SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

Similar documents
Indirect gas-fired air heater

ELECTRIC AIR HEATER INSTALLATION AND SERVICE MANUAL

ZG Shown READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

KG 092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

Bosch 80% AFUE Gas Furnace BGS80 Model

KGA092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

User s Information Manual

WARNING FIRE OR EXPLOSION HAZARD.

TGA/KGA024, 030, 036, 048, 060, 072, 090 (2, 2 1/2, 3, 4, 5, 6, and 7 1/2 TONS)

ML180UH SERIES GAS FURNACE WARNING WARNING

Gas-Fired Indoor and Outdoor Duct Furnaces

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

USER'S MANUAL PGE Single Package Rooftop

Packaged Gas/Electric

USER S INFORMATION MANUAL

WARNING FIRE OR EXPLOSION HAZARD.

TO DO IF YOU SMELL GAS

INDIRECT GAS FIRED AIR HEATERS LD(E) SERIES. Model 120, 180, 240, 300, 350 and 400 outdoor INSTALLATION AND SERVICE MANUAL

Fig. 1 - Unit PGD4, PGS4, WPG4

P.O. Box , Dallas, TX USER'S INFORMATION MANUAL Single-Stage Warm Air Gas Furnaces

USER S INFORMATION MANUAL (2,4)SG13B

INSTALLATION AND OPERATION MANUAL GAS SKILLETS MODELS: GTS-30 GTS-40

EL296UHV SERIES GAS FURNACE WARNING WARNING

EL195UHE SERIES GAS FURNACE WARNING WARNING

User s Information Manual

Owner s Information Manual

FEATURES AND BENEFITS

SLP98UH SERIES VARIABLE CAPACITY GAS FURNACE WARNING WARNING

MANUAL WARNING FIRE OR EXPLOSION HAZARD. SL280UHNV SERIES WHAT TO DO IF YOU SMELL GAS:

User's Infomation Manual

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

HTDM INSTALLATION, OPERATION AND MAINTAINANCE MANUAL

USER S INFORMATION MANUAL

USER'S INFORMATION MANUAL

USER'S INFORMATION MANUAL

1. GENERAL SAFETY RULES

HOME OWNER S INFORMATION Induced Combustion Gas Furnace

BGH Series Hot Surface Ignition Control

OIL FIRED WARM AIR FURNACE. Homeowner Instructions

G61MPV SERIES GAS FURNACE WARNING

EL195DFE SERIES GAS FURNACE WARNING

USER'S INFORMATION MANUAL

READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

KEES, INC. Installation & Maintenance Manual DFG Series Direct Gas Fired Make-up Air Heaters. Table of Contents FOR YOUR SAFETY.

USER'S INFORMATION MANUAL

USER'S INFORMATION MANUAL

USER S INFORMATION MANUAL SLP98UHV SERIES

EL195UH SERIES GAS FURNACE WARNING

User s Information Manual

ECLIPSE INFORMATION GUIDE

USER S INFORMATION MANUAL

DOMESTIC WATER HEATER OIL FIRED

Technical Manual MAY 2008 Edition

For use with models: PGM304-1, versions M-B PGM365-1, versions M-E, M-F & M-G

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

MODEL ADF/ADFH 300 and 500 INDOOR/OUTDOOR DIRECT-FIRED GAS HEATING/MAKEUP AIR SYSTEM FOR INDUSTRIAL & COMMERCIAL APPLICATIONS

SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.)

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

THC 85N / 175N INDUSTRIAL / COMMERCIAL SPACE HEATER

OPERATING INSTRUCTIONS MANUAL FLE-150 INDUSTRIAL / COMMERCIAL ELECTRIC HEATER (OPERATOR MUST RETAIN FOR FUTURE REFERENCE)

READ MANUAL CAREFULLY BEFORE INSTALLING, OR OPERATING THE HEATER. Unit Model: Serial #: Factory Job #: Installation Date:

Model 60200FR Gas Primary Control Data Sheet

Owner's Guide to Operating and Maintaining Your Gas/Electric Unit

Field Start-Up Sheet Direct Fired Gas Equipment

SERVICE FACTS WARNING M801-SF-1C. Gas Furnaces Upflow & Downflow Induced Draft 1 Stage Heat Models: DISCONNECT POWER BEFORE SERVICING M801P040AU24AA

USER'S INFORMATION MANUAL

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) F-400T DUAL FUEL CONSTRUCTION HEATER

THC 85N / 175N INDUSTRIAL / COMMERCIAL SPACE HEATER

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

USER'S INFORMATION MANUAL

This document was created with FrameMaker 4.0.4

SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.)

24 VAC SYSTEM CONTROL KIT

40 SERIES GAS BURNER MODEL 400 NATURAL GAS/PROPANE INSTALLATION INSTRUCTIONS AND OWNER S HANDBOOK

Industrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation

UNITARY PRODUCTS GROUP

ADF/ADFH 300 and 500

GAS COOKTOP MODELS: CTG365D, CTG305D, CTG304D TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

DIRECTIVE NO: D-B

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) F-1500T DUAL FUEL CONSTRUCTION HEATER

LGA/LGC036, 042, 048, 060, 072 (3, 3-1/2, 4, 5, and 6 TONS) LGA/LGC090, 102, 120, 150, (7-1/2, 8-1/2, 10, and 12-1/2 TONS)

ENERVEX ADC100 DRAFT CONTROL

ELECTRONIC FIREPLACE DAMPER

NOTE TO INSTALLER: This manual must be left with the equipment user. Model 480BAV Upflow and 481BAV Downflow/Horizontal

CMO32 CMO50 DOMESTIC WATER HEATER OIL-FIRED. Models: CMO32 CMO50

Operating instructions

USER S INFORMATION MANUAL

ADC150 Automatic Draft Control

southbend A MIDDLEBY COMPANY INSTALLATION AND OPERATION MANUAL CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) GAS BOILERS MODELS:

THC 85 / 175 INDUSTRIAL / COMMERCIAL SPACE HEATER

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

THC-175DF INDUSTRIAL / COMMERCIAL SPACE HEATER. Certified to / Certifié à CGA 2.14 M2011 Conforms to / Conforme à ANSI std Z83.

ELECTRONIC FIREPLACE DAMPER

Owner's Manual. Induced Combustion Gas Furnace ! WARNING NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER.

Transcription:

Bousquet Technologies Inc. 2121, Nobel, Ste Julie, Quebec, Canada, J3E1Z9 SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL Oil-Fired air heater for industrial and commercial use. FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Installation and service must be performed by a qualified installer, service agency or the oil supplier. WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death or property damage. Be sure to read and understand the installation, operation and service instructions in this manual. KEEP THIS MANUAL FOR CONSULTATION. Improper installation, adjustment, alteration, service or maintenance can cause serious injury, death or property damage.. HDO(H) Installation and service manual 1 V3_12 12

TABLE OF CONTENTS TABLE OF CONTENTS... 2 1) CODES AND REGULATION... 3 2) INSTRUCTION D INSTALLATION... 4 3) ELECTRICAL CONTROL SENSORS CONNECTIONS... 5 4) OIL SUPPLY CONNECTION... 5 5) START UP INSTRUCTIONS... 5 6) HDO SERIES CONTROL SEQUENCE... 6 7) HEATER SHUTDOWN/RESTART... 7 8) TROUBLESHOOTING... 8 9) UNIT MAINTENANCE... 10 10) START UP REPORT... 11 HDO(H) Installation and service manual 2 V3_12 12

1) CODES AND REGULATION IMPORTANT This appliance is for commercial or industrial use only and that the installation shall be in accordance with the standard for the Installation of Oil Burning Equipment CSA B139, National Fire Codes, Vol. 1, NFPA 31; the National Electrical code, NFPA 70; CSA C22.1; and the requirements of the inspection authorities having jurisdiction. All internal and external electrical installations must comply with electrical diagrams of the heater. To learn more, refer to the instructions starting at the sequence of operations and setup instructions. IMPORTANT CLEARANCES TO COMBUSTIBLE A minimum clearance of 24 inches between the furnace and any combustible material is required on all sides and top of the furnace. On the control side, a minimum clearance of 42 inches is necessary for access and 18 inches all around the chimney. The unit must be on a noncombustible flooring. Allow sufficient space on both sides of the duct furnace for maintenance and allow sufficient space on the air inlet hood side to prevent snow accumulation and do not block the combustion air inlets. CAUTION Improper installation, modification, adjustment or maintenance can cause property damage, injury or death. Read the installation instructions, start up and maintenance instructions before installing or servicing this equipment. For units installed indoors, it is mandatory to provide a sufficient amount of outside air for combustion in the mechanical room. Refer to CSA B139 installation code for further information. Oil fired appliances shall be connected to discharge pipes having at all times a sufficient draft to ensure proper and safe operation of the unit. HDO(H) Installation and service manual 3 V3_12 12

2) INSTRUCTION D INSTALLATION The air intake must be located and oriented in order to prevent infiltration of snow, rain and flammable toxic gas, as well as any other harmful material in the make up air heater. When the heater is hung over a work area, it must be installed at an adequate height. The installation of a service platform might be required. When fire dampers are used in the ducts, they must be equipped with an electric switch wired to the safety control circuit of the unit in order to shut down the air heater when fire is detected in ducts. These electric switches must be wired to re activate the safety circuit only when the fire dampers are completely opened. In order to prevent any risk of freeze up, the installer must install a minimal temperature detector if not supplied with the unit. Depending on unit size diameter of the flue connection vary between 6 and 12 inches. HDO series combustion systems are designed to operate safely against a back pressure of ¼ water column, with a double wall type PS chimney, either in a vertical arrangement (through the roof) or in a horizontal arrangement (through the wall), or a combination of both. N.B. : It is recommended to mechanically fix the heater to the roof curb or supporting structure with screws or other appropriate fastening means. HDO(H) Installation and service manual 4 V3_12 12

3) ELECTRICAL CONTROL SENSORS CONNECTIONS WARNING The sensors connections must be carried out by a qualified electrician, respecting the unit s electrical diagram and according to local codes. The sequence of operation of the electrical diagram must never be modified without consulting the manufacturer. Make electrical connections between the duct furnace and the ventilation unit following the wiring diagram supplied with the furnace. Consult manufacturer for any modifications. 4) OIL SUPPLY CONNECTION REFER TO BURNER MANUAL FOR OIL SUPPLY CONNECTION 5) START UP INSTRUCTIONS These instructions must be performed after the ventilation unit has been properly started up and that air is blowing at the designed flow rate through the heat exchanger. IMPORTANT The following start up information should only be used by a qualified technician for oil equipment installation (with qualification cards) with knowledge in electricity and ventilation. WARNING Smoking is not recommended during the heater start up. Do not try to light the burner if the oil has accumulated, if the combustion chamber is filled with vapors or if it is hot. FAN ADJUSTMENT Check voltage of each phase at main electrical disconnect; Check fan rotation and modify electrical connection if required. Ensure that the contactor overload relays are set according to the full load amperage (FLA) as indicated on motor name plate; Check alignment and belts tension; When dampers are completely opened, with fan running, read amperage at each motor phase and check if it corresponds to the project design BHP, as shown on the heater technical name plate. Modify fan rotation if necessary. HDO(H) Installation and service manual 5 V3_12 12

BURNER ADJUSTMENT **REFER TO BURNER MANUAL FOR INSTRUCTIONS** WARNING Do not adjust burner flame only visually. Using a combustion analyzer and combustion instruments is the only recommended method to adequately adjust burner combustion. 6) HDO SERIES CONTROL SEQUENCE (For indication purpose only) FAN START UP 1. Position selector (STOP/FAN/BURNER) to FAN position; 2. Fresh air intake damper opens; 3. The damper end switch closes; 4. Fan motor starter contactor is energized; 5. The fan is in operation. BURNER START UP 1. Position selector (STOP/FAN/BURNER) to BURNER; 2. Burner combustion air fan starts; 3. Air combustion damper opens completely to perform a complete purge of the exchanger, and returns to closed position; 4. The burner flame ignites; 5. Burner operation is proven when burner fan pressure switch and high temperature limit switch are closed; 6. The burner operates and modulates according to an external signal (0 10 volts or 4 20 ma). 7. When demand for heating is satisfied, the post purge sequence maintains the burner in operation with the combustion air fully opened in order to evacuate all remaining flue gas from heat exchanger; 8. Burner stops and is now ready for a new heat demand. HDO(H) Installation and service manual 6 V3_12 12

7) HEATER SHUTDOWN/RESTART EXTENDED SHUTDOWN When the heater is not used for a long period, it is recommended to cut the oil supply and electricity. Before replacing the heater on after a shutdown, it is recommended to make an inspection to ensure that everything is in order. EMERGENCY SHUTDOWN When it is necessary to stop the heater in case of emergency, turn the main switch OFF and disconnect the oil supply by closing the manual valve supply to the outside of the heater. RESTART AFTER A FLAME FAILURE ALARM Following a flame failure alert, perform the following checks: o FAN 1. Place main electrical disconnect to OFF position; 2. Check fan belts; replace or adjust if required; 3. Check filters conditions; replace if necessary; 4. Ensure that nothing obstructs the air inlet and outlet of the heater; 5. Ensure that nothing is restraining inlet or outlet dampers operation. o BURNER 1. Ensure that all gas supply hand valves are opened; 2. Check status of the flame safeguard relay (for problems, refer to troubleshooting section); 3. Check pilot flame rod and spark igniter; 4. Place main electrical disconnect to ON position; 5. Press the reset button of the flame safeguard relay; 6. Ensure that the blower motor is operating; 7. Ensure that the pilot ignites properly; 8. Fix all problems and repeat the start up procedure. HDO(H) Installation and service manual 7 V3_12 12

8) TROUBLESHOOTING Refer to burner manual and/or flame safeguard for alarm codes and troubleshooting. SYMPTÔMS The fan is stopped. The burner is off. Fresh air damper is closed. TROUBLESHOOTING CHECK LIST CORRECTIVE ACTION Turn ON main disconnect switch. Check line voltage. Check secondary circuit fuse (120 volts). Check selector position on remote control panel; turn it to BURNER position. If ALARM light of the flame safeguard relay flashes, press the reset button. Check adjustment of the overload relay of the fan motor; re adjust if necessary. Check freeze low temperature thermostat. Its contact opens approximately 300 seconds if supply air temperature remains below 42oF. To restart the heater, turn selector of the remote control panel to STOP, and then back to BURNER position Refer to the manufacturer. The fan is stopped. The burner is off. Fresh air damper is opened. The fan is in operation. The burner is off. The flame safeguard relay is operating normally (No flashing lights) Frequency noise Flame failure Ensure that fresh air damper end switch is closed. Refer to the manufacturer Check if the auxiliary contact of the main fan motor starter works. Check the position of the selector on the remote control panel; position it to BURNER. Refer to the manufacturer. Check for a high voltage source close to the flame safeguard relay. Check electrical wiring between building distribution panel and the heater. Refer to the manufacturer. Check oil supply. Check ignition transformer. Check flame signal intensity. Check if manual and electric pilot oil supply valves are opened. Check condition of the flame rod ceramic; replace if necessary. Refer to the manufacturer. Check the flame safeguard amplifier; replace if necessary. Perform a combustion test over the entire range of modulation. HDO(H) Installation and service manual 8 V3_12 12

SYMPTÔMS Air pressure switch opened. Ground fault (frame). Faulty programmer. Faulty amplifier. Voltage drop. Ground fault. TROUBLESHOOTING CHECK LIST (suite) CORRECTIVE ACTION There are two devices connected in series on the flame safeguard relay. A) Burner pressure switch The burner pressure switch proved that the burner is in operation. B) Safety high temperature limit switch (set at 160oF) Its contact is normally closed (N.C.) and open when air temperature exceeds 160oF downstream of the heat exchanger. Corrective action Check burner fan rotation. Check for obstruction in chimney. Check for obstruction at combustion air intake. Check sampling tubes of the pressure switch (installation and adjustment). Replace pressure switch if defective. Refer to manufacturer. At start up or when is in operation Check temperature upstream of the heater (safety high temperature limit switch opens when air temperature exceeds 160oF) Check burner modulation, all controls and temperature control signal. Check oil pressure at burner manifold for maximum fire. If required, replace the temperature switch. Refer to manufacturer. Check grounding of the heater frame and flame safeguard relay. Check for ground default in electrical wiring between the heater and main distribution panel. Refer to manufacturer. Replace the programmer. Refer to manufacturer. Replace amplifier. Refer to manufacturer. Check voltage at the relay while heater is in operation. Check relay electrical connections and installation. Refer to manufacturer. Check relay grounding. Main current and neutral wires inverted. Refer to manufacturer. HDO(H) Installation and service manual 9 V3_12 12

9) UNIT MAINTENANCE Perform the following tasks at the prescribed frequency will help keep the duct furnace in good working condition. Check list Recommended maintenance frequency Weekly Monthly Biannually Annually Check the conditions of filters; change if needed. Check bearing lubrication and condition of the belts. Ensure that no flammable material is stored near the heater Ensure that nothing obstructs the air inlets and outlet of the heater Check combustion and flame quality Check for full opening of fresh air dampers. Check that all safety controls are operational Check the operation of the high temperature limit thermostat Ensure that there is no oil leaks in piping (fittings & valves). Inspect all electrical connections Inspect the flame detector and igniters electrode; change if necessary Clean burner fan wheel Check burner installation and tighten screws and bolts if required Check the operation of the high temperature limit thermostat IMPORTANT BEFORE STARTING AND AFTER 8 HOURS OF OPERATION - Check the alignment and lubrication of bearings; - Check the bearings clamps; - Check the alignment and belt tension; AFTER 24 HOURS OF OPERATION - Check the belt tension. **REFER TO BURNER INSTRUCTION MANUAL FOR BURNER MAINTENANCE** HDO(H) Installation and service manual 10 V3_12 12

10) START UP REPORT Company: Project: Technician: Project manager: Contractor: Address : Manufacturer Infos Model number: Serial number: Burner model: # Serial Burner : Inspection Oil leak: Air duct installed: No wire located upstream of the burner: Remote panel installed: Note : Start up Flame signal : VDC Oil pressure : LOW FIRE HIGH FIRE INLET OIL PRESSURE Adjustments Inlet duct thermostat: ºF Pre purge delay: sec. Low limit stat (freezestat): ºF Delay when starting on low fire: sec. High limit thermostat: ºF Low limit delay: sec. Start up completed: If no, why? (or others): HDO(H) Installation and service manual 11 V3_12 12

Combustion Analysis Ambient temperature : F Signal % CO2 % Oxygen Temp. Gas F % Efficiency % excess air PPM CO Smoke test 0% 20% 40% 60% 80% 100% Note : Signature : Date : HDO(H) Installation and service manual 12 V3_12 12

HDO(H) Installation and service manual 13 V3_12 12