Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT

Similar documents
Early Suppression Fast Response Sprinklers and Obstructions

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

Obstructions and ESFR Sprinklers Phase 1

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers

Chimney Top Devices in International Codes FINAL REPORT TECHNICAL NOTES. PREPARED BY: Pegah Farshadmanesh, Mehdi Modares, and Jamshid Mohammadi

Protection of Storage Under Sloped Ceilings Phase 2 Full Scale Test Matrix

Today's Topics & Sustainability Themes

SFPE Austin/San Antonio Chapter Meeting

High Rise Buildings with Combustible Exterior Wall Assemblies: Fire Risk Assessment Tool

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology

Significant Advancements in Water Based Fire Suppression for Storage Occupancies

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed.

esfr pendent sprinkler vk510 (k25.2)

Storage Sprinkler U.S. Quick Reference Guide

The Effect of Large Orifice Sprinklers on High-Challenge Fires

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage

High challenge warehouse case study Summary

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

H gh-p led Combust ble Storage. Application Guide 2009 Edition

TECHNICAL DATA. * Refer the Approval Chart on page 120c and Design Criteria on page 120d for culus and FM approval requirements that must be followed.

esfr pendent sprinkler vk510 (k25.2)

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN)

TECHNICAL DATA OBSOLETE. * Refer the Approval Chart on page 121c and Design Criteria on page 121d for FM approval requirements that must be followed.

Box-in-Box Cold Storage Fire Protection Options

Plan Submittal Checklist

ESFR PENDENT SPRINKLER VK500 (K14.0) TECHNICAL DATA

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011

NFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014

Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed.

ATTIC UPRIGHT SPECIFIC APPLICATION SPRINKLER VK696 TECHNICAL DATA

Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description

TECHNICAL DATA NOTICE

culus Listed: Category VNIV Refer to the Approval Chart on page 3. VK697 Attic Upright Sprinkler Specifications:

esfr dry pendent sprinkler Vk502 (k14.0)

MODEL V-BB SPECIFIC APPLICATION TECHNICAL DATA

TECHNICAL DATA OBSOLETE

esfr dry pendent sprinkler Vk501 (k14.0)

Sprinkler Solutions for Storage Applications

standard response elo upright and pendent sprinklers (storage-density/area)

Tire Storage. Michigan Fire Inspectors Society Fall Conference

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Impact of a High Volume Low Speed Fan on Sprinkler Performance in Rack Storage Fires

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Developing Sprinkler System Design Criteria for Flammable and Combustible Liquid Storage

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment

Correlating Committee on Automatic Sprinklers

1. Revise and A to read as follows:

Sprinkler Identification Numbers

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Dave Hague NFPA Staff Liaison 12 21,

By: Russell Bainbridge March 18th, 2016 FPE 596

File EX3836 Project 05CA54707 Project 06NK13655 Project 06NK29644 Project 06NK25809 Project 08CA19260 Project 07NK04786 Project 08CA42763 REPORT

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES

HVLS Fans and Sprinkler Operation Phase 1 Research Program

High-Piled Combustible Storage

STORAGE FIRE PROTECTION SPRINKLERS

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems

Storage Sprinkler. Model LP-46 (SIN) V4603, K25, Standard Response Storage Upright Sprinkler, Patent Pending

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS

Redlands Fire Department Fire Protection Standard

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

The Science Behind Water Mist Protection of Typical Building Hazards

Deluge/Preaction Systems Annotated Instructor s Guide

Deluge/Preaction Systems Annotated Instructor s Guide

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA

NFPA 30 FLC-SWC Public Comment Report

Fire Prevention Coffee Break Training. May 2017

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

qr fusible element sprinklers (part nos , 13959, 17535, and 17536) 3. technical data Sprinkler 42h March 14, 2013

TECHNICAL DATA MODEL V-HIP SPECIFIC APPLICATION ATTIC SPRINKLER VK660

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

The Loss prevention Council. Phase 1 report

Standard Spray concealed horizontal sidewall sprinkler VK481

Standard response. elo sprinklers

quick response Sprinkler 105a October 25, 2010

TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3

QUICK RESPONSE ELO PENDENT SPRINKLER VK377 (STORAGE-DENSITY/AREA) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

QUICK RESPONSE EXTENDED COVERAGE FUSIBLE ELEMENT PENDENT SPRINKLER VK601 (K5.6) TECHNICAL DATA

Fire Sprinklers Standards And Approvals Redbook Live

standard/quick response extended coverage light and ordinary hazard elo sprinklers

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

CLOUD CEILINGS: FIRE DYNAMICS AND CODE CONTEXT

Microfast quick response Fusible element hsw sprinkler

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK468 (K4.9) TECHNICAL DATA

freedom residential horizontal sidewall sprinkler Vk450 (k4.2)

The Viking Corporation s Web site at Rated to 175 psi (12 bar) water working pressure

TECHNICAL DATA. MicrofastHP QUICK RESPONSE FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK318 (K5.6)

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE

Transcription:

Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT PREPARED BY: Garner A. Palenske, P.E., and William N. Fletcher, P.E. Aon Fire Protection Engineering San Diego, CA, USA September 2015 Fire Protection Research Foundation FIRE PROTECTION RESEARCH FOUNDATION ONE BATTERMARCH PARK QUINCY, MASSACHUSETTS, USA 02169-7471 E-MAIL: FOUNDATION@NFPA.ORG WEB: WWW.NFPA.ORG/FOUNDATION

Page i

FOREWORD ESFR s are often installed in warehouses to avoid installation of in-rack s. Due to the unique discharge pattern of the ESFR, obstructions located near the can greatly affect the distribution of water and potentially performance. The 2013 Edition of NFPA 13, Standard for the Installation of Sprinkler Systems, provides requirements which are intended to minimize the affect obstructions have on ESFR performance. Recent testing has been performed with obstructions that encroach upon the NFPA 13 obstruction limitations with successful results. The information from these tests, as well as information gathered from further testing, can be used as a technical basis for revisions to the NFPA 13 requirements. The Fire Protection Research Foundation initiated this project to ultimately develop a tool that can be used to provide reliable analysis of the impact of obstructions on ESFR performance. This tool and existing test data can be used as a basis for the NFPA 13 Technical Committees to develop new requirements and guidance for ESFR s. The second phase of this project implemented the test plan developed in the first phase. The testing in Phase 2 focused on open web bar joist obstructions and identified remaining knowledge gaps for future phases. The Fire Protection Research Foundation expresses gratitude to the report authors Garner A. Palenske, P.E., and William N. Fletcher, P.E., who are with Aon Fire Protection Engineering Corporation. The Foundation also expresses gratitude to Dan Steppan, the project director for Underwriters Laboratories (UL), who conducted the ADD and full scale testing at the UL facility. The Research Foundation appreciates the guidance provided by the Project Technical Panelists, the funding provided by the project sponsors, and all others that contributed to this research effort. The content, opinions and conclusions contained in this report are solely those of the authors. Page ii

About the Fire Protection Research Foundation The Fire Protection Research Foundation plans, manages, and communicates research on a broad range of fire safety issues in collaboration with scientists and laboratories around the world. The Foundation is an affiliate of NFPA. About the National Fire Protection Association (NFPA) Founded in 1896, NFPA is a global, nonprofit organization devoted to eliminating death, injury, property and economic loss due to fire, electrical and related hazards. The association delivers information and knowledge through more than 300 consensus codes and standards, research, training, education, outreach and advocacy; and by partnering with others who share an interest in furthering the NFPA mission. All NFPA codes and standards can be viewed online for free. NFPA's membership totals more than 65,000 individuals around the world. Keywords: ESFR s, obstructions, NFPA 13, warehouse protection, bar joists, bridging members Page iii

Page iv

PROJECT TECHNICAL PANEL Carl Anderson, The Fire Protection International Consortium Roland Asp, NFSA Jim Biggins, Global Risk Consultants Corporation Andrew Blum, Exponent Phil Brown, AFSA Scott Futrell, Futrell Fire Consult and Design John Huffstetler, Family Dollar (alternate to Kurt Smith) John Kelly, Washington DC Fire & EMS Department Russ Leavitt, Telgian Corporation Kurt Smith, Family Dollar Will Smith, Code Consultants Inc. Matt Klaus, NFPA Staff Liaison PROJECT SPONSORS Property Insurance Research Group: AIG CNA Insurance FM Global Liberty Mutual Insurance Tokio Marine Management Travelers Insurance XL Gaps Zurich Insurance Group Globe Fire Sprinkler Corporation IKEA P&G Target Tyco Viking Page v

Page vi

Executive Summary The objective of the Phase 2 research effort was to explore the threshold and tolerance of the early suppression fast response (ESFR) s to obstructions. This research utilized both intermediate scale testing and full-scale testing. ESFR s were developed to meet the demands of high challenge storage fire scenarios and are a common choice to protect warehouses. Many aspects of ESFR s are unique compared to standard spray s. Paramount to ESFR performance is the ability of the to provide large amounts of water, in a specific discharge pattern, to the fire source in the incipient phase of fire development. Obstruction of the discharge pattern could greatly affect the ability of the ESFR to achieve fire suppression. Actual delivered density (ADD) testing was utilized to identify the obstruction parameters for the full-scale testing. The variation in the performance of the various ESFR models was established so that the results of the testing program would not be product specific. ADD testing was conducted, both with and without obstructions, to evaluate this issue. Five large-scale fire tests were conducted to gather data to establish the acceptable threshold the ESFR could be obstructed until the obstruction prevented the ESFR from meeting its performance objectives. Each test was conducted using a nominal storage height of 30 feet and a ceiling height of 40 feet. The main storage array consisted of double-row rack storage and two single-row racks target arrays separated with four-foot aisles on both sides. Standard cartoned unexpanded Group A plastic test commodity was used in the testing. The ignition was located at the base of the storage array and horizontally offset approximately 2 feet from the obstructed in the transverse flue space. Due to a recent change to NFPA 13 regarding the use of K-14 ESFR s, the K-17 ESFR was selected for this test series. Two full-scale tests were performed with bar joist obstructions and three tests were performed with a combination of bar joist and bridging member obstructions. Tables 1 and 2 outline the summary of these tests and their respective results. Obstructions and ESFR Sprinklers September 4, 2015 Phase 2 Research Program Report Aon FPE Project No.: 2015004-000 Quincy, MA Page v

Table 1. Test Parameters Fire Test Number Test 1 Test 2 Test 3 Test 4 Test 5 Test Date April 14, 2015 April 16, 2015 April 20, 2015 April 22, 2015 April 24, 2015 Test Parameters Storage Type Double Row Rack Commodity Type Cartoned Unexpanded Group A Plastic (Plastic Cups in Corrugated Boxes on Hardwood Pallets) Pallet Type 2 way entry, stringer, hardwood Nominal Storage Height (feet) 30 Ceiling Height (feet) 40 Nominal Clearance (feet) 10 Aisle Width (feet) 4 Ignition Location Under One Sprinkler (offset) Sprinkler Systems Ceiling Only (no in-rack s) Sprinkler Orientation Pendent Deflector to Ceiling (inch) 14 Sprinkler Spacing, by branchline, 10 feet by 10 feet Temperature Rating ( F) 165 Sprinkler Type ESFR Nominal Sprinkler Discharge Coefficient K (gpm/psig 0.5 ) 16.8 Nominal Discharge Density (gpm/ft 2 ) 1.21 Nominal Discharge Pressure (psig) 52 steel joist, 30 inch deep Primary Obstruction edge of lower of lower chord 3 of lower chord 6 of lower chord 6 chord 6 inches inches from inches from inches from from centerline of Secondary Obstruction None None 1/2 inch bridging member; 1-1/2 inch away from 1/2 inch bridging member; Centered below 22 inch deep of lower chord 6 inches from 1/2 inch bridging member; Centered below Obstructions and ESFR Sprinklers September 4, 2015 Phase 2 Research Program Report Aon FPE Project No.: 2015004-000 Quincy, MA Page vi

Table 2. Test Results Test Results Fire Test Number Test 1 Test 2 Test 3 Test 4 Test 5 Test Date April 14, 2015 April 16, 2015 April 20, 2015 April 22, 2015 April 24, 2015 Primary Obstruction steel joist, edge of lower chord 6 inches from centerline of 30 inch deep of lower chord 3 inches from Secondary Obstruction None None of lower chord 6 inches from 1/2 inch bridging member; 1-1/2 inch away from of lower chord 6 inches from 1/2 inch bridging member; Centered below 22 inch deep of lower chord 6 inches from 1/2 inch bridging member; Centered below Length of Test (minutes) 31 32 32 32 32 First Sprinkler Operation Time (min: sec) 0:56 1:42 1:19 1:11 1:01 Last Sprinkler Operation Time (min: sec) 6:08 7:37 1:19 1:11 6:42 Number of Operated Sprinklers 3 12 1 1 23 Peak Gas Temperature at Ceiling Above Ignition ( F) Maximum 1 minute Average Gas Temperature at Ceiling Above Ignition ( F) Peak Steel Temperature at Ceiling Above Ignition ( F) Maximum 1 minute Average Steel Temperature at Ceiling Above Ignition ( F) 294 406 1 238 250 1264 129 256 * 114 115 979 128 157 * 86 84 248 126 157 * 85 83 246 Ignition Time of Target Array (min: sec) 3:36 (North Target) 3:24 (North Target) N/A N/A 2:26 (North Target) Fire Travel to Extremities of Test Array No No No No Yes (North Target) From the full-scale fire tests that were conducted, the following conclusions can be made: A K-17 ESFR obstructed by a bar joist with a 6-inch offset from the closest edge of the obstruction and without a horizontal bridging member produced acceptable results. A K-17 ESFR obstructed by a bar joist with a 3-inch offset from the closest edge of the obstruction and without a horizontal bridging member controlled the fire with 12 s activating. Tests 3 and 4 showed that regardless of horizontal offset a bridging member with a vertical separation of 19.5 inches on a 36-inch deep bar joist with a 6-inch offset provides acceptable results. 1 Due to a data system issue, data was taken at 20 second intervals during Test 2. The values reported are the peak and one minute maximum recorded values and likely not the true peak and time average maximum values. Obstructions and ESFR Sprinklers September 4, 2015 Phase 2 Research Program Report Aon FPE Project No.: 2015004-000 Quincy, MA Page vii

The failure of Test 5 can be attributed to the vertical proximity of the bridging member to the. This test illustrated that a bridging member directly underneath the with a vertical separation of 6 inches produced unacceptable results. The fire growth rates discussed in Report Section 8.3 show that the fire in Test 2 was not comparable to the other four fires and should be repeated. The following additional testing is recommended: Testing of bridging members on different bar joist depths to increase the understanding of the vertical distance effects of the obstructions A K-14 ESFR test with the worst-case successful obstruction arrangement found during the K-17 ESFR testing. ADD testing to evaluate various obstructions scenarios prior to full-scale testing. Evaluate the results of Test 2 by retesting the obstruction scenario at full-scale or by other means such as intermediate scale testing methods. Miscellaneous obstruction tests Obstructions and ESFR Sprinklers September 4, 2015 Phase 2 Research Program Report Aon FPE Project No.: 2015004-000 Quincy, MA Page viii