Installation Instructions for 116DEGEX-FJ-(R) AdaptaBeacon Fire Alarm Strobe Lights for Use in Hazardous Locations CEILING 116EX-C 3/ CONDUIT ENTRIES PENDANT 116EX-P 3/ CONDUIT ENTRY 116EX-C (WALL MOUNTED) 3/ CONDUIT ENTRIES WALL 116EX-B 3" HUB 116 SERIES HOUSING AND GLOBE ASSEMBLY WITH GUARD Figure 1. Mounting Options Description The 116DEGEX-FJ (Gray housing) and 116DEGEX-FJ-R (Red housing) AdaptaBeacons are in-rush current limited strobe lights. When pendant, wall or ceiling mounted, and with dome guard removed, they meet or exceed the requirements of UL 1971 Signaling Appliance for the Hearing Impaired. The strobe is intended for indoor use in UL 1971 (signal appliance for the hearing impaired) listed compatiable fire alarm systems. The strobe flashes a 3 - degree beam of light approximately 65 times per minute with a UL 1971 125 cd ceiling and cd wall light output per Figure 7. The strobe is also UL 1638 (visual signal appliance, private mode) listed with dome guard installed for both indoor and outdoor use, and other applications requiring electrical supervision of the signaling circuit field wiring. In addition, the strobe is rated for outdoor use in Canada, the 116DEGEX-FJ(R) is listed to ULC-S526-02 (Visual Signal Device for Fire Alarm Systems), suitable for indoor and outdoor applications. The strobe features an enhanced synchronization circuit to comply with the latest requirements of UL 1971 and CAN/ ULC-S526-02. Synchronized operation requires a separately installed synchronization control module. See Table 1a for a list of compatible synchronization modules. When assembled with an available mounting subassembly (116EX(R)-P, 116EX(R)-C, or 116EX(R)-C with 116EX(R)-B and in accordance with these instructions, the 116DEGEX-FJ-(R) visual strobe signal is UL Listed as a Signaling Applicance for the hearing impaired for use in Class I, Division 1, Groups C and D, Class I, Division 2, Groups A, B, C and D, Class II Division 1, Group E, F and G, Class II, Division 2, Group F and G, and Class III Division 1 and 2 hazardous locations with Operating Temperature Codes per table 3. See Table 1 for Electrical Specifications. This strobe is UL and cul Listed as a Type 3R and 4X enclosure. See Figure 1. Installation Install this unit in accordance with the applicable requirements in the latest edition of the National Fire Alarm Code (NFPA 72), National Electrical Code (NFPA 70), and Canadian Electrical Code and CAN/ULC-S524-01/Standard for the Installation of Fire Alarm Systems. To reduce the risks of ignition of hazardous atmospheres and shock, do not apply power to the unit until installation has been completed and unit is tightly assembled and secured. 1. Mount using the following applicable method. a. Pendant Mount Models (Figure 2): Install the catalog number 116EX(R)-P, pendant mounting module, to the 116DEGEX-FJ-(R) main housing, tighten set-screw. Install explosion-proof hanger box (not supplied). Secure 3/ (19 mm) NPT threaded conduit (not supplied) to the box. Install the unit on the conduit. Ensure conduit enguages at least five full threads and then tighten the set-screw to secure the pendant mount module to the conduit. Connect field earth ground wire to ground screw or earth ground via conduit system. Wire in accordance with Figure 5. See table 3 for required supply wire temperature ratings. http://www.edwardssignaling.com Phone: (800) 336-46 Fax: (800) 454-2363
6 3/ Set Screw(s) 12" 12 3/ Set Screw 5/16" 1" 13" 13 3/ 7 1/ 7 1/ Figure 2. Detail of Pendant Mounting Figure 3. Detail of Ceiling Mounting 12 9/16" 9 7/16" 1" 6 3/ 16 1/16" 5/16" 16 13/16" Set Screws Figure 4. Detail of Wall Bracket Mounting NOTE: DC polarity of circuit shown in supervisory state (signal inactive). Circuit polarity to reverse to activate signal. Electrical supervision requires wire run to be broken at each device. Device for constant input voltage. Do not connect to coded or pulsating voltage. KEY: Light symbol - NOTE: From Power Source or Previous Signaling Device Series 116DEX Series 116DEX Figure 5. Wiring Diagram Wire nut symbol - End-of-Line Resistor, when required with supervised system For non-fire alarm use, i.e. without field wire supervision, installer can tie the two white leads together and tie the two black leads together.
b. Ceiling Mount Models (Figure 3): Mount the catalog number 116EX(R)-C, ceiling/wall mounting module, using appropriate hardware (not supplied) suitable for the mounting surface. Connect field earth ground wire to ground screw or earth ground via conduit system. Wire the unit in accordance with Figure 5. See Table 3 for required supply wire temperature ratings. Install main housing to Ceiling mount module. Tighten the set-screw to secure the 116DEGEX-FJ-(R) main housing to the ceiling mount module. c. Bracket Mount Models (Figure 4): Install the catalog number 116EX(R)-C ceiling/wall mouting module using appropriate hardware (not supplied) for the mounting surface. Install the catalog number 116EX(R)-B wall mounting elbow to the 116DEGEX-FJ-(R) main housing. Tighten the set -screw to secure wall mounting module to the main housing. Run the unit's wiring through the elbow to the wall box. Connect field earth ground wire to ground screw or earth ground via conduit system. Wire the unit in accordance with figure 5. See table 3 for required supply wire temperature ratings. Install Table 1. 116DEGEX-FJ-(R) AdaptaBeacon Strobe Light Electrical Specifications Voltage Designation* Max RMS Operating Current (A)** Regulated 24V DC 0.5 Regulated 24V FWR 0.5 CAUTION: To prevent damage to the signal circuit and to otherwise assure continued proper functioning, DO NOT operate the unit outside of the Regulated 24V DC/FWR voltage range of 16-33V DC/FWR (US), -31V DC/FWR (Canada). *The designation Regulated 24 refers to the voltage range of 16-33 volts. **The Max RMS Operating Current is defined as the current rating over the entire voltage range. Model names Table 1a. Compatible Synchronization Modules Model numbers Auto-Sync Output SIGA-CC1S SIGA-MCC1S Module SIGA-CC1S-LG SIGA-MCC1S-LG Genesis signal Master- ADTG1M-RM MG1M-RM Remote Mount EG1M-RM XLSG1M-RM G1M-RM ZG1M-RM G1M-RM-LG main housing and 116EX(R)-B elbow subassembly to ceiling mount module. Tighten the set screw to secure the 116EX(R)-B elbow to the ceiling mount module. To reduce the risks of ignition of hazardous atmospheres and shock, keep assembly tightly closed when circuits are energized. 2. Apply power to the unit and ensure proper function. Maintenance atmospheres and shock, keep assembly tightly closed when circuits are energized. atmospheres and shock, disconnect from the supply and circuit and allow five (5) minutes for stored energy to dissipate before disassembling the unit. Disassemble the unit as follows (Figure 8): 1. Loosen the (3) guard screws and remove the guard. 2. Loosen the globe and ring assembly set screw. Insert a suitable tool into the notches in the globe and ring assembly and loosen the assembly by prying in a counterclockwise direction. Remove the ring and globe assembly. 3. Refer to Table 2 for the correct replacement catalog number and replace the necessary part. 4. To replace, simply screw the unit on until it seats firmly onto its gasket. Tighten the unit another 1/8 to 1/4 turn. Tighten the setscrew. 5. Reinstall the guard, where applicable, and secure using the three supplied screws. 6. After the unit is assembled, apply power and make sure the unit functions properly. Table 2. 116DEGEX-FJ Mounting Options Catalog Electrical Conduit Flash Strobe Tube Description Number Ratings Size Rate Replacement Housing Less 116DEGEX-FJ-(R) 16-33V DC (US) N/A Approx. N/A Mounting Module -31V DC (Canada) 65 fpm 0.5/0.5A Ceiling/Wall 116EX(R)-C N/A 3/ NPT N/A N/A Mounting Module Pendant 116EX(R)-P N/A 3/ NPT N/A N/A Mounting Module Wall Bracket 116EX(R)-B N/A N/A N/A N/A Mounting Module
Effective Candela Light Output for Wall Bracket Mount Vertical Plane (Zero degree angle at side of globe) UL REQUIRED CD FOR RATING -90 0-85 -80-75 -70-65 - -55 - -45 - -35 - -25 - -15 - -5 0 degrees 5 15 UL 1971 Hearing Impaired: cd wall 90 45 55 65 70 75 80 85 35 25 NOTE: Optional dome guard shown, candela output readings taken without optional dome guard installed. Effective Candela Light Output for Ceiling Mount X & Y Planes (Zero degree angle at bottom of of globe) 75 80 85 90 95 0 5 1 115 1 125 1 135 1 1.0 1.0 1.0 0.0 90.0 80.0 70.0.0.0.0.0.0.0 0.0 180 175 170 165 1 155 1 145 1 135 1 125 1 115 1 75 80 0 5 85 90 95 35 35 45 45 55 55 65 70 65 70 145 1 25 15 5 degrees 0 5 15 25 155 1 165 170 UL REQUIRED CD FOR 125 RATING UL 1971 Hearing Impaired: 125 cd ceiling NOTE: Optional dome guard shown, candela output readings taken without optional dome guard installed. Figure 7. Light Output Patterns for 116DEGEX-FJ-(R)
Table 3. Ratings Operating Temperature Ambient Supply Wire Class I, Div. 2 Class I, Div. 1 & 2 Class II & III, Div. 1 Class II & III, Div. 2 Temp. Temp. Marking Groups A, B Groups C, D Groups E, F, G Group F, G C 75 C T2B (2 C) T6 (85 C) T4A (1 C) T4A (1 C) 55 C 90 C T2B (2 C) T6 (85 C) T4 (135 C) T4 (135 C) 65 C 5 C T2B (2 C) T6 (85 C) T3C (1 C) T3C (1 C) atmospheres and shock, keep assembly tightly closed when circuits are energized. atmospheres and shock, disconnect from the supply and circuit and allow five (5) minutes for stored energy to dissipate before disassembling the unit. Figure 8. Disassembly of the 116DEGEX-FJ-(R) AdaptaBeacon
U.S. T 800-336-46 F 800-454-2363 Canada T 519 376 24 F 519 376 7258 Asia T 852 2907 88 F 852 2142 63 Australia T 61 3 9259 4700 F 61 3 9259 4799 Europe T 32 2 725 11 F 32 2 721 86 13 Latin America T 5 593 41 F 5 593 www.edwardssignaling.com
P/N 31131 OFFSET SPEC INSTALLATION INSTRUCTIONS FOR CATALOG SERIES 116DEGEX-FJ ADAPTABEACONS FOR USE IN HAZARD- OUS LOCATIONS (1) 11" X 17" SHEET AND (1) 8 1/2" X 11" SHEET PRINTED BOTH SIDES. FOLD 11" X 17" SHEET IN HALF AND IN- SERT 8 1/2" X 11" SHEET. FOLD TWO MORE TIMES TO DIMENSIONS SHOWN ON DETAIL WITH PART NUMBER ON THE OUTSIDE. MATERIAL: STANDARD WHITE OFFSET STOCK CHARACTERS: TO BE BLACK ON WHITE BACKGROUND NOTE: MECHANICALS HAVE ALREADY BEEN REDUCED TO ACTUAL SIZE. RETURN MECHANICALS TO: TECHNICAL WRITING EDWARDS SIGNALING 41 WOODFORD AVE. PLAINVILLE, CT 062 P/N 31131 FOLD DETAIL REFERENCE ONLY ECN: -C1923 Issue: 3 File: 31131 Approved by: GM