ART TEC Solar Differential Temperature Controller DTC-1 Manual

Similar documents
Solar Heat. Expanding & Improving an Owner-Installed System

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

Solar Hot Water. PV + Heat Pump or Thermal. Which is better?

Service Manual. DCXXXX, DEXXXX Model Compressor Refrigerators MODELS DC0040(K), DC0051(K) DE0040, DE0051 DE0240T, DE0251T DC0740(X), DE0740(X)

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

DURANGO 12V Heater HF

EG-400 Fire Detection Monitor

PCS 2000 CONTROLLER USER GUIDE PCS 2000 CONTROLLER. Contents

MODEL EUR -5A AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

Freightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3)

LC2200 Level Controller Installation and Maintenance Instructions

Information Job Sheet 4. Closed-Loop Drainback Systems. Drainback tanks

KP: Charge Air Cooler (CAC) Pump

Solar water heating system

Warranty Info: ETI s warranty policy can be viewed at:

Public Safety DAS Annunciator Panel

Installation, Operating and Maintenance Manual

CodeNotes. Solar Water Heating Systems Based on the 2018 International Solar Energy Provisions (ISEP ) Introduction OFFICIAL

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

INSTALLATION AND TROUBLE SHOOTING MANUAL for all Models of Nova Kool Remote Condensing units & Cold plates.

Using Adaptive Defrost Control Technology to Improve Energy Savings in the Food Service Industry.

Hoffman Controls 759-ECM. Installation & Operating Instructions. Introduction. Installation. Pre-Installation Information/ Instruction

SYSTEM DESIGN REQUIREMENTS

V. DIFFERENTIAL THERMOSTAT

Electric Coils. Blower Coils. Product Information

Off-Grid CyboInverter Installation Guide. For CI-Mini-1200H Solar Mini-Inverter for Electric Water Heaters

General System Layout Sketch

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

SOLAR SIX PACK TM WATER HEATING SYSTEM PICTORIAL INSTALLATION GUIDE

Retrofit an evacuated tube collector to an existing cylinder Updated

solar thermic system Solar thermic systems are devices that allow you to capture and store solar energy for later use in various utilization.

solar thermic systems

Ralf Seip. Figure 1: Basic solar hot air collector and operation.

Construction Electrical

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL AUTOBOOSTER IMPORTANT SAFETY INFORMATION

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

TYBOX PAC. * _rev1* User guide. Programmable thermostat for heat pumps

ADDITIONAL INFORMATION

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts

Aqua-Gen 3 INSTRUCTIONS

SA SIREN AMPLIFIER

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK

Models AP-10, AP-20 and AP-30

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS

Entry Level Assessment Blueprint Electrical Construction Technology

HERMS (Heat Exchanger Recirculating Mash System) Controller

Passive Solar Home Design

Product Manual SZ1009

Better Design, Better Control, Better Systems.

OPERATING INSTRUCTIONS WPSI12. Portable Soldering Station & TCP12. Soldering Tool. Weller Tech Sheet Product Code: Issue A 24/05/05

CARSON MANUFACTURING CO., INC NORTH RURAL STREET INDIANAPOLIS, IN (888) TECHNICAL BULLETIN

Ispend most of my waking hours at work, teaching college

INSTALLATION MANUAL GEO-BOOST GROUND LOOP HEAT EXCHANGER

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

Understanding Solar Types

Hydronic & HVAC Control Systems

Wig-Wag (C) Light-Flashing Module Improves Aircraft Visibility

INSTALLATION AND TROUBLE SHOOTING MANUAL for all Models of Nova Kool AC/DC and DC only Refrigerators and Freezers.

Installing and operating your Cabinet Cooling System, with Digital Thermostat

Efficient Steam System Design

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

Installing and operating your Enclosed Cabinet Cooling System and digital thermostat

MS7 Single Zone Mini Split System Air Conditioners and Heat Pumps

ENCLOSURE COOLING. Glossary

Bulletin (Jan 2011) And User s Guide

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

CARSON MANUFACTURING CO., INC NORTH RURAL STREET INDIANAPOLIS, IN (888) TECHNICAL BULLETIN

Revision B Printed Fall Elston Manufacturing HC Heater Owners Manual

Radiant Thermostat 519

Analog Room Pressure Monitor RPC Series

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

MICRO CONTROLLER S Z SERIES

CO2 Monitoring Frequently Asked Questions for the

Unit 3 Machine Composition

Installation Instructions 4 Zone Fire Panel

Installation and Operating Manual

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system

Q1. Carefully read the following extract from a safety leaflet. Then answer the questions.

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

ASHRAE JOURNAL ON REHEAT

8008 CIRCULATION UNIT FOR SOLAR THERMAL SYSTEMS, FLOW AND RETURN.

INSTRUCTIONS FOR THD-U SERIES HOT AIR MATERIAL DRYERS

Alternate Energy Technologies PO Box Jacksonville, FL INSTALLATION OPERATION MAINTENANCE MANUAL DX DRAINBACK

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Net/X Thermostat Network Installation and Troubleshooting Guide

INSTALLATION INSTRUCTIONS

Copper convection heaters:

Programmable Towel Radiator Manual

1F60-22 INSTALLATION & OPERATING MANUAL SETBACK THERMOSTAT. Homeowner: Save this booklet for future use!

2008 DOUBLE DRAWER UNDER COUNTER REFRIGERATOR / FREEZER PRODUCTS

Utilizing Finite Element Analysis (FEA) for Flexible Heater Designs

RCS Residential Control Systems Inc.

Cimco Series 21. Series 21 - Specifications INDEX. Description. Operational Specification 2

INSTALLATION/OPERATING INSTRUCTIONS BCP-3. Hot Water Reset Control For up to 3 Boilers. How the BCP-3 operates... 1:4 1:3 1:2 1:1.

General System Layout Sketch

USER MANUAL MODEL READ ALL INSTRUCTIONS BEFORE PROCEEDING. 5-2 Day Programmable Multi-Stage 2 Heat/1 Cool Heat Pump Digital Thermostat

Transcription:

ART TEC Solar Differential Temperature Controller DTC-1 Manual This controller is designed specifically for solar heating applications where the circulation pump is powered by a solar panel or DC power. The DTC-1 will improve the performance of any DC powered solar heating system. It will switch power to the pump when it determines that one sensor (S1) is hotter than the other (S2). More importantly, it shuts off the pump when the reverse is true.

Mount the DTC-1 indoors where it will be protected from weather. Remove the cover (4 screws) to access the terminals inside and simply connect power, your pump and 2 10K temperature sensors. S1 - hot sensor - 10K thermistor. This sensor reads the temperature of the incoming solar generated heat. Attach to pipe with a hose clamp, and wrap with insulation. Wrap the sensor with insulation to protect it from ambient temperatures. Solder all wire conections and weatherproof them carefully to prevent corrosion of the connections. DO NOT use wire nuts or crimp terminals outside! S2 - cool sensor - 10K thermistor reads the stored heat. Attach to pipe with a hose clamp, or affix to tank surface and insulate from ambient air. Try to locate the DTC-1 to minimize the wire length to the sensors. If the wires running to the sensor are more than 6 feet long, they should be twisted as a pair, or use pre-twisted wire. Solder and insulate all wire connections. POWER - connect to solar panel, battery or any 12 to 24VDC source. Use at least 18 gauge wire for up to 20 foot runs, heavier wire for longer runs. Outdoor wiring should be rated for exterior use Observe polarity! PUMP - 12V or 24DC load. Observe polarity! The DTC-1 will operate from 3.5 to 30 Volts and power a pump rated up to 6 Amps (72 Watts as 12 Volts). Most pumps will begin to operate at 4 Volts.

FEATURES Operates from 3.5 to 24 Volts. 30V MAX! Uses standard 10K thermistor temperature sensors Ambient Operating Temperature 32-158F (0-70C) Manual override switch has ON/AUTO/OFF to simplify testing Green LED load power indicator Switches up to 6 Amps (72 Watts) Replaceable 6 amp 3AG type fuse inside Built in surge protection protects electronic motors Under 3mA power consumption (when load is off) CONTROLS Inside the unit there is a switch with 3 positions: ON - load is always on. AUTO - load only powered if S1 is hotter than S2. OFF - load is off. The switch is intended primarily for testing, and should be left in the AUTO position for normal operation. The green LED will light to let you know when the load should be operating. When replacing the cover - be sure that the LED aligns with the hole in the cover. TROUBLESHOOTING Indicator lights, but load does not operate: Check the fuse. Check load wiring, and polarity. Check to ensure that there is light on the solar panel, most pumps will not operate/start at low voltages, however the indicator light will come on at 3.5 Volts. Load does not operate: Check the fuse. Is the green indicator light on? If not, there isn t enough solar power to run the load. In general use a panel with at least 2 times the rated wattage of the pump. E.g.: 20 Watt panel with a 10 Watt pump. Check the LOAD switch, switch it to ON to see if pump runs, and OFF to be sure it does turn off. Leave it on AUTO for normal operation. Check for at least 4 Volts at the POWER terminals. Are the sensors correctly installed? Remove the sensor wires and test for resistance, it should read 10K at 77F, or higher resistance at lower temperatures and lower resistance at Higher temperatures. E.G. 200F = 829 Ohms and 50F = 19.9K Ohms. 3

Flat plate vs. evacuated tube collectors. There is an inherent mis-match between the efficiency of PV panels and solar thermal collectors such that the PV will have enough power to run a pump when the collector is not hot enough to be useful. This is most pronounced in cold climates. This is less true of evacuated tube collectors which are more efficient and do not radiate heat the way that flat plate collectors can. Late in the day when your storage tank has accumulated a lot of heat on a cold sunny day is the point at which you may need to shut off your pump. The collectors are not getting enough sun to generate a higher temperature than the stored water. What happens if the pump continues running is that your stored heat is radiated out from flat plate collectors. With evacuated tubes you are likely to be pumping cooler water into the tank. The DTC-1 is designed to prevent this from happening. Delta-T (aka hysteresis) What does this mean? Delta is Greek symbol used to denote Difference, and T = temperature. Many other (AC powered) DTC s on the market have an adjustable Delta-T that sets the difference beween the sensor temperatures before the pump is activated. The DTC-1 does not, it simply switches the pump on the moment one sensor (S1) is hotter than the other (S2) and turns it off the moment that S1 is cooler than S2. This makes the design simple and guarantees that you are never lowering the temperature of your stored water - even by a fraction of a degree. Placement of the sensors must be carefully considered to account for temperature drops across both sides of a heat exchanger, see next page. 4

Sensor location Pressurized glycol systems. On single pumped systems (where the heat exchenager is inside the storage tank) the hot (S1) sensor should be mounted to the pipe within 6 of the exit at top of the collector. This ensures a rapid response. On double pumped systems where one pump circulates the collector to HX and another circulates from HX to storage, the hot (S1) sensor should be attached to the pipe that comes from the collectors about 2-3 feet before it enters the heat exchanger. The DTC-1 should then be used to switch the secondary pump. The cool sensor (S2) should be located where it accurately measures the average temperature of the stored water. This can be the pipe that returns to the heat exchanger from the storage tank, or if you can access the surface of the tank, then attach the sensor to the tank wall about 1/4 from the top. Be sure the sensors are insulated from exposure to ambient air, since this will affect the reading. On pipe runs the sensors can be attached with a pipe clamp and wrapped with insulation. Drain back systems The DTC-1 is not recommended for drain back systems because a Delta-T control is needed. As the water first comes out of the collector, the pipe temperature will drop which will confuse the DTC-1 and shut off the pump. This will cause rapid cycling that will prevent the system from working and could damage the pump. Most drainback pumps are AC powered, so the DTC-1 would not be appropriate in any case. 5

PV powered pumps There are basically 2 types of DC pumps used in solar heating. Regular DC pumps made by March etc. and electronic pumps like the El-Sid pumps made by Ivan Labs. There are several models of El-Sid pump, and some are optimized for solar vs battery power, be sure to choose the correct one for your system. It is recommended that if you live north of Florida that you use a panel with twice the wattage of the pump, e.g. 20 Watt solar panel for 10 Watt pump. This ensures optimal performance early and late in the day. An option for DC pumps is to use a power optimizer like the PPT line of products made by Solar Converters. These units can let you use a smaller PV panel for the pump. The disadvantage is these devices will start a pump in lower light, which makes the DTC-1 even more necessary! Surge Protection is Built in Note that the DTC-1 contains a surge protector which will protect the electronic motors and other electronics like power optimizers. Any voltage over 40 Volts will be clamped inside the DTC - and shorted back to the PV panel. DC power sources The input to the DTC-1 can come from any source of DC voltage including a solar panel, battery or a Wall power adapter (wall wart). If powering a 10 Watt pump the wall wart should be sized about double the wattage of the pump. So a 10 Watt pump would need a 12 Volt 1.5 Amp adapter. 6

High Temperature Limiting If you live in a warm climate, you may wish to add a thermal snap switch against the wall of your storage tank. This switch will open at a preset temperature such as 190F and stop the pump. Do not use this approach with glycol filled collectors. Stagnating the collector fluid will cause the antifreeze to fail. On double pumped glycol systems it is OK to shut off the secondary pump (between HX and storage), but the collector pump must be connected directly to a solar panel. High Power pumps For larger pumps that exceed the 6 Amp capacity of the DTC-1, an external solid state relay is required. Mechanical relays should not be used as they will not turn on at the lower voltages put out by the solar panel. 7

A note about solar powered pumps: Solar powered pumps vary their speed in direct proportion to the amount of sun on the solar panel. For instance a 12 Volt pump powered by solar can operate from 4 to 18 Volts. This can actually improve system performance over a fixed speed pump such as an AC, or battery powered pump. The reason is that in lower light levels the slower pump rate allows the fluid to stay in the collectors longer, thus absorbing more heat. Conversely in full sun the pump runs faster, extracting the heat more efficiently. It does seem kind of silly to use an AC circulation pump - why pay your electric utility for Kilowatts of peak use energy when you can get it for free from the sun? The relatively small investment in a solar panel (and DTC-1) will be recovered in a few years. Solar power is more reliable than our aging power grid which could fail in the middle of a hot sunny day potentially causing a catastrophic system failure. If the collectors heat the glycol fluid above 250 degrees or so it will turn acidic and eventually eat through the pipes. Of course the P/T valve may also blow, dumping fluid and depressurizing the system. ART TEC LLC www.arttecsolar.com 61 Delano Road, Woolwich, ME 04579 866 427-8832 info@arttecsolar.com toll free: 866 427-8832 www.arttec.net/dtc revised 5/29/08 8