QPA63... CO 2 /VOC Sensors. Siemens Building Technologies HVAC Products

Similar documents
Use. In ventilating and air conditioning plants to enhance room comfort and to optimize energy consumption by providing demand-controlled ventilation.

Room Air Quality Sensors

Room air quality sensors

Duct Air Quality Sensors

Technical Instructions Document No. CE1N1961 March 17, Room CO 2 and Air Quality Sensors. Description. Features. Application

QPM21 Series Duct CO 2 and Air Quality Sensors

for relative humidity and temperature

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

Room Temperature Sensors

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature

for relative humidity and temperature

Duct Temperature Sensors

Indoor Air Quality Controller

QFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature

Room Temperature Controller

Room Temperature Sensors

QFM21... Duct Sensors. Siemens Building Technologies HVAC Products

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature

for relative humidity and temperature with calibration certificates

QFM21... Duct sensors. Symaro. for relative humidity and temperature

Room Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

PRELIMINARY EDITION

Room Temperature Controller

Room Temperature Controller with LCD

QFM41.. Duct sensors QFM41.. AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

Preliminary Release. Room Temperature

Room Temperature Sensor

QAW70. Room Unit. Siemens Building Technologies HVAC Products. for use with heating controllers

Room Temperature Controllers

Immersion Temperature Controller

Semi flush-mount room thermostat

Differential pressure sensors

Universal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG DB01

Indoor Air Quality Controller

Q-Series Relative Humidity and Relative Humidity & Temperature Sensors for Critical Environments and Outdoor Air

No. Icon Name Function

The fan is switched to the selected speed via control output Q1, Q2 or Q3.

Intelligent combined sensor for Air Quality (VOC) + Humidity (rh) + Temperature (T) with analogue outputs, Modbus and LCD display. Features.

Duct Temperature Sensors

Room Temperature Controller

Room Temperature. for 2-pipe fan coil units for compressors in DX type equipment

Heating Element. Building Technologies HVAC Products

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating

ACCESSOIRES ELECTRICAL ACCESSORIES

Infrared Flame Detectors

Semi flush-mount room thermostat with KNX communications For VAV heating and cooling systems

Flush-mount room sensor KNX S-Mode / KNX LTE- Mode / KNX PL-Link

RVL479. Heating Controller. for use with a partner unit

Retroreflective sensor with polarization filter

QRA10... QRA53... QRA55...

THERMASREG TR 040 THERMASREG TR 060

UV Flame Supervision System

Room Unit. Building Technologies SYNERGYR

Self-learning Room Temperature Controller

Room thermostats with LCD for wall mounting

Control Thermostat / Thermal Reset Limit Thermostat Combination of electromechanical TR and TW

RVL481. Heating Controller. including d.h.w. heating

RVL480. Heating Controller

QRA2... QRA10... QRA53... QRA55... Flame Detectors. Siemens Building Technologies HVAC Products

QRC1... Blue-flame Detectors. Siemens Building Technologies HVAC Products

BC-R10 Series. Burner Controllers

Heating Controller for 2 heating circuits, d.h.w. and boiler, communicating

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

Flush-mounted room thermostat

QRA10... QRA53... QRA55...

Frost Protection Thermostat

43.155/1. RXE 110: Monitoring unit for fume cupboards. Sauter Components

Room thermostat with Auto Timer, Option External Input

Hygro Transducer / Hygrothermal Transducer and CO 2 Measuring Probe for Climate Monitoring

FR-A180 FR-A360. Occupancy detector. Use

Use. For 2-pipe fan coils

GE Lighting. Lighting Controls. DALI Digital Lighting Controls

QXA2100. Condensation monitor QXA2101. Monitor to prevent damage caused by condensation on chilled ceilings and HVAC plants with AC/DC 24 V power.

RVP310. Heating Controller. Building Technologies HVAC Products

Hygro Transducer, Hygrothermal Transducer, and CO 2 Measuring Probe for Building Management and Climate Monitoring

Flame detector. The QRA4.U is for use with the following types of burner control:

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

Room thermostat with Auto Timer, Option External Input

RVL470. Heating Controller. Use. Functions. Series B

QAW70. Room Unit. Building Technologies. for use with heating controllers

QRA10... QRA53... QRA55...

Wireless room thermostat with LCD

Flame Safeguards LFE10. Building Technologies HVAC Products

QRA4.U. Flame Detector. Siemens Building Technologies HVAC Products

Room thermostat with Auto Timer, Option External Input

Flame detector. Building Technologies Division Infrastructure & Cities Sector

Wind Alarm Instrument

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Sensing & Inspection Technologies.

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Sensing & Inspection Technologies.

Thermal Reset Limit Thermostats Electromechanical TW according to DIN EN 14597

Flame detector. The QRA4.U is for use with the following types of burner control:

Two-Channel Gas Controller

Room thermostat with 24-hour time switch and large LCD

P R O D U C T D ATA S H E E T

Wall-mounted room thermostat with LCD

Model 3300 Technical Support and Installation Manual

Flame Safeguards LFE10. Building Technologies HVAC Products

Transcription:

1 958 1958P01 1958P02 QPA631 QPA632 CO 2 /VOC Sensors QPA63 Sensors designed for sensing indoor air quality in rooms or air ducts; microprocessor-based units consisting of a selective photo-acoustic CO 2 sensor and a VOC 1) sensor with a heated stannic dioxide semiconductor; operating voltage AC 24 V; output signals DC 010 V 1) VOC = volatile organic compounds (also called mixed gas) Use In ventilation and air conditioning plants to enhance room comfort and to optimize energy consumption by providing demand-controlled ventilation The sensor acquires the following: CO 2 concentration as an indicator of occupancy in rooms where smoking is prohibited VOC concentration as an indicator of combustible gases and odors (tobacco smoke, body odor, material fumes) in the room air The sensor can be used as follows: As a room sensor to acquire room air quality As a duct sensor in conjunction with the duct mounting kit to acquire extract air quality CM1N1958E 05122002 Siemens Building Technologies HVAC Products

Note! Typical areas of use: Acquisition of CO 2 and VOC concentration In party rooms, lounges, fair pavilions and exhibition halls, restaurants, canteens, shopping malls, sports gymnasiums, sales rooms, and conference rooms In this case, the AQP631 ventilation demand processor, which calculates the ventilation demand signal for the ventilation controller based on the CO 2 and VOC signal, is required Acquisition of CO 2 concentration In rooms with varying occupancy at different hours where smoking is prohibited such as museums, theatres, movie theatres, auditoriums The sensors cannot be used as safety devices, such as gas or smoke warning devices! Type summary Ordering and delivery Equipment combinations Type reference QPA631 QPA632 Description CO 2 /VOC sensor without LEDs CO 2 /VOC sensor with LEDs Duct mounting kit for QPA63 When ordering, please give name and type reference, for example: CO 2 /VOC sensor QPA631 The duct mounting kit must be ordered separately; it is supplied as the standard version (with high, grey cover) Mode of operation The sensors are suited for use with all systems and devices capable of acquiring and handling the DC 010 V output signal, such as: UNIGYR, VISONIK or INTEGRAL TEC, AEROGYR RWI6502, POLYGYR RWX, DESIGO 30 or CLASSIC RKN Ventilation demand processor AQP631 (Data Sheet no 1959), to process the ventilation demand signal on CO 2 /VOC measurement The following application examples are available for the following combinations: Name Docu number Application for AEROGYR RWI6502 CM1A1958D1 Application for INTEGRAL RS CM1A1958D2 Application for POLYGYR RWX CM1A1958D3 Application for UNIGYR EMS CM1A1958D4 The sensor acquires the CO 2 and VOC concentrations in the room or in the extract air duct The CO 2 concentration is evaluated by the sensor The output signal delivered (connection terminal U2) is proportional to the CO 2 content of the ambient air The number of LEDs lit are proportional to the CO 2 concentration The poorer the air quality, the more LEDs are lit The acquired VOC concentration is also passed on to a sensor output (connection terminal U1) The output signal provided is inversely proportional to the concentration of oxidizable gases (VOCs), such as tobacco smoke, CO, alcohol and body odors This means that when the VOC concentration increases, the signal voltage will drop towards 0 V, and when the VOC concentration decreases, the signal voltage will rise towards 10 V To evaluate the output signal, the AQP631 is required 2/8 Siemens Building Technologies CO 2/ VOC sensors QPA63 CM1N1958E HVAC Products 05122002

Function diagram CO 2 output VOC output U2 [V] U1 [V] 1958D02E 10 10 8 6 4 5 2 0 0 400 800 1200 1600 2000 CO 2 [ppm] 0 clean air polluted air VOC concentration Legend U1 U2 Signal voltage at output U1 (VOC) in V Signal voltage at output U2 (CO 2 ) in V Explanation ppm = parts per million Mechanical design Sensor QPA63 Indicator lights (only with QPA632) The sensors have been designed for wall mounting They are suitable for use with most commercially available recessed conduit boxes The cables can be introduced from the rear (concealed wiring) or from below or above (surface-run wires) through knockout openings All terminals are protected against false wiring The units consist of 2 major parts: 4-sectional housing and base Both snap together but can be detached again The housing accommodates 2 sensing elements, the electronics and, depending on the type of sensor, various setting elements and LEDs The base carries the connection terminals Front view 1958Z01 1 2 3 Legend 1 Green LEDs : 01000 ppm CO 2 2 Yellow LEDs : 10001400 ppm CO 2 3 Orange LEDs : 14002000 ppm CO 2 Disposal The major plastic components bear the material references in compliance with ISO/DIS 11469 to facilitate environment-friendly disposal Siemens Building Technologies CO 2/ VOC sensors QPA63 CM1N1958E HVAC Products 05122002 3/8

Duct mounting kit Disposal The duct mounting kit has been designed to mount the sensor in the extract air duct The kit consists of a 2-sectional plastic housing and an attached metal rod with a clamped-on, adjustable duct fixing flange At the bottom part of the rod, there is an air inlet (3 holes) and an air outlet The sensor mounting plate is installed in the lower part of the housing; the plate corresponds to the mounting plate of the QPA63 The upper part of the housing consists of removable cover, rubber seal and 4 fixing screws 2 versions of the cover are available: A1: With high, grey cover (standard version) A2: With transparent cover allowing readout of the QPA632 The housing is supplied complete with a ready wired 5-wire connecting cable with transparent cover without QPA63 with transparent cover with QPA632 fitted The plastic components bear the material references in compliance with ISO/DIS 11469 to facilitate environment-friendly disposal Engineering notes The CO 2 /VOC sensors operate on AC 24 V The operating voltage must meet the requirements of safety extra-low voltage (SELV) to EN 60 730 Use safety transformers with double insulation conforming to EN 60 742; the transformers must be suited for 100 % duty The transformers must be sized and fused in compliance with local safety regulations When sizing the transformer, consider the power consumption of the QPA63 The CO 2 /VOC sensors may not be used for safety related measurements of gas concentrations Duct mounting with the help of the : 1 When installing the sensor, do not reorientate the rod with respect to the direction of flow: (Max ±10 ) 2 Maximum permissible air velocity in the duct = 5 m/s 3 Maximum permissible temperature inside and outside the duct = 35 C 4 Minimum duct immersion depth = 170 mm 4/8 Siemens Building Technologies CO 2/ VOC sensors QPA63 CM1N1958E HVAC Products 05122002

Mounting notes Sensor QPA63 Location: In the room or, with the duct mounting kit, in the extract air duct When mounting in a room, a location with typical air quality should be chosen, eg on an open wall, approximately 153 m above the floor The sensor should not be mounted in niches, shelves, behind curtains, etc, or in locations where people are constantly present The permissible ambient conditions should be observed Mounting instructions are printed on the packing Duct mounting kit Location: In the extract air duct, as close as possible to the air outlets Permissible and non-permissible mounting positions: 1958Z02 When mounting, do not reorientate the rod with respect to the direction of flow The mounting kit is supplied with mounting instructions Commissioning notes Check the CO 2 /VOC sensor functions 30 minutes following operating voltage supply as follows: Check the CO 2 function: Exhale on the sensor Check the VOC function: Touch the sensor with a cotton ball dowsed in alcohol (possibly gas from lighter, without flame) Ventilation should start as soon as the preset switching level of the connected controller is reached After supplying power to the QPA632, the LEDs will flash for about 1 minute Siemens Building Technologies CO 2/ VOC sensors QPA63 CM1N1958E HVAC Products 05122002 5/8

Technical data Power supply Range of use Operating voltage (SELV) AC 24 V ±20 % Frequency 50/ 60 Hz Power consumption max 6 VA (3 W) CO 2 sensing range 02000 ppm 1) tolerance ±100 ppm VOC sensing range 0 10 V VOC Permissible air velocity in the duct <5 m/s Measured value outputs U1, U2 Functional data Voltage Current Permissible line lengths Copper cable 05 mm dia Copper cable 1 mm 2 Copper cable 15 mm 2 Copper cable 25 mm 2 Time constant t 63 with CO 2 measurement Room Duct DC 010 V ±1 ma 60 m 220 m 300 m 450 m 8 min 8 min at v air 025 m/s Connection terminals Protective data Environmental conditions Norms and standards Screw terminals for 2 x 15 mm 2 or 1 x 25 mm 2 Degree of protection of housing QPA63 without IP 30 to EN 60 529 QPA63 with IP 54 to EN 60 529 Safety class III to EN 60 730 Operation Climatic conditions Temperature Wall mounting 5+45 C Duct mounting 10+35 C Humidity (non-condensing) 595 % rh Transport to IEC 721-3-2 Climatic conditions class 2K3 Temperature 25+70 C Humidity <95 % rh Mechanical conditions class 2M2 Electromagnetic compatibility Emissions EN 50 081-1 Immunity EN 50 082-1 Weight conformity to EMC directive QPA63 1) ppm = parts per million 89/336/EEC approx 01 kg 069 kg 6/8 Siemens Building Technologies CO 2/ VOC sensors QPA63 CM1N1958E HVAC Products 05122002

Connection diagrams QPA63 G M VOC CO2 U1 U2 M 1958G01 Legend G, M Operating voltage AC 24 V (SELV) G System potential M System neutral U1 Signal output "Measured value VOC", DC 010 V U2 Signal output "Measured value CO 2 ", DC 010 V M Measuring neutral (terminals M are interconnected inside the sensor) with QPA63 G M M CO2 U2 VOC U1 B1 1958G02E 1 2 3 4 5 G M M B2 B1 (BN) (GN) (YE) (WH) (GY) X1 A1 Legend A1 B1 X1 Duct mounting kit CO 2 /VOC sensor QPA63 Terminal strip in the duct mounting kit Wire code on connecting cable of the : G/brown (1) System potential AC 24 V (SELV) M/green (2) System neutral AC 24 V (SELV) M/yellow (3) Measuring neutral (system neutral) B1/grey (5) Signal output "Measured value VOC", DC 010 V B2/white (4) Signal output "Measured value CO 2 ", DC 010 V Siemens Building Technologies CO 2/ VOC sensors QPA63 CM1N1958E HVAC Products 05122002 7/8

Dimensions (in mm) QPA63 4,2 9,5 56 60 100 90 42 56 60 1958M01 A1: 125 A2: 76 53,5 27,5 A B 1500 320 25 max 295 min 170 ø 30 42 125 8 7 6 5 4 3 2 1 1958M02 Cross-section A B 80 35 17,5 30 5 30 60 70,2 1958M03 8/8 2000 Siemens Building Technologies Ltd Siemens Building Technologies CO 2/ VOC sensors QPA63 CM1N1958E HVAC Products 05122002