Fire Investigation in Italian Waste Treatment Plant: lessons learned and future development

Similar documents
Modeling a real backdraft incident fire

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

Research Needs for the Fire Safety Engineering Profession

Case Study 2 (Production and Storage Buildings) - Spain

NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL

Case Study 1 Underground Car Park

Water Mist-Based Fire Suppression Modelling of an Office Space Scenario

Sprinklers Modeling for Tunnel Road Fire Fighting

Smoke Layer Height and Heat Flow through a Door

CFD Model of a Specific Fire Scenario

Recent Advances in Fire Suppression Modeling Issues & Perspectives of Fire Safety Engineering Applications

COMPARISON OF CFD MODELLING WITH FIRE TESTS Comparison of CFD Modelling with Results of Full Scale Compartment Fire Tests in a Residential Unit

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand

Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel

Simulation of Engine Room Fire and Water Mist. Einar Kolstad and Bjarne P. Husted Stord/Haugesund University college

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

Considerations in the Design of Smoke Management Systems for Atriums

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

How design fires can be used in fire hazard analysis

Modeling water-mist based suppression of 34 GJ car-deck fires using FDS

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Y. ORMIERES. Fire risk analysis method for nuclear installations

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

Tunnel Fire Dynamics and Evacuation Simulations

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

An experimental study of the impact of tunnel suppression on tunnel ventilation

Advantages and Disadvantages of Fire Modelling

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN

SIMULATION OF A COMPARTMENT FLASHOVER FIRE USING HAND CALCULATIONS, ZONE MODELS AND A FIELD MODEL

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

Fire Research and Education at the University of Maryland

PREDICTING SMOKE DETECTOR ACTIVATION USING THE FIRE DYNAMICS SIMULATOR

Fire Scenario Influence of Material of Boundary Condition on Results

Fire safety engineering applied to high-rise building facades

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

Comparative Evaluation Method for Fire Safety Design of Large Storage Spaces

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

APPLYING LARGE EDDY SIMULATION IN THE STUDY OF FIRE AND SMOKE SPREAD AT UNDERGROUND CAR PARK

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

Computational simulation of road tunnel fire protection by sprinklers

Fire in an archive warehouse January 28 th 2002 Roye [Somme] France

CFD STUDY OF FIRE PROTECTION SYSTEMS IN TUNNEL FIRES

Fire Protection Regulatory Approach for Nuclear Power Plants in Canada

Hazardous Material Safety Program

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts

A study for a fire spread mechanism of residential buildings with numerical modeling

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels

PRIMATECH WHITE PAPER PROCEDURE FOR DUST HAZARD ANALYSIS (DHA)

GAS DETECTOR LOCATION. Ø.Strøm and J.R. Bakke, GexCon AS, Norway

Fire Risks of Loviisa NPP During Shutdown States

Simulation of the course of evacuation in tunnel fire conditions by FDS+Evac

A case study for integrated modelling of personnel evacuation with pool fire simulation to increase safety in design for offshore oil and gas projects

Numerical Simulation of Fluid Flow and Heat Transfer in a Water Heater

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

Yunyong P. Utiskul, Ph.D., P.E., CFEI

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

Recent BRANZFIRE enhancements and validation

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

Compression of Fins pipe and simple Heat pipe Using CFD

Case Study 1 Underground car park

Developing a fire model for offshore QRA

Smoke Layer Height and Heat Flow through a Door

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

Establishing the Risk Basis of Building Size Limits

CFD Analysis of Fire Characteristics on Subway Junction Station

Practicalities and Limitations of Coupling FDS with Evacuation Software

Uncertainty Analysis For Input Parameters Of Electrical Cabinet Fire Simulation By Coupling Latin Hypercube Sampling And CFAST

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

Investigating the Effects of Sprinkler Sprays on Fire-Induced Doorway Flows: A Two-Part Study. Jeremiah Crocker and Dr. Bin Xiao New Technology Team

IFE Level 4 Certificate in Fire Science and Fire Safety

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

FIRE PROTECTION ISSUES IN THE HOT CELLS OF A NUCLEAR FACILITY

Smoke Transport and FDS Validation

DIRECTIVE NO: D-B

Using CFD to Analyze Gas Detector Placement in Process Facilities

ISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people

Risk Management of Fire using Video Based Detection

Emergency Ventilation System Design - Preliminary Report Shishir Gupta

DRAFT NFPA 805 TRANSITION PILOT PLANT OBSERVATION GUIDANCE

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

Road tunnel safety rules in Italy: the tunnel country

Unit 6: Fire Investigation

Water Mist and Heritage Buildings Case - St. Mark s Dome, Venice

CTC Meeting #27 JUNE 17 18, 2013 NIST report on the Charleston sofa store fire

High-expansion foam plant UNI EN 13565

An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor

Heat Release Rate of an Open Kitchen Fire of Small Residential Units in Tall Buildings

ICONE DRAFT Proceedings of the 16th International Conference on Nuclear Engineering ICONE16 May 11-15, 2008, Orlando, Florida, USA

2012 International Symposium on Safety Science and Technology Investigation on compressed air foams fire-extinguishing model for oil pan fire

article continues below

NUCLEAR REGULATORY COMMISSION. [Docket No ; NRC ] Exemption Requests for Special Nuclear Material License SNM-362,

Max Fire Box Users Guide

( )

VIRTUAL FIRES via COMPUTERS

CHEMICAL ENGINEERING TRANSACTIONS

Transcription:

Fire and Evacuation Modeling Technical Conference (FEMTC) 2018 Gaithersburg, Maryland, October 1-3, 2018 Fire Investigation in Italian Waste Treatment Plant: lessons learned and future development Ing. Alfredo Romano General Manager Ing. Giovanni Romano Managing Director TRR S.R.L. Via Saore, 25 Osio Sotto, Bergamo, Italy e-mail: alfredo.romano@trr.it; giovanni.romano@trr.it ABSTRACT In 2017 a serious fire occurred in a waste treatment plant and involved the entire warehouse. TRR was charged to reconstruct the evolution of the fire, in order to establish whether the sequence of events leading up to the accident could be compatible with developing times of the accident. Documental evidences have collected in the accident place, as well as proofs of operators and rescuers who provided support on-site. The fire, the structure and materials composing the warehouse were rebuilt using Fire Dynamic Simulator (National Institute of Standard and Technology) and Pyrosim (Thunderhead Engineering). TRR carried out a three-dimensional simulation of the fire, assuming that the origin of the fire was provoked by an accumulation of crushed waste of mattresses and considering interferences with the other parts of the warehouse, where different materials (wood, rubber, ) were stocked. According to results, considering the ignition temperature of products and the presence of concrete separation walls, TRR concluded that the simulation of fire development was congruent and compatible with the development times of fire occurred. At the end, TRR demonstrated that there were not active and passive fire-prevention protections inside the warehouse; these protections, jointly with a better operative management of the warehouse, could have been avoid the fire development. In the last few years, many similar fires occurred in Italy and, for that reason the Italian Ministry of Environment has recently issued a first version of a Guideline according to risk management. These accidents and the results of the analyses will probably lead to a review of fire-prevention design criteria of these plants.

1. INTRODUCTION AND PURPOSE OF THIS ARTICLE The purpose of this article is to share a TRR S.r.l. (Tecnologia Ricerca Rischi) s experience on fire investigation. This is a fire that developed inside an Italian industrial plant that treats various types of waste. Some details are omitted because a judicial inquiry is still under way. TRR has been commissioned by the Client to proceed with a simulated "reconstruction" of the evolution of the fire. In particular, the propagation speed, intensity and persistence of the flames were investigated, in order to verify whether the fire was compatible with the materials present at the time of the accident and to verify the ignition condition of combustible material placed in the warehouse. The reconstruction of the simulation model, and in particular the materials inside the compartments, was obtained thanks to the elements provided by the Client and the verification of the evolution of the fire through interviews with staff, paper documentation and photographs. The fire simulation was performed through the calculation models called "Fire Dynamics Simulator" and the "PyroSim" interface. The definition of the fire scenario assumes a fundamental role in the characterization of the fire itself and its results; in the case under examination, TRR predefined it on the basis of the elements collected and not through a risk analysis that is usually carried out upstream the identification of the scenario itself. The purpose of the analysis was to clarify some aspects of the development of the fire, in order to evaluate appropriate improvement actions to prevent similar accidents, and in particular: a) if the fire in the warehouse was congruent in terms of propagation speed and intensity; b) if the fire in the outside container of combustible material was compatible with the development of the fire inside the warehouse that would generate temperatures of degradation of the product contained therein and consequent ignition; c) once confirmed the non-compatibility, what could be the probable causes that led to the fire. 2. SUMMARY OF THE ACCIDENT AND IDENTIFICATION OF THE CRITICAL PARAMETERS OF REFERENCE The fire developed from a combination of products deriving from the treatment of combustible materials (it has to be underlined again that some details are deliberately omitted from the present). For the purposes of the present, the potential causes of ignition have not been analyzed, but the sequences of ignition of the other materials in the warehouse have been analyzed. The critical points of the evolution are the following: Time 0: the operators, which were present, detected a beginning of fire during the normal treatment operation. Time 180 s: an operator tried to "isolate" the inflamed material from the one not yet affected by the fire, by taking the inflamed part of the pile and bringing it outside, the operation partially succeeded. Time 300 s: the fire was extended to the compartment near the pile of combustible material and, in the meantime, the internal emergency team was operative to prevent the fire as much as possible. Time 300-600 s: the vehicles inside the warehouse were moved outside from the side exit at about 40 meters. Time 600 s: In the time between 300 and 600 seconds, the fire extended to the other sectors where there were other combustible materials. Time 15-20 minutes: all the piles of rubber products were on fire and the warehouse was completely full of smoke. Page 2 of 8

3. CALCULATION MODELS USED The fire simulations described in the previous paragraph were carried out by using the Fire Dynamics Simulator calculation model (known as FDS, acronym used below) by the National Institute of Standards and Technology (NIST, USA). FDS is a Computational Fluid Dynamics calculation model (abbreviated as CFD ), specifically developed for fires, that uses LES 1 techniques ( Large Eddy Simulation ). This model permits to foreseen the heat conditions resulting from a fire in a compartment 2,3. A CFD calculation model requires that the compartment or building of interest (intended as a series of compartments) be subdivided into control volumes (computational cells) in the form of a parallelepiped or, better, cubic. The CFD calculation model estimates the density, speed, temperature, pressure and concentration of the chemical species in each cell. Based on the laws of conservation of mass, moment, species and energy, the model outlines the generation and movement of fire gases. FDS employs the material characteristics of the elements of the survey domain, in order to estimate the growth and spread of the fire. A complete description of the model can be found in the documentation annexed to it (see previous notes). The ability of the FDS model to predict accurately the temperature and speed of the gases developed by the fire was previously evaluated by the NIST by conducting appropriate experiments, both on a reduced scale and in a real scale and the subsequent analysis of the data from the field. For relatively simple flows caused by the fire, such as in the case of naked flames and flows through passages, doors and windows, the FDS predictions are compatible with the experimental uncertainty of the values measured in the experiments conducted over the years by NIST (since 1998). In large-scale test fires, temperature predictions through the use of FDS showed values characterized by a difference of 15% compared to the actual measured temperatures, while the Heat Release Rates predicted by a difference of 20% of the measures taken. 4. GEOMETRIC RECONSTRUCTION AND CHARACTERISTICS OF PRODUCTS IN THE WAREHOUSE The geometric reconstruction of the building, which is necessary for the modeling of the fire scenario, was carried out by using the PyroSim 2017 software. We proceeded to a three-dimensional survey with laser scanning technology and to a subsequent processing of the point cloud through 3D processing software. Figure 1 shows, on the left, a screenshot of the point cloud and, on the right, the three-dimensional model subsequently imported into PyroSim. 1 K. McGrattan, S. Hostikka, J. Floyd, H. Baum, R. Rehm, W. Mell, R. McDermott in cooperation with VTT Technical Research Centre of Finland, NIST Special Publication 1018-5, Fire Dynamics Simulator (Version 5) Technical Reference Guide, NIST National Institute of Standards and Technology, US Department of Commerce, June 11, 2008; 2 McGrattan, Kevin B., Hamins, Anthony, and Stroup, David, Sprinkler, Smoke & Heat Vent, Draft Curtain Interaction - Large Scale Experiments and Model Development, National Institute of Standards and Technology, Gaithersburg, MD., NISTIR 6196-1, September 1998; 3 McGrattan, Kevin B., Baum, Howard R., Rehm, Ronald G., Large Eddy Simulations of Smoke Movement, Fire Safety Journal, vol 30 (1998), p 161-178. Page 3 of 8

Figure 1: Point Cloud from laser scanning (left side) and 3dModel in PyroSim (right side). Inside the building, there were no fire-fighting compartments. In the attic, there was also a polypropylene mesh. Table 1 below shows the typical data of the materials used for modeling the fire scenario. Material Density (kg/m 3 ) Auto-ignition temperature ( C) HRRPUA 1 (kw/m 2 ) Material 1 50 250 500 Material 2 640 450 200 Material 3 640 400 200 Material 4 900 350 300 Rubber 1400 400 500 (1) HRRPUA: Heat Release Rate Per Unit Area Table 1: Typical data of materials used for the simulation The warehouse was equipped with a bird mesh screen that, in the simulation, was considered as a propylene net with density of 1 kg/m³ and melting temperature of 160 C. The HRRPUA parameter (Heat Release Rate Per Unit Area) represents the heat flow developed by combustion per unit area. Table 2 shows the main characteristics of the construction materials. Material Density (kg/m 3 ) Heat conductivity (W/m K) New Jersey barriers 2280 1,8 Sandwitch panels 40 0,02 Polycarbonate glasses 1380 0,2 Table 2: Characteristics of construction materials Page 4 of 8

5. IDENTIFICATION OF FIRE SCENARIO The study was carried out by a three-dimensional fire simulation, assuming that the fire source originated from a pile of combustible waste, placed near the entrance of the warehouse, formed after crushing operations. According to the reconstruction carried out, the initial fire ignition started from the burning of the crushed pile. The simulation was carried out without considering any fire mitigation (it should be noted that, after about 300 seconds, the internal emergency team intervened to start the first cooling operations, waiting for the Fire Brigade arrival). 6. FIRE SIMULATION The result of the three-dimensional simulation with the FDS/PYROSIM calculation model consists of a video that allows checking the development of the fire according to time and temperature profiles on the walls of the warehouse and on the virtual plans introduced during the input phase, in particular on the caissons and on the accumulation of the products. The analysis of the video highlighted the following interesting points, to which we extracted "still images" with related comments. The 33 s still image (see Figure 2) shows that the accumulation of combustible material is partially ignited but it has not yet initiated and propagated to the compartment next the combustible material. Figure 2: Accumulation of fire crushed material (Time 33 s) The accumulation of crushed material, from which the fire began, ignited the compartment next to the combustible material on the wall side of the warehouse: Figure 4 shows the initial instants of the fire, in which the temperatures are still quite basic (compare the color of the wall and the temperature scales). Page 5 of 8

Figure 3: Accumulation of fire combustible material (Time 60 s) Figure 4: Propagation of fire to compartments (Time 147 s) Figure 5 shows that the fire is propagating to the compartment next to combustible material after about 147 and, therefore, in accordance with what reported in the description of the accidents. Page 6 of 8

Figure 6: Fire involving the entire warehouse (time 1000 s) Figure 7: Temperature profile (time 1000 s) The development of the fire is congruent with the available elements. The temperature profile detected with a virtual plane on the tire caisson leads to low temperature values not able to develop the degradation of the rubber, in order to facilitate ignition. The fire (see Fig. 8) continues even if the piles of crushed material to the next compartments begin to decrease in consistency and the flames are lowered with consequent reduction of the temperatures; it should also be noted that in the compartment 2 (completely wood) there is no ignition. Page 7 of 8

7. RESULTS ACHIEVED The simulation of the fire led to exclude the presence of flammable products that may have been a source of secondary ignition such as to favor the fire in the outer caisson of combustible material. The simulation showed that the development of the fire in the tank of external combustible material is not compatible with the temperatures reached by the fire inside the warehouse. This statement is further strengthened by the conservative assumptions upstream of the simulation, which aggravated the incidental scenario with a pile of additional fuel product close to the combustible material, from which the ignition began and it did not take into account the mitigation measures carried out by the internal emergency team and the subsequent intervention of the Fire Brigade. The videos obtained by the three-dimensional simulation of the fire and the sequence of photos shown above confirm that, on the tank containing combustible material, temperatures are not reached such as to initiate and support the phenomenon of degradation of the rubber, until the hydrocarbon vapors are ignited which usually are release from this type of product. Actually, however, it was found that the fire was there and, then, it is necessary to proceed with some reflections, in order to understand and reconstruct what happened and why the results of the simulation are quite congruent with the development of the fire within the warehouse and, instead, it seems not considering the caisson placed outside. The possible hypotheses that may have led to this lack of characterization can be attributed, in our opinion, to the state of the areas on the caisson-side that, in the modeling, was considered "empty" of materials from the compartments next to the origin of the ignition up to the wall bordering the caisson and the area surrounding the caisson itself. 8. FURTHER DEVELOPMENT In the last few years, many similar fires occurred in Italy and, for that reason, the Italian Ministry of Environment has recently issued a first version of a Guideline according to risk management. These accidents and the results of the analyses will probably lead to a review of fire-prevention design criteria of these plants. During the analysis it was found that, at a design level, some measures could be taken, such as for example passive protection or the insertion of a dedicated sprinkler system, even limited to a portion of the warehouse. The fire and/or smoke detection could be considered even if the intervention of the team was timely and the high fire risk processes are carried out during the personnel supervision. Regarding the modeling of the fire, the experimental starting data of the materials should be analyzed, in order to better characterize the phenomenon. REFERENCES McGrattan K., Hostikka S., Floyd J., Baum H., Rehm R., Mell W., McDermott R. (June 11, 2008) in cooperation with VTT Technical Research Centre of Finland, NIST Special Publication 1018-5, Fire Dynamics Simulator (Version 5) Technical Reference Guide, NIST National Institute of Standards and Technology, US Department of Commerce; McGrattan, K.B., Hamins, A., and Stroup D., (September 1998) Sprinkler, Smoke & Heat Vent, Draft Curtain Interaction - Large Scale Experiments and Model Development, National Institute of Standards and Technology, Gaithersburg, MD., NISTIR 6196-1; McGrattan, K.B., Baum H., Rehm R., Large G.E. (1998) Simulations of Smoke Movement, Fire Safety Journal, vol 30, p 161-17. Page 8 of 8