Zonex Systems Intelligent Fresh Air Ventilator Installation Instructions

Similar documents
Model 8120 and 8126 Safety & Installation Instructions

Installation Instructions

io-fav-08 FRESH AIR VENTILATION

Y8150 Fresh Air Ventilation System, W8150 Fresh Air Ventilation Control

Y8150 Fresh Air Ventilation System, W8150 Fresh Air Ventilation Control

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

Model 1750A/ 1770A Dehumidifier Installation Instructions

Installation, Safety & Maintenance Manual Model 1750A/1770A

Model 1730A Compact Dehumidifier Installation Instructions

Safety and Installation Instructions Model 1700

Ventilation, Makeup and Combustion Air Calculations Submittal Form New Dwellings

SmartZone TM System Manual

Site address. Ventilation Quantity (Determine quantity by using Table N or Equation 11-1) Continuous ventilation

City of Chanhassen. Site address. Ventilation Quantity (Determine quantity by using Table R or Equation R )

Model DEHXXCDA1070 & DEHXXCDA1095 Dehumidifier Installation Instructions

Design & Installation for. Zonex Systems. System Zone Auto Changeover. System Zone Manual Changeover

Model 8140 & 8141 Fresh Air Ventilator Installation and Operations Manual

TZ-3 TotalZone Zone Control Panel

York 25-Ton VAV Rooftop Unit

Practical and Effective Approaches to Residential Ventilation for Production Builders

Installation Instructions

DIGI3U. Zoning Systems. Installation Guide. That s all we do. Three-Zone, Universal Controller for Gas/Electric or Heat Pump Applications

Model 1870 & 1870W Dehumidifier Installation Instructions

AirCycler g2-k Installation & User s Guide

S1-CD065T01 Central Dehumidifier Installation Instructions. Johnson Controls Unitary Products WARNING CAUTION SPECIFICATIONS LOCATION CONSIDERATIONS

Unico Training. Class for R E Michel Salesmen

Ventilation Products AirCycler g2/g2-k Installation & User s Guide

TECHNICAL GUIDE. Echelon MODELS: FC9T GAS-FIRED CONDENSING / HIGH EFFICIENCY UPFLOW TWO STAGE FURNACES UP TO 94% AFUE

MODELS TR & TRC TOTAL RECOVERY FOR ALL CLIMATES RESIDENTIAL OR COMMERCIAL APPLICATIONS

Ventilation Products AirCycler g2/g2-k Installation & User s Guide

Outside Air Requirements... SOLVED!

Installation and Operating Instructions

Ventilation. ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce.

SAFETY AND INSTALLATION MANUAL MODEL 8100

45 Commerce Ave., Unit #2 South Burlington, VT tel: fax:

Model CZ-4. Installation and Operating Instructions. FORM White-Rodgers by Permission B

Installation Guide ProR221J, ProR212J, ProR321J and ProR312J

INDOOR AIR QUALITY CCWH Complete Comfort Whole-Home Dehumidifier ENGINEERING DATA. Nominal Capacity - 65 to 135 pints per day CCWH - 090

Model 8142 and 8142NC Fresh Air Ventilator Installation and Operating Instructions

Automatic Digital Humidifier Control

Model 8191 & 8192 Ventilator with Dehumidification Installation and Operating Instructions

TECHNICAL GUIDE. AFFINITY MODELS: PS8*DH GAS-FIRED HIGH EFFICIENCY SINGLE STAGE DOWNFLOW/HORIZONTAL FURNACES STANDARD & Low NOx DESCRIPTION WARRANTY

Model 8191 & 8192 Ventilator with Dehumidification Installation and Operating Instructions

FEATURES AND BENEFITS

INSTALLATION MANUAL MODULAR VARIABLE SPEED AIR HANDLERS MODELS: MV LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

ICM Simple Systems. CC750 Comfort Control Center CC and CC Application Guide

Wiring: All wiring should be conventional 18 gauge thermostat wire. Thermostats and zone dampers may be located up to 300 feet from the Z-300 panel.

IMPORTANT WARNING CAUTION

Installation and Operation Manual

TECHNICAL GUIDE MODELS: GM9T-UP GAS-FIRED CONDENSING / HIGH EFFICIENCY UPFLOW TWO STAGE FURNACES UP TO 94% AFUE

Heat or Energy Recovery Ventilation System

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA

Digi-Zone Model MDP3 Ver.04

CP-6 Installation and Operation Instructions 3 Heat / 2 Cool Heat Pump with Fossil Fuel option Auto Changeover - Cooling Priority or Majority Wins

MX Series Indoor Modular Blowers ModuleFlex Electric or Hot Water Heat with available Variable-Speed High Efficiency ECM Motor

ASYSTAT625A Humidity Control

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717)

INSTALLATION INSTRUCTIONS

DDNECNJ SEQUENCE OF OPERATION This sequence assumes employment of a single enthalpy economizer using a two stage thermostat.

ZONE PANEL KIT INSTALLATION MANUAL COMMUNICATING ZONE PANEL KIT - (S1-TCZCB01A) ZONE PANEL WITH ZONING TOUCH SCREEN FIRMWARE

Installation Instructions

FEATURES. Gas Furnace provides the efficiency customers want with 78% Annual Fuel Utilization Efficiency (AFUE).

Installation Guide. Dehumidification. Fresh Air Ventilation. Compact Size. Energy Efficient. RXID-AW90A Whole House Dehumidifier

COMcheck Software Version Mechanical Compliance Certificate

OPERATIONS & MAINTENANCE MANUAL RESIDENTIAL HEAT & ENERGY RECOVERY VENTILATORS TO BE COMPLETED BY CONTRACTOR AFTER INSTALLATION

Refer to the Page 23 (inside back cover) for Model Nomenclature. Table of Contents

INSTALLATION INSTRUCTIONS

Ventilation Techniques. Topic 5 - Audio 53

Model GB1AAV UPFLOW GAS FURNACE. Series G SS-GB1A-04 FEATURES

GSR21Q PULSE21 SERIES

R7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units

S1-CVD070T01A / S1-CVD095T01A Central Dehumidifier Installation Instructions. Johnson Controls Unitary Products WARNING CAUTION

5.0 AIR HANDLER EQUIPPED WITH THE COMFORT CONTROL 2 SYSTEM INTERFACE BOARD

Product Data. 58CLA Low-Boy Oil Furnace. Series 110 Input Capacities: 70,000 thru 154,000 Btuh. The Latest in Oil Furnace Technology

VERTICAL AHU ENGINEERING SPECIFICATIONS BULLETIN

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

Vertical Air Handler Unit

Installation Instructions WARNING WARNING. Variable Speed High Efficiency Blower Kit for Gas Furnace Applications 3. INSTALLATION

Product Data. FF1DNA, FF1DNE Fan Coil Units. Sizes 018 thru 030 FEATURES/BENEFITS

INSTALLATION AND OPERATION MANUAL Model BR70/BR130

Heat Recovery Ventilator Model PVe Light Industrial Commercial Institutional

Product Data. S Unit may also be sidewall vented with an approved A S OVM units equipped with ECM 2.3 Variable Speed

LEED for Homes V4 Provisional Alternative Compliance Paths for the Canadian market March, 2017

Product Data OBM/OVM. MULTIPOISE OIL FURNACE INPUT CAPACITIES 70,000 thru 154,000 BTUH THE LATEST IN OIL FURNACE TECHNOLOGY

Product Data. FH4C Base Series Fan Coil Sizes 001 thru 004 AIR HANDLER TECHNOLOGY AT ITS FINEST

GSR21Q GAS FURNACES EXISTING NEG EXISTING NEG ENGINEERING DATA HORIZONTAL POSITION. Typical Applications DOWN-FLO POSITION

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

Product Data. 58CMA Multipoise Oil Furnace. Series 120 Input Capacities: 70,000 thru 154,000 Btuh. The Latest in Oil Furnace Technology

10-year industry best core warranty. 5-year warranty on balance of unit.

RG7D 1-Stage Heat Series

Product Data. 58CMA Multipoise Oil Furnace. Series 110 Input Capacities: 70,000 thru 154,000 Btuh. The Latest in Oil Furnace Technology

Complete Ventilation, Heat Recovery and Dehumidification Packaged System by. Maintaining Your Climate for Indoor Pools and Waterparks

Natatorium Economizer Vs. Conventional Dehumidifier

FF1DNA, FF1DNE FAN COIL UNITS. Sizes 018, 024, 030. Form No. PDS FF1D.18.3 FEATURES FF1D

GAS FURNACES G20RE/ G20RXE EXISTING NEG ENGINEERING DATA EXISTING NEG. Typical Applications

Objectives. Home Performance Diagnostics with the House of Pressure (Part 1) How can Pressure effect Building Performance?

Product Data. S Unit may also be sidewall vented with an approved A S OVL units equipped with optional ECM 2.3 Variable

ECAH SERIES ECM AIR HANDLER

Put the V back in HVAC

B SERIES ELECTRIC FURNACE

Transcription:

Zonex ystems Installation Instructions Hotline (800) 228-2966 Visit Our Website www.zonexproducts.com The easy way to et Quotes Fast Part # IFAV

introduction The Zonex ystems (PAT # IFAV) is a fresh air ventilation controller designed to meet both AHAE 62.2 ventilation requirement and provide needed strategy to meet Energy tar fresh air demand within a 24-hour operations. This is accomplished through the Intelligent Fresh Air Ventilator s sophisticated software that monitors run time and uses outside air temperature to determine when fresh air operation occurs. Insuring proper indoor air quality standards per AHAE 62.2 and Energy tar. It is recommended that the intake air hood be an open metal type with a ¼ screen. The fresh air intake should be located away from dryer or furnace vents, driveways, trash area, and pool equipment. If the application is in a cold climate, locate the fresh air intake above snow line. Verify local code requirements for your location to insure you are in compliance. In most applications, a 6 to 8 air intake duct will be used with a Zonex ystems Fresh Air damper (Part# TFAD06, TFAD07, or TFAD08). This damper is power open spring closed and can keep unwanted outside air from entering the system. In some applications, a secondary fan will be used to bring in outside air, in these applications; fan and air intake duct should be sized together. oncept Drawing Triangle Number s 1. Fresh Air Damper (Part # TFAD) 2. Optional Auxiliary Blower Motor 3. 4. Air Handler/HVA Unit 5. Isolation elay (If required) E :1 VENTILATO 3 (Part # IFAV) 1 2 T FAD DAMPE M Overview Zonex ystems (PAT # IFAV) has three adjustable functions built into the controller. Time, High and Low potentiometers are on the controller and allow the controller to be field configured for each application. An outside air sensor is provided with the Intelligent Fresh Air Ventilator in order to provide outside air lockout when outside air is above or below High and Low settings. Outside Air ensor provides with the ability to lockout fresh air operation until the outside air temperature has returned to desired temperature. In order to meet requirements for Energy tar, lockout time is tracked and once temperature has returned to desired range, the will run using stored time and current demand until all fresh air time requirements have been met. If lockout time exceeds point between lockout and demanded fresh air in a 24-hour period, the will run the balance of 24- hour period in order to meet fresh air demand. Time: Time refers to the number of minutes each hour controller will call for fan and damper operation (If set for 20, then fan and damper will be energized 20 minutes out of each hour). Time is adjustable from 10 to 40 minutes each hour, and will be set based on fresh air requirements as set by AHAE 62.2. ontrol is factory set for 25 minutes. High: The High potentiometer is used to lock out fresh air when the outside air temperature is too high. This feature provides the builder and homeowner the ability to lock out hot air from entering the house when outside air temperature is too high. High limit is adjustable from 85 to 115. ontrol is factory set for 100 Low: The Low potentiometer is used to lock out fresh air activity based on outside air temperature being too low. This feature provides the builder and homeowner with the ability to lock out cool air from entering the house when outside air temperature is too low. Low limit is adjustable from 15 to 45. ontrol is factory set for 30 Outside Air ensor (OA): Outside Air ensor TIME HIH LOW POWE DAMPE DAMPE DAMPE AIN UAD LOUVE 5-1 24 VA ELAY 120 VA ZONE DIHAE 4 W W2 Y Y2 HEATIN HAMBE FILTE ZONE DIHAE BY-PA DAMPE ETUN AI 1

Typical Installation Methods installation method #1 Air Handler/Furnace Blower with electronic fresh air damper (Part # TFAD) This application uses the air handler/furnace blower and a fresh air damper to provide fresh air into the return of the air handler/ furnace system. The unit transformer can be used to power this installation method and will power the Intelligent Fresh Air Ventilator (PAT # IFAV), blower motor and fresh air damper. For this application, an outside air duct is installed from the return air plenum to an outside air intake. A fresh air damper (part # TFAD) is installed in the outside air duct. 1. Wire and of to and of air handler/furnace 2. Wire OA ensor to terminals 3. Wire Damper and to fresh air Damper. 4. Wire Fan to terminal of air handler/furnace. When terminal of is energized, it will provide fan call at air handler/furnace. efer to Drawing 2 DAMPE MOTO installation method #2 Installation using an Independent 24-volt 40 va. Transformer to control Air Handler/Furnace Blower with Fresh Air Damper This Application is used when the Air Handler/Furnace Transformer is too small to power (PAT # IFAV) and FAD damper. For this application, an outside air duct is installed from the return air plenum to an outside fresh air intake. A fresh air damper (part # TFAD) is installed in the outside air duct and wired to the Damper outputs of the. A 24 volt single pole relay is required for this application. Isolating the Intelligent Fresh Air Ventilator from the 24-volt control voltage of the Air Handler/ Furnace. 1. In this application, an independent transformer is wired to and of the. 2. Wire OA ensor to terminals 3. Wire damper outputs and are wired to the fresh air damper 4. Wire fan and to the coil of relay (24-volt single pole relay). 5. Wire from air handler/furnace to one side of relay contact points 6. Wire from air handler/furnace to other side of contact points of relay. efer to Drawing #3 ONTOLLE FUNAE AI HANDLE DAMPE MOTO TIME HIH LOW Y 1 POWE DAMPE Y 2 W 1 /O/B ONTOLLE FUNAE AI HANDLE DAMPE DAMPE W 2 Drawing #2 TIME HIH LOW POWE DAMPE DAMPE DAMPE Y 1 Y 2 W 1 /O/B W 2-1 24 VA ELAY -1 24 VA TANFOME Drawing #3 2

installation method #3 Independent Fan, Fresh Air Damper and Independent Transformer For this application an outside air damper and secondary blower, motor is used to introduce outside air into the supply plenum. Install outside air duct from supply plenum to outside air intake. Install fresh air damper in outside air duct and install secondary blower motor in fresh air duct. A 24-volt single pole relay is needed to switch power for fan motor, as motor voltage will be greater than 24 volts. 1. Wire independent transformer to and of the. 2. Wire OA ensor to terminals 3. Wire fresh air damper from Damper and outputs to fresh air damper (part #TFAD) 4. Wire Fan to one side relay coil 5. Wire Fan to second side relay coil 6. Wire input side of one leg of blower fan to relay contact 7. Wire output side of relay to blower fan 8. Wire econd leg of blower power to blower motor sequene OF OPEATION If the OA temperature exceeds HIH or LOW settings, the will lockout fresh air operations and track run minutes not used due to lockout. These minutes will be stored and used once the OA temperature returns to HIH and LOW limit ranges. Make up time will run with the next run cycle and will run continuously until all demanded time, stored and normal operation, have been used. If based on HIH and LOW limit ranges the OA temperature does not return to desired range, the will use the TIME setting to calculate how much time is needed to run in order to meet the 24 hour fresh air demand for your application. Example If time is set for 20 minutes and high limit is set for 100 with low set for 40, then the will run for 20 minutes of each hour. If time is set for 20 minutes and OA temperature is above 100 degrees, the controller will lockout operation and store 20 minutes for each hour OA temperature is above 100 degrees. If the OA temperature drops to less than 100 degrees, the Intelligent Fresh Air Ventilator will energize outputs to run off stored minutes while also running scheduled run time until all makeup and normal operation minutes have been used. -1 24 VA TANFOME ONTOLLE TIME HIH LOW POWE DAMPE DAMPE DAMPE -1 24 VA ELAY 120 VA sequene OF OPEATION DAMPE MOTO BLOWE MOTO Drawing #4 When the is energized, the controller will memorize the TIME setting, number of minutes to run each hour and subtract this time from sixty minutes. The balance of the hour will remain off. Each minute the OA sensor is checked and compared to the HIH and LOW setting. If OA temperature is within the desired range as set by HIH and LOW setting, the Intelligent Fresh Air Ventilator will energize fan and damper outputs for TIME setting set on control 3 If OA temperature does not return to set range temperature, the will calculate run time needed, based on TIME setting range, to meet Ashrae 62.2 and Energy tar 3 requirement and once balance point is reached, energize outputs to insure fresh air requirement is met. If Time set point is 20 minutes, and the controller has been locked out on HIH or LOW limit for 16 hours, then the controller will energize for the next 8 hours to make up stored time and run normal demand time to meet 24-hour requirements. et TIME POT for 20 minutes for 50 FM house. When OA temperature exceeds HIH or LOW pot set point (ex. equal 16, fan will energize and damper will open. The Intelligent Fresh Air ontroller will operate continuously for the next 8 hours et TIME POT for 30 Minutes for 75FM house. When OA temperature exceeds HIH or LOW pot set point (ex. equal 12, fan will energize and damper will open. The Intelligent Fresh Air ontroller will operate continuously for the next 12 hours et Time Pot for 40 minutes for 100 FM house. When OA temperature exceeds HIH or LOW pot set point (ex. equal 8, fan will energize and damper will open. The Intelligent Fresh Air ontroller will operate continuously for the next 16 hours Note: The above time settings and airflows are based on 150 cfm of air being provided for the system.

VENTILATION NEEDED equired ventilation per hour is established by AHAE 62.2. To calculate air requirement, the following formula can be used. AHAE FOMULA to find Fresh Air Ventilation House ize (q.ft.) x.01 + ((#Bedrooms + 1) x 7.5) = FM Example 2000 (q.ft) house with 3 bedrooms 2000 x.01 + ((3 + 1) x 7.5) 20 + (4x7.5) 20 + 30 = 50 FM Work heet House ize sq. ft. Number of Bedrooms EOVEY The Zonex ystems is designed to insure minimum fresh air requirements per AHAE 62.2 and Energy tar Ventilation. In order to meet minimum demands while using High and LOW temperature lockout, the is programmed to use three time range settings to control intelligent recovery. When TIME potentiometer is set and powered ON the controller will lock in TIME in minutes for intelligent recovery. x.01 + (( + 1 ) x 7.5) = FM required. q. Ft.of House Bedrooms DETEMININ FM OF A DUT The following table provides airflow delivery information to introduce 150 cfm of outside air for a 6, 7, or 8 pipe. (Note: Each elbow adds 8 to the total duct length). Inlet screen and hood losses are included..3 of negative static pressure was used for these estimates. You can use the chart above for an estimate of fresh air provided from fresh air duct. However, more precise measurement can be found by using an airflow measuring tool, device by Nailor, etc. DETEMININ NEEDED UN TIME FM required (Transfer value from calculation above) FM Measured (Transfer value from measurement above) To determine run time needed, use the following formula. equired FM/FM Measured x 60 minute TIME ETTIN 10-25 Minutes If is locked out due to HIH or LOW ettings for 16 hours, Intelligent ecovery will occur and run fan and damper for the next 8 hours to insure minimum 26-32 Minutes If is locked out due to HIH or LOW ettings for 12 hours, Intelligent ecovery will occur and run fan and damper for the next 12 hours to insure minimum 33-40 Minutes If is locked out due to High or LOW ettings for 8 hours, Intelligent ecovery will occur and run fan and damper for the next 16 hours to insure minimum Example: Based on 150 FM of air delivered thru the Fresh Air Duct equired FM 50 Measured 150 FM 50/150 x 60 = untime per hour.3 x 60 = 20 minutes of runtime per hour A time setting of 20 minutes will provide 50 FM per hour at normal temperature range. When the outside temperature exceeds HIH or LOW pot settings, 20 minutes is in the 10 to 25 minute range. If the temperature stays out of range for 16 hours, the damper will open and fan will operate for next 8 hours. This will provide 8 x 150 FM or 1200 FM to match the 50 FM x 24 hour (50 cfm x 24 hours = 1200) daily requirement. 4