Pipe Sizing Table. Hydraulic Load Served (fixture units)

Similar documents
Read Only Document Not For Distribution

Sanitary Drainage Systems

Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016

PLUMBING INSTALLATIONS

2. Sanitary Plumbing General Installation Requirements

STACKS AND STACK VENTS

CHAPTER VI BUILDING PLUMBING

CHAPTER 31. VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R

CHAPTER 10 TRAPS AND INTERCEPTORS

Read Only Document Not For Distribution

REGISTRATION EXAMINATION, NOVEMBER 2017 TRADESMAN PLUMBER QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

PLUMBING REQUIREMENTS

2016 Plumbing Supplemental Plan Review List

CHAPTER 9 VENTS. run undiminished in size and as directly as possible from the building drain through to the open air above the roof.

CHAPTER 9 VENTS SECTION

Building Utilities 1 Plumbing and Sanitary Systems

REGISTRATION EXAMINATION, JUNE 2015 LICENSED PLUMBER QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

CHAPTER 10 TRAPS AND INTERCEPTORS TABLE 10-1 HORIZONTAL LENGTHS OF TRAP ARMS (EXCEPT FOR WATER CLOSETS AND SIMILAR FIXTURES) 1, 2

Level I Chapter 1 Worksheet

PLAN REVIEW SUBMITTAL GUIDE

STUDENT NOTES Plan, size and layout sanitary pipe work and fixtures

MATERIALS Traps TRAPS. No. IPC IRC Description

APPENDIX J ILLUSTRATIONS

1 Exam Prep Plumber s Handbook Tabs and Highlights

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- PLUMBING

ICP Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

GIANT. Little. Guidelines for Sizing. Pump Company. Sewage Pumps & Systems. Sewage Pumps & Systems

APPENDIX L ALTERNATE PLUMBING SYSTEMS

CUSTOMIZED TEACHER ASSESSMENT BLUEPRINT PLUMBING. Test Code: 5924 Version: 01

Test Code: 8117 / Version 1

CRAFTSMAN EXAMINATION, NOVEMBER 2009 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

CHAPTER 10 TRAPS AND INTERCEPTORS The vent pipe opening from a soil or waste No more than one (1) approved slip joint

CHaPTeR 10. TRaPS and INTeRCePTORS. Table 10-1 Horizontal lengths of Trap arms (except for water closets and similar fixtures)*

Wastewater. Guidelines for Sizing mscdirect.com. Call MSC today to learn about the latest LittleGiant products.

2009 IPC ,IMC Q &A ANDIFGC

Land Use and Environmental Service Agency (Code Enforcement) Plumbing 2010

Read Only Document Not For Distribution

ProVent Systems Plumbing Fundamentals. Educational Literature. Comparison of ProVent Design Rules and The International Plumbing Code

REGISTRATION EXAMINATION, NOVEMBER 2014 LICENSED PLUMBER QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

Plumbing. Definitions. Background Factors. Air Chambers. Air Gap (Drainage System) Air Gap (Water Distribution System) Air Lock.

Special Requirements For Health Care Facilities

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

SUBCOURSE EDITION EN5155 US ARMY ENGINEER SCHOOL CLEAR WASTE SYSTEM STOPPAGES PLUMBING VI

Perkins Statewide Articulation Agreement. Documentation item: Secondary Competency Task List Coversheet

plumbing for greywater

WATER HAMMER ARRESTORS & MISC. SPECIALTIES

TABLE OF CONTENTS. CHAPTER 2 DEFINITIONS General Applicability Definition of Terms General...

GARCIA GALUSKA DESOUSA Consulting Engineers

ENERGY MARKETING SERVICES

REGISTRATION EXAMINATION, NOVEMBER 2017 TRADESMAN PLUMBER ANSWER SCHEDULE

A GUIDE TO PASSING THE PLUMBING EXAM

CHAPTER 10 TRAPS AND INTERCEPTORS

Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire

2. All necessary storm and sanitary pumps shall be tied into emergency power, and sump levels shall be monitored electronically through the B.A.S.

2015 UPC CODE - CHAPTER 8 INDIRECT WASTES

Union County Vocational - Technical Schools Scotch Plains, New Jersey

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

Plumber Level 3 Rev. May 2011

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

1. You are required to use a 20 foot ladder placed up against a building that is 40 high. At what

Trade of Plumbing. Module 2: Domestic Hot and Cold Water Service Unit 11: Sanitary Appliances Phase 2

Is Sewer Gas Giving Your Customers the Wrong Impression?

TRUMAN STATE UNIVERSITY PRESIDENT S RESIDENCE RENOVATION

The following test is Continuing Education for: Master Plumbers, Journeyman Plumbers, UDC Plumbing Inspectors, and Commercial Plumbing Inspectors.

PLUMBING FIXTURES Reserved

Plumbing Technology/Plumber CIP Task Grid

TABLE OF CONTENTS. Part I Administrative... 1

Denotes a new question! Denotes a revised/revisited question. September 2009 General:

REGISTRATION EXAMINATION, NOVEMBER 2011 CERTIFYING PLUMBER ANSWER SCHEDULE

BUILDING MATERIALS EVALUATION COMMISSION (BMEC) AUTHORIZATION REPORT

TABLE OF CONTENTS Limitations of Authority...6 Table Plumbing Permit Fees...7

Methods of Venting Plumbing Fixtures and Traps in the 2018 IPC

Matrix of changes for the National Standard Plumbing Code July 2013

SAFETY PLUMBING PACKAGES. Quality Products & Value Packages SUSTAINABILITY. Residential Solutions ANTI-SCALE SYSTEMS FIRE PROTECTION

1 Exam Prep Plumbing State Contractors Practice Exam 2

Lecture : Introduction to building services I - Plumbing & Drainage Services 22 September 2016

TREVI BLEND SINGLE LEVER SHOWER VALVES. INSTALLER After installation pass to user for future reference

Tighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance

CRAFTSMAN EXAMINATION, JUNE 2007 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

Drain and Vent Systems 6 CE Hours

TABLE OF CONTENTS. CHAPTER 2 DEFINITIONS General Applicability Definition of Terms General...

Chapter 4: Fixtures, Faucets & Fittings:

Building and Safety Division Civic Center Dr, Bellflower, CA, (562) x

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter X X X Adopt Entire Chapter as amended (amended sections listed below) X X X X X X X

Schedule of Fees Schedule B

2015 UPC Chapter 8 Indirect Wastes RV

B. Shop Drawings: Include diagrams for power, signal, and control wiring.

The following test is Continuing Education for: Master Plumbers, Journeyman Plumbers, UDC Plumbing Inspectors, and Commercial Plumbing Inspectors.

Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B POTENTIAL CHANGE TO ONTARIO S BUILDING CODE:

ENERGY EFFICIENCY AFTER DECEMBER 31, 2016

Query: Do water heater installations and replacements require a plumbing license, permit, and inspection in the state of Colorado?

FEATURES. Other Fed-Flush Arrangements

PLUMBING CURRICULA OUTLINE

4. Committee Member presentation of New Items for consideration by the committee (Written ideas with discussion, maximum 5 minutes each.

PLUMBING FIXTURES CHAPTER 27

Tips from the Drain Cleaning Pro s

WARRANTY POLICY & RECOMMENDED MAINTENANCE

BACKFLOW PREVENTION GUIDE FOR COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL DEVELOPMENTS

A. This Section includes the following emergency plumbing fixtures:

Bill de Blasio, MAYOR. build safe live safe. Rick D. Chandler P.E., COMMISSIONER

Transcription:

MODULE 1 INTRODUCTION Notes: A Pipe Type Horizontal branch Pipe Sizing Table Hydraulic Load Served (fixture units) Size (in.) Code Reference 2 + 1.5 = 3.5 2 7.4.9.1.(1) B Soil stack 13.5 + 13.5 = 27 3 Table 7.4.10.6. C Soil stack 27 + 13.5 + 13.5 = 54 4 7.4.9.2.(3) D Building drain 54 + 5 = 59 + 13.5 = 72.5 4 7.4.9.4.(1) E Vent stack 54 + 13.5 = 67.5 + 5 = 72.5 3 Table 7.5.8.4. END OF MODULE 1.18 PLUMBING - ALL BUILDINGS 2012 QUEEN S PRINTER FOR ONTARIO 2013

MODULE CONTENTS PAGE LEARNING OBJECTIVES... 2.4 INTRODUCTION... 2.4 DRAINAGE TERMS... 2.4 FIXTURE UNITS AND FLOW RATES... 2.8 2 HYDRAULIC LOADS... 2.11 SIZING THE SANITARY DRAINAGE PIPING...2.12 SIZING PROCEDURE...2.14 CLEANOUTS AND MANHOLE REQUIREMENTS... 2.17 CONSTRUCTION OF A MANHOLE... 2.22 PRIVATE SEWER REQUIREMENTS... 2.24 PROTECTION FROM BACKFLOW... 2.24 DIRECT AND INDIRECT CONNECTIONS... 2.27 PUMP DISCHARGE... 2.32 TESTING... 2.33 STORM DRAINAGE SYSTEMS... 2.36 EXAMPLE SIZING STORM DRAINAGE PIPING... 2.38 MODULE 2 QUIZ... 2.43 QUEEN S PRINTER FOR ONTARIO 2013 PLUMBING - ALL BUILDINGS 2012 2.3

SIZING THE SANITARY DRAINAGE PIPING The OBC includes tables in Subsection 7.4.10. that show the maximum hydraulic loads horizontal and vertical drainage pipes can carry. It is important that you are able to interpret these tables in order to calculate pipe sizes and verify pipe sizes. Three tables in Subsection 7.4.10. show the maximum hydraulic loads for horizontal and vertical sanitary drainage pipes. These tables deal with horizontal sanitary drainage pipes: those that are less than 3 inches, and those that are 3 inches or larger where the slope of the pipe must be known. Review Subsection 7.4.10 and complete Exercise 2-5. EXERCISE 2-5 Fill in the table on the next page as a summary of the OBC sizing tables for sanitary drainage piping. List the information that is needed to size the pipe. OBC Tables for Sizing Sanitary Drainage Piping Table 7.4.10.6. Type of Pipe Table Applies To Information Required to Use Table 7.4.10.7. 7.4.10.8. STOP 2.12 PLUMBING - ALL BUILDINGS 2012 QUEEN S PRINTER FOR ONTARIO 2013

Washroom C: 2-1¼ lavatories - fixture units 2 bathtubs - fixture units 2 flush tank water closet - fixture units 2 shower stalls - fixture units Total Hydraulic Load fixture units 2. What is the minimum slope of the horizontal drainage pipes? 3. Determine Minimum Size of Branches Branch A @ 1:100 slope: Reason: Branch B @ 1:50 slope: Reason: Branch C @ 1:50 slope: Reason: Branch D @ 1:100 slope: Reason: 2.16 PLUMBING - ALL BUILDINGS 2012 QUEEN S PRINTER FOR ONTARIO 2013

TESTING The OBC requires after a section of drainage system has been roughed in and before any piping is covered, a water or an air test must be conducted. However, Sentence 7.3.6.1.(6) states a sewer lateral extension need not be tested and inspected if the sewer lateral extension was constructed, tested and inspected at the time of installation of the public sewer. A sewer lateral extension is defined in Article 1.4.1.2. of Division A of the OBC; 2 Sewer lateral extension means the portion of a storm building sewer or sanitary building sewer that extends from the public sewer up to 1.5 m into the property. EXERCISE 2-13 Subsection 7.3.6 states which tests may be done on the drainage and venting system. Read through this Subsection; spend five minutes discussing the following questions with your group. Use your flipchart. 1. Which of the four tests outlined in this Subsection are suitable during inspection of drainage and venting system? 2. Which tests must be done at the wastes and stacks inspection? QUEEN S PRINTER FOR ONTARIO 2013 PLUMBING - ALL BUILDINGS 2012 2.33

MODULE 2 QUIZ 1. A Fixture unit (as applying to the drainage system) is a) unit of measure based on the rate of discharge b) unit of measure based on the rate of supply c) a plumbing appliance d) a plumbing receptacle 2 2. Sanitary sewage means liquid or water borne wastes of: a) industrial or commercial origin b) domestic origin c) toilet or other bathroom waste d) residential occupancies 3. When can a minimum sized soil pipe be connected to a smaller drainage pipe? a) when the discharge is not from a sanitary unit b) when a horizontal branch draining 3 water closets connects to a 3 soil stack c) connection of any horizontal branch to a vertical stack d) a connection to a smaller sized drainage pipe is not permitted 4. The maximum number of water closets that may be served by a 3 horizontal branch is:: a) 1 b) 2 c) 3 d) 5 QUEEN S PRINTER FOR ONTARIO 2013 PLUMBING - ALL BUILDINGS 2012 2.43

9. The sequence of valves on a discharge pipe from a sewage ejector is: a) union, check valve, shut off b) shut off, union, check valve c) check valve, shut off, union d) it doesn t matter as long as all three are installed 2 10. The maximum loading on horizontal drainage pipe is: a) 30% b) 29% c) 65% d) 100% 11. What is the minimum one size vertical stack serving 4 storeys with the following loading: First Floor 6 Fixture units Second Floor 6 fixture units Third Floor 4 fixture units Fourth Floor 4 fixture units QUEEN S PRINTER FOR ONTARIO 2013 PLUMBING - ALL BUILDINGS 2012 2.45

Stack No. Fixtures F.U.s Total F.U.s Soil Stack 1 6 - bathroom groups 6 - kitchen sinks Waste Stack 1 6 3 in. floor drains 6 1 ½ in auto washers Soil Stack 2 3 bathroom groups 3 kitchen sinks Waste Stack 2 3 2 in. floor drains 3 1 ½ in. auto washers Soil Stack 3 2 bathroom groups 2 kitchen sinks 2 2 in. floor drains 2 1 ½ auto washers 2.46 PLUMBING - ALL BUILDINGS 2012 QUEEN S PRINTER FOR ONTARIO 2013

Location Fixture Units/Sizing Considerations Pipe Size A 22 fu, 2WCs B 10.5 fu, no WCs, Table 7.4.10.6. C 22.5 fu, 3WCs D 27 fu, no WCs, but 3 in floor drains require 3 in. drain 7.4.9.1.(1) E 45 fu, 6 WCs, 7.4.9.2.(3) not yet applicable, max 2 WC per floor so 3 in. horizontal branches, Table 7.4.10.6. requires 3 in. 1 22 fu, 2 WCs, building drain min 4 in. 7.4.9.4.(1) 2 B+C = 33 fu, 3 WCs, downstream of 3rd WC fixture drain, 7.4.9.2.(2) 3 A+B+C = 55 fu, 5 WCs, building drain min 4 in. 7.4.9.4.(1), also not lesser than upstream drainage pipes 7.4.9.1.(1) 4 D+E = 72 fu, 6WCs, 3 in. pipes upstream, Table 7.4.10.8 5 A+B+C+D+E or 3+4 = 127 fu, 11 WCs, building drain min 4 in. 7.4.9.4.(1), 4 in. ok Table 7.4.10.8. 2 QUEEN S PRINTER FOR ONTARIO 2013 PLUMBING - ALL BUILDINGS 2012 2.47

MODULE 3 TRAPS or other fixture, so that water from that fixture will feed into the floor drain trap. Prefabricated floor drains are often equipped with tapping to connect to a primer line. Leakage of a trap can also cause trap seal loss. The leak could be caused by a number of things. Improper installation, clean out plug not tightened, etc. High winds blowing over the stack terminal can cause rapid fluctuations of air pressure within the drainage and vent system. This causes oscillating (back and forth rocking) movement of trap seals with some spillage into the waste pipe each time the water slops up and over the trap weir. This is usually a temporary condition due to weather. There is not much that can be done other than relocating the stack terminal. Capillary action is caused by suspension of a foreign object such as hair, a rag, string or lint into the trap seal extending over the trap weir. It soaks up water until it drops from the end reaching into the outlet of the trap. Momentum is caused where a vertical section of fixture outlet pipe is excessive. The maximum developed length of a fixture outlet pipe shall not exceed 1 200 mm. It is possible to pull the trap seal if the vertical distance is more. 3.18 PLUMBING - ALL BUILDINGS 2012 QUEEN S PRINTER FOR ONTARIO 2013

MODULE 4 VENTING Step 1. Determine the hydraulic loads of each fixture. Find these from Table 7.4.9.3. Lavatory Basin 1 fixture unit Kitchen Sink 1.5 fixture units 2 head shower 3 fixture units WC (flush tank) 4 fixture units Step 2. Determine the hydraulic load carried by the wet vent. The wet vent does not drain the water closet, so this is not included in the calculation, as per Sentence 7.5.8.1.(2). But the wet vent must consider the hydraulic load of the kitchen sink that drains to the trap arm of the water closet as per 7.5.2.1.(f). Wet vent hydraulic load = lavatory + lavatory + 2-head shower + 2-head shower + kitchen sink = 9.5 fixture units Step 3. Size the wet vent. 4 From Table 7.5.8.1., the wet vent is serving a water closet, so Column 3 is used. Since the hydraulic load is 9.5 fixture units, the wet vent pipe size is 4 in. Step 4. Determine the hydraulic load served by the continuous vent. Use only the hydraulic load that is wet vented as per Clause 7.5.2.1.(1)(g). The kitchen sink is separately vented, and is not included in the calculation. Continuous vent hydraulic load = lavatory + lavatory + 2-head shower + 2-head shower + flush tank WC = 12 fixture units Step 5. Size the continuous vent. From Table 7.5.8.3., a hydraulic load of 12 fixture units and a length of 4 metres will be adequately served by a 1 ¼ in. vent pipe. However, since the wet vent serves a water closet with a 3 in. trap, the continuous vent is required to be 1 1/2 in. QUEEN S PRINTER FOR ONTARIO 2013 PLUMBING - ALL BUILDINGS 2012 4.49

MODULE 4 VENTING Note that the branch drain downstream of the wet vent is sized based on the hydraulic load served. Branch hydraulic load = 2 lavatories, 2 2-head showers + kitchen sink + flush tank WC = 13.5 fixture units. The minimum size for this pipe is 3 inches based on Table 7.4.10.8. However 7.4.9.1.(1) prohibits a drainage pipe to drain to one of lesser size, so the branch drain downstream is required to be 4 in. STOP EXERCISE 4-19 Calculate the size of the wet vent and the continuous vent serving the wet vent in the Figure 4:24. The continuous vent is 4 metres long. The lavatories have 1 1/4 in. traps. CONTINUOUS VENT LAVATORY LAVATORY CONTINUOUS VENT WET VENT KITCHEN SINK 2 HEAD SHOWER BRANCH 2 HEAD SHOWER WET VENT WC WITH (FLUSH TANK) FIGURE 4:24 SIZING A WET VENT AND CONTINUOUS VENT (EX.4-19) Same as 4-18, except the kitchen sink is now wet venting the WC, so there are now 2 wet vents. Lavatory Wet Vent Wet vent hydraulic load = lavatory + lavatory + 2-head shower = fixture units. From Table 7.5.8.1., the wet vent is not serving a water closet, so Column 2 is used. Since the hydraulic load is 5 fixture units, the wet vent pipe size is in. 4.50 PLUMBING - ALL BUILDINGS 2012 QUEEN S PRINTER FOR ONTARIO 2013

MODULE 5 WATER SUPPLY SYSTEM This module illustrates how to use the NPC sizing method to size a water pipe system. STOP DRINKING WATER SYSTEMS Potable water systems are supplied by drinking-water systems, a term that has the same meaning as defined in the Safe Drinking Water Act, 2002: drinking-water system means a system of works, excluding plumbing, that is established for the purpose of providing users of the system with drinking water and that includes, (a) any thing used for the collection, production, treatment, storage, supply or distribution of water, (b) any thing related to the management of residue from the treatment process or the management of the discharge of a substance into the natural environment from the treatment system, and (c) a well or intake that serves as the source or entry point of raw water supply for the system. 5 Sentence 7.2.10.17(1) of the OBC requires all drinking water treatment systems or devices to be certified to CAN/CSA-B483.1, Drinking Water Treatment Systems within a plumbing system (i.e. NOT in a drinking water system). Examples of drinking water treatment systems or devices are; Reverse osmosis Ultra violet lights OBJECTIVES AND FUNCTIONAL STATEMENTS The objectives of the 2012 OBC are set out in Division A, Sentence 2.2.1.1(1). Some key objectives linked to potable water systems and water supply pipe sizing are listed below. EXERCISE 5-1 Complete the following exercise by filling in the blanks, then discuss your answers with your group. The first objective is completed as an example. QUEEN S PRINTER FOR ONTARIO 2013 PLUMBING - ALL BUILDINGS 2012 5.5

MODULE 5 WATER SUPPLY SYSTEM 9. The maximum permitted single flush cycle water closet cannot be more than 4.8 Litres if it serves a) an assembly occupancy b) a residential occupancy c) a business and personal services occupancy d) an industrial occupancy 10. Where the hot water supply is controlled by a master thermostatic-mixing valve, the shower valves: a) must be pressure-balanced valves b) must be thermostatic-mixing valves c) must be either pressure-balanced or thermostatic-mixing valves d) do not require to be either pressure-balanced or thermostatic-mixing valves 11. Copper joints using compression type fittings: a) must be used under a building b) must be used within a building c) must not be used underground outside a building d) must not be used under a building END OF MODULE 5.42 PLUMBING - ALL BUILDINGS 2012 QUEEN S PRINTER FOR ONTARIO 2013

MODULE 6 FITTINGS AND FIXTURES 9. In a dwelling unit, an adequate supply of service hot water with a temperature range from a) 40 C to 60 C b) 45 C to 60 C c) 49 C to 60 C d) 40 C to 49 C 10. Normally closed backwater valves are permitted to be installed on: a) a building sewer b) a horizontal branch c) a building drain d) no drainage piping; backwater valves are not permitted to be normally closed END OF MODULE 6 QUEEN S PRINTER FOR ONTARIO 2013 PLUMBING - ALL BUILDINGS 2012 6.29