Basic information about quick steam generators/boilers System GEKA Heat Technology Gottfried Kneifel

Similar documents
WELCOME TO THE AWT REGIONAL TRAINING PROGRAM

Boiler Basics. Design and operation

Condensate Recovery and Return System SDR A

Adca Training. Part 2

SECTION Boiler Controls & Waste Heat Recovery

Reactor-Boiler and Auxiliaries - Course 433 BOILER STEAM AND WATER SYSTEMS

Kube Engineering. Industry Guide. Power Industry

CHAPTER 6. HEATING PRODUCTION EQUIPMENT AND SYSTEMS

Open System Condensate receiver tank of cylindrical. design type SDR A with highpressure

Beneficial Use of Landfill Gas for Leachate Evaporation and Power Generation

Thermal Fluid Heaters

Electronic Pellet Burner Controller NPBC-V3-1

9. Cooling Water System

Electronic Pellet Burner Controller NPBC-V3M

S. P. THERMAL SYSTEMS INC.

Steam Fundamentals. (in heating & processing applications)

Self-supporting hot water high pressure cleaner on trailer Designed for Weed Control WeedMaster TM 221

Product overview. the optimum components for every application

Volume 10 Summer Understanding Terminology Key to Treatment Program Success

Presentation On Industrial Boiler Operation And Maintenance

Water Treatment Improves Your Bottom Line DAVE PICOU WATER CARE SERVICES DIVISION JOHN SCHULTZ TEXTILE CARE DIVISON

Savile Plus. Steam Boiler. Suitable for Pressure Jet burners Oil, gas or dual fuel firing. Outputs kg/h

Strategies in Optimizing Condensate Return

9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax:

Condensate Recovery and Return System SDR A

Metropolitan. Steam Boiler. Suitable for Pressure Jet or Rotary Cup burners Oil, gas or dual fuel firing. Outputs kg/h

Boiler. Fire tube Boiler:

Development of Boiler Design

GESTRA. Product Overview. The optimum components for every application

Evaporation The process in which a liquid dissipates or emits vapor, fumes, or invisible minute particles.

PIPING SYSTEM EQUIPMENTS

GAS FIRED ATMOSPHERIC ELECTRONIC VERSION kw

MECHANICAL SCIENCE Module 2 Heat Exchangers

BOILER SYSTEM CHEMICAL TREATMENT 101

SCHNEIDER-KESSEL BERLIN

TECHNICAL MANUAL ASGX

CONDOR RAPID CONDOR RAPID/V STEAM FORCED CIRCULATION. Design pressure 11,76 bar Steam production from 45 to Kg/h

Spray Flow II cc/liter Atmospheric Deaerator. industrialsteam.com

Spray Flow II cc/liter Atmospheric Deaerator. industrialsteam.com

In the first years of the 1950 decade, the MSF system was developed by the U.S.A. navy.

BASIC BOILERS NAME :- DATE :-

Efficient Steam System Design

UNFIRED STEAM GENERATORS STANDARD EQUIPMENT

INSTALLATION AND OPERATION MANUAL

CHAPTER 3 BASIC STEAM CYCLE

QHT Manual for: SU-2A Gas Burner

GESTRA. Product Overview. The optimum components for every application

Installation, Operation and Maintenance Guide. Steam Coil Installation, Operation and Maintenance. steam coils

PART 1 - GENERAL 1.1 WORK INCLUDED

Fig.: macroscopic kinetic energy is an organized form of energy and is much more useful


Math & Physics. Complete combustion requires an Air-FuelRatio of 14.7 to 1 for combustion.

Appendix A. Glossary of Common Terms

Fuel-Fired Vertical Tubeless Boilers

THERMODYNAMICS STEAM P7690 AND STEAM BENCHES CUSSONS TECHNOLOGY LABORATORY RECOMMENDATION

FUEL-FIRED VERTICAL TUBELESS BOILERS

Protective Chemistry for Steam Boiler Wet Layup posted to DPS client area on:

Attention is drawn to the following places, which may be of interest for search:

Efficiency of Application the Condensing Heat Utilizers in the Existing Boiler's Unit in Heat Power Station

Typical damages to Boilers & Economizers

Tray ST5. Tray Type Deaerator Pressurized.005 cc/liter. industrialsteam.com

ALDRICH COMPANY THREE PASS FIRETUBE BOILER CLASSIC SERIES OPERATING & MAINTENANCE MANUAL

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

A CASE OF BOILER FAILURE DUE TO OVERSIZING OF BOILER FEED PUMP

Diocese of Cleveland Facilities Services Corporation

Boiler Draft Equipment

Products Solutions Services. Energy Solutions. Food & Beverage industry. Slide 2

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM

Boiler Basics: Design & Application Differences. Presented by Steve Connor July 30, 2014

southbend A MIDDLEBY COMPANY INSTALLATION AND OPERATION MANUAL CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) GAS BOILERS MODELS:

Trade of Plumbing. Module 2: Domestic Hot and Cold Water Service Unit 10: Hot Water Supply Phase 2

PUROTAP easy. Installation Function Operation Service. fast efficient safe. Demineralised heating water perfect for every system

PUROTAP leader. Installation Function Operation Service. Demineralised heating water perfect for every system

Understanding Process Vacuum for Process Improvement

How to Select and Size Enclosure Thermal Management Systems: White Paper, Title Page. How to Select and Size Enclosure Thermal Management Systems

TMCI Padovan Evaporators

2x58 MW Coal Fired Power Plant at Mauritius

Technology Menu Commercial Laundry

Deaerators for Industrial Applications

Evaporation System: Types and Design Aspects

INDUSTRIAL RANGE ACCESSORIES AND COMPONENTS

Technical guide VITOMAX 200 HS. Notes on design and operation. Vitotec technical guide folder, register 1. File in:

GESTRA Valves for Pure and Sterile Steam Systems. Intelligent solutions for sensitive processes

The equipment and materials shall be designed and constructed in accordance with the ASME code section I 2001 ED A02 and Chinese Standards.

VIESMANN VITOROND 100. Datasheet Part numbers and prices: see pricelist VITOROND 100. Cast iron low temperature oil and gas fired boiler.

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215)

Solutions to Pollution

ENERGY RECOVERY SOLUTIONS. Recover wasted energy to increase efficiency and save money immediately.

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!!

REGISTRATION EXAMINATION, NOVEMBER 2016 LICENSED GASFITTER QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

Silhouette. Feedwater Heater. Boiler Feedwater

So old fashioned... As the combustion chamber is completely room sealed, it does not release any smells and does not dirty.

Forced Draft Boiler Flue Gas Venting: Problems & Solutions. Presented by Steve Connor and Patrice Gouin January 27, 2016

SECTION PLUMBING EQUIPMENT

Study and Design Considerations of HRSG Evaporators in Fast Start Combined Cycle Plants. Govind Rengarajan, P.E.CEM, Dan Taylor

ROTARY DRYER CONSTRUCTION

Multifunction pump for handling gaseous liquids in process engineering

CRYOGENIC PRODUCTS SEB Series Trim Heater

Transcription:

Basic information about quick steam generators/boilers System GEKA Heat Technology Gottfried Kneifel 1. Definition The term quick steam generator or boiler is used in the TRD 001, point 4.4 (technical rules for pressure vessels) for steam generators in accordance with the once-through system. These boilers are described in the TRD 401, point 2.1 as pass through steam generators. Due to the construction pass through steam generators do not have a defined water level. Groups acc. TRD technical rules for pressure vessels: group I steam generators with max. 10 l water content (DE-Z 50) group III steam generators with max. 50 l water content DE-Z 150 up to DE-Z 600, DE-ZUK 100) group IV a. steam generators with max. 150 l water content (DE-Z 800 and DE-Z 1100, DE-ZUK 150 and DE-ZUK 340) b. steam generators with max. 350 l water content (DE-Z 1500 and DE-Z 1750, DE-ZUK 550) c. steam generators with water content over 350 l (SDE-Z 2300, SDE-Z 2600, SDE-Z/2-4000, SDE-Z/2-6000, SDE-Z/2-8000 and DE-ZUK 750) Conformity Assessment Procedure acc. PED 97/23/EC: Cat. I and II with EC-design examination or type examination, Cat. III and IV with EC-type examination. Choice of modules acc. annex II PED 97/23/EC Equipment, Installation and Running of Steam Generators: EC: see national rules acc. PED 97/23/EC Overseas: acc. TRD or national law. Our offers for standard boilers include at least the equipment demanded by TRD. Further equipment on request. 1/8

2. Construction A. System Benson The quick steam generators system GEKA heat technology type DE-Z and SDE-Z are single tube once-through boilers. These boilers consist of a furnace built by tube cylinders. In this tube cylinder the burner - fuel oil, natural gas or dual fuel burners with fast automatic control can be operated without direct contact to the furnace. After this 1 st pass there s a 2 nd and 3 rd pass the convection heating surfaces consisting of a second tube cylinder mounted coaxial to the furnace tube cylinder. The convection tubes are built in series. The water is pumped in the entrance of the tube system and then almost entirely evaporated until the exit of the tube system. This system is called Benson boiler and was already patent pending in 1904 (torpedo boat boiler). The first GEKA (Gottfried Kneifel) quick steam generator type SDE-150 was manufactured in 1957 in Berlin and then running in a dry cleaner s for more than 35 years. By that time only two American import boilers were available on the German market: Vapor boilers - consisting of only 2 coaxial cylinders - and Clayton boilers. Clayton boilers are no once-through boilers but forced circulation boilers (La Mont/Velox system see B.) but also with a single tube system with 5 times water circulation and equipped with a separate steam drum. The same time the first Kärcher steam generators with a capacity of 150 up to 800 kg/h came on the German market. There the evaporating system also consists of 2 coaxial tube cylinders. The small tube sizes of this Kärcher-types, the Vapor and the Clayton boilers lead to furnace load two or three times higher than the GEKA boilers. Under these preconditions the allowed flue gas emissions of the EC couldn t be reached. Due to the construction especially the CO-emissions were too high. For these reasons Kärcher stopped the production. B. System La Mont/Velox Our quick steam generators type DE-ZUK were engineered from the types DE-Z and SDE-Z. They are constructed according to the forced circulation system. This kind of boilers need circulation pumps and the system is connected non-lockable with the steam drum. Both tube cylinders are flowed from the top to the bottom therefore the system can be operated in emergency service even in case of malfunction of the circulation pumps. The La Mont system can t reach unsteady flow. These types of quick steam generators are only suitable for hermetically closed condensate systems up to an operational pressure of max. 10 bars (190 C). The advantage is the hermetically closed system no feedwater treatment is needed. The system is imposed with nitrogen as inert gas therefore the feedwater does not need further chemical dosing. 2/8

This type of quick steam generator is especially suitable for heating single heat consumers in a hot water circulation system (see types RDE). Heat Load The furnace of our types DE-Z, SDE-Z and DE-ZUK is built by the tube cylinders. The average heat load of our quick steam generators is less than 100 kw/m². - The diameter of the furnace is approx. 2 x larger than the largest flame diameter - The length of the furnace is 10% larger than the length of the flame. - The average load of the heating surface is approx. 25-26 kw/m². The inner heat transmission coefficient of once-through boilers and forced circulation boilers depends on the flow rate of the fluid (water, hot water, water vapor or steam). To reach a high inner heat transmission coefficient αi the diameter of the tube should be as small as possible. On the other hand the flow resistance raises with the flow speed to the second power. In addition to that the length of the tube cylinder depends on the heating surface and the steam capacity. So the flow resistance raises from 1 to 2 bars (type DE-Z 50) up to 25 30 bars in larger quick steam generators (type SDE-Z 2600, SDE-Z/2-4000 and 8000). The tube wall temperature excursion in a quick steam generator at steady-state operation level is significant lower than in large water-tube boilers. For our quick steam generators we found the following flow rates at 10 bars working pressure: water water vapour (x = 0,5) steam (x = 0,95) 0,7 to 1,4 m/sec. 35 m/sec. 70 to 80 m/sec. 3. Pure Steam or Clean Steam Generators Due to the regulations of the new DIN EN 285 the demand for clean steam generators raises significant. Our clean steam generators type RDE are indirectly heated heat exchanger supplied by primary steam or hot water. For primary circuit we recommend our quick steam generators with hermetically closed condensate or hot water system. The tube bundle and the case of pure steam generators are manufactured from highquality stainless steel. For more information please see our product information type RDE. 3/8

4. operating status Steady State Flow Status At steady flow status the amount of feedwater is vaporized at the same time and lead out at the steam exit as mass flow with same size. Unsteady Flow Status Before starting the burner the entire tube system of the quick steam generator is filled with water. The flow speed ensures the cooling of the evaporating tube system. Therefore the unsteady flow status is not problematic in our single tube once-through boilers type DE-Z and SDE-Z. In forced circulation boilers type DE-ZUK there s unsteady flow status possible because both tube cylinders are flowed from the top to the bottom. After an automatic stop of the quick steam generator it must be ensured that the steady state flow status is reached again before automatic restart by a short lead time of the pumps. The steady status is reached again within 2-3 sec. by smaller quick steam generators with a tube length up to 100 m. For larger steam generators (type DE-Z 800 and larger sizes) a flow control is installed. When operating the quick steam generator in vertical design parallel to a steam system or two vertical quick steam generators parallel, the first boiler could be operated with a closed return valve in stand-by circuit until the second quick steam generator reaches it s working pressure. But in that case the flow at the evaporating area tends to 0 and a local overheating of the tube wall could take place. Within 30 to 50 sec. tube wall temperatures up to 500 or 600 C could be reached. At this temperature catalytic-thermal cracking of the water steam already happens. In this overheating areas perforations due to oxygen inducted corrosion were found. We therefore manufacture larger quick steam generators only in horizontal design because condensing water remains in each single tube bend. When restarting the system the steady state flow status is reached within short time. 5. Automatic control Automatic control is effected by steam pressure switch. Except type DE-Z 50 all our quick steam generators are 2-stage controlled. Controlling is made by rate 40:60%. Safety Devices (see also P+I diagrams): 1. flue gas thermostat 2. steam thermostat with PT 100 3. electronic steam temperature limiter with contact and PT 100 4. flow control on water in AND steam out line (see flow control above) 5. pressure limiter 4/8

The flue gas thermostat is a reliable device against dry-running because the flue gas temperature raises spontaneously in case there's no water in the evaporating tubes. Flow Control The volume of the steam is measured by a metering orifice accordingly DIN EN ISO 5167 with a differential pressure manometer. In case of low flow volume (low differential pressure) the burner will be automatically switched of. During this process the feedwater pump is operated with max. rpm. After the selected time of e. g. 2 to 3 min. the burner starts again. In case the steam volume flow isn't reached within the next 30 to 60 sec. the cycle starts again. This process continues 3 times, in case of further lack of steam volume flow the quick steam generator is stopped automatically. 6. Accessories The accessories are usually delivered in module design, ready for operation. The necessary components are mounted on one or two frames ready for operation - on customer's demand and considering the given space at site. The modules are equipped with inner tubing and wiring. This means lower cost for mounting and installation at site. Main demands on manufacturing and choice of equipment: - easy operation and mounting - possibility of combining modules - easy maintenance and repair 6.1 Water Steam Separator, Steam Accumulators and Blow-Down Vessel Due to the construction the forced circulation quick steam generator (system Benson) is producing saturated steam with a humidity of 2 to 7%. In this remaining humidity there is concentrated remaining salt from the water treatment and remaining ingredients of the chemical dosing unit. Depending on the given status of operation it has to be decided how to drain this water: When starting the boiler the drain water should be dumped. The drain valve should be opened until a temperature of 40 to 50 C will be reached to dump the water into the sewage system. At higher temperatures an automatic draining is effected by a blowdown vessel (water-steam separator). Normally this drain water could be passed to the feedwater or condensate tank because it contains important chemicals from the dosing unit that should be saved. 5/8

In case of high dissolved solid content of the feedwater (high hardness of untreated water) the drain water could be treated in 2 ways: - drain water will be passed through a condensate heat exchanger for heating purposes - drain water will be passed though a blow-down vessel (water steam separator) and mixed with cold fresh water before dumping in the sewage system at 40 C. The water steam separator also can be constructed as larger vessel for steam accumulation in case of fluctuating steam demand or to cover highest consumption of steam. When starting the system the (descending) steam accumulator is filled with water by the feedwater pump of the steam generator. The steam produced by the steam generator then will be injected into the steam accumulator to heat up the system to working temperature and pressure. The blow-down vessel consists of a cylindric casing with an overrun towards the sewage and an injector for the cold fresh water. The vessel also can be equipped with automatic controlling devices (thermostat and magnetic valve for fresh water). 6.2 Feedwater and Condensate Tanks/Deaerators The feedwater and condensate tanks for our quick steam generators are made from stainless steel 1.4301. The water level is controlled by electrodes with up to 5 possible switches. This enables to choose the water level in the feedwater tank. In case of high life-steam demand the feedwater tank is filled with water up to a high level, in case of high condensate return the fresh feedwater is filled in at the lowest level allowed. HSK has improved the deaeration of the feedwater on the highest level by using jet-steam injectors. This jet-steam injector is mixing the feedwater in the tank in a very fast way, so that each water molecule is heated up to 85-90 C. This process deaerates the non-condensable parts of the gas like oxygen and carbon dioxide. This process is also called stripping. This stripping ensures deaerated feedwater within minutes after starting the quick steam generator. This system of degassing where the feedwater tank is constructed for unpressurized status is equally good as the system of pressure degassing. At 85 C there's less than 0,1 mg remaining oxygen. In addition the unpressurized degassing has higher efficiency from the economical and energetic point of view. In case of higher condensate temperatures than 90 C the feedwater has to be cooled down to prevent the water boiling up in the tank and to protect the ceramic pistons of the feedwater pumps. 6/8

In smaller units a cooling grill has to be installed. Cooling down is effected with raw water. For middle size units we recommend a condensate heat exchanger, mounted in the pressure line from the feedwater pump to the quick steam generator. In large systems we recommend installation of a separate condensate tank where the treated feedwater from the Na-cation exchanger is passed into. From there the treated feedwater and condensate is pumped into the feedwater tank/deaerator. 6.3 Feedwater Treatment For feedwater treatment we recommend Na-cation exchanger in single or double units. To save costs and for easy operation and maintenance we prefer manual operated Na-cation exchangers for smaller units. On the other hand the manual system requires permanent maintenance and daily control. For larger units we recommend automatic operated double Na-cation exchangers. with hardness sensor. The Na-cation exchanger softens the water to 0,1 dh. The chemical dosing unit has an additional effect of softening the water. Since introducing the fully automatic operated Na-cation exchangers damage of the tube system by boiler scale is no longer a problem. For operation of the cation exchanger a sufficient pressure of the raw water is essential. The raw water also has to be clean and free of suspended matters. For operation of once-through boilers (system Benson) - also with hard raw water - no demineralized water is needed, except high steam quality is required. No further reducing or leading is taking place than the produced steam contains at 5% remaining humidity. Regarding forced circulation boilers (system La Mont/Velox) the operating conditions are vice versa. In case of high demands on the steam quality (salt content 20 to 40 µs) a reverse osmosis unit for producing demineralized water has to be installed. 7/8

6.4 Chemical Dosing Unit The treated feedwater is slightly subacid (ph < 7). For operation of quick steam generators the feedwater should not have less than ph 10 or 11. For correction solvent water with trisodium phosphate (T.S.P.) has to be added (ca. 30-50 mg/m³ raw water). Except alkalinization the T.S.P. has the important function to cover the steel of the inner tubes with iron phosphate to get resistant against oxygen induced corrosion. Further softening of the feedwater is an additional effect. The dosing pump is operated by a float switch timer regulating the amount of incoming water. In larger units the dosing pump is controlled by a water meter with pulsor. 6.5 Firing/Heating of Boiler Steam generators have to be operated with burners with fast automatic control. Therefore only fuel oil, natural gas or dual fuel burners are suitable. Our steam generators are normally equipped with Weishaupt burners. On customer's demand we can offer suitable burners of other manufacturers. For more information on our products and service please go to our homepages www.quicksteamgenerators.com last updated October 2004 8/8