THE IMPACT OF FIXED FIRE FIGHTING SYSTEMS ON TUNNEL SAFETY THE BURNLEY INCIDENT IN A CURRENT THEORETICAL PERSPECTIVE

Similar documents
An experimental study of the impact of tunnel suppression on tunnel ventilation

VENTILATION AND SUPPRESSION SYSTEMS IN ROAD TUNNELS: SOME ISSUES REGARDING THEIR APPROPRIATE USE IN A FIRE EMERGENCY

The first tunnel fire. Benefits of fire

SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM

TECHNICAL TRADE-OFFS USING FIXED FIRE FIGHTING SYSTEMS

CERBERUS: A NEW MODEL TO ESTIMATE SIZE AND SPREAD FOR FIRES IN TUNNELS WITH LONGITUDINAL VENTILATION

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

Sprinklers Modeling for Tunnel Road Fire Fighting

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen

Impact of Tunnel Ventilation on Tunnel Fixed Fire Suppression System

Impact of quick incident detection on safety in terms of ventilation response

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

COMPENSATORY EFFECTY OF FIXED FIRE FIGHTING SYSTEMS IN TUNNELS

Hot Issues in Fire Engineering 12 March 2013

Fire Dynamics During the Channel Tunnel Fires

Large scale fire tests with fixed fire fighting system in Runehamar tunnel

FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

CFD STUDY OF FIRE PROTECTION SYSTEMS IN TUNNEL FIRES

Tunnel Fire Dynamics

Abstract. Introduction

Fire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition

COMPENSATORY EFFECTS OF FIXED FIRE FIGHTING SYSTEMS IN TUNNELS. Stefan Kratzmeir Managing Director.

The Mont Blanc tunnel project. Eric CESMAT, Sylvain DESANGHERE

EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT TASK 363)

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection

Full-scale Experiment of Longitudinal Ventilation Smoke Control System and Central Smoke Exhaust System in City Underwater Tunnel

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

Tunnel Fire Dynamics and Evacuation Simulations

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

Road Tunnel Classification System for Fire Brigades Prof. Haukur Ingason SP

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS

Increasing Fire Safety of Cologne Main Station by High Pressure Water Mist

REVIEW ON WATER MIST FIRE SUPPRESSION SYSTEM

Jonathan Redding Area Sales Manager FOGTEC Fire Protection Cologne, Germany

Residential Fire Injury and Death Rates in British Columbia

and Sprinkler System in Resalat Tunnel of Tehran

Fire Protection and Safety in Tunnels Conference Opening Remarks. Dr Fathi Tarada Secretary, PIARC Tunnel Operations Committee

IMPROVING VENTILATION AND PASSIVE PROTECTION WITH FFFS

Sprinkler Systems and Fire Outcomes in Multi-Level Residential Buildings

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

3rd International Conference Polymers in Mining", University of Lancaster, United Kingdom (The Plastics and Rubber Institute), September 26-27, 1989

Before we look at the alternative approach, lets have a brief look at where Australian fire safety design has come from.

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

Optimisation of ventilation systems costs by using fixed fire fighting systems (FFFS) in tunnels

How design fires can be used in fire hazard analysis

Considerations in the Design of Smoke Management Systems for Atriums

Innovative Solutions for Active Fire Protection in Road/Rail Tunnels and Underground Facilities

Heat Release Rate of an Open Kitchen Fire of Small Residential Units in Tall Buildings

Yunyong P. Utiskul, Ph.D., P.E., CFEI

Effective Firefighting Operations in Road Tunnels

Effects of Smoke on Evacuation Martin Lopušniak 1, a

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

Edinburgh Research Explorer

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation

MIST FIRES AND EXPLOSIONS: FACT OR MYTH? Introduction

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016)

Fire Dynamics Simulation and Evacuation for a Large Shopping Center (Mall), Part II, Evacuation Scenarios

Underground fires in metro systems failures, accidents and terrorism

Modeling a real backdraft incident fire

Hot Issues in Fire Engineering 28 February 2012

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

Tampa, FL Fire Cause Classification Task Group Tue, 14 April 2011

General Principles of Smoke Control

NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL

Modeling water-mist based suppression of 34 GJ car-deck fires using FDS

City of Hume Planning Scheme Amendment C207. Statement of Expert Evidence Provided to Planning Panels Victoria

EARLY FIRE DETECTION IN SWISS ROAD TUNNELS WITH MORE THAN FIREGUARD SENSORS

Development of a test method for fire detection in road tunnels

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

TUNPROTEC. Active Tunnel Fire Protection

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro

SIL DETERMINATION AND PROBLEMS WITH THE APPLICATION OF LOPA

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

Fire Cause Determination

ENVIRONMENTAL IMPACT ASSESSMENT AND THE PURSUIT OF SUSTAINABLE DEVELOPMET IOME CHRISTA 1

GAS DETECTOR LOCATION. Ø.Strøm and J.R. Bakke, GexCon AS, Norway

CFD Model of a Specific Fire Scenario

Copy of article submitted to Fire Safety Engineering for publication January/February 2009

Proceedings from 1st International Conference on FIVE Fires in Vehicles September 29-30, 2010 Gothenburg, Sweden,

USING A REAL TIME SIMULATOR IN A LARGE AND COMPLEX ROAD TUNNEL FOR TIME AND COST SAVINGS

Detection of Fires in Heavy Duty (HD) Vehicles

International Safety Guide Chapter 30 for Inland Navigation Tank-barges and Terminals. Chapter 30 FIRE-FIGHTING

A study for a fire spread mechanism of residential buildings with numerical modeling

Tokyo-wan Aqualine - Experience of Traffic and Safety

Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel

INSTRUCTORS MANUAL SAMPLE ONLY

Fixed fire protection solutions

Fire Engineering in the UK

POWER Selecting Shell Side Design Temperature for Feedwater Heaters

Appendix SPAIN Madrid M30-Río-TUNNEL

Aspirating Gas Detection CFD Modelling Predicts Application Performance

Fire & Life Safety Design Considerations for the Tugun Bypass Tunnel

WATER MIST CONVENTION AND EXHIBITION

Project description and planning of large-scale tests in Runehamar tunnel

Tunnels, Risks & Design Mitigation

Transcription:

THE IMPACT OF FIXED FIRE FIGHTING SYSTEMS ON TUNNEL SAFETY THE BURNLEY INCIDENT IN A CURRENT THEORETICAL PERSPECTIVE ABSTRACT Arnold Dix Scientist and Lawyer Associate Professor, University of Western Sydney, Australia Renewed interest in FFFS has resulted in new scientific data on the effectiveness of FFFS and its interrelationship with ventilation, incident detection, water application rates and FFFS type. When this new data is compared with the real experience in the Burnley tunnel fire of 2007 the results appear consistent. Keywords: Fire, ventilation, deluge, mist, FFFS, safety, asset protection 1. INTRODUCTION Fixed fire fighting systems (FFFS) are the subject of renewed interest following recent recalculations of fire size and a series of extreme tunnel fire events. FFFS have been used extensively in Japan for more than 40 years and are also found in all of Australia s congested urban road tunnels. However there remains little theoretical data in the literature about their performance. Recent investigations by both FFFS vendors and researchers are finally revealing some of the details of how FFFS work and how to optimise them in a tunnel. The fatal Burnley Tunnel incident in Australia of 23 March 2007 provides a rare insight into the effectiveness of these fixed fire fighting systems. Unfortunately most of the technical details of the Burnley Incident remain secret. The detailed investigation report is subject to a legal suppression order and the Report to the Victorian Coroner, The Fatal Burnley Tunnel Crashes Melbourne, Victoria, Australia (Arnold Dix 2008) cannot be made public. This paper uses evidence from the Supreme Court criminal proceedings of mid 2009 which is not suppressed to reveal some of the events of 2007. Although it must be conceded that the statistical significance of the Japanese and Australian experience is unclear, neither Japan nor Australia has experienced a catastrophic tunnel fire despite numerous tunnel fire incidents. The Burnley fire provides a critical insight into how fires in Japanese and Australian tunnels are managed. 2. NEW LEARNINGS Recently published literature is providing insights into the effects of FFFS and how to optimise its integration into tunnel safety systems. 2.1. Unshielded Fire Growth Large scale tests by SP Technical Research Institute of Sweden examine the water discharge density, water pressure and its effect on cargo fires. 1

The results of these tests clearly established a relationship between water application rates, fire growth rates and heat release rates. Importantly the research suggests that there are critical water application rates below which the FFFS has virtually no effect. 2 Interestingly discharge densities of 15mm/min provided immediate fire suppression, 10mm/min fire suppression and 5mm/min fire control. This relationship was also influenced by operating pressure the higher the pressure the better the performance. Mist systems were also investigated and as a general rule were found less effective than the same application rate in a sprinkler system. See Figure 1. Neither system was effective against shielded fires. 2 Figure 1: Total heat release rate histories for the fire tests using various water application rates and pressures without shielding. (Arvidson 2010 2 ) However water mist systems are generally regarded as a viable alternative to sprinklers because they are able to achieve good attenuation of heat radiation and cooling although they have reduced fire suppression performance. Mist systems require early activation to minimise fire growth and reduce peak heat release rates. 3,4,5 Computational analysis using CFD has recently been undertaken for varying FFFS water application rates. 6 The results of this analysis suggest that for an unshielded fire there is a critical water application rate under which fire growth is not significantly reduced. In this CFD analysis the authors suggest it is around 4mm/min, however review of their CFD results suggests it may be higher (perhaps around 6mm/min). Like the scaled experiment results (above) shielded fires perform poorly no matter what the application rates although in all instances fire spread is controlled. A summary of predicted heat release rates with varying water application rates is found in Figure 2. Figure 2: Predicted CFD Fire Heat Release Rate for Varying Water Application Rates-Unshielded Fires (Harris 2010 6 )

This scale model and CFD experimental data is compared with the actual experience in the Burnley tunnel fire in the first section of this paper. In short it is consistent with the experience from Japan and Australia about the effectiveness of their deluge systems at fire fighting application rates of in the order of 10mm/min. The role of droplet size distribution in this performance warrants further investigation. 2.2. Shielded Fire Growth All recent analysis suggests that FFFS has minimal impact on shielded fires. 6, 7 Figure 3: Total heat release rate for shielded fires in full scale test (Arvidson 2010 2 ) Figure 4: Fire heat release rate for shielded tests using CFD analysis (Harris 2010 6 ) These results are consistent with earlier concerns by NFPA502 and PIARC that FFFS does not put out fires within vehicles. However in all instances fire spread is predicted to be substantially reduced despite the fire not being constrained when shielded. Furthermore the effects of FFFS activation upstream of an event and the migration of droplets horizontally beneath a shield have not yet been modelled in detail. In practice multiple FFFS zones are operated in a real tunnel and the horizontal migration of water droplets under the effect of longitudinal ventilation may be the reason for enhanced FFFS performance even in shielded situations. This should be the subject of further research. The effects of FFFS in this regard are noted in the examination of the Burnley event in this paper. Fires were not extinguished by the FFFS in shielded environments nor in the Burnley fires. One of the largest effects of FFFS is the reduction in radiated energy levels and the substantial reduction in the risk of flashover.

3. THE IMPACT OF FFFS ON TUNNEL VENTILATION 3.1. Backlayering Increased interest in FFFS has rightly raised questions with respect to the management of backlayering during FFFS activation in an emergency. There has been literature on the phenomenon without FFFS but little or no published data with FFFS use. 8 Experimental data is now emerging which confirms that the control of backlayering is not an issue with FFFS activation. The longitudinal airflow is able to maintain backlayering because the FFFS reduced the smoke temperature thereby reducing the driving force propagating the smoke which reduces the amount of ventilation required to prevent backlayering. 7 Although this is a theoretical study (based on a scale model) and does not take into full regard the effects of destratification it nonetheless is consistent with the experience from Japan and Australia that preventing backlayering is not an issue in tunnels with FFFS. Figure 3: A comparison of heat fluxes measured 5m downstream and 6m upstream over time (Yoon J. Ko and George Hadjisophocleous 2010 7 ) The reduction in heat flux is thought to reduce the amount of energy required to stop backlayering. 3.2. Longitudinal Airflow With a theoretical reduction in fire growth rates and heat release rates as a result of FFFS use it also follows that achieving critical airflow velocities remains a high priority in FFFS equipped tunnels. Indeed this is required in order to achieve both control of backlayering and not to increase the fire size by virtue of unnecessarily large longitudinal velocities. It is already well established that increases in longitudinal ventilation velocity can increase 9, 10, 11, 12 heat release rates significantly. Balancing the need to control backlayering with the undesirable acceleration of fire growth remains a high priority in real tunnels. The most recent research suggests that the rate of burning of charring fuels (such as wood and thermo setting plastics) exhibits a clear dependence on ventilation velocity while pool fires are less sensitive to such changes. 13

Figure 4: The fire growth rate as a function of the longitudinal ventilation 13, 14 velocity It is conceivable that early tests which relied upon pool fires for the test methodology would have failed to detect this phenomenon. Furthermore even where tests were conducted using non-charring fuels (the majority of synthetic polymers) they would have behaved like a pool fire. This may be an explanation for why such phenomenon has been poorly understood. The consequences of this are likely to have adversely impacted the size of fires in tunnels because of insistence by operators in operating high longitudinal velocities during emergency mode despite pleas from Fire Brigades to do otherwise. 15 The positive impact of this phenomenon was revealed in the Burnley fire event where longitudinal velocities were rapidly reduced following the outbreak of fire and backlayering controlled while the FFFS concurrently operated successfully. 4. BURNLEY TUNNEL FIRE - MARCH 2007 The Burnley tunnel is a single direction, 3 lane tunnel of 2.9km length. It has a traffic flow of around 100,000 vehicles per day. On 23 March 2007, at 09:52:30 am a truck travelling eastbound made an unscheduled stop in Melbourne s CityLink Burnley tunnel. Over the next two minutes 103 vehicles passed the stopped truck without incident. Two minutes later, by 09:54:24 seconds several vehicles, including 4 HGVs and 7 light vehicles had crashed, 3 people were dead and fire and a series of explosions were initiated. By 09:56:00am (two minutes after ignition) emergency ventilation and a fixed fire suppression system had been activated. The following eye witness evidence from the criminal court case against the driver graphically illustrates the sequence of events: ---Essentially I heard the screeching of tyres. I looked in the rear vision mirror; saw the car careering into the back of the truck. The nose of the car went down, the car lifted up like that so - and then there was another smash from behind by a truck. ---I saw the truck hit it and the - I can only assume that it was the gas tank of the vehicle that exploded.

---I saw the explosion. ---Well I continued to drive through the tunnel. There were - there was another explosion shortly after that which was a much bigger explosion. I remember the windows of my car vibrating as a result. There was also another announcement that came over the speaker saying that there had now been an incident in the tunnel and that vehicles were to slow down to 60 kilometres an hour This evidence graphically describes the crash, fires and subsequent explosions. The initiating events for this incident were large large in the context of prior catastrophic events such as the engine compartment fire at Mont Blanc. Yet, despite the severity of these initiating events the fires were contained, with no flash over or other significant fire growth occurring once the deluge fixed fire fighting system was initiated. However, it was not merely the presence of the fixed fire fighting system which was critical it was that the ventilation system was effective in that it stopped backlayering (up a steep tunnel grade of 6%) and reduced the longitudinal airflow rapidly (to approximately 2m/sec) in order to optimize smoke extraction and minimize ventilation induced fire growth. It was the fire brigade that put the fires out the deluge system merely kept the fires small enough to allow effective emergency services intervention. Following is a summary of key events for the 2007 Burnley Tunnel Fires as given in evidence in the Supreme Court Proceedings DIRECTOR OF PUBLIC PROSECUTIONS v. DAVID LAWRENCE KALWIG 16/07/2009 [This evidence is indicative only of the events the currently suppressed Technical Report for the Coroner (Dix 2008)] contains detailed technical information on the events): At 9:52:30 a truck stopped in the left (slow) of three lanes in the east bound Burnley Tunnel. Between 9:54:26 and 9:54:30 a series of collisions, explosions and fires occur when a truck crashes into several cars and HGVs in the region immediately behind the stopped truck. Eventually the truck which initiated the series of crashes hit the stopped truck and pushing it many metres forward. At 9:55:37 the tunnel operator enabled emergency mode in preparation for the smoke extraction, deluge operation and evacuation. At 9:55:50 the emergency response plan was initiated by the tunnel controller including activation of emergency smoke extraction and the deluge system. At 9:55:54 the smoke extraction system was activated. At 9:56 the fixed fire suppression (Deluge) was activated. Three people were killed in three different vehicles. Two of the three deaths were determined to be effects of fire. The fires which killed these people were not, and could not, be extinguished by the deluge system as expected from the experimental results. 2, 6 All those killed suffered fatal serious physical injuries in the car crashes. The lack of demand to the outsides of the vehicles involved in the fires, and the lack of fire spread by flashover is also to be expected from theoretical observations. 16 The incident resulted in several hundred people being evacuated from the tunnel and their vehicles. None of the evacuees or their vehicles was injured or damaged. The tunnel only

suffered minor damage, and could have been re-opened 10 s of hours later if the extent of the damage could have been more rapidly determined. Mont Blanc Tunnel after fire (no suppression system.) Burnley Tunnel after fire - road surface and tunnel walls and services still intact. 4.1. Discussion In the Burnley incident the ventilation system rapidly reduced the longitudinal velocity to approximately 2m/sec. This low ventilation rate was sufficient to stop backlayering despite the buoyancy effect caused by the tunnels steep grade of in excess of 6.2% at the incident location. The rapid activation of the FFFS and the comparatively low longitudinal velocities coincided with only minimal fire growth following the crash, explosions and subsequent fire. This is entirely consistent with the theoretical results noted in this report. The fire inside the structure of the prime mover was not extinguished by the FFFS but by the intervention of fire fighters. This is entirely consistent with the expectations derived from experiments involving shielded fires. The absence of flashover and lack of accelerated fire growth is consistent with the experimental data on the effects of a FFFS with water application rates roughly in the order of 10mm/min. 5. CONCLUSIONS The rapid and accurate use of Burnley s FFFS coupled with effective longitudinal air velocity control coincided with minimal tunnel damage, no non crash human victim fire related injuries and rapid reopening of the infrastructure. There is now growing theoretical research which supports the view taken in Australia and in Japan that the use of FFFS coupled with advanced tunnel ventilation control, rapid incident detection and accurate response positively contributes to tunnel fire safety and asset protection. The differences in the performance of FFFS systems as a function of droplet size distribution warrants further analysis in the tunnel fires context.

REFERENCES 1. Arvidson, Magnus, Large-scale ro-ro deck fire suppression tests, SP Report 2009:29, SP Technical Research Institute of Sweden 2. Arvidson, Magnus, Large scale water Spray and Water Mist Fire Suppression Systems Tests, Proceedings from the Fourth International Symposium on Tunnel Safety and Security, Frankfurt am Main, Germany, 283-296 March 17-19, 2010 3. Mawhinney Jack, R. and Back III, Gerard, Water Mist Fire Suppression Systems, The SFPE Handbook of Fire Protection Engineering, Fourth Edition, National Fire Protection Association and Society of Fire Protection Engineers 4. Kratzmeir, Stefan and Lakkonen, Max, Road tunnel protection by water mist systems Implementation of full scale fire test results into a real project, Proceedings from the Third International Symposium on Tunnel Safety and Security, 195-2-3, Stockholm, Sweden, March 12-14, 2008 5. Palle, Alex and Palle, Carsten, Full scale tunnel tests of VIC Fire-Kill low pressure water mist tunnel fire protection system in Runehamar test tunnel, spring 2009, Proceedings from the 9 th International Water Mist Conference, London, United Kingdom, September 23-24, 2009 6. Harris, K.J., Water Application Rates for Fixed Fire Fighting Systems in Road Tunnels, proceedings from the Fourth International Symposium on Tunnel Safety and Security, Frankfurt am Main, Germany, 351-362 March 17-19, 2010 7. Yoon J, Ko and George Hadjisophocleous, An experimental study of the impact of tunnel suppression on tunnel ventilation, proceedings from the Fourth International Symposium on Tunnel Safety and Security, Germany, 341-349 March 17-19, 2010 8. Wu, Y., and Bakar, M.Z.A., Control of Smoke Flow in Tunnel Fires using Longitudinal Ventilation systems a Study of the Critical Velocity, Fire Safety Journal, 35, 363-9-, 2000 9. Carvel, R.O., Beard, A.N., Jowitt, P.W., and Drysdale, D.D., Variation of Heat Release Rate with Forced Longitudinal ventilation for Vehicle Fires in Tunnels, Fire Safety Journal, 36, 6, 569-596, 2001 10. Carvel, R.O., Beard, A.N., and Jowitt, P.W., The Influence of Longitudinal Ventilation systems on Fires in Tunnels, Tunnelling and Underground Space Technology, 16, 3-21, 2001 11. Carvel, R.O., Beard, A.N., and Jowitt, P.W., The Influence of Longitudinal Ventilation and Tunnel Size on HGV Fires in Tunnels, 10 th International Fire Science & Engineering Conference (Interflam 2004), 815-820, Scotland, 5-7 July, 2004 12. Lonnermark, A., and Ingason, H., The Effect of Air Velocity on Heat Release Rate and Fire Development during Fires in Tunnels, 9 th International Symposium on Fire Safety Science, pp701-712, Karlsruhe, Germany, 21-26 September 2008 13. Ingason, H., and Lonnermark, A., Effects of longitudinal ventilation on fire growth and maximum heat release rate, Proceedings from the Fourth International Symposium on Tunnel Safety and Security, Germany, 395-406 March 17-19, 2010 14. Ingason, H., Model Scale Tunnel Fire Tests Longitudinal Ventilation, SP Swedish National Testing and Research Institute, SP Report 2005:49, Boras, Sweden, 2005 15. Personal communication Gotthard Tunnel Fire November, Fireman, 2001. 16. Lemaire, T., and Meeussem, V., Experimental determination of B>EVE-risk near very large fires in a tunnel with a sprinkler/water mist system, Proceedings from the Fourth International Symposium on Tunnel Safety and Security, Frankfurt am Main, Germany, 283-296 March 17-19, 2010