Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Similar documents
Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

A study of Transient Performance of A Cascade Heat Pump System

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Available online at ScienceDirect. Energy Procedia 70 (2015 ) Yanjun Dai*, Xian Li, Ruzhu Wang

Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

INDOOR HUMAN THERMAL COMFORT OPTIMAL CONTROL WITH DESICCANT WHEEL COOLING SYSTEM

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

The Performance of Mixture Refrigerant R134a/R152a in a Novel Gas Engine-Driven Heat Pump System

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

K.F. Fong *, C.K. Lee, T.T. Chow

Impact of indirect evaporative air cooler type on the performance of desiccant systems

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

Design of Humidity Monitoring System Based on Virtual Instrument

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

ScienceDirect. Development progress of critical equipment in the CSNS cryogenic hydrogen system

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Performance evaluation of a liquid desiccant solar air conditioning system

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

中国科技论文在线 Energy Conversion and Management 52 (2011)

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Study on an Air-Side Heating Source Liquid Desiccant Regeneration Model

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

EVALUATION OF A LIQUID DESICCANT AIR CONDITIONING SYSTEM WITH SOLAR THERMAL REGENERATION

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Available online at ScienceDirect. Energy Procedia 52 (2014 ) Vishal Vadabhat, Rangan Banerjee

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Study of R161 Refrigerant for Residential Airconditioning

Available online at ScienceDirect. Procedia Engineering 135 (2016 )

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Performance of solid desiccant-based evaporative cooling system under the climatic zones of India

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

Available online at ScienceDirect. Energy Procedia 91 (2016 ) 35 41

Performance analysis of a liquid desiccant evaporative cooling airconditioning system powered by solar energy

A Statistical Analysis of a Liquid Desiccant Dehumidifier/Regenerator in an Air Conditioning System

The Effect of Quantity of Salt on the Drying Characteristics of Fresh Noodles

Simulation of Evacuation Process in a Supermarket with Cellular Automata

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Recent Advances in Energy, Environment and Economic Development

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Efficient adsorption refrigerators integrated with heat pipes

Carbon Dioxide based Heat Pump Dryer in Food Industry

Simulation of Full-scale Smoke Control in Atrium

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

Experimental Study on Performance of Double pipe Length on Instantaneous Air Source Heat Pump Water Heater. Yin Shaoyou 1, a

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants

REVIEW OF DESIGN OF SINGLE EFFECT SOLAR POWERED VAPOUR ABSORPTION AIR CONDITIONING SYSTEM

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Enhancement of COP using Nanoadditives in Domestic Refrigerator

DEEPAK PALIWAL, S.P.S.RAJPUT

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Performance of non-cfc refrigerator driven by chilled water from 35 kw LiBr/H2O solar absorption cooling system

Novel Liquid Desiccant Systems

Performance Study of a Water-to-Water Heat Pump Using Non-azeotropic Refrigerant Mixtures R407C

Adsorption refrigeration system using waste heat

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

Study on an environmental simulation system of low/high temperature. for great space

STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Modeling and Testing of an R-23/R-134a Mixed Refrigerant System for Low Temperature Refrigeration

Capillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

ScienceDirect. The Undrained Shear Strength of Overconsolidated Clays

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

International Journal Of Core Engineering & Management (IJCEM) Volume 2, Issue 9, December 2015

Available online at ScienceDirect. Procedia Engineering 84 (2014 )

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Effect of operating conditions on performance of silica gel-water air-fluidised desiccant cooler

Purdue e-pubs. Purdue University

Dynamic performance of a novel dew point air conditioning for the UK buildings

*Corresponding author;

Thermodynamics I. Refrigeration and Heat Pump Cycles

Efficiency evaluation for the heat pump system in sharp continental climate

Available online at ScienceDirect. Physics Procedia 67 (2015 )

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

CHAPTER 1 INTRODUCTION

Transcription:

Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 1222 1229 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International Conference on Building Energy and Environment (COBEE) Performance Analysis of a Novel Double-Temperature Chilling Water Unit Using Large Temperature Glide Zeotropic Mixture Jian Liu a, Xiao Song Zhang a, * a School of Energy and Environment, Southeast University, Nanjing 210096, China Abstract Accordingly to the properties of zeotropic mixture R32:R236fa, a novel double-temperature chilling water unit was proposal in this paper, this unit can produce two different temperature of chilled water (such as low temperature is 7 C, high temperature is 16 C). An experimental system is established to test the performance of the unit. The paper studied the effects of mass component concentrations of the zeotropic mixture and high - low temperature evaporator s source temperature on the performance of the unit. The results show that, when the inlet water temperature of the condenser is 32 C, outlet water temperature of the evaporator is 7 C and 16 C. The coefficient of performance (COP) of the unit can reach 4.14 when the mass component concentration of R32 is 60% and the COP of the unit increase with the increase of mass component concentration of R32 and the chilled water temperature. 2015 Published The Authors. by Elsevier Published Ltd. This by is Elsevier an open Ltd. access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/). Peer-review under responsibility of the organizing committee of ISHVACCOBEE 2015. Peer-review under responsibility of the organizing committee of ISHVAC-COBEE 2015 Keywords: COP; Zeotropic; Large temperature glide; Double-temperature; chilling water unit Nomenclature COP ODP GWP The coefficient of performance Ozone depression potential Global warming potential * Corresponding author. Tel.:+1-510-517-7032; fax: +1-510-517-7032. E-mail address: rachpe@seu.edu.cn 1877-7058 2015 Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/). Peer-review under responsibility of the organizing committee of ISHVAC-COBEE 2015 doi:10.1016/j.proeng.2015.09.145

Jian Liu and Xiao Song Zhang / Procedia Engineering 121 ( 2015 ) 1222 1229 1223 C P Specific heat at constant pressure J (kg K) 1 uncertainty % G Heat transfer media (water) m 3 /h P Pressure MPa Q e Refrigerating capacity kw Q air flow rate (m 3 /s) M Mass component concentration R Compressing ratio T Temperature C W Power consumption of compressor kw c condenser e evaporator d low temperature chilling water ex Exhausting Eva Evaporation g high temperature chilling water in inlet out outlet suc suction t,i measure value t,tol calculated values 1. Introduction With the development of China s economy and society, building energy consumption accounts for the proportion of the national total energy consumption is increasing. The building energy consumption accounts for about 25% of the social total energy consumption and air conditioning system is one of the major energy-consuming equipment [1]. Therefore, the energy conservation of air conditioning system is important for improvement of energy intensity of China. The temperature and humidity independent control air conditioning system [THICS] gets widely attention because of the advantages of energy saving and air quality [2].At present, the realization of THICS is mainly through the liquid dehumidification and solid adsorption desiccant dehumidification to bear the latent heat of air conditioning system, the sensible heat always removal by chilled water which produced by chilling water unit. The result of study and application shows that THICS have a good effect on energy-saving [3-5]. However, liquid dehumidification systems have some problems, such as corrosion of pipeline and dehumidification efficiency is low and so on [6], there are many problems for solid adsorption desiccant too, such as the large amount of adsorbent filling increase the costs. In addition, solid desiccant regeneration calls for high temperature and needs high-grade heat consumption (such as the regeneration temperature of silica gel is usually expected to be above 100 for practical application) [7]. Therefore, Liang [8-9] proposes heat and humidity segment treatment air conditioning system which based on THICS. The result shows that compared to the present method, the COP (coefficient of performance) can be enhanced by more than 9.14% when the set cooler temperature difference is 7 and outlet air temperature is 16 ; In addition, researchers have done a lot of theoretical and experimental studies on the chilling water unit which refrigerant is zeotropic mixture. Mehmet [10] presented the performance analysis of an air-to- water vapor compression heat pump system using pure refrigerants and zeotropic refrigerant mixture. The results show that the COP and second law efficiency for the pure refrigerants could be improved by using an appropriate mixture of the refrigerant. Chen [11] proposal a novel domestic air conditioning system based on R32/R134a, the result of the theoretical analysis show that compared with traditional refrigerant R22, COP could be improved 8-9%. To sum up, this paper proposal a novel double temperature chilling water unit base on large temperature glide zeotropic mixture refrigerant. This unit can produce two different temperature of chilled water. The unit adopts

1224 Jian Liu and Xiao Song Zhang / Procedia Engineering 121 ( 2015 ) 1222 1229 environment-friendly large temperature glide zeotropic mixture R32/R236fa as refrigerant and utilizes the characteristic of the phase change process to realize the Lorenz cycle, improves the COP of the unit [10-11]. Finally, the effect of the mass component concentration of R32/R236fa, evaporating pressure and different temperature chilled water on the COP of the unit were experimentally studied. The result of the experiment provides the database for the application and design of double temperature chilling water unit. 2. Methods 2.1. Test apparatus The experimental apparatus used in this investigation was water -to- water chilling water unit, and the schematic diagram is shown in fig1. Fig. 1. (a) Schematic diagram of experimental system (1)-Compressor (2) -Condenser, (3) -Reservoir (4) -Electronic expansion valve, (5) -Low temperature evaporator, (6) -High temperature evaporator. (7-9) -Water pump, (10-12) -Electrical heater, (13-15) -Flow meter, (16-18) -Water tank (19-21) -Stop valve. 2.2. Test conditions and measurements The temperature and pressure of the zeotropic mixture were measured at several locations of system. T-type thermocouples were used to measure temperature of the unit. The zeotropic mixture temperatures were measured at the inlet and outlet of the condenser, compressor, evaporator, temperature before electronic expansion valve. The temperature of the cooling water and the chilled water were measured at the inlet and outlet of the condenser and two evaporators. Four manometers were installed at the inlet and outlet of the compressor, the outlet of the condenser and the inlet of the low temperature evaporator. The flow rate of the cooling water and chilled water were measured with three turbine flow-meters. Compressor input power was measured using a digital wattmeter. After each experimental run, the raw dates were recorded. All the measurements of the parameters were collected via a person computer acquisition system every 10seconds. The dates were saved to the database for deeply investigation. A list of accuracies for measurements and parameters is shown in the table 1.

Jian Liu and Xiao Song Zhang / Procedia Engineering 121 ( 2015 ) 1222 1229 1225 Table 1. Spcification of different measurements. Device Parameter uncertainly% Thermocouples(omega) Temperature/ C 0.15 Pressure sensors Evaporating Pressure /MPa Condensing pressure /MPa 0.10 0.10 Liquid flow-meter Flow rate/m3 h-1 1.00 Digital wattmeter Power/ kw 0.10 2.3. Experimental refrigerant In this paper, R32/R236fa was the refrigerant for the chilling water unit. Phase change characteristics of refrigerant were calculated by NIST8.0 software. Results were shown in table 2. The minimum temperature glide of the mixtures at different mass component concentrations is 14.7 C. It can satisfy the requirements of double temperature chilling water unit. Table 2. Thermodynamic properties at different mass component concentrations of R-32/R-236fa mixtures. M of R32 [%] 30 40 50 60 Evaporating pressure(mpa) 0.45 0.52 0.6 0.64 Tf [ C] -1.9-1.7-1.6-1.1 Tg[ C] 19.5 17.9 15.7 13.4 Temperature glide [ C] 21.4 19.6 17.3 14.5 ODP 0 0 0 0 GWP 4612 4050 3850 2925 2.4. Performance analysis of the unit 1). Coefficient of performance For a chilling water unit, the coefficient of performance (COP) of the unit is a very important index, which indicates the overall power consumption for a desired output and is calculated using the following equation (1): COP W Q e comp Refrigerating capacity of the unit is calculated using the equation (2) 1 e,,,, Q C G t t C G t t P e g in g out P d d in d out 2 2). Exhausting pressure and temperature of the unit Exhausting pressure and temperature is important for the operation of the chilling water unit. So in this paper the exhausting pressure and temperature of the unit is also recognized as the performance indexes.

1226 Jian Liu and Xiao Song Zhang / Procedia Engineering 121 ( 2015 ) 1222 1229 3. Results and discussion Table3 shows the experimental condition of this study. Table 3. Experimental conditions of the unit. Td( ) Tg( ) M (%) Ge,g (m3/h) Ge,d (m3/h) Gc (m3/h) Fig2a 6-8 15-18 30 0.22 0.21 0.47 Fig2b 6-8 15-18 40 0.30 0.30 0.65 Fig2c 6-8 15-18 50 0.32 0.31 0.71 Fig2d 6-8 15-18 60 0.35 0.35 0.75 Fig3a 7-8 16-18 30-70 0.22-0.35 0.21-0.35 0.47-0.75 Fig3b 7-8 16-18 30-70 0.22-0.35 0.21-0.35 0.47-0.75 Fig4a 7-8 16-18 30-70 0.22-0.35 0.21-0.35 0.47-0.75 Fig4b 7-8 16-18 30-70 0.22-0.35 0.21-0.35 0.47-0.75 Fig5 7-8 16-18 30-70 0.22-0.35 0.21-0.35 0.47-0.75 3.1. Uncertainty analysis The uncertainties of calculated values are calculated by the following equation (3) [12]. 3 f f f f 2 2 2 ttol, t,1 t,2 tn, The average uncertainties of the calculated values as the table 4 show. Table.4. Uncertainty of calculated values. Calculated variable Uncertainty /% Coefficient of performance 1.77 Refrigerating capacity 1.76 As the results, the uncertainties of the calculated values are less than 2% and satisfy the requirement of accuracy. 3.2. Effect of high - low temperature evaporator s source temperature on COP The COP of the conventional chiller dropped from the full load COP at lower capacities as reflected from the dotted trend line. The relationship between COP and high-low temperature evaporator s source outlet temperature are shown in Fig.2. At first, it can be seen that the system can produce different temperature chilling water, such as low temperature equal 6 7 8, high temperature equal 15 16 17 18. Second, the COP generally increases as the high-low temperature evaporator s source outlet temperature increases. Third, in fig2b and fig2c, the changes of high temperature chilled water temperature have greater effect on COP than low temperature chilled water. But this characteristic is not obvious in fig2d. The reason should be study further. As the increases of chilling water temperature, the COP of the unit increases. Because as the increases of the chilled water temperature the evaporating pressure increases and then the condensing pressure not increase, so the COP increases.

Jian Liu and Xiao Song Zhang / Procedia Engineering 121 ( 2015 ) 1222 1229 1227 The results of the Fig.2.show that the unit can be applied in heat and humidity segment handle air conditioning system. Fig. 2. COP under different high-low temperature chilling water. (a)-30-70%r32/re236fa; (b)-40-60%r32/re236fa; (c)-50-50%r32/re236fa; (d)-60-40%r32/re236fa. 3.3. Effect of mass component concentrations of R-32/R-236fa on COP and refrigerating capacity Fig3 shows that the COP and refrigerating capacity of the unit increases oblivious as the mass component concentration of R32 increases from 0.3 to 0.6. The maximum COP and refrigerating capacity occurs at a mixture ratio of 60-40%R32/R236fa, the maximum COP values is 4.14, the maximum refrigerating capacity values is 4.42.It can be seen that the refrigerating capacity per unit weight of R32 is high than R236fa. As a result, the refrigerating capacity of the unit increases as the mass component concentration of R32 increases. In addition, the compressor power consumption changes smaller than refrigerating capacity. Therefore, the COP of the unit changes significantly. The results of this plot reveal that mixture ratio of R32 have important effect on the COP and refrigerating capacity of the unit. The results of the fig2 not only show the effect of mass component concentration of R32 on COP and refrigerating capacity of the unit, but also provide the experimental data for other researchers to study or design the system based on large temperature glide zeotropic mixture.

1228 Jian Liu and Xiao Song Zhang / Procedia Engineering 121 ( 2015 ) 1222 1229 Fig. 3a. Refrigeration capacity at different mass component concentrations of R-32/R-236fa mixtures (A- Td=7 Tg=16 B- Td=7 Tg=17 C- Td=8 Tg=17, D- Td=8 Tg=18 ). Fig. 3b. COP at different mass component Concentration of R-32/R-236fa mixtures (A- Td=7 Tg=16 B- Td=7 Tg=17 C- Td=8 Tg=17, D- Td=8 Tg=18 ). 3.4. Effect of mass component concentrations of R-32/R-236fa on exhausting pressure and compressing ratio Fig4 shows the relationship between mixture ratio of R-32/R-236fa and exhausting pressure, compressing ratio. It can be seen that the exhausting pressure of the unit will be increasing as the increasing of mass component concentration of R32 and the maximum value occurs at a mixture ratio of 60-40% R32/R236fa, the maximum value is about 1.930MPa.The compressing ratio of unit will be decreasing as the increasing of mass component concentration of R32 and the minimum value occurs at a mixture ratio of 60-40%R32/R236fa, the minimum value is about 2.8. It can be seen that the bobble point of R32 is lower than R326fa, so as the increases of mass component concentration of R32, the exhausting pressure of the unit increases. Also as the increases of mass component concentration of R32, the evaporating pressure of the unit increases too. So the compressing ratio decreases. The result shows that 50-50%R32/R236fa should be recommended as the refrigerant for the double temperature chilling water unit. Because of the exhausting pressure and compressing ratio are relatively low. The COP and refrigerating capacity are relatively high. Fig. 4. Exhausting pressure and compressing ratio at different mass component concentrations of R-32/R-236fa mixtures (A- Td=7 Tg=16 B- Td=7 Tg=17 C- Td=8 Tg=17, D- Td=8 Tg=18 ). 3.5. Effect of the mass component concentration of R32/R236fa on the exhausting temperature Fig4 demonstrates the effect of mass component concentration of R32/R236fa on the exhausting temperature of the unit. In the fig.4, it can be seen the exhausting temperature of the unit is low, about 70 and with the increase of mass component concentration of R32, exhausting temperature first increase and then decrease, the maximum temperature occurs at 50-50%R32/R236fa. The reason should be study further. The exhausting temperature of the unit is low, so the system operating safety

Jian Liu and Xiao Song Zhang / Procedia Engineering 121 ( 2015 ) 1222 1229 1229 Fig. 5. Exhausting temperature at different mass component concentrations of R-32/R-236fa mixtures (A- Td=7 Tg=16 B- Td=7 Tg=17 C- Td=8 Tg=17, D- Td=8 Tg=18 ). 4. Conclusions In the present study, a novel double temperature chilling water unit was proposed, and the performance of the unit was investigated by the experiment. The result show as following: The unit proposed by this paper can produce two kinds of chilling water which have different temperature. The high temperature chilling water could be about17, the low temperature chilling water could be about 7. The COP enhances with the increase of evaporator source inlet temperature for the refrigerant mixture. The mixture ratio has great affect on COP and the COP can be improved by using appropriate mixtures of the refrigerant. The maximum COP occurs at a mixture ratio of around 60-40%R32/R236fa and the value is 4.14. With the increase of mass ratio of R32, the exhausting temperature of the unit first increase and then decrease. Acknowledgements This work was partially supported by supported by the national key technology R&D program (2011BAJ03B14) and the Natural Science Foundation of China (51376044) References [1] Y. Jiang, Current building energy consumption in China and effective energy efficiency measures, HV&AC. 35(5) (2005) 30-40. [2] Y. Jiang, Z Li, X.Y. Chen, Liquid desiccant air conditioning system and its applications, HV&AC. 34(11) (2004) 88-97. [3] B. Shaji Mohan, M. Prakash Maiya, Shaligram Tiwari, Performance characterisation of liquid desiccant columns for a hybrid air-conditioner, Appl. Therm. Eng. 28(2008) 1342 1355. [4] Y.G. Yin, X.S. Zhang, Z.Q. Chen, Experimental study on dehumidifier and regenerator of liquid desiccant cooling air conditioning system, Build. Environ. 2007, 81(1) (2007) 131-138. [5] T.S. Ge, Y.J. Dai, R.Z. Wang, Performance study of silica gel coated fin-tube heat exchanger cooling system based on a developed mathematical model, Energ. Conver. Management. 52(2011) 2329-2338. [6] A. Lowenstein, S. Slayzak, E. Kozubal, A zero carryover liquid-desiccant air conditioner for solar applications, In: Proceedings of the ASME international solar energy conference, P (2007) 397-407. [7] K. Yang, Y. Yao, S.Q. Liu, Effect of applying ultrasonic on the regeneration of silica gel under different air conditions, Int. J. Therm. Sci. 61(2012) 67-78. [8] C.H. Liang, X.S. Zhang, Z.Y. Jiang, X.W. Li, Novel air handling method and its energy-saving potential in air-condition system, Journal of Southeast University (Natural Science Edition), 39(5) (2009) 973-977. [9] W. Li. Optimization and control strategy analysis of the segmented handling air-conditioning system, Ph.D. Thesis, China, Southeast University, 2012, 113pages. [10] J.Y. Chen, J.L. Yu, Performance of a new refrigeration cycle using refrigerant mixture R32/R134a for residential air-conditioner application, Energ. Buildings. 40(2008) 2022-2027. [11] Y. Mehmet, Performance analysis of a vapor compression heat pump using zeotropic refrigerant mixtures, Energ. Conver. Management. 44 (2003) 267-282. [12] Z.Y. Liu, L. Zhao, X.Z. Zhao, Heat exchange characteristics of zeotropic mixture in heat exchangers in high temperature heat pump, CIESC Journal, 62(12) (2011) 3386-3393.