Improving the (museum) indoor climate in a flooded castle

Similar documents
Museum indoor climate and energy use. Henk Schellen Rick Kramer

INTERNATIONAL JOURNAL OF CONSERVATION SCIENCE

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Next Generation Passivhaus Archives

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

Hygrothermal evaluation of a museum storage building based on actual measurements and simulations

Figure 1: Mini One and display case connections

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

Eindhoven University of Technology MASTER. Optimizing climate systems and control for museums a case study for the Zeeuws Museum. Kersten, B.

Optimizing Electric Humidifier Operation with an Air Side Economizer

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Desiccant Evaporative Cooling

HUMIDITY CONTROL IN A BASEMENT ART VAULT

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

DEHUMIDIFIERS & VENTILATORS

indirect evaporative cooling: interaction between thermal performance and room moisture balance

LAF 50 / 100 / 150. Condensing dehumidifiers for professional use. Accessories. Design. Approvals LAF

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Case Study of an Innovative HVAC System with Integral Dehumidifier. Florida Solar Energy Center Cocoa, Florida

DOMESTIC DEHUMIDIFIERS IN COOL CONDITIONS: I PERFORMANCE FACTORS

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Optimisation of cooling coil performance during operation stage for improved humidity control

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

,Chaojian He6, f. School of Guangxi University, Nanning , China.

Museum of Bavarian History Regensburg, Germany

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

HEATING - the largest part p your home's energy bill

Brine Generation Study

Psychrometric Engineering Applications

Victoria & Albert Museum, London Medieval & Renaissance Galleries: A Passive Approach to Humidity Control

Field Test of Combined Desiccant-Evaporator Cycle Providing Lower Dew Points and Enhanced Dehumidification

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY

EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY

Fifteen Years of Dehumidification Results from Heat Pump Water Heaters

Recent Advances in Energy, Environment and Economic Development

Air Conditioning and process cooling Energy Components at a Glance

USERS MANUAL. Desiccant Dehumidifier. Model: ECO DD322FW CLASSIC

New Construction Builders Challenge: Sealed Attic and High Efficiency HVAC in Central Florida: A Year in Review

Museum Archive Dehumidification in Hot & Humid Climates

Efficiency of Non-Azeotropic Refrigerant Cycle

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Optimal Use of Air Conditioner

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Figure 1: Low energy dwellings testsite

Study into the operation of a convector heater at low temperatures

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY

Thermal Performance of a Loop Thermosyphon

DEHUMIDIFICATION ADVANTAGES FOR WATER TREATMENT PLANTS

Drink Showcase Equipped with Inverter Freezer

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

INDOOR HUMAN THERMAL COMFORT OPTIMAL CONTROL WITH DESICCANT WHEEL COOLING SYSTEM

DAYLIGHTING PERFORMANCE ON VENETIAN BLIND FOR HEALTHY APARTMENT HOUSING

MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia

Temperature. In the HVAC area, we talk about two kinds of temperatures.

Connect North and South Korean Separated Families Higher Comfort Lower Energy

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Effects of Greenhouse Conditions on the Quality and Vase Life of Freesia 'Yvonne'. A Nursery Comparison

Effect of Vacuum Cooling Operation Parameters on Cooling Time and Weight Loss of Chinese Cabbage

March 2014 AHRI Presents Research Findings at Low-GWP AREP Conference

Heat pump supplemental heating system for motor vehicles

PERFORMANCE EVALUATION OF THE MINIATRIZED CATALYTIC COMBUSTION TYPE HYDROGEN SENSOR

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

HOT IN HERE: OFFICE OCCUPANT THERMAL COMFORT IN LAWRENCE HALL

Temperature and Relative Humidity agents of deterioration. 22 September 2015 Mikkel Scharff Sarah Staniforth

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Model 1700 Whole-Home Dehumidifier

HUMIDITY RELATIONSHIP DETERMINATED IN THE DRYING CEREAL SEED FLUIDIZED BED

Thermo-Fluid Simulation Technique for Achieving Energy Saving in Open Showcases

HOW THE FIRST OCCUPANT BEHAVIOR DEHUMIDIFICATION SOLUTION FOR APARTMENT LIVING WAS CREATED

EXPERIMENTAL STUDY OF AIR FLOW RATE EFFECTS ON HUMIDIFICATION PARAMETERS WITH PREHEATING AND DEHUMIDIFICATION PROCESS CHANGING

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS

Humidity Control & Psychrometrics

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Evaluation of Collector Size for Low Pressure, Fixed-Plate Sprinklers for Center Pivots 1

USERS MANUAL. Desiccant Dehumidifier. Model: ECO DD322FW SIMPLE. Read This Manual

17 Interior Climate Control

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

Ventilation in Humid Climates: Data from Field Experiments

CRAWL SPACE MOISTURE CONTROL - A Fundamental Misunderstanding By Peter Carpenter, member ASHRAE, SBCCI

Energy efficient climate control in museum stores. Poul Klenz Larsen

Experimental Research on Monomial Cooling Measure of Greenhouse in Summer

Drying principles and general considerations

Transcription:

Improving the (museum) indoor climate in a flooded castle H.L. Schellen Eindhoven University of Technology M.T.P. Ritmeijer Eindhoven University of Technology ABSTRACT: Amerongen Castle, built in de period of 1674-1680, is an acknowledged special national museum with a historic cultural value (Kanjerproject). Next to the monumental value of the building, it has a special collection that exists of for example a Van Meekeren cupboard, a valuable atlas called Amsterdam 1724 and painted portraits of monarchs like Willem de Zwijger. The building and the collection are subject to deterioration. As a result of a flood of the river Nederrijn, the basement was completely flooded with water in 1993 and in 1996. This made the deterioration worse. For a period of approximately a year and a half ICN (The Netherlands Institute for Cultural Heritage) has been measuring the indoor climate in the castle. It appeared that the indoor climate was indeed not favourable for the conservation of the collection. The purpose of the work is to understand the effects of flooding of a monumental building, to understand the impact of visitors and the presence of hygroscopic materials on the indoor climate. Finally the indoor climate of the building should be improved. On the basis of the measurements made by ICN the indoor climate of the different museum rooms was mapped. For the judgement of the indoor climate several techniques have been used, namely the climate evaluation chart, the climate evaluations map and the climate evaluation tables. A simulation model has been used to study the effects of flooding, visitor impact and hygroscopic materials in several museum rooms of Amerongen Castle. Finally the model was used to predict the effects of additional heating. The indoor climate of the building has long been influenced by flooding in the past. Visitors of the museum rooms nowadays influence the indoor climate with their heat and moisture production. Generally, the heat production of persons is normative for the relative humidity in the room compared to the moisture production. The result is a decrease of the relative humidity in the room and an increase of RH near the cold walls. It appears that the indoor climate also depends for a large part on the furniture of the room. It is stabilized by the presence of hygroscopic materials in the room (furniture, carpet, curtains, etc.). The library e.g. has a filled bookcase. The presence of these hygroscopic objects (books) in the library seems to be responsible for the comparatively stable relative humidity, in combination with the use of a mobile dehumidifier. Two studied heating systems (humidistatically controlled heating and floor heating) will lead to a more favorable indoor climate. Floor heating will be applied in the basement and the hall and long corridor on the first floor (beletage) and the humidistatically controlled heating system in the remaining museum rooms. The results seem to be promising. 1 INTRODUCTION Castle Amerongen was built in the period from 1674 to 1680. It is an important governmental museum with a large cultural historical value. Besides the important value of the monumental building itself it holds an important museum collection of objects like the Van Meekeren cabinet, an important and valuable atlas of Amsterdam 1724 and the kings paintings like Willem de Zwijger. The Dutch castle is located in the middle of The Netherlands at the river foreland of the river Nederrijn. Part of the building is still in use for a living function. The building as well as the collection are in a process of slowly being deteriorated. In 1993 and 1996 the building was flooded by the river Nederrijn. The basement of the building at that time was full of water. The indoor climate of the building was measured in a measurement campaign from 2003 to 2004. The measurement results were compared to guidelines for the preservation of the museum collection and

the building itself. The comfort of the people was decided to be less important. The measurement campaign is described in section 2. The guidelines for preservation of collection and building are determined in section 3. The discussion on the indoor climate and the effects of visitors are described in section 4. The improvement of the indoor climate and the measures to be taken are discussed in section 5. The paper ends with the conclusions in section 6. Figure 1. Amerongen Castle (a) and some museum rooms: the Grand Saloon (b), the Library (c), the basement (d) and the Tapestry Room (e). 2 MEASUREMENTS The Netherlands Institute for Cultural Heritage (Instituut Collectie Nederland, ICN) is a leading knowledge institute for the preservation and management of moveable cultural heritage. The institute started a measurement campaign for one and a half year in the air temperatures, air relative humidities, inside surface temperatures of external walls and light and UV intensity levels. Besides the outdoor climate was measured. Apart from these long term measurements short time measurements like ventilation/infiltration measurements and infrared thermography were conducted. 3 GUIDELINES The results of the indoor climate were compared with guidelines for the preservation of building and collection. The aim of these guidelines is to minimize the deterioration of the valuable collection and the building itself. In the Netherlands these guidelines originally were formulated by ICN. At the moment these guidelines are under construction. Internationally ASHRAE (the American Society for Heating and Refrigerating Air Conditioning Engineers) formulated classes for the indoor climate in museums. The control of relative humidity is most important for the preservation of most collections. A lower limit of about 40 %RH is important to preserve materials from drying out. As an upper limit for the indoor air relative humidity 60 %RH is held. Relative humidity at cold surfaces should be limited to a maximum of about 80 %RH to protect surfaces for mould formation. Fluctuations of relative humidity should be avoided to prevent objects from contraction and expansion. The day lighting of objects is also an important deterioration factor. The UV component should be eliminated and the product of exposure time and intensity value should be limited. A way to do so is making use special spectral filters for windows illumination sources and limitation of intensity and exposure time. castle in 2003. Long term measured parameters were Figure 2. The museum rooms of Amerongen Castle with the different functions of the rooms.

4 EVALUATION TECHNIQUES The indoor climate of the museum rooms in Castle Amerongen was evaluated making use of different techniques. For these purposes climate evaluation charts, climate evaluation tables and floor plan sections were constructed. The climate evaluation chart was developed at Eindhoven university of Technology (Martens, 2007). It consists of a psychrometric chart with upper and lower guidelines for temperature and relative humidity (figure 3). These limits form a (blue) evaluation area. Measurements of temperature and relative humidity falling within this area are within the guidelines for preservation of the objects. The colors of the plotted values indicate the time of season. Percentages of time the measured values are within or outside the limits are indicated in tables. The place in the table corresponds to the place in the psychrometric chart, in relation to the blue marked area (to the left, right, below or above). Fluctuations of temperature and relative humidity are indicated in histograms. The percentage of time of exceeding a certain limit of fluctuations per hour or twenty-four hours is indicated. The climate evaluation tables are based on the climate evaluation charts and consist of two types of tables. The first type of table indicates the exceeding of the upper and lower limits of air temperature and relative humidity. The indication for each room is constructed analogue to the nine value table indication in the climate evaluation chart. A division in different seasons is indicated too (figure 4). For each season the values indicate the percentage of time the measured values are within the specific area of the nine area structure. The color of the middle area is an indication of values within the guidelines and is indicated in a color scale. The second type of table gives an indication of the exceeding of maximum fluctuations for each hour and day (figure 5). Different rooms are indicated at the top of the figure. The guidelines for the maximum fluctuations are evaluated for each season. The numbers indicate the percentage of time the measured values are within the guidelines for maximum fluctuations and get a color according to the color code. The advantage of these tables in relation to the climate evaluation chart is that in one view the evaluation of the museal room of the castle can be evaluated. The third tool the climate evaluation floor section is based on the first type of climate evaluation table. For each room a division in four seasons is made to assess the air temperature and relative humidity (figure 6). The numbers indicate the percentage of time the guidelines for temperature and relative humidity are satisfied or exceeded. The judgment of both parameters is processed in two different areas in the floor plan of the room. The color of the area indicates the distance between the actual values and the guideline value. The extensive color coding is used for the assess of each room and each season. In this way the assess for each floor of the castle can be judged in a glance. A comparison for each room to another, e.g. for each orientation, is simple in this way. Figure 3. The climate evaluation chart of a museum room with explanation of the different components of the chart.

ble (type 1) with explanation of the different components (example: Tapestry room).

season during wintertime the relative humidity in these heated rooms is lower than 40 %RH (figure 8). 5 ASSESS OF THE INDOOR CLIMATE Most museum rooms in the castle are not heated. The air temperature of these rooms is below 15 o C most of the time. An exception is the summertime. The lowest values of air temperature are located in the basement. The relative humidity has the highest values in the basement (φ mean > 70 %RH). The prolonged high relative humidity values in the basement indicate risks for mould generation for the basement to be the largest. In general most unheated museum rooms in the castle have high relative humidity values (φ mean > 60 %RH) which are not beneficial for the preservation of the collection. The indoor climate of the library, the small library and the Kings room are an exception. The relative humidity in these rooms indicates values between 40 and 60 %RH (figure 7). The fluctuations of relative humidity for each twenty-four hours period are larger than 3 %. The heated rooms indicate variations in temperature too high for preservation. In the heating 5.1 Effect of visitors Heat and moist production of tourists visiting the museum rooms of Castle Amerongen affect the indoor climate. In two museum rooms this effect is studied by simulation. The simulation model HAM- Base (Wit, 2006) which is developed for the study of heat and moisture in building environments was used. The heat generation by people in the room has more effect on the decrease of relative humidity than the moisture production has on the increase of RH. The result of this effect is a decrease of relative humidity in the room. The materials of furnishing of the room have a hygroscopic nature (furniture, carpets, and curtains). In a closed empty room an increase of temperature will lead to a decrease of relative humidity. The hygroscopic materials in a room however have a stabilizing effect on RH (Padfield et al. 1996). The materials will absorb or desorb vapor from the indoor air, depending on the change in RH. This effect has been studied by simulation of the heat and moisture effects in a simulated room of the castle. An empty

not used for living. The system makes use of a measuring and control unit for temperature and RH. The heating source may be an electrical heating device. Figure 7. The relative humidity in the Library indicates values within 40-60% RH. Figure 8. The relative humidity in a heated room is lower than 40% RH in the heating season during wintertime. room was filled by different materials and different quantities of materials (figure 9). The library in Castle Amerongen has a large amount of hygroscopic materials. Most of these materials are formed by books in bookcases. The combination of these hygroscopic materials and a dehumidification apparatus lead to a very stabile indoor climate regarding relative humidity. The proximity of heated rooms near the library have a positive effect on the lowering of relative humidity in the library. In general there is a mutual effect of heat and moisture exchange between different rooms in the castle. 6 IMPROVEMENT OF THE INDOOR CLIMATE By means of two variant studies in HAMBase possibilities to improve the indoor climate were studied. 6.1 Conservation heating The first variant was a study on hygrostatic heating of the building, so called conservation heating. In this case heating is not only controlled by a thermostatic device, but also by a hygrostat. Heating will start at an upper level of RH and will stop when a lower limit is reached. In this way it is possible to control RH for the preservation of object is museum rooms. The temperature is controlled within certain limits, but is not leading for thermal comfort and has a minor importance, compared to RH. In this way it is possible that heating will continue in summertime to limit RH in the room. This kind of heating is often used in historic buildings in Great Britain which are Figure 9. The relative humidity in a simulated room (V=38 m 3 ) with six different indoor walls (S=14.7 m 2 ), moistening 30g/h, ventilation 0.2 h -1. According to the simulation study it must be possible to control RH in most museum rooms on the beletage and 1 st floor of the castle between 40 and 60%RH (figure 10). The setup adjustments were an upper limit of air temperature of 25 o C and a lower limit of 10 o C. 6.2 Floor heating The second variant of the simulation study was a floor heating system. For the basement it was decided that a floor heating system could have a posi-

tive effect to lower relative humidity in the basement. A floor heating would have a positive effect on the drying of the walls and floor. Flooding in the past lead to an increase of the moisture content of these constructions. A drawback of the use of floor heating may be an increase of salt transport to the inner surface due to moisture transport and evaporation at the indoor surfaces. 8 REFERENCES Ritmeijer, M.T.P., Castle Amerongen, indoor climate research, TU Eindhoven, Eindhoven, 2007. Dutch Msc thesis. Museums, libraries and archives, ASHRAE, ASHRAE Applications Handbook (chapter 21), 2003. De Wit, M.H., 2006. Hambase. Heat, Air and Moisture Model for Building and Systems Evaluation (Bouwstenen 100), TU Eindhoven, Eindhoven. Padfield, T., 1996. Low Energy Climate Control in Museum Stores- a postscript, ICOM-CC Conference, Edinburgh. Neuhaus, Edgar; Schellen, Henk, 2007. Conservation Heating for a Museum Environment in a Monumental Building. Performance of Exterior Envelopes of Whole Buildings X International Conference. Florida. Martens, Marco; Schijndel, Jos van; Schellen, Henk, 2007. Evaluation of indoor climates using the Climate Evaluation Chart. AIVC Conference, Lyon Schijndel, Jos van; Schellen, Henk, 2007. Application of a Combined Indoor Climate and HVAC Model for the Indoor Climate Performance of a Museum. AIVC Conference, Lyon Figure 10. The relative humidity (simulated) in a museum room without conservation heating (blue) and with conservation heating (red) during a year. 7 CONCLUSION The indoor climate of Castle Amerongen does not satisfy the museum guidelines for the preservation of valuable objects. Apart from the high relative humidity levels in most museum rooms (φ > 60%RH) the daily fluctuations are too high ( ϕ 24h > 3%). Especially the indoor climate in the basement has very high RH levels (φ > 70%RH). To improve the indoor climate in the basement floor heating is a good alternative. It has a positive effect of indoor relative humidity levels and will dry out the flooded floor and walls. Apart from this effect the heat exchange between basement and other floors will have a positive effect on the indoor climate of these other floors too. Conservation heating is a good alternative to conventional thermostatic heating. Especially for rooms where thermal comfort is not the most important factor it may lead to much more stabilized indoor climate conditions for relative humidity.