SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

Similar documents
A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

SPECIFICATION: ARGONITE Engineered Fire Suppression System

FM-200 In-Cabinet Series

SECTION FM-200 FIRE SUPPRESSION SYSTEM

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

Hospitals and Major Medical Centers

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

Liberty Township Fire Department Fire Prevention Bureau. Clean Agent Fire Protection Plan Submittal Checklist

KIDDE WHDR WET CHEMICAL FIRE SUPPRESSION AND INTELLIGENT CONTROL SYSTEM FOR COOKING OPERATIONS WITH ARIES-NET MULTI-LOOP INTELLIGENT CONTROL UNIT

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

Capital Projects Group Fire Extinguishers Specification

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS

D. Reference Standards (Utilize latest editions available):

Twin-Agent Fire Fighting/Securing Systems Specifications

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Fire Safety Compliance

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

Design & Construction Standards, Revised January

Product Alert September 20, 2012

Model DDX Deluge Valve

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA. 319a. January 27, 2012

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM

CertifiedSafetyPassion. CertifiedSafetyPassion. Distributors and UL AML

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

Linear Heat Detection Engineering Specifications

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

PRODUCT LISTING DATA SHEET (Active Fire Protection Equipment)

UFGS (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

CERTIFICATE OF APPROVAL No. ME 5008 EMIRATES FIRE FIGHTING EQUIPMENT FACTORY LLC (FIREX)

CORE Protection Fire System Specification

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

CERTIFICATE OF APPROVAL No. ME 5005 EMIRATES FIRE FIGHTING EQUIPMENT FACTORY LLC (FIREX)

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

Certificate of Conformity Certificate num. Registration date Version Valid until

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

New Construction Fire Inspection Process

Carbon Dioxide Fire Suppression Systems

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

FIRE SUPPRESSION SYSTEM

Data/ Specification Sheet

TECHNICAL DATA OBSOLETE

TECHNICAL DATA. Page 1 of 5

CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

MSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

June 20, 2011 PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

UNIFIED FACILITIES GUIDE SPECIFICATIONS

special request FACTORY ASSEMBLED UPRIGHT WITH SCREW FIELD ASSEMBLED MODEL S2 SHIELD (SEE INSTALLATION SECTION) WRENCH FLATS *

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

Engineering Specifications

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

SERVICE MANUAL (v1) UL / ULC. WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK

LaserFOCUS VLF-250 Engineering Specification

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Superior by Design The Kidde ADS TM FM-200 System

standard response dry horizontal sidewall sprinklers

TotalPac X Single interlock SUREFIRE system

standard response Fusible Link Upright sprinkler VK204 (K8.0)

quick response Sprinkler 105a October 25, 2010

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

DETECT-A-FIRE Heat Detectors

TotalPac X Firecycle III Preaction Double interlock system

CERTIFICATE OF FIRE APPROVAL

TECHNICAL DATA. Viking Technical Data may be found on UNS-C84400 for Sprinkler VK202.

standard response elo upright sprinkler

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

TECHNICAL DATA. Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements that must be followed.

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

TotalPac 3 Firecyle III Deluge Remote controlled system

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

PERFORMANCE TECHNICAL SPECIFICATION *************************************************************************** SECTION D40 FIRE PROTECTION 02/18

micromatic standard response Upright sprinkler VK100 (K5.6)

Agent Tanks PCL PCL PCL PCL - 600

STANDARD/QUICK RESPONSE CONCEALED PENDENT SPRINKLER VK352-D (K8.0) TECHNICAL DATA

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

Design Criteria. Installation

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK498 (K5.8) TECHNICAL DATA

Model/Sprinkler Identification Numbers

Transcription:

1. GENERAL SPECIFICATION 1.1 An Engineered Carbon Dioxide Fire Suppression System shall be installed to meet a minimum design concentration of %, by volume in all designated spaces/areas to be protected. 1.2 The system shall be meet the design criteria for either total flooding or local application in accordance with the documents listed in section 2. 2. CODES/STANDARDS COMPLIANCE 2.1 The design, installation, testing and maintenance of the above stated Engineered Carbon Dioxide Fire Suppression System shall be in accordance to the following codes, standards and regulatory bodies: A. NFPA 12 Standard for Carbon Dioxide Fire Extinguishing Systems 2005 edition. B. Factory Mutual Approval Guide C. ANSI B1.20.1 Standard for pipe threads, General Purpose, 1992 D. ANSI B31.1 Power Piping Code E. NFPA 70 - NEC National Electrical Code F. NFPA 72 National Fire Alarm Code G. NFPA 72E Standard for Automatic Fire Detectors H. Design and installation practices set forth by system manufacturer I. Requirements of the Local Authorities Having Jurisdiction (AHJ) 2.2 The Fire suppression system, at a minimum, must have the following listings and approvals: A. FM Approved Factory Mutual Research Center B. UL Listed Underwriters Laboratories, Inc. 2.3 The manufacturer shall meet ISO 9001 requirements for the design, production and distribution of the Carbon Dioxide fire suppression systems. March 2005 1 of 9 www.kiddefiresystems.com

3. SYSTEM DESCRIPTION 3.1 All Carbon Dioxide Engineered Fire Suppression System equipment and accessories must be manufactured by: Kidde Fire Systems 400 Main Street Ashland, MA 01721 U.S.A. phone: (508) 881-2000 URL: http://www.kiddefiresystems.com 3.2 The manufacturer shall warrant all Engineered Carbon Dioxide Fire Suppression System products for 36 months from date of shipment or one (1) full year from the date of installation. 3.3 The system shall be supplied and installed by a factory-authorized, Kidde Fire Systems distributor. The distributor / Installer shall be trained by the manufacturer to calculate / design, install, test and maintain the Engineered Carbon Dioxide Fire Suppression System and shall be able to produce a certificate stating such on request. 3.4 The systems design can be total flood or local application. Total flooding applications shall be designed to meet a minimum design concentration of 34% v/v. Higher design concentrations shall be used where appropriate. 3.5 Total flood systems shall be installed in operating conditions where the ambient temperature is not less that 0 0 F and does not exceed 130 0 F. 3.6 Local Application systems shall be installed in operating conditions where the ambient temperature is not less that 32 0 F and does not exceed 120 0 F. 3.7 The Engineered Carbon Dioxide System shall consist of the following mechanical components: Agent Cylinders, Actuation Hardware, Cylinder Mounting Hardware, Pressure Operated Ancillaries, Check/Stop Valves and Distribution Nozzles. March 2005 2 of 9 www.kiddefiresystems.com

3.8 Where applicable the Engineered Carbon Dioxide System shall also include the following electrical components: Fire Alarm-Suppression Control Panel, Detection System consisting of Smoke and/or Heat Detectors, Manual Release Station(s), Audio- Visual Notification Appliances. Abort Stations shall not be used. 4. COMPONENTS 4.1 The contractor shall supply the mechanical elements of the Engineered Carbon Dioxide System that shall consist of the following components: A. Kidde Carbon Dioxide Storage Cylinder(s). 1. The Carbon Dioxide agent shall be stored as liquid under-pressure in seamless steel containers manufactured to DOT3A - 2015 or DOT3AA - 2300 standard. The fill pressure shall be not less than 850psi at 70 0 F. Cylinders shall have a stated capacity of 25, 35, 50, 75 or 100-lbs of Carbon Dioxide. Cylinders shall not be charged in excess of 68% of their water capacity. B. Kidde Carbon Dioxide Cylinder Valve(s). 1. Cylinders of 25, 35 and 50-lb capacity shall be fitted with a ½ discharge valve and a bent siphon tube to facilitate horizontal installation. Cylinders of 75 and 100-lb capacity shall be fitted with a 5/8 discharge valve and straight siphon tube. The cylinder valve shall be fitted with a safety relief device designed to relieve pressure in accordance with US DOT requirements (reference CGA S- 1.1). Cylinders shall be shipped with a steel protection cap installed over the valve and securely threaded to the cylinder neck. March 2005 3 of 9 www.kiddefiresystems.com

C. Kidde Actuation Hardware 1. Cylinder Discharge Head. The discharge valve shall accept the installation of Kidde discharge heads that facilitate; the operation of the valve; transport of the agent into the pipework and operate as check valves when disconnected from the cylinder valve. Two variations of the discharge head shall be available. The plain nut discharge head, P/N 872450 shall allow manifold pressure to discharge the cylinder. The grooved nut discharge head, P/N 872442 shall not allow manifold pressure to discharge the cylinder. Removal of the discharge head shall prevent cylinder discharge 2. Cylinder Valve Actuators (Control Heads). The Cylinder valve shall accept the installation of Kidde Control Heads. Electric/manual, Electric, Electric/cable, Cable/manual, Pneumatic and Manual only control heads may be used. Control heads must be designed for use on Kidde Carbon Dioxide discharge valves. Where the system is located in a Hazardous environment that requires electrical equipment to meet class I Div 1 Grps C & D/ Class II Div 1 E, F & G electric control heads P/N 81-100000-001 or P/N 897494 shall be used. D. Kidde Cylinder Straps or Racking 1. Cylinders shall be mounted securely using single or double hoop straps at the manufacturers specified height. (OPTIONAL) Framing kits shall be used where multiple rows of cylinders are required or where additional structural support is required. March 2005 4 of 9 www.kiddefiresystems.com

E. Kidde Check, Stop and Isolation Valves 1. Check Valves Where main and reserve agent storage containers are connected into the discharge manifold check valves must be installed to ensure the reserve bank does not actuate upon main bank discharge. 2. Stop Valves Where agent is to be distributed to one of two or more areas, directional control is to be achieved using Kidde stop valves fitted with Kidde control heads. 3. Isolation Valves An isolation valve must be provided space to prevent discharge on or in to an occupiable hazard. The valve shall be operable by a local manual control and shall prevent discharge during access or maintenance in the hazard location. A Kidde isolation valve or stop valve shall be used for this purpose. The valve shall be capable of being monitored for open and closed positions. F. Kidde Pressure Operated System Ancillaries 1. Pressure Switches Release of extinguishant shall be evidenced by the operation of a discharge pressure switch that shall provide visual indication and shall allow the connection of up to three electrical circuits for equipment shutdown and alarm notification. Where the equipment is installed in a class I, grp D hazardous location P/N 981332 shall be used. March 2005 5 of 9 www.kiddefiresystems.com

2. Pressure Trips Where the control of equipment in the hazard is to be achieved mechanically as a result of the discharge of carbon dioxide, a pressure trip P/N 874290 shall be used. The load applied to the unit shall not exceed 100-lb. G. Kidde Agent Distribution Nozzles 1. Nozzles shall be supplied with orifice coding in accordance with NFPA 12. The orifice codes shall be determined by computer hydraulic flow calculation software. Only software approved by the system manufacturer shall be acceptable. 2. Nozzles shall be selected to provide the correct phase and distribution of agent according to the system design requirements. 3. Nozzles shall be manufactured from brass and/or steel. Steel parts shall be painted or zinc plated to provide corrosion resistance. 4. Nozzles with orifices smaller than N5 shall be fitted with a strainer to prevent nozzle clogging 5. The contractor shall supply, where relevant code and the AHJ require, a complete Fire Alarm-Suppression Control System designed to operate with the Kidde Engineered Carbon Dioxide System. Kidde Fire Systems shall manufacture all components of the detection and alarm system. H. Pipe Network 1. Distribution piping, fittings and hangers shall be installed in accordance with NFPA 12, approved piping standards and the Kidde Engineered Carbon Dioxide Fire Suppression System Manual. 5. SUBMITTALS 5.1 Engineered Design Drawings A. The factory-authorized Kidde Fire Systems Distributor shall provide all required installation drawings per NFPA 12. March 2005 6 of 9 www.kiddefiresystems.com

5.2 Flow Calculation Reports A. The contractor shall provide the following information in the flow calculation report. 1. Customer Information and Project Data 2. Enclosure Information at a minimum enclosure information is to include Minimum and adjusted design concentrations, Minimum and maximum enclosure temperatures, minimum agent required and volume of enclosures, including nonpermeable volume if applicable. 3. Agent information at a minimum agent information is to include Cylinder size and part number, quantity of cylinders, main and / or reserve cylinders, pipe take off direction and the floor loading for agent cylinder. 4. Pipe network information at a minimum pipe network information is to include pipe type, pipe diameter, pipe length, change in direction or elevation, pipe equivalent length and any added accessory equivalent length. In addition, the following nozzle information shall be provided; number of nozzles and identification of enclosure location, flow rate of associated nozzle, nozzle nominal size, nozzle type and nozzle orifice code. 5. Detailed list of all Pipes and Pipe Fittings designed in the pipe network 5.3 Commissioning Equipment List A. The contractor shall provide a commissioning equipment list for each installed Carbon Dioxide Fire Suppression System. The equipment list shall identify all installed equipment and configurations. 5.4 Test Plan A. The contractor / Installer shall submit a test plan which describes how the system equipment and room integrity shall be tested. This shall include a step-by-step description of all tests and shall indicate type and location of test apparatus to be used. At a minimum, the tests to be conducted shall be per NFPA 12 and any additional supplemental tests required by the AHJ. Tests shall not be scheduled or conducted until the engineer of record approves the test plan. 5.5 Installation Drawings A. Four (4) sets of installation drawings for each installed Carbon Dioxide Fire Suppression System and One (1) set of the calculation report, owners manual and product data sheets shall be submitted to the end-user / owner. March 2005 7 of 9 www.kiddefiresystems.com

B. Upon completion of installation and commissioning acceptance, two (2) sets of As- Built installation drawings and One (1) set of the calculation report for each installed Carbon Dioxide Fire Suppression System shall be given to the owner / end-user for use and reference. 5.6 Operation and Maintenance Manuals A. Two (2) copies of the Kidde Carbon Dioxide Fire Suppression System, Operation and Maintenance Manual shall be submitted after complete installation. 6. SYSTEM INSTALLATION AND COMMISSIONING 6.1 Carbon Dioxide Fire Suppression System Equipment A. The contractor shall install the system in accordance with the manufacturer s installation, operation and maintenance manual. 6.2 Training Requirements A. The contractor shall be certified and trained by the manufacturer on installation, design and maintenance of the Kidde Engineered Carbon Dioxide Fire Suppression System. 6.3 Commissioning A. The commissioning agent shall verify that the system has been designed and installed in accordance with the specifications detailed in the codes, standards and documentation as listed in section 2. B. All signage, safety training instruction and on-site documentation shall be reviewed prior to system testing. C. The commissioning agent shall verify that the that the system is in operable condition by performing a controlled discharge test D. Commissioning shall not be completed until the system can be left in a (re)charged live condition. 6.4 Routine Maintenance A. Routine maintenance and inspection shall be performed as recommended by the manufacturer s installation, operation and maintenance manual. Inspection shall be carried out at least every 30 days in accordance with NFPA 12: 2000 edition. At a minimum the routine maintenance will include the following: 1. Verification of system operability. March 2005 8 of 9 www.kiddefiresystems.com

2. Visual Check of Pipe network and distribution nozzles 3. Charge mass verification of all Carbon Dioxide cylinder(s) 4. Inspection of all cylinders and equipment for damage, corrosion or tampering. March 2005 9 of 9 www.kiddefiresystems.com