GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER

Similar documents
Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Recent Advances in Energy, Environment and Economic Development

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

BALANCING OPERATION FOR THE OPTIMISATION OF HYDRONIC NETWORKS

HSPF Calculation of a System Allowing Switching Between a Single-Stage to a Two-Stage Compression System

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Comfort and health-indoor air quality

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

Case Study of an Innovative HVAC System with Integral Dehumidifier. Florida Solar Energy Center Cocoa, Florida

Thermal Comfort with Convective and Radiant Cooling Systems

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

A STUDY ON THE APPLICATION OF THE RADIANT FLOOR COOLING SYSTEM INTEGRATED WITH A DEHUMIDIFICATION SYSTEM

K.F. Fong *, C.K. Lee, T.T. Chow

Effect of domestic storage and cooking conditions on the risk distribution in ready to cook meat products

Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type Display Cases

A study of radiant cooling for a room with daytime application in tropical climate

Optimizing energy efficiency and occupant comfort with climate specific design of the building

ENERGY EFFICIENCY BRIEF REPORT

EMBEDDED PIPE SYSTEMS. SURFACE HEATING AND COOLING Heat transfer coefficient COOLING CAPACITY. Max. heating-cooling-capacity

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff

Experimental study of space cooling using ceiling panels equipped with capillary mats

White Paper Dehumidification in Humid Climates - A Theoretical Case Study

How to ensure Thermal Comfort in buildings with CFD

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Climate control precision in Hi-tech environments Jupiter and Mercury Close Control Units

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

Liquid Desiccant Technology Delivers Energy Cost Reductions and Indoor Air Quality Improvements. White Paper

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

Chilled Beams. Getting a Warmer Reception

Green Roofs Impact on Buildings Cooling Load

A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Optimisation of cooling coil performance during operation stage for improved humidity control

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

Don t Turn Active Beams Into Expensive Diffusers

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

Comparison of Energy Efficiencies of Commercial Refrigeration Direct and Indirect Systems

Desiccant Cooling with Solar Energy

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

Passive building in Hot and Humid Climates

Museum of Bavarian History Regensburg, Germany

DESIGN AND CONSTRUCTION OF FORCED/NATURAL CONVECTION SOLAR VEGETABLE DRYER WITH HEAT STORAGE

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

*Bioenergy GmbH Gewerbepark Haag 3, 3250 Wieselburg Land, Austria

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Integrated Building Environmental Design Case Study: Beijing Parkview Green

Preliminary Findings on the Performance of a New Residential Solar Desiccant Air-Conditioner

The Corbioli House is a single-family house situated

Heat Exchanger. The purpose may be either to remove heat from a fluid or to add heat to a fluid.

2013 Guideline for Specifying the Thermal Performance of Cool Storage Equipment. AHRI Guideline T (I-P)

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS

Chilled Ceilings / Beams Working Principles & Applications

EVALUATION OF THE THERMAL PERFORMANCE OF METAL ROOFING UNDER TROPICAL CLIMATIC CONDITIONS

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

PhD Candidate, Université Paris-Est (France) and Institut d Urbanisme de l ALBA - Univerité de Balamand (Lebanon) 2

2. CURRICULUM. Sl. No.

Potential and Simulation of Open-Cycle Solar-Assisted Climatisation-Plants in Single-Family-Houses

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Radiant Heating & Cooling for Commercial Buildings

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

A New Control Approach for a Direct Expansion (DX) Air Conditioning (A/C)System with Variable Speed Compressor and Variable Speed Supply Fan

Scholars Research Library

Energy Consequences of Non-optimal Heat Pump Parameterization

High Efficiency Heat Pump for Domestic Hot Water Generation

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Chapter 10. Passive Cooling Contents

Thermodynamics II Chapter 6 Mixtures & Psychrometry

Radiant Cooling Nonresidential HVAC Stakeholder Meeting #2

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

Modular Active. Chilled. Beams

HEAT LOAD AND SOLAR GAIN PREDICTION FOR SOLID WALL DWELLINGS RETROFITTED WITH TRIPLE VACUUM GLAZING FOR SELECTED WINDOW TO WALL AREA RATIOS

Smart Green Roofs: Cooling with variable insulation

Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings

Dynamic performance of a novel dew point air conditioning for the UK buildings

Oxyvap Evaporative Cooling Applications

Solar Heating and Cooling Systems

RADIANT COOLING SYSTEMS OPPORTUNITIES FOR RADIANT COOLING IN NORTH AMERICAN CONSTRUCTION DALE HANSCOMB, REHAU Sales Manager Building Technology

DES CHAMPS PRODUCTS. Specializing in: -- Air-to-Air Energy Recovery -- Conditioning Outdoor Air -- Controlling IAQ -- Indirect Evaporative Cooling

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

Air and operative temperature measurements in a plus-energy house under different heating strategies

Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

Experimental & Analytical Investigation on Modified Solar Dryer with Recirculation of Air

Transcription:

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER A. Bolher 1, E. Fleury 1, J.R. Millet 1, D. Marchio 2 and P. Stabat 2. 1 Centre Scientifique et Technique du bâtiment, 84, avenue Jean Jaurès Champs sur Marne BP 02, F-77421 Marne-la-Vallée cedex 2 - France 2 Center for Energy Studies, Ecole des Mines de Paris 60, boulevard Saint Michel, F 75272 Paris cedex 06 -France ABSTRACT The combination of an open wet cooling tower with chilled ceilings is a CFC free, cheap and low energy cooling solution. The efficiency of this alternative to mechanical cooling is very dependent on climate. There is a need for specific tools to help designers to size the system and to estimate its energy and water consumption. A building simulation tool, called ConsoClim, has been used to predict the performance of this system for different French climatic locations, thermal inertia, internal loads and solar gains. Since the system is climate dependent and has a limited maximum cooling power, an adapted control strategy is proposed to take advantage of the building thermal mass, allowing night cooling. The air conditioning plant and its control strategy are presented. A radiant system model and an open wet cooling tower model with possible air flow rate variation have been implemented in the simulation tool ConsoClim. From the calculations of the detailed design tool, pre-design guidance are given. The results show the promising potential of this technology in most of the climatic zones of France when associated with an anticipative control strategy and for buildings with low or medium loads. KEYWORDS Chilled ceiling, cooling tower, simulation tool, sizing, control strategy INTRODUCTION Chilled ceiling is a fully developed technology which is commonly used in central and northern European countries. Its main advantages are the thermal comfort, no ground cluttering, the low maintenance and the energetic efficiency. Since the heat transfer is mainly due to thermal radiation, heat loads can be carried off at relatively small temperature differences between room air and cooled ceiling surface. The system can so run at supply water temperatures between 16 and 20 C. The system generally runs with a chiller but it could be possible to deliver the cold water with a cooling tower only. Sprecher et al. (2000) have experimented this solution on a building in Switzerland. The tests have shown that the combination of a chilled ceiling with a closed cooling tower can maintain indoor air temperature below 27 C. The use of this technology for cooling buildings results in a low energy consumption, a low cost and a CFC free cooling system. The initial and running costs are low compared with a conventional (all-air) air-conditioning system (Oliveira, 2000). The energy consumption is limited to the pumps and the tower fan. This results in high coefficient of performance and so in lower CO 2 emissions. The cooling tower takes advantage of the evaporation of water in air and the cooled water approaches the outdoor air wet-bulb temperature depending on the

effectiveness of the heat transfer process. Thus, the minimum water temperature entering the ceiling panel is few degrees above the wet-bulb temperature. Since the cooling performance depends deeply on outdoor air conditions, short overheating periods can occur in the building. A night control strategy taking advantage of cooling energy storage in the building mass can reduce or even suppress the number of discomfort hours. What is the potential of this technology combining chilled ceilings with cooling tower in France? The performance of this cooling system is simulated using ConsoClim (Bolher, 1999), a software package to calculate energy consumption of air-conditioned buildings. A control strategy, including night cooling, is introduced in the simulation. The applicability of the system is studied for few climatic zones of France, two building inertia, two internal loads and two solar gains. METHODOLGY Simulation tool Consoclim (Bolher, 1999) is a building simulation tool in which HVAC equipments such as cooling coil, radiant panel and cooling tower have been implemented. The HVAC equipment models have been developed in order to be simple to parameterize by using one nominal rating point available in manufacturer s catalogs. Meteorological data For sizing, the simulations are carried about from a reference hot day defined in (RT2000 Règles Th-E, 2000). As the cooling system is very dependant on wet-bulb temperature, the daily variation of the humidity ratio is taken into account (Bolher et al., 2001). The selected climates of France are those of Trappes (near Paris), Carpentras (South of France) and Nice (South Est of France). Figure 1 shows the frequency of occurrence of wet-bulb temperatures in France in two climatic zones : Nice close to Mediterranean sea and Trappes close to Paris. 100 100 90 80 fourteen year weather data in TRAPPES 90 80 fourteen year weather data in NICE 70 70 occurrence (%) 60 50 40 occurrence (%) 60 50 40 30 30 20 20 10 10 0 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Wet-bulb temperature ( C) 0 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Wet-bulb temperature ( C) Figure 1 : frequency occurence of the wet-bulb temperature in Trappes and Nice One can see that wet-bulb temperature in Trappes is rarely above 20 C. On the other hand, the wet-bulb temperature in Nice is 20% of time above 20 C. We can conclude that the cooling potential of the system will be more important in Trappes than in Nice. Moreover, the system will not be able to cool the building all the time in Nice. Case studies The test cases are office building zones with the following characteristics: floor area A room : 3 m 5 m = 15 m 2 front wall : 3 m 2.7 m including a window area, A glaz, of 3 m 1 m room height : 2.7 m double glazing window: two solar gains are studied.

The results are given in the form of a solar gain index defined as A glaz F glaz /A room where F glaz is the solar factor. The minimal value is fixed at 0.05. In order to respect the new French thermal regulation (RT2000 Règles Th-E, 2000), the maximal value is fixed at 0.10 for medium inertia buildings and at 0.15 for high inertia buildings. Two thermal inertia are taken into account: medium and high according to the definition of RT2000 Règles Th-E (2000). Orientation : East, West The other parameters are: occupation : 9 h to 18 h weekdays internal sensible gains (convection part : 0.5) : 10 W/m 2 and 30 W/m 2 during occupancy internal moisture gains : 110 g/h during occupancy airflow rates: 1 ac/h and the corresponding fan energy rate: 15 W. SYSTEM DESIGN AND CONTROL Description of the cooling system The chilled ceilings consist of water pipe parallel circuits embedded on the upper side of metal panels. These large surface emitters transfer heat by radiation and convection. The chilled ceiling transfers directly heat with occupants, equipment (computers, fax ) and room surfaces by radiation, what brings better comfort and allows to operate at quite high inlet water temperature. The water temperature difference between the inlet and the outlet is about 3 K. In order to avoid the risks of condensation on the emitter surface, the water temperature should not be too low or a dew point sensor should be installed otherwise the supply air should be dehumidified. The cooling power depends on the total active surface of the ceiling which is generally limited to about 80% of total ceiling surface since some place should be reserved for the lighting The heat transfer rate varies between 50 and 80 W/m 2 at 8K difference between air and mean water temperature depending on the conductance of the emitter. The ceiling is fed with water cooled by using a cooling tower. Two cooling tower options can be selected: a closed wet cooling tower or an open wet cooling tower with a heat exchanger to separate the cooling tower circuit and the chilled ceiling circuit. In open cooling tower, the water could be dirtied by direct contact with outdoor air and it is better to use clean water in the ceiling to avoid maintenance. In the present study, open cooling tower has been selected since its price is much lower than closed cooling tower at same heat exchange capacity. The cooled water in the tower approaches the wet-bulb temperature of outdoor air with a pinch of 2 to 4 C. As the water temperature entering the ceiling tube is always higher than air wetbulb temperature, the risk of condensation is avoided unless the indoor moisture gains are very important. Concerning ventilation, it has been chosen to cool the supply air by using a cooling coil fed with the water coming out of the tower. More comfortable supply air temperatures are obtained and the maximum indoor air temperature during occupancy is slightly lowered of 0.5 C (see Table 1). TABLE 1 Impact of the use of a cooling coil in the air handling unit for a reference hot day in Trappes Trappes Air Handling Unit Building case : medium inertia, high solar gain, low internal gains With cooling coil Without cooling coil Maximum supply air temperature ( C) 25.7 31.4 Maximum indoor air temperature during occupancy ( C) 26.8 27.3

The system is represented on Figure 2. Leaving air Outdoor air Open wet cooling tower Heat exchanger Air handling unit Outdoor air fan Cooling coil Figure 2: schematic representation of the cooling system using chilled ceiling combined with a cooling tower Control Strategy The set point indoor air temperature is 25 C during occupancy and 22 C during inoccupancy. The inoccupancy set point value is lowered in order to pre-cool the building during night. The water flow rate in the emitter tubes is adjusted to maintain the set point conditions. The set point supply air temperature is fixed at 25 C during occupancy. The air handling unit is off during inoccupancy in order to limit fan consumption and because cooling potential of the ceiling emitter is more important than the one of the night ventilation. The cooling tower operates as long as cooled water is required in the radiant panel to keep the set point conditions. Sizing parameters Chilled ceiling panel have large surface area. The influence of the emitter surface on the cooling power and the operative temperature on a reference hot day is presented in Figure 3. In this example, a surface emitter between 60% and 100% of total ceiling surface can keep acceptable indoor air conditions. The deviation of the maximum operative temperature is quite small when the emitter surface decreases since the night control strategy allows to compensate the diminution of maximum cooling capacity and the slight increase of room air temperature augments the heat transfer between the room and the chilled ceiling. However, below a certain limit of emitter surface, the chilled ceiling is not anymore efficient to remove internal loads. Afterwards, an emitter surface of 80% of the ceiling surface is selected, which corresponds to the ceiling surface generally available in office buildings. The performance of the chilled ceiling is an important sizing parameter. A survey of manufacturer s catalogs shows that large differences of heat transfer exist versus the technology of the ceiling. The given performance data are based on the German standard DIN 4715 (1994).

600 29 cooling power (W) 500 400 300 200 Trappes, medium inertia high solar factor low internal gains East 27 25 23 21 operative temperature ( C) surface of emitter in % of floor surface 100% 80% 60% 40% 100% 80% 60% 40% 100 19 0 17 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 hours Figure 3: influence of emitter surface on operative temperature and cooling power on a reference hot day in Trappes The simulations of cooling system are carried out with the following parameters: Counterflow open cooling tower performance: water temperature range of 32 / 28 C at 21 C wet-bulb temperature and fan energy rate of 45 W; Heat exchanger efficiency: 0.8; Radiant panel heat transfer rate: 30W/m 2, 40 W/m 2 and 50 W/m 2 at 6K difference between room air temperature and mean water temperature. Notice that 50W/m 2 at 6K corresponds to about 90W/m 2 at 10K. SIMULATION RESULTS The simulation results presented in Table 2 are: the mean indoor operative temperature on the three hottest hours of occupancy; the maximum total loads (sensible + latent) determined according to classical HVAC sizing procedure. The maximum loads determined with the software Consoclim are about 30% lower mainly because building thermal inertia is taken into account; the mean indoor operative temperature on the three hottest hours of occupancy reached if the building was not equipped with an Air Conditioning (A.C.) System (RT2000 Règles Th-E, 2000). In this case, the building is only cooled down by the opening of the window. Results show that set point temperatures can be respected in Trappes in most of building cases when the maximum loads are below 80W/m_. The chilled ceiling combined with a wet cooling tower can not keep comfort conditions in Nice except for building with very low loads. The wet-bulb temperatures are quite high in Nice and the water temperatures entering the ceiling are too high to provide the required cooling demand. In Carpentras, the cooling system is adapted provided that solar protections are used and the building inertia is high. A radiant panel with a high conductance can help to lower the maximum operative temperature up to 2.5 C.

TABLE 2 Simulation results inertia medium high Solar gain index 0.05 0.1 0.05 0.15 Internal gains (W/m?) 10 30 10 30 10 30 10 30 Orientation E W E W E W E W E W E W E W E W TRAPPES (closed to Paris) Max loads (W/m?) 37.5 49 57.5 69 62.5 75.5 82.5 95.5 37.5 49 57.5 69 88.5 103 109 123 Max. Temp. without A.C. system ( C) 29.5 30.5 33 34 31 33.5 34 36.5 29 29.5 32 32.5 31.5 33.5 34.5 36.5 ceiling panel heat transfer rate at 6 K MEAN OPERATIVE TEMPERATURE on the three hottest hours ( C) 30 W/m? 25.5 26 28 28 27.5 27.5 30 29.5 25 25 26.5 26.5 28.5 28 31 30.5 40 W/m? 25.5 25.5 27.5 27 27 27 29 29 25 25 26 26 27.5 27 29.5 29 50 W/m? 25.5 25.5 27 27 26.5 26.5 28.5 28 25 25 25.5 25.5 27 26.5 28.5 28.5 NICE (seaside Mediterranean climate) Max loads (W/m?) 54 63 74 83 85 93.5 105 114 54 63 74 83 116 125 136 145 Max. Temp. without A.C. system ( C) 31.5 33 34.5 36 33 35.5 35.5 38.5 31 32 34 34.5 34 36 36.5 39 ceiling panel heat transfer rate at 6 K MEAN OPERATIVE TEMPERATURE on the three hottest hours ( C) 30 W/m? 27.5 27.5 30.5 30 30 29.5 33 32.5 27 27 29.5 29.5 31.5 31 34 33.5 40 W/m? 27 27 29.5 29.5 29 28.5 31.5 31.5 26.5 26 28.5 28.5 30.5 30 32.5 32 50 W/m? 26.5 26.5 29 29 28.5 28 31 30.5 26 26 28 28 29.5 29 31.5 31.5 CARPENTRAS (inland Mediterranean climate) Max 47 59.5 67 79.5 76 90.5 96 111 47 59.5 67 79.5 107 122 127 142 loads Max. Temp. without A.C. system ( C) 32.5 34 36 37.5 34.5 37 37.5 40 32 32.5 35 35.5 35 37.5 37.5 40 ceiling panel heat transfer rate at 6 K MEAN OPERATIVE TEMPERATURE on the three hottest hours ( C) 30 W/m? 26.5 27 29 29 28.5 28.5 31.5 31 26 26 28 28 30 29.5 33 32.5 40 W/m? 26 26.5 28.5 28 28 28 30.5 30 25.5 25.5 27 27 29 28.5 31 31 50 W/m? 26 26 28 28 27.5 27.5 29.5 29.5 25.5 25.5 26.5 26.5 28 27.5 30 30 Building Case temperature between 28 C and 32 C temperature over 32 C CONCLUSION The combination of a chilled ceiling with a cooling tower is a friendly air-conditioning solution which can maintain comfortable indoor air conditions in main climatic regions of France provided that the building loads are not too high. In the case of high building loads, the use of a chiller with its condenser cooled by the cooling tower in the peak cooling load days and the use of the cooling tower only by bypassing the chiller in medium cooling load days could limit energy consumption of air-conditioned buildings. The wet-bulb temperature is an essential parameter in sizing the cooling plant. Inasmuch as HVAC designers have no experience in sizing of this air-conditioning solution unlike conventional air-conditioning system, building simulation tools can help them in this task. The ConsoClim software package remains at the moment a research product. A sizing guidebook for low energy cooling technologies will be published in 2003 including tables similar to Table 2 for all climate zones of France and giving energy consumption examples. REFERENCES Sprecher, P., Borth J. and Niessen R. (2000). Des plafonds froids qui consomment moins d énergie. Sulzer Technical Review 1, 10-11 Oliveira A. (2000). Ecological cooling for buildings by combining a closed wet cooling tower with chilled ceilings. Draft Final Report. Faculty of engineering, University of Porto RT2000 Règles Th-E. (2000). Guide Réglementation Thermique 2000, CSTB Publications - Diffusions Bolher, A., Casari, R., Collignan, B., Fleury, E., Marchio, D., Millet, J.R. and Morisot, O. (1999). Méthode de calcul des consommations des bâtiments climatisés, ConsoClim. Rapport final, ENEA/CVA n 99.176R, CSTB. Bolher, A., Fleury, E., Marchio, D., Millet, J.R. and Stabat, P. (2001). Indirect Evaporative Cooling System Tools and Sizing Guidelines. Clima 2001, Napoli World Congress, September. DIN 4715. (1994). Cooling Surfaces for Rooms; Measuring Performance with Free Flow; Test Rules. DIN standard, Germany.