7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

Similar documents
1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S20 User Guide. Arc Fault Monitor. Advanced Protection Devices. relay monitoring systems pty ltd. User Guide. Test Manual

7XG3130 ReyArc30 Optical Arc Fault Sensor Energy Management

1S26 User Guide. Arc Fault Monitor + Integrated Current Check Relay. Advanced Protection Devices. relay monitoring systems pty ltd.

7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for Infrastructure & Cities.

Reyrolle Protection Devices. 7PG26 DAD High Impedance Current Relay. Answers for energy

VAMP 120 & 121. Arc flash detection units. Product picture

REA 105 Arc Protection Module. Operator s Manual

VAMP 120 & 121. Arc Flash Protection Units. Arc Protection. Customer benefits

VAMP 121. Arc protection unit. User manual

PGR-8800 TECHNICAL FAQ

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits

Electrical Energy department

D1000 Arc-fault Protection System

Arc Fault Protection System D1000

7SG17-Rho 3 Multifunction Protection Relays Answers for energy

Operation and use. Functions and characteristics

Delta XRD. Supervision Relays. rms A U X I L I A R Y T R I P P I N G S U P E R V I S I O N

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24

Welcome to Hager Presentation

i-con Switchgear Condition Monitoring HV Switchgear Integrated Substation Condition Monitoring ISCM Answers for Infrastructure & Cities.

SEL Arc-Flash Solutions

SEL Arc-Flash Solutions

AQ 100 Series. Arc Flash Protection System

LINETRAXX RCMA420. Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24..

Applications and Discussions of Arc Flash Protection Relay as a Main Busbar Protection in MV Switchboards

C-Bus Four Channel Analogue Output Unit Installation Instructions

CIRCUIT BREAKER FAIL PROTECTION

Table of Contents. Protective Relays

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage

Instruction Manual December 2001 ENACOCU02

1.7. Insulation fault evaluators EDS460/490 EDS461/491

Monitoring Devices 11/1

1X30 Trip Circuit Supervision Relay

1.7. Insulation fault evaluators EDS460/490 EDS461/491

17 TH APRIL 2017 Switch Board Monitoring Protecting Switchboard. Courtesy of ABB. Paul Lee

M2500 Engine Controller Installation Manual

BE1-50/51B with S1 Case or FT-11 sized Case and Cover For non-retrofit applications, see Product Bulletin UHD.

EARTH LEAKAGE RELAY. User Manual - Issue 1.0

C-Bus Four Channel General Input Unit Installation Instructions

Panel Mounted Fault Annunciator Series

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

MR3CCUHV Temperature/Defrost Control

LC3000 Level Controller Installation and Maintenance Instructions

Soft Starter AC Semiconductor Motor Controller Type RSBS23..A2V.2C24..

Electrical Safety Through Design. Mersen EP formerly Ferraz Shawmut

SECTION AUTOMATIC TRANSFER SWITCHES

Development of standards for MV Switchgear for Arc Flash protection. ABB Group May 20, 2013 Slide 1

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

SENTINEL D - Fault Passage Monitoring

Molded Case Circuit Breakers, Bulletin 140G

Analog Annunciator Unit SACO 16 A3. Product Guide

Scope of functions 32 VAR 51/37 64 DC 64 R

Instruction Manual August sitrans CU 02

1S25 User Guide. Arc Fault Monitor. Advanced Protection Devices. relay monitoring systems pty ltd. User Guide

LINETRAXX VMD420. Multi-functional voltage relay for 3(N)AC systems, frequency/overvoltage/undervoltage, phase, phase failure, asymmetry

Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents)

Annunciator Unit SACO 16 D1. Product Guide

MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack

Numerical Relay MELPRO TM -S Series

SACE PR021/K SIGNALLING UNIT

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

Annunciator unit. Application

4 & 8-POINT ANNUNCIATORS Instruction Manual

SENTINEL A - Fault Passage Indicator

CMD420 / CMD421 Series

Insulation fault evaluator EDS460-DG

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Panel Mounted Fault Annunciator Series

Power Supply Display Module PSDM. Installation and Operation Manual

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

Guide Specification Model CTG Automatic Transfer Switch

Laboratory Honeywell Technology Solutions, Bangalore-EMC Lab, 19/2, Devarabisanahalli Village, K.R. Puram, Varthur Hobli, Bangalore, Karnataka

Pump Logic User Manual CB-1000 P/N ILK-CB1000-1

Arc Fault - Minimize damage

Remote alarm indicator and test combination MK2430

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Microgrid Fault Protection Based on Symmetrical and Differential Current Components

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

CU-02 with Senaco Plus

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

1. General Safety Block diagram Description of operation Connections Commissioning...11

PD154 & PD158 VIGILANTE II ANNUNCIATORS Instruction Manual

ECO N DATE DESCRIPTION OF CHANGE CHG

Specification/ Data Sheet

Mors Smitt Industrial Technology. Substation Protection & Control. High Performance Electromechanical Relays. RMS Mors Smitt A Wabtec company

AO Annunciator Module

RE-PR3-E-27 3-Phase Panel Mount 27kW

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

Engineering Guideline. pac-carriers Type for Yokogawa ProSafe-RS

PIR movement and presence detectors 10 A

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

Transcription:

Reyrolle Protection Devices 7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

7XG3120 - Arc Fault Monitor Relay The over-current caused by an arc is, due to its resistance, lower than the over-current caused by a metallic short circuit. The over-current caused by the arc may also be lower than the protection start current when energising circuits or starting large motors. The consequence of these conditions is that a protection system based solely on over-current detection cannot effectively discriminate between normal system currents & an arc fault condition: For moderate arc fault currents the trip time of the overcurrent IDMT stage will be too slow; For very low arc fault currents the instantaneous trip stage of a standard over-current relay cannot be set low enough. ARC Fault Protection Features Compact economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high-speed, tripping duty output contacts Push-button reset Continuous arc sensor supervision Integrated self supervision Fail alarm contact AC or DC operation 3 options for auxiliary supply range, suitable for 24 to 250V supplies Introduction Medium voltage switchgear is a key element in the power supply chain. Existing protection systems operate effectively under most circumstances, but they are too slow to effectively clear arcing short circuits before significant damage is caused. Arcing faults can occur as a result of insulation breakdown due to equipment age and/or poor maintenance. The degree of damage caused by arcing depends principally on the duration of the arc. If an arc lasts only 100ms, the switchgear needs to be checked & the insulation resistance measured before power can be re-established. With a 200ms arc, the power supply will be interrupted; the switchgear must be checked; power is re-established only after minor repairs. In the event of a 500ms arc the supply is interrupted, metal parts of the switchgear are destroyed & poisonous gases are emitted. A 1s arc destroys most of the switchgear & may cause a fire, injury to personnel & damage to property. Arc fault protection is a technique employed for the fast clearance of arcing faults on BUS bars & within metal clad switchgear & associated cable boxes. The arc is detected using an optical sensor & the signal input to a protection device which also monitors the load current on the system. A trip signal can be achieved in less than 10 ms using arc detection only or within 20 ms when using overcurrent check. This is considerably faster than a traditional IDMT overcurrent relay & provides additional protection from the onset of arcing faults with relatively low fault currents. Arguably the greatest risk of arc fault damage exists at the CB cable termination & in the CB chamber itself due to the slow clearance times of the IDMT feeder protection. The problem of arc faults is most prevalent in older metal clad switchgear which already has operational protection systems. The (Reyarc20) Arc Fault Monitor has therefore been designed for the following applications: Existing Switchgear Where a requirement exists to retrofit arc fault protection to metal clad switchgear utilizing the existing overcurrent protection relay. New Switchgear Where a requirement exists to install arc fault protection to new switchgear for integration with the customer preferred overcurrent feeder protection relay. Switchgear Applications Switchgear ARC Protection Risk of arc fault damage exists at the CB cable termination & in the CB chamber itself. The CB cable termination is particularly at risk to ingress of moisture & rodent damage. One, two or three arc sensors may be connected to the Arc Fault Monitors as depicted in the single line application diagrams (Figures 1, 2 & 3). Figures 1 & 2 show the trip signals being used to trip the feeder circuit breaker in the event of an arc fault occurring at any sensor provided the overcurrent relay starter contact is picked up. In these applications the overcurrent check stage is optional as the consequence of a single feeder outage is less than the loss of an entire BUS. Figure 3 shows an application where a single is applied for the protection of the Cable box, CT chamber & CB chamber using three sensors. In this configuration one arc trip output is used to trip the feeder circuit breaker in the event of an arc fault in the cable box / CT chamber. The second trip Siemens Protection Devices Limited 2

output is set for independent operation to trip the BUS breaker (BUS overcurrent check not shown), in the event of an arc fault in the CB chamber. Existing switchgear applications The existing overcurrent relay protecting the feeder will normally provide an independent output contact associated with the start current setting of the relay. That is an output contact that will close when a phase or earth fault current is detected above the threshold which starts the internal relay timers. An Arc Fault Monitor relay is installed on the switchgear panel adjacent to the protection relay. The is specifically designed for simple retrofit to existing panels & requires only a single 31mm mounting hole to be drilled. The fits through this hole, the designation label supplied with the unit positioned & the retention shroud fitted. Refer Figure 14 & 16. Figure 1: Single arc sensor - Cable box only (Optional overcurrent check stage depicted) optical arc sensors are fitted in the cable termination box & CT chamber as depicted in figure 2. The overcurrent relay starter contact may optionally be wired in series with the arc fault detection trip output contact as depicted in figure 6. The resulting AND function trip output is wired to trip the breaker in ~15ms in the event that an arc fault is detected while the overcurrent start element is picked up. The second arc trip & fail alarm contacts may be employed for interface to a SCADA system for fault reporting. New switchgear applications For new switchgear installations a modern numeric feeder protection relay is likely to be employed which will have numerous programming & configuration options. The basic concept is the same as for the existing switchgear application described above except that the additional features & flexibility of modern feeder protection relay allows improved system integration. Figure 2: Two arc sensors - Cable box & CT chamber (Optional overcurrent check stage depicted) This may be achieved by using the second arc trip output contact to interface to a programmable status input on the feeder protection relay. Depending on the model of protection relay being used this input may be programmed to provide an alarm message on the HMI, time stamped event record available via its communications link. Where this level of system integration is employed the does not need to be mounted on the front panel as the alarm indications are available on the feeder relay. Remote reset of the LED is achieved by momentary interruption of the power supply using a SCADA controlled series contact. The DIN rail mounting option is a convenient alternative in this situation. 1S30 1S30 1S30 Trip BUS CB(s ) Figure 3: Two arc sensors - Cable box & CT chamber Independent trip to CB (Optional overcurrent check stage depicted) One arc sensor - CB chamber Independent trip to BUS breaker (BUS overcurrent check stage not shown) Siemens Protection Devices Limited 3

Busbar Applications Combined BUS bar & switchgear Arc Protection Figure 4 shows an application where a single is applied for the protection of the Cable box & CT chamber plus the CB chamber & BUS chamber using three sensors. In this configuration one arc trip output is used to trip the feeder circuit breaker in the event of an arc fault in the cable box / CT chamber. The second trip output is set for independent operation to trip the BUS breaker (BUS overcurrent check stage not shown), in the event of an arc fault in the CB chamber or BUS chamber. BUS bar ARC Protection Figure 5 depicts how the may also be applied for the protection of bus bars. The number of sensors in the bus chamber is dictated by the switchgear design and the length of switchboard. In most indoor metal clad switchgear the bus bar chamber is a continuous chamber between panels only broken into segregated sections at a bus section breaker & as such the strategic placement of one or two arc sensors in each bus bar chamber run is normally adequate. Some indoor metal clad switchgear may segregate the bus chamber of each panel from the next via insulated bus chamber side barriers per panel, if this is the case then each bus chamber per panel would need to be monitored by at least one arc sensor. 1S30 Trip BUS CB(s) In large enclosures the arc sensors should be placed at approximately 5m intervals. 1S30 1S30 1S20 Figure 4: One arc sensor - Cable box / CT chamber Independent trip to CB Two arc sensors - CB chamber & BUS chamber Independent trip to BUS breaker (BUS overcurrent check stage not shown) Figure 5: One, two or three arc sensors located in the BUS chamber Siemens Protection Devices Limited 4

Operation CB SENSOR ARC FAULT MONITOR OVER-CURRENT RELAY 3 Pole OC + EF Operation Indicator A single tri-colour LED is integrated into the front panel reset push button to provide the following status indications: System healthy Green solid ARC FAULT TRIP INITIATE Power up test OK Arc fault trip Arc Sensor 1 service Arc Sensor 2 or 3 service Arc Sensor continuous pick up Flash green 3 times Solid red for 2s followed by: Alternate red & green until reset. Orange solid Orange flashing Alternate orange & red. Figure 6: Key components required to implement an Arc Fault Protection scheme with an overcurrent check stage to enhance system security The application examples in figures 1 to 5 utilize this concept for enhanced system security in that both the AND the OC 50 starter contact must be picked up for a CB trip signal to be initiated. As the arc fault trip contact closes considerably faster than the overcurrent relay starter element picks up, the CB trip time will be dictated by the overcurrent relay performance. Low current arcing faults Arc sensor circuit supervision The Arc Sensor is the heart of the system & supervision of circuit continuity is critical for correct operation. To monitor the integrity of the wiring between the arc sensor & Arc Monitor, a continuous 2mA supervision current flows between the units. The alarm contact will drop out after a 1s time delay if it fails to detect this current. Where a fault is detected on the Arc Sensor 1 circuit the front panel LED will give a solid orange indication. Where a fault is detected on Arc Sensor 2 or 3 circuits the front panel LED will give a flashing orange indication. Where a fault is detected on Arc Sensor 1 & 2 or 1& 3 circuits the front panel LED will give a solid orange indication. Arc Sensor Function The is an optical sensor that responds to the flash of light emitted during the incidence of an arcing fault. Onset of the light flash & detection by the occurs in a few milliseconds. When an arc is detected, the resistance presented by the drops to a level where the current flow increases to approximately 20mA. This increased current flow is instantaneously detected by the and its trip output contacts close. Refer to the Technical catalogue sheet for further details. Arc fault tripping using current check Fast operation of a tripping scheme usually results in reduced system security. The arc detection method can however, combine the optical detection technique with a traditional overcurrent method to maximize system security particularly for BUS bar protection schemes. Both conditions must coexist for the trip condition to be met as depicted in figure 6. Arcing faults can occur at low current levels & it is possible for the over-current starter element to be set above this level. To avoid this problem & obtain very fast clearance (<10ms), of an arc fault, the arc fault trip contact may be wired directly to the breaker operate coil. It should be noted that this method may lead to reduced system security. ARC detection reset time (effect of multiple arc trips) A delay of 2s is required to reset the after an initial arc sensor trip. Subsequent arc detection will cause the trip output contacts to re-operate & reset the time delays described under Configuration Switch Settings. Independent trip output contacts The may be set using configuration switch 3 for both trip output contacts to pick up when an arc is detected by any sensor input. Alternatively arc sensor 1 can be linked to trip contact 1 & arc sensor 2 (& 3 if fitted), to trip contact 2. This function may be applied where an arc fault detected in the cable box is directed to trip the feeder circuit breaker while an arc fault in the BUS chamber is to be directed to trip the BUS. ARC sensor continuously picked up High ambient light levels may cause a to be continuously picked up. This condition could occur for example if the CB cable box cover was left open in very high ambient light level conditions. A non arc fault over-current pick up would then result in an arc fault trip operation. To avoid possible mal-operation due to this condition, the is designed to automatically disable the arc fault tripping function if the sensor is picked up for >10s. The alarm contact will be set & the front LED flash alternate orange & red until the ambient light level problem is corrected. The will then perform an arc sensor test function & automatically reset. Siemens Protection Devices Limited 5

Configuration Figure 7: rear view showing configuration switches Configuration switch The configuration switches are accessible to the user by first unplugging the electronic module from the terminal base as shown in Figure 7. Configuration switch settings The internal wiring label identifies the position of the following switch functions: Switch 1: Arc sensor 2 ON - Arc Sensor 2 fitted OFF - Arc Sensor 2 not fitted Switch 2: Arc fault trip indication LED reset ON - Latching until manually reset OFF - Automatic self reset (Extinguish) after 4 hours will also reset contacts set for latching function Switch 3: Independent arc trip output contacts ON - Arc Sensor 1 activates trip output contact 1 & Arc sensor 2 or 3 activates trip output contact 2 OFF - Arc Sensor 1, 2 or 3 activate both trip outputs Switch 4: Arc fault trip output contact reset ON - Latching Reset with trip LED OFF - Self reset after 2s Switch 5: Arc sensor 3 ON - Arc Sensor 3 fitted OFF - Arc Sensor 3 not fitted 1: ARC SENSOR 2 2: LATCHING TRIP LED 3: INDEPENDENT ARC TRIP 4: LATCHING TRIP CONTACTS 5: ARC SENSOR 3 ON ON ON ON ON OFF OFF OFF OFF OFF Siemens Protection Devices Limited 6

Wiring Diagram 1 2 3 4 5 6 N/O ARC Fault trip contact 2 N/O ARC Fault trip contact 1 N/C Fail alarm P/U when healthy ARC Sensor 3 8 9 10 11 ARC 2&3 COMMON ARC 1 ARC Sensor 2 * ARC Sensor Sensor 1 12 DC AUXILIARY SUPPLY Figure 8: Socket Terminal Layout viewed from the front when un-plugged from the main housing Note: * Always wire Arc Sensor 1. Arc Sensors 2 & 3 are optional. Protection + Vx 12 11 10 Arc fault relay Overcurrent relay Arc 1 9 (Must be wired) Control + 5 6 Fail Alarm 1 2 I>start I> CB Aux Switch 52 - a Trip Coil 52 T application Figure 1 diagram - Circuits shown in de-energised condition Figure 9: Wiring application diagram (Refers to Figure 1 Line Diagram) Siemens Protection Devices Limited 7

Protection + Vx 12 8 11 Arc 2 9 10 Arc fault relay Overcurrent Relay Arc 1 (Must be wired) Control + 9 or 11 5 1 6 2 Fail Alarm Trip Bus CB Signal 3 4 I>start I> CB Aux Switch 52 - a Trip Coil 52 T application Figure 2 diagram - Circuits shown in de-energised condition Figure 10: Wiring application diagram (Refers to Figure 2 Line Diagram) Siemens Protection Devices Limited 8

Protection + Vx 12 11 8 Arc 3 Arc 2 9 10 Arc fault relay Overcurrent relay Arc 1 9 or 11 (Must be wired) Control + 5 1 6 2 Fail Alarm Trip Bus CB Signal 3 4 I>start I> CB Aux Switch 52 - a Trip Coil 52 T application Figure 3 diagram - Circuits shown in de-energised condition Figure 11 : Wiring application diagram (Refers to Figure 3 Line Diagram) Siemens Protection Devices Limited 9

Mounting Options The is available in two versions: 1. A surface mount version which has a separate reset button & LED indicator on the front panel. The advantage of this version is the lower cost & where front panel space in limited. 2. A panel mount version which has a combined reset button & LED indication. The advantage of this version is that it can be either panel or surface mounted. Panel mount version This version is suitable for mounting on the front panel of a cubicle or door. This is achieved using a 31mm diameter hole in the panel adjacent to the protection relay as depicted in figures 14, 15 & 16. This version may also be surface mounted by reversing the terminal block retaining screws. It may also be DIN rail mounting when the optional DIN Rail Mounting Kit is fitted. Refer figures 17, 18 & 21. Surface mount version This version is suitable for location in the rear of a cubicle. It may be surface mounted as shown in figures 12 & 19. It may also be DIN rail mounting when the optional DIN Rail Mounting Kit is fitted. Refer figures 13, 18 & 21. Figure 14: through-hole panel mount version Slide out cable Entry points 3 on one side 1 at each end Figure 12: surface mount version front panel 6 4 5 3 1 2 B) N : A ( C S / C K 2 D 0 V S 2 5 0 1 3 6-1 X : U A Top & bottom rear Terminal Block Retaining screws Serial no. & Rating label on Module side for panel mount version Remove for Rear cable Entry options Slide out cabel entry points 3 on one side 1 at each end Top & Bottom rear Terminal Block retaining screws Maximum Relay panel 3mm thick Retention Shroud Figure 13: Surface mount version side view Remove for two M4 or 4BA mounting screws Figure 15: Panel mount version side view Siemens Protection Devices Limited 10

Panel Mount Version igure 16: Panel mounting cut out detail Figure 17: Surface mounting detail Figure 18: DIN rail mounting detail Siemens Protection Devices Limited 11

Surface Mount Version Figure 19: Surface mounting detail Figure 20: DIN rail mounting detail Figure 21: DIN rail clip fitting detail Siemens Protection Devices Limited 12

Technical Data Auxiliary Supply burden (at 110V DC) Monitoring mode: Arc fault detected: Auxiliary Supply Less than 4W Less than 10W for 2s 3 options are available for the auxiliary supply: 24/32/48V AC or DC nominal 110/125V AC or DC nominal 220/240/250V AC or DC nominal Operate Time Arc fault trip contacts guaranteed to pick up in less than 10ms including bounce. Typical operate time is 7ms. Minimum arc duration The minimum arc flash duration required to guarantee operation of the output contacts is 1.25ms. Trip contact reset time Once operated, the trip output contacts will reset in 2 seconds as per the configuration switch 4 setting. Manual reset Press front reset button or interrupt power supply to reset the unit. Output contacts Arc fault trip contacts: 2 N/O Fail alarm: 1 N/C for the power supply / CPU fail Normally picked up & drops out to signal an alarm condition. Output contact ratings IEC60255-0-2 CRO trace showing nominal operation time of the trip contacts at 7ms. First contact touch at 6.25ms and fully closed by 7.25ms. Operation in <10ms is considered acceptable as overcurrent relay operate time is ~25ms. 7SR21/22: 50 Instantaneous Overcurrent Element Operate Time Operate and Reset Time Attribute Value t basic Element basic operate time ARC sensor inputs 0 to 2 xis: 30 ms, ± 10ms 0 to 5 xis: 20 ms, ± 10ms Carry continuously Make & carry L/R 40ms & V 300V Break capacity I 5A & V 300V 5A AC or DC 0.5s 20A AC or DC 0.2s 30A AC or DC AC resistive AC inductive DC resistive DC inductive Minimum number of operations Minimum recommended load Transient overvoltage 1,250VA 250VA @ PF 0.4 75W 30W @ L/R 40ms 50W @ L/R 10ms 10 6 at maximum load 0.5W limit 10mA / 5V IEC60255-5 Between all terminals & earth 5kV 1.2/50us 0.5J Between independent circuits without damage or flashover 5kV 1.2/50us 0.5J Insulation coordination Between all terminals & earth Between independent circuits Across normally open contacts Auxiliary supply IEC60255-11 IEC60255-5 2.0kV RMS for 1 minute 2.0kV RMS for 1 minute 1.0kV RMS for 1 minute Two or three independent arc sensor inputs for type arc sensors. Allowable breaks / dips in supply Collapse to zero from nominal voltage 20ms High frequency disturbance - IEC60255-22-1 Class III 2.5kV 1MHz common mode 1.0kV 1MHz differential mode No mal operation Electrostatic discharge - IEC60255-22-2 Class III 6kV contact discharge No mal operation Figure 22: Arc Fault Sensor (Refer Technical Bulletin) Siemens Protection Devices Limited 13

Technical Data (Contd.) Radio frequency interference IEC60255-22-3 Class III 10V/m, 80 TO 1,000MHz No mal operation Fast transient IEC60255-22-4 Class III 4kV, 5/50ns, 100KHz repetitive No mal operation Conducted RFI IEC60255-22-6 Class III 10V, 0.15 to 80MHz No mal operation Temperature range IEC68-2-1/2 Operating: Storage: -5 to +55 o C -25 to +75 o C Humidity IEC68-2-78 40 o C & 93% RH non-condensing Case ZA12 flush or DIN rail mount type 12 M4 screw terminals Plug-in module to facilitate easy wiring & fast changeover Siemens Protection Devices Limited 14

Ordering Information Product description Variants Order No. 7 X G 3 1 2 0-0 0-0 A A 0 Arc Fault Protection Category Components Arc Protection 3 1 Device Arc Fault Monitor Relay 2 0 Sensor Inputs Two sensor inputs 2 Three sensor inputs 3 Operating Voltage 24/32/48V AC or DC Nominal F 110/125V AC or DC Nominal G 220/240/250V AC or DC Nominal H Mounting Panel or Surface Mount, No DIN Rail kit. A Panel or Surface Mount, With DIN Rail kit. B Surface Mount only, No DIN Rail kit. C Surface Mount, With DIN Rail kit. D Siemens Protection Devices Limited 15

Published by and copyright 2016: Siemens Protection Devices Limited P.O. Box 8 North Farm Road Hebburn Tyne & Wear NE31 1TZ United Kingdom Phone: +44 (0)191 401 7901 Fax: +44 (0)191 401 5575 E-mail: marketing.spdl.gb@siemens.com EMEA-C10039-00-76GB December 2016 For enquires please contact our Customer Support Center Phone: +49 180/524 8437 (24hrs) Fax: +49 180/524 24 71 E-mail: support.ic@siemens.com www.siemens.com/protection Subject to change without notice, Printed in the UK. www. siemens.com/energy Siemens Protection Devices Limited 16