous Gas Monitors 4Calibration Stations 4Data Management 4Pipe Locators GOVERNMENT SERVICES

RK-05 Carbon Monoxide Detector Operator s Manual

Refrigerant Leak Detector

RK-02 Multi Point Detector Operator s Manual

Model C-380. Instruction Manual. Refrigerant Leak Detector. reedinstruments

RK / RK Methane Detector Operator s Manual

D-TEK Select. Refrigerant Leak Detector

YELLOW JACKET. H 2 Tracer Gas Leak Detector. Operations Manual. Detects 5% H 2 in 95% Nitrogen Tracer Gas. Model 69341

Macurco HD-11 Hydrogen Gas Detector User Instructions. Important: Keep these User Instructions for reference

RK Carbon Monoxide Transmitter Operator s Manual

Macurco HD-11 Hydrogen Gas Detector

Model LP USER S MANUAL AND INSTALLATION INSTRUCTIONS

For the Safety of Your

OPERATION & MAINTENANCE MANUAL

MODEL: SP12C7. (Portable 4 gas detector) Operating Manual

RK/ RK Carbon Monoxide Detector Operator s Manual

THL2. Temperature/Humidity USB Datalogger INSTRUCTION MANUAL

NATURAL GAS DETECTOR. Confined Space Monitor. Leak Investigation. Line Purge Testing. Bar Hole Sampling

SENSIT GOLD G2 INSTRUCTION MANUAL For use with combustible gases and optionally available oxygen and toxic gases.

Model R9100. REED Instruments Instruction Manual. Ultrasonic Leak Detectortor

SENSIT GOLD G2 II 2 G INSTRUCTION MANUAL. Gas Detection Instrument. Read and understand instructions before use.

Safe Operation Manual. Honeywell IQ Force Gas Detector

RK-05 Combustible Gas Transmitter Operator s Manual

SENSIT NATURAL GAS. 4Gas Leak Detectors 4Hazardous Gas Monitors 4Calibration Stations 4Data Management 4Pipe Locators ENERGY INDUSTRIES

Whisper. Ultrasonic Leak Detector

MiniCO, MiniH 2 S, MiniOX, MiniOX Remote, MiniCl 2. , and MiniClO 2. Responder Detectors Instruction Manual "! WARNING

Instruction Manual Model GX-82 Portable Three Gas Monitor

Model 850 Investigator s Aid Accelerant and Gas Detector Operation and Maintenance

EAGLE 2. 6 Channel Capacity. Inlet fitting. Loud buzzer (95dB) IrDA communication port Low flow shutoff and alarm Alarm LED s with wide visibility

TEK-Mate. Refrigerant Leak Detector

RK Hydrogen Sulfide Transmitter Operator s Manual

NJSP HMRU. Module 5 B HM Operations 1

Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.com INSTRUCTION MANUAL THL1

TEK-Mate. Refrigerant Leak Detector

RK-03 Hydrogen Detector Operator s Manual

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots

COMBUSTIBLE GAS LEAK DETECTOR PEN

RK-05 Carbon Monoxide Transmitter Operator s Manual

INSTRUCTION MANUAL FOR RIKEN PORTABLE TOXIC GAS MONITOR

GasAlertMicroClip X3 Specifications

III. 99 Washington Street Melrose, MA Phone Toll Free Visit us at OPERATING INSTRUCTIONS

GasAlert. Introduction. WWarning. Table 1. GasAlert Models. Gas Monitored

RK Combustible Gas Transmitter Operator s Manual

Instruction Manual Model GX-86 Portable Four Gas Monitor

RK/ RK Oxygen Detector Operator s Manual

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

LD920. User Manual. H2/N2 Tracer Gas Leak Detector. Detects 5% H2 in 95% Nitrogen Tracer Gas. Made in U.S.A. LeakDetectors-LD920-UserManual.

GL-CO-RFG Channel Gas Leak Alarm System

INSTRUCTION MANUAL MODEL GX-82A

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model ABM - 715

Safety Siren. Owner's Manual. Family Safety Products Inc. Carbon Monoxide, Propane & Methane. Model Number HS80004 HS80104 HS80204 HS80504 DETECTOR

LD-5000 REFRIGERANT LEAK DETECTOR

MODEL: SP12C7. (Portable 4 gas detector) Operating Manual

IRwin. Methane Leak Detector INNOVATIVE METHANE DETECTOR SYSTEM QUALITY ASSURANCE IN THE AUTOMOTIVE INDUSTRY FOR EASY SURVEY OF GAS PIPELINES

GAS MONITOR Model Model

RK Carbon Monoxide Transmitter Operator s Manual

RK/ RK Oxygen Detector Operator s Manual

Combustible Gas Detection and Control System

Warranty Registration

IRwin. Methane Leak Detector INNOVATIVE METHANE DETECTOR SYSTEM QUALITY ASSURANCE IN THE AUTOMOTIVE INDUSTRY FOR EASY SURVEY OF GAS PIPELINES

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model ABM - 700

ALTAIR 5X Multigas Detector Product Specification

SENSIT GOLD CGI INSTRUCTION MANUAL For use with combustible gases and optionally available oxygen and toxic gases. SENSIT Technologies

LD 5000 REFRIGERANT LEAK DETECTOR JB INDUSTRIES INC.

RLD-H10G Refrigerant Leak Detectors

RD99 REFRIGERANT GAS LEAK DETECTOR WARNING!

RK / RK CO 2 Detector Operator s Manual

actoolsupply.com User Guide Extech RD300 Air Conditioning AC Refrigerant Leak Detector Refrigerant Leakage Detector Model RD300 actoolsupply.

Gas leak detectors. For a quick overview. testo testo testo testo gas detector testo 316-Ex.

Model ATD Refrigerant Gas Leak Detector. User Manual. Detects all CFC, HFC, HCFC, HFO Refrigerants including blends

This instruction manual explains the use of three models listed on the left.

T.ex Single Gas Detector VISA

Transcription:

SENSIT HXG-2 Instruction Manual For use with combustible gases Gas Leak Detector CLASSIFIED 7WA6 Approved UL913, For Class 1, Division 1, Groups C & D hazardous locations when used with alkaline batteries. Meets Gas Research Institute (GRI) requirements for testing residential gas furnace heat exchangers using GRI procedure number 84/0162. J And N Enterprises, Inc. P.O. Box 183 Wheeler, IN 46393 Phone: (219) 759-1142 Fax: (219) 759-1835 Order Line (800) 820-6199 www.jandnent.com

CONTENTS Page # 1. Caution 2. Product Features 3. General Description 4. Operating Tips 6. Battery Replacement 7. Calibration 8. Specifications 8. Accessories 9. Warranty and Repair/Exchange Policy 10. Safety 10. Other J And N Products CAUTION This safety symbol is use to indicate a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION The SENSIT HXG-2 instrument is factory calibrated for methane in air. The alarm will indicate when the gas concentration at the sensor approaches the Alarm Set Point. The Alarm Set Point is adjustable by the user for any gas concentration within the range of 0% to 40% of the lower explosive limit. The alarm response in the presence of any other gas will be different. SENSIT is a registered trademark of J And N Associates, Inc. 1

PRODUCT FEATURES SENSIT HXG-2 On/Off Switch Power On Light Gooseneck Alarm Light Solid State Sensor Alarm Set Gooseneck Clip Lanyard Loop Tick Adjustment Earphone Jack Quiet Alarm Battery Compartment 2

GENERAL DESCRIPTION The SENSIT HXG-2 instrument is an advanced state-of-the-art leak detector capable of detecting many combustible, noncombustible and toxic gases. The SENSIT HXG-2 solid-state sensor is sensitive to most combustible and/or toxic gases. A partial list of these gases is: Acetone, Alcohol, Ammonia, Steam, Carbon Monoxide*, Butane, Gasoline, Jet Fuel, Hydrogen Sulfide, Smoke, Industrial Solvents, Methane, Lacquer Thinners, Naphtha, Propane, Natural Gas. * Not to be used to quantify the amount of CO present. WARNING This instrument cannot be used for finding low level carbon monoxide leaks in furnaces or in the home. Order a Heat Exchanger Test Kit accessory for testing furnace heat exchangers. 3

OPERATING TIPS 1. Turn the instrument on in a noncontaminated atmosphere. The instrument will go through a warm-up process. 2. During warm-up it is normal but not required that the ticking sound increases and the alarm indicates for a short time. While the instrument is warming up the tick rate will slowly decrease until it becomes steady. The alarm will also stop indicating as the instrument completes warm-up. The time required for this will vary depending on the duration of time since the instrument was last used. CAUTION: If the instrument is in an area where detectable gases are present, the alarm may not stop. 3. Once warm-up is complete adjust the Tick Adjust control to establish a slow uniform tick rate. Only after the tick rate remains steady is the instrument ready for calibrated use. To identify the presence of gas vapors or leaks listen for any change in the tick rate. If the tick rate increases, the instrument has detected the presence or location of a leak. As the level of gas increases the tick rate will increase accordingly. If the alarm is indicating, the level of gas is near or above 0.5% gas or approximately at a minimum of 10% of LEL methane. This indicates a potentially hazardous atmosphere. When the instrument alarms a flashing red light will appear and an audible warbling tone will sound. 4

OPERATING TIPS continued 4. To pinpoint a leak source it may be necessary to readjust the tick rate. The Nullable Tick Rate feature of the HXG-2 allows the rate to be slowed and reestablished even in high gas concentrations. By turning the tick adjust counterclockwise and reestablishing a slow tick rate as needed the HXG-2 will continually identify higher levels of gas thereby locating the leak source. Remember, an increase in the tick rate means you are getting closer while a decrease means you are moving further away from the leak source. 5. To continue searching for a leak while the alarm is sounding, you may choose to depress the Quiet Alarm button on the back of the instrument. This will silence the audible portion of the alarm and allow the user to listen to the tick rate pattern. The visual red flashing light will still be seen when the instrument is alarming even if the Quiet Alarm button is used. You will note that the tick rate is independent of the alarm which is calibrated to the appropriate gas concentration. 6. The earphone can be plugged into the unit if there is high background noise or the operator does not want to disturb other people. The speaker is disabled by inserting the earphone. 5

OPERATING TIPS continued 7. If the green light flashes or does not illuminate this is an indication that the batteries need replacement. 8. The unit will respond to some leak finding solutions (soap). Use your SENSIT HXG-2 instrument first. 9. If the sensor is overexposed to some gases, the unit may take an extended period of time to return to calibrated ready condition. 10. To increase battery life turn the unit to OFF when not in use. BATTERY REPLACEMENT If the SENSIT HXG-2 green ready light fails to operate or if it blinks and the audio does not work, the batteries need replacement. Depress the latch using a coin and slide the battery compartment cover off. Replace the batteries with 3 fresh C alkaline batteries. NOTE: When replacing batteries observe polarity markings in the battery compartment. A fresh set of alkaline batteries should operate the unit for approximately 30 hours. 6

CALIBRATION ADJUSTMENT To confirm the original factory calibrated alarm set point of 0.5% methane (10% LEL methane) use calibration kit part #S0157-1 for the following proceedures. 1. Turn on the unit in a gas free environment for a 10 minute warm up. 2. Attach the regulator to the calibration gas cylinder (0.5% methane). Attach the calibration adapter to the regulator, gas flow starts automatically. Immediately insert the sensor into the calibration adapter. 3. If necessary, adjust the alarm set knob slowly until the red alarm light and alarm tone activate. 4. Disconnect the calibration adapter from the regulator to conserve gas. CAUTION: To verify the operation of this instrument it is necessary to apply combustible gas to the sensor head. The tick should increase and alarms may sound. To verify accuracy calibration must be performed. A calibration kit complete with regulator, calibration gas, calibration cup and easy to use instructions is available from your distributor or J And N Enterprises, Inc. 7

SPECIFICATIONS Power Supply: Three C size alkaline batteries. Sensitivity: 10 ppm methane Sensor: Solid State Alarm: Visual and audio at approximately 10% of L.E.L. with an absolute maximum of 40% of L.E.L. for methane. Can be calibrated for other concentrations or gases. Warm-up: Approximately 1 minute Response Time: < 2 seconds (to 40% L.E.L.) Recovery Time: < 4 seconds (to 40% L.E.L.) Duty Cycle: Intermittent Battery Life: Approximately 30 hours. Dimensions: 3.5 x 10 x 1.6 Weight: 1.3 lbs. Probe Length: 16 Approvals: UL913 Intrinsically safe OPERATION ENVIRONMENT Temperature: 0-120 F Humidity: 10%-90% R.H. ACCESSORIES S0157-1 Calibration Kit (small) C0130-0.5 Replacement Cal. Cylinder 21 liter 0.5% Methane/Air 8

WARRANTY & REPAIR POLICY Your SENSIT HXG-2 instrument is warranted to be free from defects in materials and workmanship for a period of two years after purchase (excluding sensor, calibration and batteries). If within the warranty period your instrument should become inoperative from such defects, the unit will be repaired or replaced at our option. This warranty covers normal use and does not cover damage which occurs in shipment or failure which results from alteration, tampering, accident, misuse, abuse, neglect, or improper maintenance. A purchase receipt or other proof of date of original purchase will be required before warranty performance will be rendered. Instruments out of warranty will be repaired for a service charge. Return the unit postpaid and insured to: J And N Enterprises, Inc. 648 W 300 N Valparaiso, IN 46385 Phone: (219) 759-1142 Fax: (219) 759-1835 Order Number: (800) 820-6199 This warranty gives you specific legal rights and you may also have other rights which vary from state to state. 9

OTHER PRODUCTS Ask about these other fine instruments from J And N. SENSIT HXG-3 - Combustible Gas Indicator SENSIT - Refrigerant Gas Detectors SENSIT GOLD - Confined Space and Leak Detection Products SENSIT GOLD CGI - Up to 4 Gas Combustible Gas Indicator TRAK-IT lll CGI - Combustible Gas Indicator GAS TRAC - Combustible Gas Detector TRAK-IT DM/DMS-CO - CO Attachments for Digital Multimeters SAFETY SENSIT HXG-2 is approved by Underwriters Laboratories to UL913, for Class 1, Division 1, Groups C & D hazardous locations when used with alkaline batteries. 10

1991 J And N Associates, Inc. Patented in the USA 6/03 R4