Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers

Similar documents
Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide

Fan Coil Unit (FCU) Application Guide

VT8600 Series Installation Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller

VT8300 Series Installation Guide 24 Vac Low Voltage

PIR Cover. Install Guide for PIR Cover for SE7000 Room Controller

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

PIR Application Guide for the for VT76xxX5x00(X) Series thermostats (Issue Date: November, 2015)

Document # R01

CONTENTS. Installation Guide. VT7200 Series

Document # R00

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

VT8000 Series Replacement Procedure to Replace VT8000 Series Room Controller and Pair with ZigBee Pro Sensors

TB7300 Series Communicating Fan Coil Thermostats 24 VAC/FOR COMMERCIAL AND LODGING HVAC APPLICATIONS

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

LG ELECTRONICS Air Conditioning Technologies LG Guide Specifications Controls

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

T600MEP-2 Programmable Economizer Thermostat

Table of Contents. WSHP Open v3

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

TEC Networked Multi-Stage Economizer Thermostat

ARO Series. Description. Features. Modbus CO2 VOC. Networkable* ARO AROB24TGVH AROB24TGH. room controller. (AROB series only) or network

Verasys System Operation Overview Technical Bulletin

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

Models available. Features and benefits. Models available with internal humidity sensing Advanced occupancy functions

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

TB7200 Series Communicating Zone Thermostats

TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Catalog Page


Multi-Zone Wireless Control Training Systems ( )

SE7200 Series Installation Guide

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

Dual Technology Wall Mounted Occupancy Sensor. Manual & Specification

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

Digital Precise Air Control - DPAC

Installation Instructions. Applications. North American Emissions Compliance. Installation. Part No , Rev. Issued February 8, 2010

PIR Ready VT7200 Series 24 Vac Low Voltage Zoning Thermostats For Commercial HVAC Applications September 1, 2010

Product Manual SZ1022/SZ1031/SZ1035/

Pioneer Gold Controller Technical Guide

TEC BACnet MS/TP Networked Thermostat Controller with Single Proportional Output and One-Speed Fan Control

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

MicroTech Self-Contained Air Conditioning System

Fan Coil for AppController overview and specifications

Pioneer Gold Controller Technical Guide. Pioneer Gold Controller Code: Version 1.1 Used with AAON WSHP WV Series Vertical and WH Series Horizontal

York 25-Ton VAV Rooftop Unit

Reference Guide for Microprocessor Controller

Unit Vent for AppController overview and specifications

Reference Guide for Microprocessor Controller

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

T606MSx-4 and T606MSx-4+PIR Series Multi-Stage

Installation, Service, and Troubleshooting Instructions

Table of Contents. Unit Ventilator

ETNC24-FC-BAC-PIR-01 Owner s manual & Technician Settings

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

74 Humidity 66 % MultiSITE CRC1 Series Controllers INSTALLATION MANUAL. PREMTBVC0 MultiSITE CRC1 PREMTBVC1 MultiSITE CRC1+ Occ Auto Heat.

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Introduction. What is the W2W Open controller?

TC-9102 Applications

SER7300 Series Installation Guide for HVAC FCU Applications

Omnistat3 Hospitality Energy Management Thermostat

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

Owner s Manual. Part Number 33CS250-RC

ZonexCommander. ZonexCommander(Plus) Installation and Applications Manual. Network All Your HVAC Equipment

CLEANROOM MONITOR CR3A Network - Installation Instructions

Reciprocating Chiller

PSC-ID-x-CM Series Ceiling Mount Occupancy Sensor

Dual Technology Wall Switch Occupancy Sensor. Manual & Specification

INSTALLATION, OPERATION & QUICK START GUIDE

VCB-X Modular Service Tool Technical Guide. VCB-X Controller Code: SS1051 Version 2.0 Requires Service Tool Code: SS1041 Version 2.

Product Manual SZ1009

TEC2664Z-2 BACnet MS/TP Rooftop Controller for Stand-Alone and Networked Zoning Systems Part No , Rev. C

1.0 Digital Controller

Touch Screen Thermostat. MTSC/SUPER/CO2, MTSC24/SUPER/CO2 Series. MTS/SUPER/CO2, MTS24/SUPER/CO2 Series. Owner s manual and technician settings

PIR Ready VT76xx Series Programmable & Non-Programmable Thermostats For Commercial HVAC Applications. BACnet Integration Manual September 1, 2010

Bryant Evolution Connex Control (SYSTXBBECC01-B) Occupancy Sensing Sequence of Operation

Product Manual SZ1145

Water Source Heat Pump Module Technical Guide

Product Guide. Ceiling PIR HS presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs.

TEC210x-2 Series Networked Thermostats

AIRFLOW MEASUREMENT AND CONTROL PRODUCT CATALOG. Phone: 877-4GNTROL ( ) - Internet: GreenTrol.com. r1f

TEC and TEC PIR BACnet MS/TP Network Multi-Stage Temperature and Humidity Controllers

TEC and TEC PIR BACnet MS/TP Networked Multi-Stage Thermostat Controllers

IMC BACnet Module. Service Literature. Table of Contents. General. Field Connections. Physical

VH7200 Humidistat Series For Humidification & Dehumidification Control For Commercial HVAC Applications (Issue Date January 22, R7)

TEC2100 Series Networked Thermostats

PSC-BL-I-FM-DC0(-BLE) Bi-level Dimming PIR Sensor

Carbon Monoxide Transmitter

Touch Screen Thermostat. MTSC/SUPER, MTSC24/SUPER Series. MTS/SUPER, MTS24/SUPER Series. Owner s manual and technician settings

I/O ZONE 560/583 USERS GUIDE

ZonexCommander. ZonexCommander(Plus) Installation and Applications Manual. Network All Your HVAC Equipment

Sensors and Detectors

Models Available. Features and benefits. Through the network or smart local occupancy sensing. Advanced occupancy functions

Product Manual SZ1144

TEC Networked Multi-Stage Thermostat

Allure EC-Smart-Vue Sensor Series Line of communicating sensors with backlit display and graphical menus

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Wireless Thermostat (WTS10) Keypad Operation Guide

MicroTech Rooftop/RMC

Transcription:

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers TABLE OF CONTENTS Overview 2 VT86X0U5X00B 2 heating / 2 Cooling for Rooftop unit and Indoor air quality 3 VT86X0U5X00B Cooling / Modulating Heat for Rootop Unit and Indoor Air Quality 5 Fresh Air Damper Control Sequences 7 Economizer Control Only 7 Economizer Control Mode and Fresh Air Measurement Station 8 Economize Control Mode and CO2 Level Control 9 Economizer Control Mode, CO2 Level Control and Fresh Air Measurement Station 10 Appendix A - Passive infra-red (PIR) motion detector cover specifications 11 Deployment 13 Appendix B - Optional Netwwork Setup 15 Appendix C - Controllers Occupancy Sequence and Operation Schematic 15 Appendix D - SED Series Wireless Sensors 16 Appendix E - Terminal Correspondence 17

2 OVERVIEW VT8600 The VT8600 Rooftop, Heat Pump and Indoor Air Quality Controller is cost-effective solution for upgrading rooftop unit thermostats. The application allows existing wiring between the rooftop unit and the Room Controller to be re-used, reducing overall costs and installation time. The VT8600 can also add features like CO 2 and fresh air monitoring to the existing functions of a rooftop unit. The VT8600 Rooftop, Heat Pump, and Indoor Air Quality Controller can be configured to handle a broad variety of applications covering all the standard implementations necessary for rooftop HVAC systems. In addition to controlling heating, cooling and air quality, depending on the model and accessories, the VT8600 can handle wireless networking and switches, Passive Infrared (PIR) occupancy detection using either onboard or remote sensors, and can have custom programs implemented to fulfill specific User requirements. The applications described here cover all these features in combination with the VT8600 s advanced scheduling and occupancy controls to provide the functionality for any required rooftop HVAC implementation. VT8600 ROOFTOP UNIT, HEAT PUMP AND INDOOR AIR QUALITY ROOM CONTROLLERS Commercial and Hospitality Interface (Local Override and Degrees C/F Selection) Power Part Number Description PIR Sensor Communication VT86X0U5X00B BACnet fan coil terminal equipment controller No BACnet VT86X0U5X00B BACnet fan coil terminal equipment controller Yes BACnet ZigBee Pro Module Part Number Description Power VCM8000V5000P Optional ZigBee Pro module for VT8600 Series room controllers. CO 2 Detection Sensor Module Part Number Description Power VCM8001V5045 Optional CO 2 sensor module for VT8600 Series room controllers. Wireless Accessories for VT8600 Series Power Part Number Description SED-CMS-P-5045 Wireless ceiling mounted motion sensor SED-WDS-P-5045 Wireless window and door switch SED-WMS-P-5045 Wireless wall mounted motion sensor

3 VT86X0U5X00B 2 HEATING / 2 COOLING FOR ROOFTOP UNIT AND INDOOR AIR QUALITY Fresh air measurement station Filter Cooling coil Fan Heating coil Outside air sensor Outside air DPS Control Board Supply air Return air Supply air sensor CO2 air sensor BACnet MS/TP Wired communication protocol ZigBee Pro Optional wireless communication Configuration Parameter Name Configuration Settings UI17 UI19 Econo. Config FA Range Min fresh air Max fresh air Min CO2 Max CO2 Filter CO2 On Set Max CFM, cannot be zero Set Min CFM, cannot be zero Set Max CFM, cannot be zero Set Min CO2, cannot be zero Set Max CO2, cannot be zero Note: Only required configuration parameters are listed. Other settings are configurable as needed by user.

4 VT8600 2 Heating / 2 Cooling BO 1 - Aux BO 2 - Y2 BO 3 - Y1 BO 4 - G RC (24 Vac) C (Common) RH BO 8 - W1 UO 9 - W2 UO 10 - Econo UO 11 - Heat UO 12 1 2 3 4 5 6 7 8 9 10 11 12 ECONO W2 W1 C R G Y1 Y2 C R CO2 TRANSMITTER (0-10 VDC) OUT FILTER DPS C OUT R AIR FLOW MEASURING STATION (0-10 VDC) SAT SENSOR OAT SENSOR 13 14 15 16 17 18 19 20 21 22 23 24 BACnet + BACnet - BACnet REF UI 16 UI 17 Common UI 19 - CO2 UI 20 - RS Common UI 22 - SS UI 23 - OS UI 24 - Airflow Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Options Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). 3 universal inputs can be used and configured for advanced functionality as required by the application. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by ToccTime parameter. In all Occupancy Modes If room relative humidity is higher than the user-defined Dehumidification setpoint, both Dehumidification, UO12 and Fan BO4, outputs are energized to reach the setpoint and the Room Controller Cooling and Heating outputs will not trigger. If room relative humidity is higher than the dehumidification set point + hysteresis, the Room Controller will energize dehumidification terminal UO12, BO8 and the cooling terminal BO3. During the dehumidification cycle, the Room Controller modulates heating output UO11 to maintain the room temperature set point. *A multi-pole relay may be required to activate Cooling and Heating stage(s).

5 VT86X0U5X00B 2 COOLING / MODULATING HEAT FOR ROOFTOP UNIT AND INDOOR AIR QUALITY Optional economizer damper control output Cooling coil Fan Heating coil Airflow direction Outdoor air sensor DPS Control Board Supply air Return air Supply air sensor ZigBee Pro Optional wireless communication BACnet MS/TP Wired communication protocol Configuration Parameter Name Configuration Settings UI17 UI19 Econo. Config FA Range Min fresh air Max fresh air Min CO2 Max CO2 Filter CO2 On Set Max CFM, cannot be zero Set Min CFM, cannot be zero Set Max CFM, cannot be zero Set Min CO2, cannot be zero Set Max CO2, cannot be zero Note: Only required configuration parameters are listed. Other settings are configurable as needed by user.

6 VT8600 BO 1 - Aux BO 2 - Y2 BO 3 - Y1 BO 4 - G RC (24 Vac) C (Common) 1 2 3 4 5 6 2 Cooling / Modulating Heat RH BO 8 - W1 UO 9 - W2 UO 10 - Econo UO 11 - Heat UO 12 7 8 9 10 11 12 Mod. Heat (0-10 VDC) C R CO2 TRANSMITTER (0-10 VDC) C OUT R AIR FLOW MEASURING STATION (0-10 VDC) ECONO C R G Y1 Y2 OUT FILTER DPS SAT SENSOR OAT SENSOR 13 14 15 16 17 18 19 20 21 22 23 24 BACnet + BACnet - BACnet REF UI 16 UI 17 Common UI 19 - CO2 UI 20 - RS Common UI 22 - SS UI 23 - OS UI 24 - Airflow Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Options Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). 3 universal inputs can be used and configured for advanced functionality as required by the application. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by ToccTime parameter. In all Occupancy Modes If room relative humidity is higher than the user-defined Dehumidification setpoint, both Dehumidification, UO12 and Fan BO4, outputs are energized to reach the setpoint and the Room Controller Cooling and Heating outputs will not trigger. If room relative humidity is higher than the dehumidification set point + hysteresis, the Room Controller will energize dehumidification terminal UO12, BO8 and the cooling terminal BO3. During the dehumidification cycle, the Room Controller modulates heating output UO11 to maintain the room temperature set point. *A multi-pole relay may be required to activate Cooling and Heating stage(s).

7 FRESH AIR DAMPER CONTROL SEQUENCES The fresh air damper can be controlled through more than one sequence to achieve different control strategies such as free cooling (economizer mode), minimum fresh air control and CO2 level control. Here are the control sequences available: Note: For the sequences mentioned below, the following conditions must be met in order for the sequences to be performed as stated: Max Pos parameter value must be greater than Min Pos Parameter value. Mac CO2 parameter value must be greater than Min CO2 Parameter value. Max FA parameter value must be greater than Min FA Parameter value. Economizer Control Mode Only Cooling coil Fan Heating coil Outside air sensor Outside air Control Board Supply air Return air Supply air sensor BACnet MS/TP Wired communication protocol ZigBee Pro Optional wireless communication If the fresh air damper is to be used only for free cooling purposes (economizer mode, without fresh air measurement station or CO2 control), only the Min Pos parameter and the free cooling sequence will be active. The FA Range parameter should be set to 0 CFM. (Default Value = 0 CFM) Set the Chngstpt parameter to desired value which free cooling is enabled. (Default Value = 55 F) If the outside air temperature is greater than the changeover setpoint, then normal mechanical cooling will be used. If the outside air temperature is less than or equal to the changeover setpoint, then free cooling will be enabled and mechanical cooling stages will be locked out.

8 Economizer Control Mode and Fresh Air Measurement Station Fresh air measurement station Cooling coil Fan Heating coil Outside air sensor Outside air Control Board Supply air Return air Supply air sensor BACnet MS/TP Wired communication protocol ZigBee Pro Optional wireless communication If the fresh air damper is to be used for both free cooling and minimum fresh air volume control (economizer mode and fresh air measurement station, but without CO2 level control), only the Min FA parameter and the free cooling sequence will be active. The FA Range parameter should be set to a value higher than 0 CFM (0 CFM disables the fresh air control). Min FA (minimum fresh air) parameter should be set to the desired level. The FA Range parameter value should be set to the maximum capacity of the fresh air measurement station. Therefore the relationship between air volumes and input signals can be established. For example, if the fresh air station capacity is 10000 CFM, set FA Range to 10000. This will set the relationship of 0 VDC = 0 CFM and 10VDC = 10000 CFM.

9 Economizer Control Mode and CO2 Level Control Cooling coil Fan Heating coil Outside air sensor Outside air Control Board Supply air Return air Supply air sensor CO2 air sensor BACnet MS/TP Wired communication protocol ZigBee Pro Optional wireless communication If the fresh air damper is to be used for both free cooling and CO2 level control (economizer mode and CO2 level control, but without fresh air measurement station), only the Min Pos, Max Pos, Min CO2 and Max CO2 parameters as well as the free cooling sequence will be active. Max Pos Current Fresh Air Setpoint Min Pos Min CO 2 Current CO2 Level The FA Range parameter should be set to 0 CFM. Set AI1 parameter to CO2 (0 VDC = 0ppm ; 10VDC = 2000ppm) Max CO 2 Min Pos, Max Pos, Min CO2 and Max CO2 parameters should be set according to the required setting. The highest value between free cooling demand output and interpolation output for the fresh air setpoint will be the output to the fresh air damper.

10 Economizer Control Mode, CO2 Level Control and Fresh Air Measurement Station Fresh air measurement station Cooling coil Fan Heating coil Outside air sensor Outside air Control Board Supply air Return air Supply air sensor CO2 air sensor BACnet MS/TP Wired communication protocol ZigBee Pro Optional wireless communication If the fresh air damper is to be used for both free cooling and CO2 level control with a fresh air measurement station, only the Min FA, Max FA, Min CO2 and Max CO2 parameters as well as the free cooling sequence will be active. The FA Range parameter should be set to something other than 0 CFM. Use an air flow transmitter to read fresh air level with AI2 input (0-5 VDC input) Min FA, Max FA, Min CO2 and Max CO2 parameters should be set according to the required setting. Max FA Setpoint Current Fresh Setpoint Min FA Setpoint Min CO 2 Current CO2 Level Max CO 2 The highest value between free cooling demand output and interpolation output for the fresh air setpoint based on the CO2 level will be the output to the fresh air damper.

11 APPENDIX A - PASSIVE INFRA-RED SENSOR Sequence of Operation Initially, the Room Controller is in Stand-by mode and Stand-by setpoints are used. When the Passive Infra-Red (PIR) sensor detects motion, the Occupancy status switches to Occupied and the Stand-By Time timer is reset. The Occupied setpoints are used for this operation. If no motion is detected in the room for the entire Stand-By Time duration (adjustable parameter), the room switches to Stand-by mode and Stand-by setpoints are used. While in Stand-by mode, if no motion is detected for the entire Unoccupied Time period (adjustable parameter), the room switches to Unoccupied mode and uses its Unoccupied setpoints. While in Stand-By or Unoccupied mode, any motion switches the room back to Occupied mode. PIR ranges measure 20 feet (6 meters) at 140 and 13 feet (4.5 meters) minimum between 15 to 30 laterally. A typical installation height of approximately 5 feet (1.5 meters) is considered in these measurements. The below illustrates the resolution. 140 O Side view 60 O 15 O 25 O 25 O 15 O 15 O 15 O 20 ft 16 ft 13 ft 13 ft 16 ft 20 ft (6 m) (5 m) (4 m) Top view (4 m) (5 m) (6 m) 20 ft (6 m) Fresnel lens beam and detection field Forward movement Lateral movement 140 O 20 ft (6 m) 20 ft (6 m) Top view

12 Energy Savings PIR can maximize your energy saving from 10-30% by adjusting temperature set points in unoccupied zones during scheduled periods. Energy Usage (KWh) 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 Typical Savings of 10-30% 0% 0 2 4 6 8 10 12 14 16 18 20 22 24 Time of Day (EST) Typical Consumption PIR Thermostat Consumption Savings 50% 40% 30% 20% 10% Saving Percentage

Deployment 13 Placement of the Room Controller must be given consideration. It is recommended to install the Room Controller as close to a door as possible (but not so as to be blocked by the door), or in an area with high occupant movement. Ideally the Room Controller should be installed 5 feet (1.5 meters) above the floor surface to ensure maximum detection range is achieved. As well, Room Controller placement should ensure the occupant crosses the lens beam in a perpendicular path within the prescribed detection zone. Example of Recommended Deployment The below shows Room Controllers installed in ideal locations for two rooms. The examination room shows one Room Controller installed adjacent to the door. In this area of the room, occupant traffic is high and ensures the occupant will almost always cross the PIR detection path laterally and within the detection range. The waiting room shows one Room Controller installed beside a door in the middle of the room. As shown in the diagram below, occupant traffic is high in several areas of the room including the entrance, waiting room, access to the door and activity around the reception desk. Moreover, for each case aforementioned, occupant movement almost always moves lateral to the PIR, which ensures detection by the PIR, as well as respecting the PIR detection range. Recommended Installation

14 Example of Non-Recommended Deployment The below shows four Room Controllers (two for each room) installed in non-ideal locations for the two rooms. The examination room shows one Room Controller installed in a low traffic area near the door, and a second Room Controller installed on the wall directly opposite the door. For the Room Controller installed in the corner wall, the PIR could be blocked by the opened door, while occupant traffic cold also be minimal in this area of the room. For the second Room Controller installed opposite the door, the PIR detection could fall outside the specified detection zone, while at the same time most occupant movement would be not be lateral to the PIR, thereby not respecting optimal crossing patterns for PIR detection. The waiting room shows one Room Controller installed in the corner of the room, and a second Room Controller installed beside the reception area. For the Room Controller installed in the corner, the opening/closing of the door creates high probability that the PIR would get blocked, and therefore, occupancy going undetected. For the Room Controller installed beside the reception area, occupant traffic could fall outside the detection zone, and the receptionist would often be below the 5 foot recommended installation height for the Room Controller. Non-Recommended Installation

15 APPENDIX B OPTIONAL NETWORK SET-UP BACnet communication wiring Wireless Communication BACnet thermostat 1 BACnet thermostat 2 BACnet thermostat 3 + - ref + - ref + - ref Notes: - Wiring should be daisy chained - Respect polarity - If using 2 conductors shielded wires, connect the shield of each feed together on the back of the controller. ONLY ground the shield at one location. DO NOT connect the shield to the ref terminal. No communication wires required APPENDIX C CONTROLLERS OCCUPANCY SEQUENCE OF OPERATION SCHEMATIC Setpoints Unoccupied cool Stand-by cool Occupied cool Occupied heat Stand-by heat Unoccupied heat 22 C 72 F Deadband Stand-by time 24.5 C 76 F Deadband Unoccupied time 26.5 C 80 F 70 F 70 F 21 C 21 C 66 F 19 C Deadband 62 F 16.5 C 22 C 72 F Time Movement detected - Stand-by timer reset Into Stand-by mode - Unoccupied timer reset Into Unoccupied mode Next movement detected

16 APPENDIX D SED SERIES WIRELESS SENSORS Wireless ZigBee Pro Motion Sensors Rooftop Unit and Indoor Air Quality Controllers with ZigBee Pro wireless sensors can be used in stand-alone mode, or with integration to a central management system, to allow for advanced functions such as central reservation and occupancy functions. Up to ten different ZigBee motion sensors and switches (SED-WMS, SED-CMS, or SED-WDS) can be used with a VT8600 Room Controller. No tools are required for commissioning or servicing the ZigBee devices. A simple interface on the devices with an on-board LED and hidden switch provides all required functions for local interaction. The SE8600 user interface has screens used to pair and configure ZigBee devices (SED-WMS, SED-CMS, or SED-WDS only). Local information for battery life and connectivity (heartbeat) are also displayed through the ZigBee Pro wireless network. Model Selection Window Switch Door Switch Door/window switch Wall mounted motion sensor Ceiling mounted motion sensor SED-WDS-P-5045 SED-WMS-P-5045 SED-CMS-P-5045

17 LED LED LED SED-CMS SED-WMS SED-WDS SED-WIN SED-DOR LED Hidden switch Hidden switch Hidden switch Hidden switch APPENDIX E TERMINAL CORRESPONDENCE The terminals of an VT8600 are identified differently and have a wider range of possible functions compared to those of any of the VT7000 series Room Controllers. Nonetheless, there is a direct correspondence of functions between the terminals of the VT7000 series and the VT8600 series. Consult the table below to verify the appropriate terminal when replacing a VT7000 Room Controller with a VT8600 Room Controller. VT7000 VT8600 Terminal name Terminal ID Terminal name Terminal ID Binary Input 1 BI1 Universal Input 16 UI16 Binary Input 2 BI2 Universal Input 17 UI17 Universal Input 3 UI3 Universal Input 19 UI19 Sensor Common Scom Terminal 18 Common COM Remote Sensor RS Universal Input 20 UI20 - RS Sensor Common Scom Terminal 21 Common COM Mix/Supply Sensor MS Universal Input 22 UI22 - SS