Snow melting for ramps, access ways, and footpaths

Similar documents
Polymer solutions Heating mat EM2-CM

Technical handbook. Temperature maintenance and frost protection systems

Technical Handbook

Hot water temperature maintenance. Less water volume and less heat loss in the pipe work help prevent bacteriological

DESIGN GUIDELINES. THERMAL building SOLUTIONS

F1202 TRACE HEATING. Road & Ramp

XL-Trace System Application and Design Guide

Freezer Frost Heave Prevention

Installation Guide. Heating cables. Thin concrete (< 3 cm) Intelligent solutions with lasting effect. Visit DEVI.com

ACS-30-EU-EMDR- 10-MOD

Pipe Freeze Protection. Flow Maintenance. Introduction. XL-Trace System

Keep your home snow and ice free with. WARMUP Outdoor Heating Solutions. From the world s best-selling electric floor heating brand

Roof and Gutter De-Icing

Technical Databook for Industrial Heat-Tracing Systems 2006/2007

Danfoss Self-limiting Heating Cables SLPG-10/26/33, SLPG-18, SLHW-55/70, SLPH-10

Documentation. Glass -/quartz insulated Heating Cable. Factory terminated. Type: ELK-H, -HS, -Q ELW-H, -HS, -Q

Installation Guide. Heating cables. Pipe tracing. Intelligent solutions with lasting effect. Visit DEVI.com

SPECIFICATION GUIDELINE FROST PROTECTION FOR PIPES. Tender Specification. Engineering Specification for Pipe Frost Protection. Contents.

Anti frost. Snow Melting USA 2012 USA 2014

Technical Databook for Industrial Heating Systems

Documentation. Parallel Heating Cable. Type: ELP

CABLE SERVICES. Data Input Sheet - Fax Back

Uponor Comfort E AL-Foil Mat

CERTIFIED UNDERFLOOR HEATING WITH 15 YEARS GUARANTEE

GB/DAS Installation Instructions

Hot Water Temperature Maintenance. HWAT System. Product Selection and Design Guide

Installation Guide Soil, Asphalt & Concrete De-icing Heating Ribbons

Data Sheet. Self regulating process heating tapes RS stock numbers ,

ACS-30-EU-VIA-DU-20-MOD

COMMERCIAL & RESIDENTIAL MARKETS U.S. ELECTRICAL

MW & EW 10 & 15 Litre Unvented Water Heaters HANDBOOK. IMPORTANT: This booklet should be given to the customer after installation and demonstration.

QuickNet System Installation Manual Manuel d installation du système QuickNet Manual de instalación del sistema QuickNet

SECTION RADIANT-HEATING ELECTRIC CABLES / MATS

HANDBOOK FOR COMFORTABLE WARM FLOORS

RayClic Connection System

Technology for human beings that is, compatible with nature, creating permanent HEAT TRACING Dreams that can greatly improve the quality of life,

HOT WATER TEMPERATURE MAINTENANCE HWAT SYSTEM

AKOCable Heating Cable Solutions Electrical Tracing

Frost Heave Protection System Installation and Operation Manual

SMPG1 SNOW MELTING AND DE-ICING POWER DISTRIBUTION AND CONTROL PANEL FOR SINGLE-PHASE HEATING CABLES PRODUCT OVERVIEW

AKOCABLE Heating Cable Solutions Electrical Tracing

THERMAL MANAGEMENT SOLUTIONS

COMMERCIAL HEAT TRACING PRODUCTS AND SERVICES

SMPG3 SNOW MELTING AND DE-ICING POWER DISTRIBUTION AND CONTROL PANEL. For three-phase heating cables PRODUCT OVERVIEW

Flo~mate Mains Boost Pump Installation & Maintenance Instructions

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation.

Ground application. Ice & Snow Melting. Application manual. Intelligent solutions with lasting effect Visit devi.com

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

C A Heating Cable Gland Kit

protection Constant wattage heating cables Self-regulating heating cables Temperature controllers

INSTRUCTION. Danfoss heating cable mats type 100/150 Danfoss heating cable mats for thin floors. Danfoss heating cable mat type 100/150

Design Guide Design Notes Design Examples Technical Data Sheets Expanded Capabilities Specifications Warranty

Toll Free:

Hot Water Temperature Maintenance Product Selection and Design Guide

Consignes d installation

First Trace Heating Product Details

ECW-GF, ECW-GF-DP DIGITAL ELECTRONIC CONTROLLERS AND REMOTE DISPLAY PANEL PRODUCT OVERVIEW

Installation Instruction

Selection guide for self-regulating heat-tracing systems

UNIQ HEAT BATTERIES REFERENCE MANUAL_V2.2. Version: 2018_07_19_v2.2

Inspect bath carefully and report any damage or faults before installation. No claims can be entered in to after installation.

VIESMANN. Installation instructions. Mixer extension kit. for contractors. Mixer extension kit. For one heating circuit with mixer

HHS-WWH HOPPER HEATING SYSTEM WRAP-WOUND HEATER INSTALLATION INSTRUCTIONS DESCRIPTION. HHS-WWH PRODUCT SPECIfICATIONS

LIFETIME. INSTALLATION MANUAL emat Pro 100w/150w/200w WARRANTY

TECHNICAL PROPERTIES OF THE APPLIANCE

ROOF ICE MELT (RIM) SYSTEM

CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated)

Ready-to-Use Heat Tracing Solutions for Laboratory Applications. innovations in heat tracing

BOILING UNIT REDITAP. Installation and User Guide. IMPORTANT: This booklet should be left with the user after installation and demonstration

SECTION RADIANT-HEATING ELECTRIC CABLES PART 1 - GENERAL 1.1 SECTIONS INCLUDES

Surface Snow Melting and. Icing ElectroMelt. Introduction. ElectroMelt Self-Regulating Heating Cable System

IMPORTANT NOTES. Electric Underfloor Heating Mats For use with Touchsceen underfloor heating Thermostat

EUROBOX SERIES TYPES CM... SM... MM...

Assembly and Operating

THERMAL MANAGEMENT SOLUTIONS

Underfloor Heating Mat Installation Manual

Underfloor Heating Inscreed Cable System

Flomate Mains Boost Pump Installation & Maintenance Instructions

Data Sheet. Self regulating heating tapes. RS stock numbers

COMMERCIAL HEAT TRACING. Products and Services

Settings and Maintenance of the CombinAir

SAFETY & COMFORT FOR THE HOME RESIDENTIAL MARKET U.S. PLUMBING CANADA PLUMBING AND ELECTRICAL

Overview Frost Heave Prevention for Freezer floors on ground.

Product Data Sheet 4114 N/17HH-218. The engineer's choice

GENERAL FITTING GUIDE THERMOSTATIC BAR SHOWER MIXER with RIGID RISER KIT

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l

Inverter Swimming Pool Heat Pump

NEPTUNE Tubular MI Electric Immersion Heater

Popcorn Warmer Cabinet

Max HT Air Heater FOR SAFETY & LONG HEATER LIFE, CAREFULLY READ THIS MANUAL BEFORE USE.

Product catalogue. Outdoors

Moisture inside the drum is due to final testing.

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions

Installation Guide - Heating Cables. Installation Guide. Heating cables. for In-Slab and In-Screed Applications BROCDEV135.1

COMMERCIAL HEAT TRACING PRODUCTS AND SERVICES. thermal ManaGeMent.

3. RCCB (residual current operated circuit-breaker without integral overcurrent protection)

O CRC100. Comfort Room Controller (2015/01) en

ADDITIONAL INFORMATION

LC2200 Level Controller Installation and Maintenance Instructions

1. Take the hoses and elbow out of the holders, depending on model. max. 100 cm. min. * cm

Transcription:

Snow melting for ramps, access ways, and footpaths Ice and snow on paths, loading bays, driveways, ramps, stairs and other access ways, can present a major problem causing accidents and delays. To help prevent this liability, Raychem provides a complete range of ground heating solutions to prevent snow and ice formation. Application in concrete The Raychem range of products has been specifically designed to meet the requirements of commercial, industrial, and residential applications. Whether in concrete, sand, or asphalt, a Raychem system exists to provide a fast, reliable, and easy- to- install solution. Each Raychem heating solution is complete with a Smart control and monitoring unit, providing useful user data and excellent energy efficient performance. The multi-sensor control and monitoring device (VIA-DU-20) is compatible with all ramp snow melting solutions. Ambient temperature sensor* VIA-DU-A10 (incl.) Temperature and moisture sensor VIA-DU-S20 Connection and end seal kit (VIA-CE1) Connection cable (VIA-L1) Control unit (VIA-DU-20) Snowmelting of ramps, steps and footpaths Connection and end seal kit (VIA-CE1) Self-regulating heating cable (EM2-XR) or constant power heating cable (EM4-CW) * Optional, only needed when local detection is selected. Raychem Solutions for concrete Product Description Reinforced concrete ramp EM2-XR Self-Regulating heating cable for reinforced concrete ramps Domestic/private garagetrack heating Stairs; wheelchair access ramps EM2-CM EM4-CW Pre-terminated constant wattage heating mat for ramp, pavement and track heating 400V Pre-terminated constant wattage heating cable solution for larger concrete areas and stairs CDE-0517 Rev.6 09/07 RTechnical handbook 43

Snow melting for ramps, access ways, and footpaths Application in asphalt Ambient temperature sensor* VIA-DU-A10 (incl.) Temperature and moisture sensor VIA-DU-S20 Connection between heater cable and cold lead (Pre-engineered) Mineral-Insulated heating cable (EM2-MI) Pre-engineered cold lead Control unit (VIA-DU-20) Snowmelting of ramps, steps and footpaths Raychem Solutions for asphalt Loading bay and asphalt layer Product EM2-MI * Optional, only needed when local detection is selected. Description Mineral insulated, high temperature resistant heating cable for asphalt ramps RTechnical handbook 44 CDE-0517 Rev.6 09/07

Raychem Ramp heating systems: Product Features & Selection Guide: Product Features EM2-XR EM2-MI EM2-CM EM4-CW Product Description Self-regulating heating cable Mineral Insulated constant power heating cable Constant power polymeric pre-terminated ramp heating mat system Constant power polymeric pre-terminated heating cable system Features Extremely robust selfregulating heating cable for flexible installation under severe site conditions. Pre-terminated heating cable with exceptional resistance to high temperature asphalt surfaces. Pre-terminated ramp, walkway, and track heating (Roll-out) mat for fast and simple installation. Pre-terminated constant power heating cable for larger areas & 400 V power supplies. Voltage Rating 230 Vac 230 Vac 230 Vac 400 Vac Nominal power output 90 W/m @ 0 C. 25-30 W/m 300 W/m 2 25 W/m Maximum circuit length 85 m 136 m 12.6 m 2 (Mat size = 21 m x 0,60 m) 250 m Maximum exposure temperature Connections & termination 100 C 250 C 65 C 65 C Cut-to-length system for flexible field termination (using Raychem heatshrink components). Pre-terminated cable lengths (fixed or configured) available. Contact us. Factory pre-terminated Factory pre-terminated Factory pre-terminated Snowmelting of ramps, steps and footpaths Compatible control unit VIA-DU-20 VIA-DU-20 VIA-DU-20 VIA-DU-20 Approvals VDE / CE VDE / CE VDE / CE VDE / CE Suitable for installation on reinforcement bar Suitable for installation in direct contact with hot poured asphalt Suitable for embedding in sand sub-level Cold lead included Not as standard. Contact Tyco Thermal Controls for information on Configured EM2-XR heating elements. 3 m (at each end of heater cable) 4 m 4 m Dual Wire / Single Wire construction Dual Single Dual Dual CDE-0517 Rev.6 09/07 RTechnical handbook 45

General installation instructions Checklist for problem-free installation and safe operation Typical installation schedule for hot water temperature maintenance General order of events The system is designed and the installation planned The pipework is pressure tested or otherwise checked for leaks The HWAT-L/M/R cable is tested and then installed on the designated pipes The components are installed and each circuit is tested The correct thermal insulation is applied, without delay, labelled and the system test repeated The supply voltage cables and circuit breakers are installed to each circuit The system is commissioned (see System start-up below) Circuit protection, testing and operation for all systems Circuit protection Supply voltage 230 VAC, 50 Hz The required protective measures of the relevant regulations must be complied with. C type circuit breaker (anti-surge fuse) Residual current device (rcd 30 ma) required. Maximum approx. 500 m of self-regulating heating cable can be monitored per rcd Measurement A Measurement B Testing Visual inspection for damage and fault-free installation of the accessories Proper installation of the system Heating cable affixed to all necessary pipes No mechanical damage to heating cable (e.g. cuts, cracks, etc.) No thermal damage Proper connection of all components including power supplies Insulation resistance measurement when heating cable is received and before and after installation of the thermal insulation. The test voltage should be 2500 VAC, but it must not be lower than 500 VAC. The insulation resistance, irrespective of the cable length, must not be less than 100 Mohms. If the resistance falls below this value, the source of the fault must be investigated, eliminated, and re-tested. Measurement A: Phase and neutral to the braid Measurement B: Braid to the pipework After switching on, the cable ends must be warm after 5 to 10 minutes Instructions for the placing of the heat insulation For problem-free operation of the self-regulating heating cables, the material quality and thickness of the thermal insulation should be in accordance with the design parameters, and this insulation must be installed correctly All parts of the pipework, including valves, wall transit points, etc. must be fully insulated General installation instructions Operation / System start-up 1) For small installations, turn on the circuit breakers and preferably leave the system overnight for the water to warm up and stabilise 2) For bigger installations or for a faster start-up, first turn on the main water heater and open the outlet/tap at the end of the pipework run until the water feels warm and then turn on the circuit breakers If the piping system is closed, such as by pressure-reducing valves or isolation valves, you must provide some method of pressure relief to allow for thermal expansion of the water during heat-up Under normal operating conditions, the heating cables are maintenance-free. Tyco Thermal Controls recommend that the insulation resistance should be checked periodically and compared with the original values. If the reading falls below the minimum value (100 Mohms) determine the cause and rectify before re-use The specified maximum ambient and operating temperatures should not be exceeded In the event of repair to the pipework, the heating cable must be protected against damage. Correct function of the electrical protection system should be maintained. To prevent shock or personal injury, turn off the power at the circuit breaker before testing or working on the heating cable or piping RTechnical handbook 50 CDE-0517 Rev.6 09/07

Following the completion of the repair work, the circuit should once again be tested (see above) All the important parts of the controls, thermostats, etc. must be checked for correct operation once a year, normally in the autumn Only for hot water temperature maintenance Newly installed heating cables have lower power at start-up of the installation. The nominal power will be reached after approximately 4 weeks of continuous operation The maintenance temperature should be 5 C to 10 C below the hot water temperature in the boiler Standard assembly times The actual assembly times achieved may deviate according to the conditions on site. Pipework Assembly of heating cable on pipes including fastening, standard installation: 25 m/hour Connection system (electrical connection) RayClic-CE-02 RayClic-S-02/RayClic-PS-02 RayClic-T-02/RayClic-PT-02 RayClic-X-02 RayClic-E-02 2 min/pc. 4 min/pc. 6 min/pc. 8 min/pc. 1 min/pc. Heat-shrink connection system (electrical connection) C25-21 15 min/pc. E-06 5 min/pc. CE20-01 20 min/pc. Other Testing, visual inspection, insulation resistance measurement (2x) Connecting the heating circuit in the switch box 10 min/heating circuit 10 min/heating circuit General installation instructions CDE-0517 Rev.6 09/07 RTechnical handbook 51

General installation instructions Trouble shooting guide Fault Possible causes Measures Circuit-breaker trips: Circuit breaker wrong type: Change to C Type e.g. type B instead of C: Circuit breaker undersized Circuit too long Short-circuit/earth fault Circuit breaker faulty No end seal Conductor (or cable) twisted If the power supply cable permits, install a larger circuit breaker Split the circuit on 2 circuit breakers Eliminate short-circuit/earth fault (cable ends should not be twisted) Replace faulty circuit breaker Install end seal Untwist and install end seal RCD residual current device trips: More than 500 m of frost protection Install additional rcd residual current heating cable installed per rcd device Earth fault at connection or in end seal Cable damaged Moisture in the junction box Rectify earth fault Repair cable where damaged Eliminate moisture Pipeline does not become warm - Circuit-breaker has tripped See section circuit breaker Heating cable cold: Residual current device has tripped See section residual current device No mains voltage Switch on Cable or cold lead not connected Connect cable or cold lead Cable not inserted correctly in Insert cable according to installation connection system or end seal instructions (fully insert cable) Water temperature is not maintained No insulation Insulation according to tables in but the cable gives high output: Insulation thickness insufficient design guides Insulation wet Cold water is running from the boiler Cold water is pumping through mixer tap into the hot water pipe. Insulation according to tables in design guides. Dry insulation Test boiler temperature Test the mixer tap General installation instructions RTechnical handbook 52 CDE-0517 Rev.6 09/07

Technical data Choice of accessoires Hot water temperature maintenance Frost protection for pipes Frost protection for gutters and downpipes Snow melting for ramps, access ways, and footpaths Cable type HWAT-L HWAT-M HWAT-R FS-A-2X FS-B-2X FS-C-2X GM-2X 8BTV-2-CT EM2-XR EM2-MI EM2-CM EM4-CW Colour Matt Glossy Nominal voltage 230 VAC 230 VAC 230 VAC 230 VAC 230 VAC 230 VAC 230 VAC 230 VAC 230 VAC 230 VAC 230 VAC 400 VAC Nominal power output (*on insulated metal pipes) 7 W/m at 45 C 9 W/m at 55 C 12 W/m at 70 C 10 W/m at 5 C 26 W/m at 5 C 31 W/m at 5 C 22 W/m at 40 C 36 W/m in ice and 18 W/m in air at 0 C 18 W/m in air at 0 C 36 W/m in ice at 0 C 90 W/m at 0 C 30 W/m 300 W/m 2 25 W/m C-type circuitbreaker according to selected kit max. max. max. max. 16 A max. 16 A max. 16 A max. max. max. 50 A max. max. max. Max. circuit length 180 m 100 m 100 m 150 m 16 A 105 m 16 A 90 m 16 A 80 m 80 m 85 m 50 A 136 m 21 m (12.6 m 2 ) 250 m Min. bending radius 10 mm 10 mm 10 mm 10 mm 10 mm 10 mm 10 mm 12,7 mm (at 20 C) 50 mm 50 mm 30 mm Max. continous exposure temperature 65 C 65 C 80 C 65 C 65 C 95 C 65 C 65 C 100 C 250 C 65 C 65 C Max. exposure temperature (power-on condition 800 h. cumulative) 85 C 85 C 90 C 85 C 85 C 95 C 85 C 85 C 110 C 250 C 65 C 65 C Max. dimensions in mm (W x H) 13.8 x 6.8 13.7 x 7.6 16.1 x 6.7 13.7 x 6.2 13.7 x 6.2 12.7 x 5.3 13.7 x 6.2 16.1 x 6.2 18.9 x 9.5 min 4,8; max. 6,3 5,0 x 7,0 5,0 x 7,0 Weight 0.12 kg/m 0.12 kg/m 0.14 kg/m 0.13 kg/m 0.13 kg/m 0.13 kg/m 0.13 kg/m 0.13 kg/m 0.27 kg/m Approvals BS / ÖVE / VDE / SEV / CSTB / SVGW / DVGW / CE / VDE CE / VDE Control units QWT-04 HWAT- ECO HWAT- ECO AT-TS-13 AT-TS-14 RAYSTAT-CONTROL RAYSTAT-ECO AT-TS-13 AT-TS-14 RAYSTAT-CONTROL RAYSTAT-ECO AT-TS-13 AT-TS-14 RAYSTAT-CONTROL EMDR-10 HTS-D VIA-DU-20 VIA-DU-20 VIA-DU-20 VIA-DU-20 Connection system Junction box JB16-02 JB16-02 VIA-JB2 VIA-JB-2 VIA-JB-2 VIA-JB-2 Connection kit RayClic RayClic RayClic RayClic RayClic CE20-01 RayClic CE25-21 E-06 VIA-CE1 Pre-installed Support bracket included in included in included in included in included in JB-SB-08 included in JB-SB-08 Approvals: BS/VDE/ÖVE/ERFA/CE CDE-0517 Rev.6 09/07 RTechnical handbook 55