BACnet Points List for Single Compressor Water to Water PROSSWWE-01

Similar documents
BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller

WaterFurnace FX10 Application Guide Reversible Chiller

York 25-Ton VAV Rooftop Unit

OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES

I/O ZONE 560/583 USERS GUIDE

Reciprocating Chiller

CXM/DXM. Application, Operation & Maintenance Instructions 97B0003N08 Revision: 01/10/05. CXM/DXM Digital Heat Pump Controllers.

Introduction. What is the W2W Open controller?

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

MicroTech Water-Cooled Screw Chiller Controller

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS

I/O ZONE 560/583 AND OPERATION MANUAL

L SERIES UNITS 504,908M. 10/2004 Supersedes 9/2004

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

UPM I. Unit Protection Module. Installation and Operation Manual (2015/06)

L SERIES UNITS 505,191M. 4/2006 Supersedes 504,908M

Verasys System Operation Overview Technical Bulletin

Heat Pump Defrost Board Replacement Kit

Table of Contents. W2W Open

DXM CONTROLS. DXM Digital Heat Pump Controllers. Application, Operation, & Maintenance. Table of Contents

Operation and Maintenance Manual OM MicroTech III Unit Controller with I/O Expansion Module for Two Compressor Water Source Heat Pumps

Digital Precise Air Control - DPAC

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Heat Pump Water Heater (Generation 4) Troubleshooting (Effective 1 Nov 2016)

Table of Contents. WSHP Open v3

User s Manual

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

Reference Guide for Microprocessor Controller

UNIT DIGITAL CONTROLS APPLICATION, OPERATION & MAINTENANCE

TC-9102 Applications

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

DXM2 Digital Heat Pump Controller

Installation and Maintenance Manual OM

MicroTech Series 200 Centrifugal Chiller

Application and Instructions for Field Adjustment of the Control (Model FX06) in Digital Control Option D12A, Space Control with Discharge Air Reset

Document # R01

SPECIFICATION CATALOG. Console 0.75 to 1.5 Tons. Geothermal/Water Source Heat Pump

L SERIES UNITS 504,520M. 10/2001 Supersedes 504,413M

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

1F90W-51 OPERATION GUIDE WHITE-RODGERS. Operator: Save this booklet for future use! 5 Day/2 Day Electronic Digital Thermostat WHITE-RODGERS

HP727S. Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS

Operating Functions Temperature Parameters

Rooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422

200i/KN2, KN4 Firmware Revision Sheet

OPERATION MANUAL. ComfortSense 3000 Series Model No. L3021H Non Programmable Thermostat. Table of Contents. Description. Initial Thermostat Power up

OPERATION MANUAL. ComfortSense 3000 Series Model No. L3011C Non-Programmable Thermostat. Table of Contents. L3011C Thermostat

OCT For Cool Touch Controller OPERATOR S MANUAL. Technicold Marine Systems

CCH/CCW, VFC/VFW, MHC/MHW, LVC/LVW

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

Some alarms can be manually cleared from the current alarms list. This is indicated for the alarms where this is possible.

1F90-71 OPERATION GUIDE WHITE-RODGERS. Operator: Save this booklet for future use! 5 Day/2 Day Electronic Digital Thermostat

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Ice Rink (Single and Dual Configurations) Custom Control Features

MicroTech Self-Contained Air Conditioning System

HEAT HEAT HEAT COOL COOL

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

1F91W-71 OPERATION GUIDE WHITE-RODGERS. Operator: Save this booklet for future use! Multi-stage Electronic Digital Thermostat

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Water Source Heat Pump Module Technical Guide

SPECIFICATIONS for AIR CONDITIONING CONTROLLER ZONE CONTROL

Contents. FX-1 Operations Manual Micro Air Corporation 124 Route 526 Allentown, NJ 08501

Parts Diagram. Up button. Down button. Right (fan) button. Left (system) button. RC/RH Jumper. Field programming pins

SPECIFICATION CATALOG. Low Sill Console 0.75 to 1.5 Ton. Geothermal/Water Source Heat Pump

OWNER S MANUAL. Part Number P CONTENTS

SPECIFICATION CATALOG. NSW Commercial 1.5 to 6 Tons. Geothermal Hydronic Heat Pump

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

Safety & Installation Instructions

NDW Installation Manual

Smart Temp. Model

Refrigeration and Air Conditioning Controls. User s manual. Degree Master Controller in AKC 55 Systems ADAP-KOOL REFRIGERATION AND AIR CONDITIONING

ATA11U03. Non-Programmable Heat Pump Thermostat. Installation Manual. 97B0082N06 Revised: 16 September, 2013 FOR INSTALLER AND OWNER ONLY

HEAT PUMP PROGRAMMABLE THERMOSTAT

Heating and Air Conditioning

OPERATING INSTRUCTIONS

Heating and Air Conditioning

RCS Residential Control Systems Inc.

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

Installation Instructions

TXU Energy ithermostat In-Home User Manual. Model: 1F Day Programming

Pioneer Gold Controller Technical Guide

Q-Logic Digital Controls The Q3 and Qht for Direct Expansion Systems

MicroTech Series-200 Flooded Screw Chiller

NDW Installation Manual

Document # R00

HEAT HEAT HEAT COOL COOL PUMP OWNER S MANUAL 7-DAY TOTALINE

1F97-51 OPERATION GUIDE WHITE-RODGERS. Operator: Save this booklet for future use! 7-Day Programmable Electronic Digital Thermostat

Product Manual SZ1009

MicroTech Rooftop/RMC

Reference Guide for Microprocessor Controller

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION Telephone:

Model Universal Oil Primary Control

tcu.z Commercial Programmable Thermostat Installation Instructions

SPECIFICATION CATALOG. Commercial 7 to 25 Tons. Geothermal/Water Source Heat Pump

Transcription:

The network variables will be listed by point type instance convention. 2:1 would mean point type 2, point instance 1. All volatile (Output) type points will revert to the uncommanded values after a power interruption. These have no limit on the number of writes in a lifetime. The nonvolatile (Value) type points have their values stored in flash memory and they retain their values through a power outage. These have a limited lifetime number of write cycles, about 2,000,000. Analog Input (Type 0) 0:1 Source Frz [Read, shows the refrigerant temp entering the source heat exchanger] 0:2 Load Frz [Read, shows the refrigerant temp entering the Load heat exchanger] 0:3 Enter Load Temp [Read, water temperature entering load heat exchanger] 0:4 Leave Load temp [Read, water temperature leaving the load heat exchanger] 0:5 Enter Source Temp [Read, water temperature entering the source heat exchanger] 0:6 Leave Source Temp [Read, water temperature leaving the source heat exchanger] 0:7 Source Frz Setpt [Read, low temperature limit of the source heat Exchangers to avoid freezing] 0:8 Load Frz Setpt [Read, low temperature limit of the load heat Exchangers to avoid freezing] 0:14 Alarms Enumerated [Read, shows the active alarm condition of the machine: 0=No alarms, 1=Load Flow Switch, 2=Compressor Low Suction Pressure, 3=Source Low Temp alarm, 4=Load Low Temp alarm,5=source Flow Switch, 6=Hi Pressure Alarm, 7=Bad Sensor Source Low Limit, 8=Bad Sensor Load Low Limit,9=Loss of Charge, 10=High Limit Shutdown]

Multistate Input (Type 13) 13:1 Mode of Operation [Read, 1 means Unit in Auto, 7 means unit in Shutdown] 13:2 Comp Cmd Status [Read, 1 means the compressor is Off ; 2 means the compressor is On] 13:3 Rev Vlv Status [Read, 1 means heating; 2 means cooling] 13:4 LoadPmpStatus [Read, 1 means accessory 1 is Off; 2 means accessory1 is On] 13:5 SrcPmpStatus [Read, 1 means accessory2 is Off; 2 means accessory2 is On] 13:6 Alarm Status [Read, 1 means the alarm is Off; 2 means the alarm is On] 13:7 Comp Status Prove [Read, 1 means the compressor is Off; 2 means the compressor is On] optional field mounted 13:8 BI9 Status [Read, 1 means open contacts; 2 means closed contacts] 13:9 Load Flow Status [Read, 1 means the switch is Off; 2 means the switch is On] 13:10 Src Flow Status [Read, 1 means the switch is Off; 2 means the switch is On] 13:11 BI6 Status [Read, 1 means open contacts; 2 means closed contacts] Multistate Output (Type 14) These are volatile memory and allow unlimited writes. 14:1 Compressor Enable [Write, Control lead compressor (Y1), 1=OFF, 2=ON.] 14:2 Valve Enable [Write, Control reversing valve (B), 1=Cooling; 2=Heating.] 14:3 Emerg Override [Write, 1 puts the unit in normal operation 5 puts the unit in shutdown] 14:5 Alarm Reset [Write, Changing the value from 1 to 2 Will reset lock-out alarms]

The Envision heatpump is equipped with an OEM DDC controller produced by Johnson Controls, Inc. This controller the FX10 has 6 analog inputs, 12 digital inputs, and 9 digital outputs. The FX10 is depicted below. Physical I/O Assignment The asterisk * denotes a point that is integral to the heatpump control algorithms. Channel Name Pin Number Type AI1 Page1-LoadEWT(AI-1) 36 A99 AI2 Page1-LoadLWT(AI-2) 33 A99

AI3 Page1-SourceLWT(AI-3) 25 A99 AI4 Page2-SourceFrzProtect AI4 29 A99 AI5 Page2-LdFrzProtTemp(AI- 5) 27 A99 AI6 Page1-SourceEWT(AI-6) 31 A99 DI1 Page2-ComprProve(BI-1) 56 Binary DI2 Page2- EmergencyShutdn(BI2) 54 Binary DI3 Page2-LoPrsSwitch(BI-3) 53 Binary DI4 Page2-SrcFrzStptSel(BI-4) 52 Binary DI5 Page2-LdFrzSetptSel(BI- 5) 51 Binary DI6 Page2-BI-6 50 Binary DI7 Page2-Y1/SysEna(BI-7) 48 Binary DI8 Page2- SourceFlowSwitchBI-8 47 Binary DI9 Page2-O/Heat-Cool (BI-9) 46 Binary DI10 Page1-PrimaryOvride(BI- 10) 45 Binary DI11 Page2-1stStgHiPrsSw(BI- 11) 44 Binary

DI12 Page2-LoadFlowSw(BI-12) 43 Binary DO1 Page1-ReversingVlv(BO- 1) 3 Binary DO2 Page1-Compressor(BO-2) 4 Binary DO3 Page1-2ndaryHeat/Cool BO-3 7 Binary DO4 Page1-2ndaryUnitEna(BO- 4) 10 Binary DO5 Page1-2ndaryPrimryOvr(BO5) 11 Binary DO6 Page1-AlarmOutput(BO-6) 13 Binary DO7 Page1-Accy1 Output(BO- 7) 15 Binary DO8 Page1-Accy2 Output(BO- 8) 18 Binary DO9 Page1- LoadWtrVlvOut(BO-9) 19 Binary

Sequence of Operation When the controller is first powered up, the outputs will be disabled for a random start delay time. The delay is provided to prevent simultaneous starting of multiple heat pumps. Once the timer expires, the controller will operate normally. A restart status variable is available for indication of this occurrence. This delay will be used after every power failure, as well as the first time the compressor is started after the control exits the emergency shutdown mode. The default time period for the start delay will be random between 1 and 120 seconds. The source flow proving switch shall be a normally open flow switch that will close when the water flow through the source side heat exchanger reaches an acceptable level. The source flow proving switch must be closed 15 seconds prior to enabling the compressor output (BO-2). If the source flow proving switch opens at any time the compressor output (BO-2) must be disabled immediately. Once the flow switch has opened the alarm output will be energized after a 5 minute delay time. If the flow switch closed at any time after it has been sensed open the fault will clear and the unit will return to normal operation. The source side freeze protection selection input allows you to adjust the source side freeze protection temperature set point (AI-4). When the jumper is installed on BI-4 the source side freeze protection temperature set point is factory set for 30 F. When you remove the jumper on BI-9 the source side freeze protection temperature set point will be 15 F. The load side freeze protection selection input allows you to adjust the load side freeze protection temperature set point (AI-5). When the jumper is installed on BI-5 the load side freeze protection temperature set point is factory set for 30 F. When you remove the jumper on BI-10 the load side freeze protection temperature set point will be 15 F. Both Water-to-Water types are operated by externally generated compressor and reversing valve calls ONLY. There is no internal temperature setpoint operation mode in these units. The compressor and reversing valve calls may be issued via the terminal board connections or over the supervisory network. When a Y1 call is issued, the X1 output will turn on. After a 90 second delay (to allow time for the isolation valve to open) the compressor will run. Cycling the reversing valve will shut down the compressor. The Compressor Fixed On Delay Time will ensure that the compressor output (B02) is not enabled for (90) seconds after the control receives a call to start the compressor. This will allow for the isolation valve to open fully before the compressor starts.

The compressor minimum on delay will ensure that the compressor output is enabled for a minimum of (2) minute each time the compressor output is enabled. This will apply in every instance except in the event the high pressure switch is tripped or emergency shutdown then the compressor output will be disabled immediately. During a heating/cooling cycle, the reversing valve will be positioned for heating/cooling operation. If an aqua stat is being used, the aqua stat will command the reversing valve On or Off based on a call for heating/cooling. If the compressor short cycle time delay has been satisfied, the compressor and accessory outputs 1 and 2 will turn on after the fixed compressor start delay timer has been satisfied. When heating/cooling is no longer required, the compressor and accessory outputs 1 and 2 will be turned off immediately after the compressor minimum on delay has been satisfied. After the compressor output is turned off, it will remain off for the time specified in the compressor short cycle time delay. The controller is allowed to operate the heat pump in the heating/cooling mode regardless of the outdoor air temperature. The emergency shutdown mode can be activated by a command from a facility management system or a closed contact on BI-2. The default state for the emergency shutdown data point is off. When the emergency shutdown mode is activated, all outputs will be turned off immediately and will remain off until the emergency shutdown mode is de-activated. The first time the compressor starts after the emergency shutdown mode has been de-activated, there will be a random start delay present. Lockout mode can be activated by any of the following fault signals: refrigerant system high pressure, refrigerant system low pressure, heating freeze protection, and low flow on either the source or load sides of the unit. When any valid fault signal remains continuously active for the length of its recognition delay, the controller will go into fault retry mode, which will turn off the compressor. After the Compressor short cycle delay, the compressor will attempt to operate once again. If three consecutive faults are recognized during a single heating or cooling demand, the unit will go into lockout mode, turning off the compressor and enabling the alarm output until the controller is reset. The fault count will automatically reset when the heating or cooling command becomes satisfied. The lockout condition can be reset by powering down the controller, or by a command from the facility management system.