INDEPENDENT DOMESTIC CALORIFIERS

Similar documents
ZENA PLUS EASYLIFE WALL-HUNG GAS BOILERS

GT 120 >> >> >> << >> Sustainable Comfort. Longlasting comfort

BSC...E - BSP...E - BESC...E

HPI REVERSIBLE AIR/WATER HEAT PUMPS SPLIT INVERTER

GT 220 PROJECT CAST IRON FLOOR-STANDING FUEL OIL-/GAS-FIRED BOILERS

WALL-HUNG GAS CONDENSING BOILERS MCR-P 24/28 BIC. HOMOLOGATION B 23P - C 13x - C 33x - C 93x -C 53 - C 43x - C 83x *

4FLOOR-STANDING GAS CONDENSING BOILERS

B 150p to B 500p. Independent domestic hot water tanks. Installation instructions. Instructions for use. Technical instructions.

Industrial and collective. With coil exchanger. Technical data. Initial heat-up. surface area. Exchanger. Exchanger capacity.

ADVANCE EASYLIFE PROJECT

<< >> Condensing technology at the service of oil. Controlling energy to save money

8FUEL OIL CONDENSING BOILERS

ALEZIO REVERSIBLE AIR/WATER HEAT PUMPS SPLIT INVERTER CONDITIONS OF USE

FLOOR STANDING GAS CONDENSING BOILERS CONDITION OF USE CLASSIFICATION

GT 220 CAST IRON FLOOR-STANDING FUEL OIL- / GAS-FIRED BOILERS

PMC-M WALL-HUNG GAS CONDENSING BOILERS

=Classic range= Classic range technologies. Magnesium anode. Sheathed heating element

Domestic hot water tank SR130. Installation, User and Service Manual

Hamworthy. Powerstock. Calorifiers and Storage Tanks Single and Twin Coils Capacities 160 litres to 995 litres

NANEO EMC-M WALL-HUNG GAS CONDENSING BOILERS

Solar Thermal Energy

Installation, Operating and Servicing Instructions

GTU C 220 FUEL OIL CONDENSING BOILERS

FLOOR-STANDING GAS CONDENSING BOILERS FROM 3.4 TO 35.9KW. by 160 litre enamelled calorifier with coil placed CONDITIONS OF USE HOMOLOGATION

WHE 2.24 / WHE 2.24 FF

ARTESIAN 220 & 340 Instantaneous Indirect Water Heater By Dunkirk Boilers INSTALLATION AND OPERATING INSTRUCTIONS ENGINEERING MANUAL

>> >> >> High technology with oil. High performance modulating burner Compact boiler design. Compatible with renewable energies. Sustainable Comfort

Installation, Operating and Servicing Instructions

DIEMATIC VM isystem WALL-MOUNTED CONTROL SYSTEM. DIMENSIONS Length: 320 mm Height: 260 mm Depth: 130 mm. POWER SUPPLY 230 V, 50 Hz, 6 A

Modulens G >> >> >> Condensing in excellence mode

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

UNVENTED WATER HEATERS. Water Heater Display Stand

PRODUCT CATALOGUE

TERMO Combi Cylinder TECHNICAL INFORMATION

NANEO EMC-M EASYLIFE WALL-HUNG GAS CONDENSING BOILERS

ALEZIO EVOLUTION EASYLIFE REVERSIBLE AIR/WATER HEAT PUMPS SPLIT INVERTER

VERTINOX. AISI 316 stainless steel accumulators with one or two heat exchangers, fixed or removable type

DTG Eco / V130

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS,

High performances NEW ELECTRIC STORAGE WATER HEATERS

STORAGE WATER HEATERS

SATK wall-mounted Heat Interface Unit (HIU) Instantaneous domestic hot water production

Hamworthy. Dorchester DR-SA & DR-SE Fully Automatic and Permanent Pilot Direct Gas-Fired Storage Water Heaters. Exceeds Minimum Requirements

VIESMANN. Datasheet Part numbers and prices: see pricelist VITOCELL 300-V. Vertical DHW cylinder. 130to500litrecapacity. Vitotec folder, register 17

RENEWABLE ENERGY THERMAL SOLAR ENERGY. RENEWABLE ENERGY...pag. 05

Electric Water Heaters. The STRENGTHS of the product range in detail:

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS, for the User and the Installer. SMART Line. Smart ME A Y2000 B

CALORIFIERS (Energy Storage Tanks) for domestic, commercial and industrial applications.

FREQUENTLY ASKED QUESTIONS

ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT

ACCUMULATION OF EUROPEAN CLASS

Solar heating systems

Installation, operating and. Comfort

Precision Storage Vessels ELECTRIC WATER HEATERS

Heat Accumulation. thermal stores hot water storage tanks. Energy-saving solutions

Introduction...from 3 to 4 Tanks for the production and storage of DHW. Domestic use....from to 8 Tanks for the production and storage of DHW. Industr

Cylinders for Domestic Purposes Heat Pumps

SMART Line Smart E

Aquamatic Instantaneous DHW production unit with integrated storage tank

Series 1000 & Storage Water Heaters

MPX 24/28 MI Compact MPX 28/33 MI Compact CONDITIONS OF USE HOMOLOGATION. B 23 - C 13x - C 33x - C 53x - C 93x - C 83x* B 23p - B 33 - C 43x

Mains pressure hot water for fast filling baths and powerful showers Simultaneous supply of water to all bathrooms Long life low maintenance hot

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500

Components for solar heating systems

Range GT GTU C GT 220

USER MANUAL INSTALLATION INSTRUCTIONS WARRANTY REGISTER

MAXIMISER Semi-Storage Calorifiers

Installation Manual STOR C. Solar combination storage cylinder. Installation Manual

ECOplus Solar Cylinder

Installation, Operation and Maintenance Instructions for Electric Storage Calorifier

Hot Water Supply. Dr. Sam C M Hui Department of Mechanical Engineering The University of Hong Kong

Contact person RISE Date Reference Page Björn Folkeson P (13) Energy and circular economy

Accumulator tank. 1000, 750 and 500 litres Aqualux Teknik Aqualux UB Aqualux 750 CU

5231 Series. Low Lead High Flow Thermostatic Mixing Valves. Installation, commissioning and service instructions ASSE 1017 NA10341

Xcel HEATBANK Thermal Store The solution to multi-fuel heating. Renewable Energy Solutions

New Zip AquaFlo. Stainless steel cylinders for mains pressure hot water

AGUAdens TM 100% residential condensing D.H.W. wall-mounted water heaters ( litres) AISI 316 D.H.W. WORKING PRESSURE TITANIUM CONDENSING

Contact person Date Reference Page Daniel Månsson P (13) Energy and circular economy

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier

EXPLORER HEAT PUMP WATER HEATER. A+ in READY Smart heat pump

ALKON CARGO. A precise and fast delivery rate. A very high specific flow rate (20 litres per minute with Dt 25)

S SOLAR RANGE

BORA BORA. BORA gas: the best suns THE MODELS BORA GAS ALL INNOVATION STRENGTHS

Contact person RISE Date Reference Page Daniel Månsson P (13) Energy and circular economy

Contact person RISE Date Reference Page. Daniel Månsson P (13) Energy and circular economy

SOTTOSTAZIONI PER TELERISCALDAMENTO DISTRICT HEATING SUBSTATIONS

Installation & Operation Manual Models: TSU

A Guide to Commercial Hot Water from Hamworthy. Introducing Hamworthy s Product Ranges for Hot Water Generation:

Flamco. Water heaters, storage tanks and accessories DUO WATER HEATER SUPASTOR WATER HEATER LS STORAGE TANKS WATER HEATERS, STORAGE TANKS

CALEFFI. SATK wall-mounted heat interface unit Fitted for connection to DHW storage. SATK40 series 01216/14 GB

Technical Data Manual Model Nos. and pricing: see Price List

HEATBANK Xcel Thermal Store The solution to multi-fuel heating. Renewable Energy Solutions

HPI EVOLUTION ADVANCE REVERSIBLE AIR/WATER HEAT PUMPS SPLIT INVERTER

Tank systems. Layered tank Solar layered tank Hygienic layered tank Modular layered tank Hot water tank NEW:

Contact person RISE Date Reference Page Björn Folkeson P03675B 1 (11) Energy and circular economy

MCR 24 MCR 24/28 MI MCR 30/35 MI MCR 34/39 MI

ThermoDual Domestic hot water charging system

rinnaihumans.it Infinity TANKLESS GAS WATER HEATERS A and A+ water heaters

The slightest variation in use conditions will be passed along to the same operating chain : first the distributor and then the large water passages.

HT V2 HT Split

Transcription:

BPB-BLC /BEPC /B /FWS INDEPENDENT DOMESTIC CALORIFIERS BPB : Performance, independent calorifiers, capacity to litres BLC : Comfort, independent calorifiers, capacity to litres BEPC : DHW calorifier litres for heat pump B : Large capacity independent DHW calorifiers, FWS : Instantaneous DHW calorifiers and, and litres litres BPB BLC Stored DHW: BPB/BLC/B BEPC instantaneous DHW: FWS For connection to a boiler up to an exchanged of : - for BLC/BEPC - for BPB - for B // - for FWS BEPC B FWS / BPB/BLC /BEPC : Range of independent DHW calorifiers from to litres with exchanger in the form of an enamelled coil for connection to a central heating boiler, tank in enamelled steel and protection by magnesium anode. B //: Range of independent DHW calorifiers from to litres with exchanger in the form of an enamelled coil for connection to a central heating boiler, tank in enamelled steel and Correx imposed current anode offering Integral Anti-Corrosion protection (B and B ). B is protected by two magnesium anode. FWS : Range of instantaneous domestic hot water (DHW) calorifiers, from to, with water storage and DHW production via a stainless-steel coil exchanger for applications where prevention of legionellosis is essential. CONDITIONS OF USE Maximum operating temperature - (exchanger): BPB/BLC : C B / BEPC : C - (tank): FWS : C Maximum operating pressure - (exchanger): BPB/BLC : bar BEPC : bar - (tank): FWS : bar - secondary (tank): BPB/BLC : C B : C BEPC : C - DHW exchanger: FWS : C - secondary (tank): BPB/BLC : bar BEPC : bar - DHW exchanger: FWS : bar FWS : bar

PRESENTATION OF THE RANGES THE BPB/BLC RANGE OF INDEPENDENT DHW CALORIFIERS The independent DHW calorifiers in the ranges BPB and BLC are used to produce domestic hot water both in individual and collective housing and in commercial or industrial premises. They are made of very thick sheet steel allowing a maximum operating pressure of bar for domestic hot water. Their interior is protected by food quality standard high quartz content vitrified enamel and by a magnesium anode. BPB/BLC DHW calorifiers are fitted with an exchanger in the form of an enamelled coil with a larger exchange surface for the BPB than for the BLC Insulation is provided by %-CFC polyurethane foam, injected directly into the casing, with a thickness of mm for the BPB range and mm for the BLC range. The white ABS casing has a smooth appearance for the BPB and a granular appearance for the BLC. Note: The choice of a BPB or BLC DHW calorifier will be made according to its intended use as well as according to its volume : - if the flow over minutes (l/ min) is the main criterion, both ranges, BPB or BLC, offer equal performances; - if, on the other hand, continuous flow (l/h) is the main requirement, one or other DHW calorifier will be selected according to the larger exchanger on the BPB than on the BLC at an equivalent capacity. THE BEPC INDEPENDENT CALORIFIER The BEPC is a mixed DHW calorifier, to be used in association with a heat pump, and hence has a exchanger that is oversized in comparison with the volume of the tank. It is fitted with a steatite, W electrical heater with integrated thermostat. It is made of very thick sheet steel allowing a maximum DHW operating pressure of bar. The interior is protected by food quality standard, high quartz content, vitrified enamel and by a magnesium anode. The insulation is mm thick, %-CFC polyurethane foam, injected directly into the casing. THE B // RANGE OF INDEPENDENT DHW CALORIFIERS Like BPB/BLC... DHW calorifiers, B / and DHW calorifiers are used to produce domestic hot water in collective housing as well as in industrial or commercial premises. They are made of very thick sheet steel allowing a maximum operating pressure for domestic hot water of bar. Their interior is protected by food quality standard vitrified enamel with a high quartz content. This protection against corrosion is further reinforced by a Correx self-adapting current anode with a practically unlimited life span (B and B ). B is protected by two magnesium anode. They are fitted with an exchanger in the form of a large enamelled coil. The casing, in beige and grey on the B //, is constructed using rigid shells in polyurethane foam with % CFCs ; this class M casing allows the use of these DHW calorifiers in establishments open to the public and can be put in place once the tank has been installed and connected. THE FWS / RANGE OF INDEPENDENT DHW CALORIFIERS Multi-zone steel calorifiers for production of instantaneous DHW, to which all types of boiler can be connected and with the option of connecting a solar circuit. It is comprised of a stratification storage tank and an exchanger in the form of a high performance stainless steel coil incorporated in the tank for the production of DHW (up to l/min). Model FWS contains a double exchanger. The main applications of this tank can be found in the service sector: retirement homes, hospitals, schools, etc. where prevention of legionella is essential. WATER QUALITY Our calorifiers from the B range are fitted with enamelled tanks allowing use of water with a hard-water mineral content of between f and f on the French hard water scale. If this is not the case, we recommend pre-treating the water before injection into the tank. The stainless steel exchanger in our FWS calorifiers is suitable for all water qualities intended for human consumption.

CHOOSING THE DOMESTIC HOT WATER CALORIFIER The domestic hot water calorifier must be chosen in full knowledge of the facts in order to ensure permanent DHW availability at the desired temperature. It is therefore important accurately to determine the DHW needs necessary to meet this requirement, which depends largely on the number of people living in the home and their consumption habits. It will also depend on the risk of legionellosis, which would direct the choice towards a calorifier with instantaneous DHW production. Below are a number of points which may help you in this choice : DETERMINING YOUR DOMESTIC HOT WATER NEEDS Determining these needs will condition : - The choice of the DHW calorifier s capacity; - The power of its exchanger; - And possibly the power of the generator with which it is combined. Actual needs will therefore have to be determined for a given temperature over a given duration (hour/day) and the peak flows (litre/minute) assessed according to DHW use at a given moment. In collective housing, it will also mean factoring in simultaneous use. METHODS FOR DETERMINING YOUR DHW NEEDS Using the DHW Needs software available in our DIEMATOOLS offer This software (or any other software which you may have acquired) will offer you an effective guide in assessing your needs. Other methods - Using the tables below, it is possible to approximate your daily domestic hot water needs. Important: To determine the capacity of the DHW calorifier, it is necessary to factor in any peak flows caused by simultaneous use at different draw-off points in addition to these daily needs. As for the calculation of the installation, this will have to be made in accordance with prevailing standards. Station to be supplied Number of people Daily DHW needs ( to C) Sink - to kitchen - to Sink - to + washbasin - to + shower - to Note: These tables do not cover multi-jet showers ( l/min) or spa type bathtubs Station to be supplied Number of people Daily DHW needs ( to C) Washbasin + - to small bathtub - to Sink - to + washbasin - to + bathtub - to Special cases : domestic hot water requirements in the tertiary sector Hotels with no restaurant Restaurants Hotel category no* * * * * DHW needs at C (l/room) Camp sites Number of shower cabins DHW needs at C (l) Seaside Not seaside Restaurant collective () private (*) () Number of place settings DHW needs at C (l) () l/place setting with dishwashing for h. () l/place setting with dishwashing for h. Hairdressing salons Number of basins DHW needs at C (l) Others Retirement home: l at C per bed per day + l per meal (lunch and dinner). Offices: l at C per occupant per day. Hospitals and clinics: l at C per bed per day + l per day per meal (lunch and dinner). Schools: l at C per pupil per day. Military barracks: l at C per person per day. Gymnasiums:. l at C per person with timed shower. Stadiums: l at C per person with timed shower.

BPB TO DHW CALORIFIERS: TECHNICAL SPECIFICATIONS PRINCIPAL DIMENSIONS (IN MM AND INCHES) øh G () A () B C E F BPB_FA Domestic hot water outlet G " Circulation G /" Exchanger inlet G " Location DHW sensor int. Ø, mm Exchanger outlet G " Cold water inlet and drainage G " Thermometer Anode () Feet adjustable from to mm () by models, and litres G: cylindrical external thread (water tightness by flat gasket) A B C E F G Ø H BPB BPB BPB BPB BPB TECHNICAL SPECIFICATIONS Maximum operating temperature: - (exchanger): C - secondary (tank): C Maximum operating pressure: - (exchanger): bar - secondary (tank): bar Model BPB BPB BPB BPB BPB Calorifier capacity l Exchanger surface m..... Nominal liquid flow m /h..... P circuit at nominal flow kpa..... at temp. Primary inlet temp. C outlet Exchanged.............. DHW = C Flow per hour at T = K l/h at temp. Primary inlet temp. C - - - - - outlet Exchanged -... -.. -... -.. -... DHW = C Flow per hour at T = K l/h - - - - - Flow over min at T = K () l/ min Cooling constant Wh/ h.k.l..... Standby consumption at T = K h/h..... Net weight kg () Cold water temp.: C, inlet temp.: C Note: Pressure drop according to the exchanger flow and continuous performance : see page.

BPB TO DHW CALORIFIERS: TECHNICAL SPECIFICATIONS PRESSURE DROP ACCORDING TO THE PRIMARY EXCHANGER FLOW kpa Loss of pressure BPB BPB BPB BPB BPB,... Water BPB_F CONTINUOUS PERFORMANCE OF BPB TO The following diagrams give the continuous performance in according to the T or the flow, inlet and DHW outlet temperatures ( to C). Cold water temp.: C m /h inlet temperature m /h in m /h BPB K t m /h inlet temperature BPB t K m /h in m /h inlet temperature m /h m /h in m /h BPB K t m /h inlet temperature t K m /h BPB in m /h BPB_F inlet temperature m /h m /h BPB in m /h K t How to use the diagrams a) BPB data: inlet t /outlet t : / C i.e. t = K domestic inlet t /outlet t : / C results: flow = m /h continuous = b) BPB data: inlet t : C domestic inlet t /outlet t : / C flow : m /h results: t = K continuous = K = C

BLC TO DHW CALORIFIERS: TECHNICAL SPECIFICATIONS PRINCIPAL DIMENSIONS (IN MM AND INCHES) BLC Domestic hot water outlet G " Circulation G /" Exchanger inlet G " Location DHW sensor int. Ø, mm Exchanger outlet G " Cold water inlet G " () Feet adjustable from to mm G: cylindrical external thread (water tightness by flat gasket) () BLC /// øh () A B C D G () BLC_FB BLC_FA Domestic hot water outlet G " Circulation G /" Exchanger inlet G " Location DHW sensor int. Ø, mm Exchanger outlet G " Cold water inlet and drainage G " Anode () Feet adjustable from to mm () By models, and litres G: cylindrical external thread (water tightness by flat gasket) A B C D G Ø H BLC BLC BLC BLC TECHNICAL SPECIFICATIONS Maximum operating temperature: - (exchanger): C - secondary (tank): C Maximum operating pressure: - (exchanger): bar - secondary (tank): bar Model BLC BLC BLC BLC BLC Calorifier capacity l Exchanger surface m..... Nominal liquid flow m /h..... P circuit at nominal flow kpa at temp. Primary inlet temp. C outlet Exchanged............... DHW = C Flow per hour at T = K l/h at temp. Primary inlet temp. C - - - - - outlet Exchanged -... -... -.. -... -.. DHW = C Flow per hour at T = K l/h - - - - - Flow over min at T = K () l/ min Cooling constant Wh/ h.k.l..... Standby consumption at T = K h/h.... Net weight kg () Cold water temp.: C, inlet temp.: C Note: Pressure drop according to the exchanger flow and continuous performance : see page.

BLC TO DHW CALORIFIERS: TECHNICAL SPECIFICATIONS PRESSURE DROP ACCORDING TO THE PRIMARY EXCHANGER FLOW kpa Loss of pressure BLC BLC BLC BLC BLC.... Water BLC_F CONTINUOUS PERFORMANCE OF BLC TO The following diagrams give the continuous performance in according to the T or the flow, inlet and DHW outlet temperatures ( to C). Cold water temp.: C m /h m /h inlet temperature in m /h BLC K t m /h BLC t K m /h inlet temperature in m /h BLC m /h inlet temperature m /h BLC in m /h K t m /h inlet temperature t K m /h in m /h BLC_F m /h m /h BLC inlet temperature in m /h K t How to use the diagrams a) BLC data: inlet t /outlet t : / C i.e. t = K domestic inlet t /outlet t : / C results: flow = m /h continuous = b) BLC data: inlet t : C domestic inlet t /outlet t : / C flow : m /h results: t = K continuous = K = C

B, B AND DHW CALORIFIERS: TECHNICAL SPECIFICATIONS PRINCIPAL DIMENSIONS (IN MM AND INCHES) B FA Domestic hot water outlet Rp /" Circulation Rp /" Exchanger inlet Rp /" Exchanger outlet Rp /" Domestic cold water inlet Rp /" Drainage Rp " Location for thermometer Magnesium anode Rp /" Sensor location x M on Ø mm Location for air vent Rp /" plugged R: threading Rp: tapped connection B - FG Domestic hot water outlet Ø C Circulation Rp /" Exchanger inlet Rp /" Exchanger outlet Rp /" Domestic cold water inlet Ø C Drainage Rp /" Location for thermometer Rp / plugged Impose current anode Sensor tube interior Ø int. x M on Ø mm Location for air vent Rp /" plugged R: threading Rp: tapped connection A Ø B Ø C D E F G H J Ø K B Rp / B Rp / TECHNICAL SPECIFICATIONS Maximum operating temperature: - (exchanger): C - secondary (tank): C Maximum operating pressure: - (exchanger): bar - secondary (tank): bar Model B B B Calorifier capacity l Exchanger surface m... Exchanger capacity l... Nominal liquid flow m /h... P circuit at nominal flow kpa... at temp. Primary inlet temp. C outlet Exchanged......... DHW = C Flow per hour at T = K l/h at temp. Primary inlet temp. C - - - outlet Exchanged -.. -... -... DHW = C Flow per hour at T = K l/h - - - Flow over min at T = K () l/ min Cooling constant Wh/ h.k.l... Standby consumption at T = K W Net weight kg () Cold water temp.: C, inlet temp.: C

B, B AND DHW CALORIFIERS: TECHNICAL SPECIFICATIONS PRESSURE DROP ACCORDING TO THE PRIMARY EXCHANGER FLOW kpa Water FB CONTINUOUS PERFORMANCE OF B CALORIFIERS The following diagrams give the continuous performance in according to the T or the flow, inlet and DHW outlet temperatures ( to C). Cold water temp.: C FB

BPB/BLC TO, B CALORIFIERS: OPTIONS OPTIONS AM BPB - BLC + GT/GTU (C) (Package EA ) Q Q GTUC_F Q Inert electrical anode with self-adapting current Package AJ : for BPB/BLC to Package AM : for BPB/BLC and Kit Titan Activ System - Package EC (for DHW calorifier combined with a boiler fitted with the DIEMATIC control panel) The self-adapting current anode consists essentially of a titanium, platinum-coated rod powered at low voltage. Its advantage over a traditional magnesium anode is that the material is free of wear. Therefore it does not need to be monitored as its life span is practically unlimited. The self-adapting current anode is mounted in the lateral flange, in the place and instead of the magnesium anode ; for the calorifiers calorifiers BPB to and BLC, and with anodes, the nd anode Electrical resistor with thermostat - Package ER This resistor is fitted to a flange / in the place and instead of the existing lateral flange. In this case, it will not be possible to mount the ABS side-cover. This resistor is equipped with a safety thermostat and is powered independently of the DHW control system on the boiler circuit. should also be removed and the opening plugged (kit delivered with the anode). The imposed current anode is delivered with a cable. m long and a transformer which can be plugged into a V socket, to be fitted close to the DHW calorifier. Important: The self-adapting current anode is not compatible with the installation of a shielded electrical resistor. Important : Fitting a shielded electrical resistor is not compatible with using a self-adapting current anode. BPB/BLC calorifier/boiler connection kit Package EA : for GT/GTU (C), Elidens DTG - Eco.NOx Plus Package EA : for GT, GT Package EA : for GT to, DTG Package EA : for Elitec DTG (E), Elidens DTG -/ Eco.NOx Plus Package EA : for Elidens DTG - à Eco.NOx Plus, Innovens Pro MCA à Package EA : for Elidens DTG E - Eco.NOx Plus Package EH : for heat pump ALEZIO AWHP-II As a general rule, the DHW calorifier can be placed to the right or left of the boiler according to the details given in the technical instructions for the boiler. The connection kits include an air vent, a non-return valve, a load pump (or reversal valve for package EA ) and all the pipes required to make the connection. Thermometer (option for B calorifiers) - Package AJ The thermometer is delivered with a sensor tube to be inserted into the opening provided for this Note : The hydraulic specifications of the load pumps provided with these connection kits make it possible to reach flow values of between and m /h depending on the pressure drop in the boiler connected to the DHW calorifier. purpose on the front of the DHW calorifier after first taking out the plug. Reversal valve heating + DHW sensor - Package EH EH_Q Control unit for loading pump SLA - Package EC Q

BEPC DHW CALORIFIER: TECHNICAL SPECIFICATIONS PRINCIPAL DIMENSIONS (IN MM AND INCHES) Ø DHW outlet G " Exchanger inlet G " Circulation G /" Domestic cold water inlet G " Exchanger outlet G " Drainage G " Anode Electrical resistance () FA () Feet adjustable from to mm G: cylindrical external thread (water tightness by flat gasket) TECHNICAL SPECIFICATIONS Maximum operating temperature: - (exchanger): C - secondary (tank): C Maximum operating pressure: - (exchanger): bar - secondary (tank): bar Model BEPC Calorifier capacity l Exchanger surface m. Exchanger capacity l. Intensity: single phase( V)/three phase ( V)/three phase ( V) W././. DHW flow (with flow ) m /h at temp. Primary inlet temp. C outlet Exchanged............ DHW = C Flow per hour at T = K l/h at temp. Primary inlet temp. C outlet Exchanged -... -... -... DHW = C Flow per hour at T = K l/h - - - Electrical power W «Electric» heating time from to C h. Cooling constant Wh/h.K.l. Qpr h/h. Primary circuit pressure drop at flow of m /h kpa Net weight kg PRESSURE DROP ACCORDING TO THE PRIMARY EXCHANGER FLOW - CONTINUOUS PERFORMANCE The following diagrams give the continuous performance in outlet temperatures ( to C). according to the T or the flow, inlet and DHW Cold water temp.: C kpa Loss of pressure Water BEPC_F m /h m /h BEPC t K in m /h inlet temperature BEPC_F

FWS INSTANTANEOUS DHW CALORIFIER: TECHNICAL SPECIFICATIONS PRINCIPAL DIMENSIONS (IN MM AND INCHES) FWS Ø Ø FWS_F FWS FWS Domestic hot water outlet Rp " R" Boiler inlet R /" R /" Boiler return (maxi solar) R /" R /" Solar circuit inlet R /" R /" Solar volume input R /" - Boiler return (mini solar) R /" R /" Domestic cold water inlet Rp " R " Solar circuit outlet/drainage Boiler outlet if no solar circuit R /" R /" Sensor tube Ø mm mm Thermometer Rp /" - Air vent Rp /" R " R: threading Rp: tapped connection FWS Ø Ø DHW exchanger FWS : annealed stainless steel tube, DN, with connection ( bar) FWS : rigid, stainless-steel tubes individually connected to the same circuit or to separate circuits ( bar) Material: Stainless steel FWS_F TECHNICAL SPECIFICATIONS Operating pressure: - tank: bar - DHW exchanger : FWS : bar FWS : bar Max. operating temperature: - tank: C Model FWS FWS Total storage volume l Total solar storage volume maxi/mini l / / DHW coil capacity l DHW exchange surface m (single coil) (double coil) Exchange power maxi DHW coil pressure drop at m /h / m /h / m /h bar././.././. DHW flow (with flow ) m /h at temp. Primary inlet temp. C outlet Exchanged - - - - - - - - - - - - DHW = C Flow per hour at T = K () l/h - - - - - - - - - - - - at temp. Primary inlet temp. C outlet Exchanged - DHW = C Flow per hour at T = K () l/h - Cooling constant Wh/h.K.l.. Net weight kg () boiler connected in and (without solar) PRESSURE DROP ACCORDING TO THE DHW EXCHANGER FLOW Loss of pressure Comment : The maximum permissible flow through the DHW exchanger on the FWS is l/h ( l/min) because of the noise in the * exchanger. kpa FSW FSW l/min Water FWS_F * exchangers connected in parallel

FWS INSTANTANEOUS DHW CALORIFIER: TECHNICAL SPECIFICATIONS CONTINUOUS PERFORMANCE FWS m /h m /h m /h inlet temperature in m /h m /h DHW flow per hour (l/h) at t in (K) FWS_FB Example: GTU C with - DHW need: l/h - Target DHW outlet temp.: C (T DHW: K) DHW setpoint temp. C above inlet temp.: C Min. required boiler :. Primary flow rate required to fill the tank:. m /h, T : K Boiler selected: GTU C with Recalculated flow with T of K:. m /h Note: max. flow rate through the DHW exchanger: l/h FWS t in (K) m /h m /h in m /h m /h inlet temperature m /h DHW flow per hour (l/h) at FWS_FA Example: C ECO with - DHW need: l/h - Target DHW outlet temp.: C (T DHW: K) DHW setpoint temp. C above inlet temp.: C Min. required boiler : Primary flow rate required to fill the tank: m /h, T : K ( T max. K for C ECO) Boiler selected: C - ECO with Recalculated flow with T of K:. m /h () the max. T permitted on these boilers ensures that they are protected against insufficient water supply. INFORMATION REQUIRED FOR INSTALLATION ELECTRICAL CONNECTIONS Generally, the DHW calorifiers are managed by a control system incorporated in the De Dietrich boiler control panel. In this case, a domestic hot water sensor with a connection cable is delivered as optional equipment or with the control system. This sensor is inserted into the sensor tube provided for this purpose in the DHW calorifier. If using a boiler without a domestic hot water control system incorporated in the control panel, you should fit the option : Differential control system for controlling the load pump which controls load pump operation according to the domestic hot water temperature selected. The electrical resistor and the imposed current electrical anode equipment (options for BPB/BLC ) are connected separately. ANTI-CORROSION PROTECTION AND WATER QUALITY The service life of enamelled calorifiers depends on the water quality and the anti corrosion protection of the internal lining of the tank. - Water is termed hard ( f < TH < f) if it contains a lot of magnesium or calcium. These two elements have a protective role for the tank. Protection by magnesium anode is therefore sufficient. In contrast, the tank should be inspected periodically to prevent scaling. - When the water is soft (TH < f), it becomes aggressive to the enamel and requires periodic monitoring of the magnesium anode. We recommend the installation of an imposed current anode to ensure effective long-term protection and a periodic check of the state of the tank lining.

EXAMPLES OF INSTALLATION The purpose of the diagrams represented is to facilitate the drawing up of the quotation by the installer. They are given as examples. Other connections are possible. It is necessary to abide by the codes of practice and prevailing regulations. Note: In accordance with safety rules, a calibrated, sealed safety valve must be fitted to the calorifier s domestic cold water inlet. We recommend hydraulic safety units with membrane. Installation of an independent BPB/BLC or B calorifier and a boiler When the heating installation includes a - or -way mixing valve, the exchanger must be connected between the boiler and the valve and must be as direct as possible. To improve efficiency, the independent DHW calorifier must be positioned as close as possible to the boiler and the connecting pipes must be insulated. The DHW calorifier can be placed to the right or left of the boiler. Note: To connect the domestic hot water, a sleeve made of steel, cast iron or any other insulating material must be interposed between the hot water outlet and the distribution pipes to prevent any corrosion to the connections if these pipes are made of copper. * * * * EA cm () FA Installation with FWS calorifiers connected in parallel FWS_FA The FWS connects to the boiler like a calorifier with coil. The boiler reheats the hot water storage volume, which then provides heating of the DHW exchanger for instantaneous DHW production. The DHW sensor circuit is placed in the lower / of the FWS calorifier, for which the set point should be adjusted to K above (*) Note: The unit (,,, ) can be replaced to your advantage by a membrane safety unit, as long as you respect the following obligations : - The safety unit and its connection to the DHW calorifier must be of the same diameter as the cold water supply pipes on the calorifier s domestic circuit (a minimum of /" up to litres and " over litres); the desired DHW temperature at the calorifier outlet. The storage volume compensates for low usage and for the revival time of the boiler during the times of largest demand. The choice of boiler power should be made with respect to the t that it allows. - The level of the safety unit must be lower than the level of the cold water inlet (see below); - The drainage pipe must have sufficient continuous gradient and its cross-section must be at least equal to that of the safety unit outlet opening (to avoid hindering the flow of water in the event of overpressure). B A C D E cm () FA - Safety unit calibrated and sealed at bar A - Cold water inlet including a non-return valve B - Connection to the calorifier s cold water inlet C - Stop valve D - Manual safety and drainage valve E - Drainage opening Key: see page

EXAMPLES OF INSTALLATION Installation of independent BPB/BLC or B DHW calorifiers and a boiler It is necessary to ensure that all parallel hydraulic connections, and secondary, are correctly balanced. a) Parallel hydraulic connections - (exchangers) and secondary (DHW) This type of connection is recommended when you want to also allows operation with a single DHW calorifier when this is give priority to the continuous performance of the calorifiers. It sufficient. Emplacement of the control system sensor The control system sensor will be placed in the DHW calorifier which can be allowed to operate alone or in the DHW calorifier connected to the circulation loop. Note: It is advisable to fit a control system for the domestic hot water temperature (mixer tap) on the calorifier outlet, as a fault in the hydraulic balance of the circuits may lead to overheating in a calorifier not fitted with the control system sensor. (It is also necessary to ensure that the reverse phenomenon does not occur, i.e. insufficient heating in the same calorifier). * * * * * * * EA * EA cm () cm () FB *see note on page b) Hydraulic connections - (exchangers) in parallel - secondary (DHW) in series This type of connection is recommended when you wish to avoiding any mixing at the calorifier outlet due to domestic maintain maximum performance of the DHW calorifiers, hydraulic circuits not being correctly balanced. Emplacement of the control system sensor The control system sensor will be placed in the DHW calorifier. Note: It is necessary to fit a device to control the domestic hot water temperature (mixer tap) on the DHW calorifier outlet Apart from a hydraulic balance fault on the circuits which may lead to overheating on calorifiers not fitted with the control system sensor, the serial connection of the secondary circuits may lead to the need to reload the calorifier whilst calorifier is still at temperature. A B * * * * * * * EA * EA cm () cm () FB *see note on page Key Heating flow Heating return bar safety valve Manometer Automatic air vent Stop valve Expansion vessel Drainage valve Filling the heating circuit Primary exchanger inlet Primary exchanger outlet DHW load pump Non-return valve Domestic cold water inlet Pressure reducer if mains pressure >. bar DHW loop pump (optional) DHW temperature sensor Balancing valve Disconnector EA type protection unit comprising a stop valve and a controllable class A non-return valve (Standard P.) YA type load break (health regulations) Membrane safety valve calibrated and sealed at bar DHW circulation return loop Domestic hot water outlet Plugged opening Thermostatic mixer tap

INFORMATION ON THE PREVENTION OF SCALDING BY DOMESTIC HOT WATER AND THE DEVELOPMENT OF LEGIONELLA To restrict the development of bacteria, the temperature of the hot water distributed must be at least C on leaving storage and, if the installation includes a recirculation loop, the return water temperature RECOMMENDATION REGARDING SCALDING Scalding caused by domestic hot water is a common accident which has serious consequences, particularly because of its potential extent. Around % of scalds are thought to be caused by the domestic hot water temperature being to high, occurring principally in the bathroom. must be at least C. In all cases, users must be protected against the risk of scalding at the draw-off points where the temperature of the water drawn off must not exceed C.. In order to limit the risk of being scalded : - in rooms intended for ablutions, the maximum temperature of the domestic hot water is set at C at the draw-off points ; - in the other rooms, the maximum temperature of the domestic hot water is limited to C at the draw-off points ; - in the kitchens and laundries of establishments open to the public, the temperature of the water distributed may be raised to a maximum of C at certain points which are indicated by special warning signs. Example Room not intended for ablutions Room intended for ablutions Network supply point T C C T C C T C C KEY Cold water Domestic hot water production RECOMMENDATION REGARDING LEGIONELLA IN STORAGE SYSTEMS AND DISTRIBUTION NETWORKS Legionella is caused by the inhalation of water spray temperature must be higher than or equal to C at all points contaminated by legionella. Water temperature is a significant in the distribution system with the exception of the final supply factor in preventing the development of legionella in distribution pipes. The volume in these final supply pipes must be as low as networks as the Legionella bacterium multiplies significantly in possible and at all times less than or equal to litres ; water presenting temperature of between and C. - When the total storage volume is higher than or equal to In order to limit the risk connected to the development of litres, the water contained in the storage equipment, excluding legionella in domestic hot water distribution systems to which preheating calorifiers, must: draw-off points which may be at risk at likely to be connected, Always be at a temperature higher than or equal to C at the following requirements must be respected when using the equipment outlet ; domestic hot water production and distribution systems and Or be raised to a sufficient temperature at least once every during the hours proceeding their use : hours. Annex gives the minimum water temperature - When the volume between the distribution point and the maintenance time to be respected. most distant draw-off point is more than litres, the water Annex : minimum duration of the daily increase in the water temperature in storage equipment, excluding preheating calorifiers Minimum time for which the Water temperature ( C) temperature must be increased (min) Higher than or equal to Cold water Draw-off point at NO PARTICULAR RISK from legionella Domestic hot water production (without storage) Network supply point Draw-off point at RISK from legionella Area subject to prescriptions in the example Source : excerpt from a draft DGS circular Example : storage tanks present in the distribution system Storage tank T > C at the network supply point or increased in temperature on a daily basis F F /.. Strasbourg Companies Register Document not contractually binding - Printed in France - OTT Imprimeurs Wasselonne - DE DIETRICH THERMIQUE Simplified Share Company with registered capital of, rue de la Gare - F- MERTZWILLER Tel. + () - Fax + () www.dedietrich-heating.com