Session Four Functional safety: the next edition of IEC Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd

Similar documents
Functional Safety: the Next Edition of IEC 61511

Session Ten Achieving Compliance in Hardware Fault Tolerance

Technical Paper. Functional Safety Update IEC Edition 2 Standards Update

New Developments in the IEC61511 Edition 2

67 th Canadian Chemical Engineering Conference EDMONTON, AB OCTOBER 22-25, 2017

ADIPEC 2013 Technical Conference Manuscript

New requirements for IEC best practice compliance

PRIMATECH WHITE PAPER CHANGES IN THE SECOND EDITION OF IEC 61511: A PROCESS SAFETY PERSPECTIVE

Australian Standard. Functional safety Safety instrumented systems for the process industry sector

PPA Michaël GROSSI - FSCE PR electronics

Digital EPIC 2 Safety manual

Value Paper Authors: Stuart Nunns CEng, BSc, FIET, FInstMC. Compliance to IEC means more than just Pfd!

INTERNATIONAL STANDARD

InstrumentationTools.com

Safety Integrity Verification and Validation of a High Integrity Pressure Protection System to IEC 61511

Changes in IEC Ed 2

INTERNATIONAL STANDARD

Assessment of the Safety Integrity of Electrical Protection Systems in the Petrochemical Industry

INTERNATIONAL STANDARD

Is your current safety system compliant to today's safety standard?

Options for Developing a Compliant PLC-based BMS

SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators

FUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK

100 & 120 Series Pressure and Temperature Switches Safety Manual

2015 Functional Safety Training & Workshops

Failure Modes, Effects and Diagnostic Analysis

Process Safety - Market Requirements. V.P.Raman Mott MacDonald Pvt. Ltd.

This document is a preview generated by EVS

INTERNATIONAL STANDARD

NEW CENELEC STANDARDS & CSM-RA NEW CENELEC STANDARDS & CSM-RA 2017

USER APPROVAL OF SAFETY INSTRUMENTED SYSTEM DEVICES

Failure Modes, Effects and Diagnostic Analysis

Certification Report of the ST 3000 Pressure Transmitter with HART 6

United Electric Controls One Series Safety Transmitter Safety Manual

The SIL Concept in the process industry International standards IEC 61508/ 61511


Addressing Challenges in HIPPS Design and Implementation

Certification Report of the ST3000 Pressure Transmitter

Failure Modes, Effects and Diagnostic Analysis

IEC Functional Safety Assessment

White Paper. Integrated Safety for a Single BMS Evaluation Based on Siemens Simatic PCS7 System

Safety Instrumented Systems

Measurement of Safety Integrity of E/E/PES according to IEC61508

IEC61511 Standard Overview

INTERNATIONAL STANDARD

Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options. TÜVRheinland

Integrated but separate

High Integrity Pressure Protection System

The agri-motive safety performance integrity level Or how do you call it?

Safety Instrumented Systems The Smart Approach

Safety Transmitter / Logic Solver Hybrids. Standards Certification Education & Training Publishing Conferences & Exhibits

IEC Functional Safety Assessment

Safety in the process industry

Functional Safety of Machinery: EN ISO Stewart Robinson. Overview of the presentation. References. TÜV SÜD Product Service

Session Ten: The importance of a clear Safety Requirements Specification as part of the overall Safety Lifecycle

INTERNATIONAL STANDARD

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis

INTERNATIONAL STANDARD

Fire and gas safety systems:

Why AC800M High Integrity is used in Burner Management System Applications?

Guidelines. Safety Integrity Level - SIL - Valves and valve actuators. February Valves

FUNCTIONAL SAFETY CERTIFICATE. BG Break Glass Unit

Failure Modes, Effects and Diagnostic Analysis

This document is a preview generated by EVS

SIL DETERMINATION AND PROBLEMS WITH THE APPLICATION OF LOPA

Safety Instrumented Systems Overview and Awareness. Workbook and Study Guide

Functional safety according to IEC / IEC Important user information. Major changes in IEC nd Edition

Applying Buncefield Recommendations and IEC61508 and IEC Standards to Fuel Storage Sites

FUNCTIONAL SAFETY: A PRACTICAL APPROACH FOR END-USERS AND SYSTEM INTEGRATORS

Where Process Safety meets Machine Safety

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, Minnesota USA

TECHNICAL SPECIFICATION

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany

SITRANS. Temperature transmitter Functional safety for SITRANS TW. Introduction. General safety instructions 2. Device-specific safety instructions

Process Safety Workshop. Avoiding Major Accident Hazards the Key to Profitable Operations

Safety lnstrumentation Simplified

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

The Use of an Operator as a SIL 1 component in a Tank Overfill Protection System

Functional Safety: What It Is, Why It s Important And How to Comply

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

FINAL REPORT ON THE 4 TH JOINT CROSS-BORDER EMC MARKET SURVEILLANCE CAMPAIGN (2011) LED LIGHTING PRODUCTS

Failure Modes, Effects and Diagnostic Analysis. PR electronics A/S Rønde Denmark

Implementing Safety Instrumented Burner Management Systems: Challenges and Opportunities

Failure Modes, Effects and Diagnostic Analysis

This is a preview - click here to buy the full publication

2015 Honeywell Users Group Europe, Middle East and Africa

Beyond Compliance Auditing: Drill til you find the pain points and release the pressure!

IEC an aid to COMAH and Safety Case Regulations compliance

FUNCTIONAL SAFETY CERTIFICATE

Technical Report Proven In Use SITRANS P500

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL

SAFETY INTEGRITY LEVEL MANUAL. IEC and IEC XP95 and Discovery SIL Approved Product Range

FMEDA Report. Failure Modes, Effects and Diagnostic Analysis. KFD0-CS-Ex*.54* and KFD0-CS-Ex*.56* Project: X7300

Presenter Joe Pittman

Understanding and implementing an electrical safety regime in your organisation. Dispelling the myths and promoting a risk-based approach

Functional Safety of Machinery Presented by Greg Richards Manufacturing in America 02/22-23/2017

CO-ORDINATION OF NOTIFIED BODIES PPE Regulation 2016/425 RECOMMENDATION FOR USE

Fire and Gas Detection and Mitigation Systems

Transcription:

Abstract Session Four Functional safety: the next edition of IEC 61511 Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd The functional safety standard IEC 61511 provides a framework for managing instrumented safety systems in the process sector. The overall objective is to ensure that the systems reliably deliver sufficient risk reduction to reduce risk to acceptable levels. The standard was first developed in the USA and originally released in 1996 as ISA S84. It was adopted by the IEC as an international standard and released in the form IEC 61511 in 2003. At the same time the ISA version was revised and reissued as ANSI/ISA-84.00.01-2004. The ISA and IEC versions are virtually identical. The Australian version AS IEC 61511 is also identical. With almost 20 years of experience since the original ISA S84, a new edition of IEC 61511 has now been prepared. Part 1 of the new edition was released in February 2016. Parts 2 and 3 will follow shortly. This paper outlines: A brief history of the standard An overview of how the standard works to achieve reliable risk reduction The changes that are likely to be adopted Why those changes are necessary. The Legal Basis: Duty of Care IEC 61511 is not directly referenced in legislation, though it is referenced in some Codes of Practice. The legal requirement to apply IEC 61511 arises from duty of care. Everybody involved in owning, operating, designing, building or maintaining hazardous facilities has a duty of care under occupational health and safety legislation. Due diligence in fulfilling our duty care requires us to: Identify appropriate standards Take reasonable steps to apply the standards Monitor compliance Demonstrate compliance IEC 61511 is now a well-established in Australia and around the world. Failing to comply with this standard would leave us open to being accused of negligence. 6 th Safety Control Systems Conference Melbourne 2016 1

Over the past 20 years the ISA S84 / IEC 61511 standard has been applied widely and shown to be practicable. It is unarguably the most appropriate standard to apply for instrumented safety systems in the process sector. IEC 61511 applies to all of us who are in a position to influence those hazards. It is not simply a standard for equipment suppliers or just for instrumentation and control engineers. The changes make the standard simpler and should improve the level of compliance that can be readily achieved. Regulators now expect users to demonstrate a reasonable level of compliance to the standard. Owners, end users and EPC/EPCM contractors will need to improve and to formalise the way they execute engineering activities in order to comply with the standard requirements. The Evolution of Functional Safety Safety instrumented systems have been delivering risk reduction for at least half a century. In the early years of automation after the Second World War safety instrumented functions were implemented using simple pneumatic, hydraulic or hardwired electrical circuits. These simple functions were easy to understand and had failure modes that were well defined. The behaviour under fault conditions could be completely determined and predicted. Electronic and programmable electronic systems came into use in safety functions during the 1970s. Electronic and programmable electronic systems have indeterminate failure modes. They do not inherently fail into a safe state. They are subject to hidden or latent faults that can be difficult to eliminate. Failure modes and behaviours cannot be completely determined and predicted. Programmable systems in particular have hidden complexity, and the complexity has been increasing exponentially for several decades. Complex systems are subject to the risk of systematic failures, failures caused by errors and failures in the design and implementation of the systems. Engineering practices evolved over decades in response to increasing complexity. 6 th Safety Control Systems Conference Melbourne 2016 2

Moore s Law Applies to Instrumentation Standards Evolution Various standards were developed in the 1980s and 1990s to provide guidance in controlling the risk of both systematic failures and random failures: Health and Safety Executive (HSE UK) Guidelines 1987, Programmable Electronic Systems in Safety Related Application ISA S84 1996, Application of Safety Instrumented Systems for the Process Industry IEC 61508 Ed. 1 1998, Ed. 2 2010, Functional safety of electrical/electronic/programmable electronic safety-related systems IEC 61511 2003 (ANSI/ISA 84.00.01-2004) Functional safety Safety instrumented systems for the process industry sector Risk Reduction Factor Functional Safety refers to Safety Instrumented Systems (SIS) that implement Safety Instrumented Functions (SIFs) as part of a company s overall risk management strategy. Safety Instrumented Functions Respond to a specific, defined hazard Implement a specific action Put the equipment into (or maintain) a safe state Provide a defined degree of risk reduction 6 th Safety Control Systems Conference Melbourne 2016 3

DETECT DECIDE DO The risk reduction required from a function is characterised by the Safety Integrity Level or SIL. To put it simply, each safety function is designed to deliver either 1, 2 or 3 orders of magnitude in risk reduction. SIL 1, SIL 2 and SIL 3 correspond to Risk Reduction Factors of at least 10, 100 and 1,000. Reliable Risk Reduction Safety functions can fail due to Systematic failures, caused by errors and failures in the design, implementation, operation and maintenance of the systems OR Random hardware failures, those failures that can never be completely eliminated by controlling the design, implementation, operation and maintenance. Systematic Integrity IEC 61511 outlines well defined and detailed quality management practices to avoid or to control the risk of systematic failures. The degree of attention to detail and the level of effectiveness in the techniques applied depend on the risk reduction required. SIL 3 safety functions need to be 100 times as reliable as SIL 1 safety functions. Design, checking, inspection and testing techniques need to be proportionately more effective. 6 th Safety Control Systems Conference Melbourne 2016 4

IEC 61511 defines a safety lifecycle (similar to a quality process): Safety requirements are defined in objective terms to achieve measurable risk reduction. The hazard and risk assessment and the safety requirements derived from it provide the basis for the whole system. Management and planning provide a framework to ensure systematic integrity and dependability. The safety lifecycle applies traceability, verification and validation to ensure that the requirements are fulfilled. The owners, end users and process designers play a fundamental role in the IEC 61511 safety lifecycle because they are ultimately accountable for the risk management. Hardware Integrity To deliver a risk reduction factor of 10, the probability of failure on demand must be less than 0.1 To deliver a risk reduction factor of 1000, the probability of failure on demand must be less than 0.001 IEC 61511 and the related standard IEC 61508 describe techniques to evaluate the probability of random hardware failure. The probability of failure of a function can be reduced by increasing the coverage and/or frequency of regular testing. It can be reduced by selecting devices with lower failure rates. It can also be reduced by applying a fault tolerant design which means that the function will continue to function successfully with one or more failed components. For instance if two block valves are used in series the probability that both will fail concurrently is lower than the probability of a single valve failing. 6 th Safety Control Systems Conference Melbourne 2016 5

Minimum Acceptable Fault Tolerance When the standards were developed it was recognised that the there was a great deal of uncertainty in the failure rate statistics and in the assumptions made in the design. To compensate for the uncertainty the standards set minimum levels of fault tolerance for each part of a safety function. The level of fault tolerance that is appropriate increases with the risk reduction required. IEC 61511 defines minimum hardware fault tolerance (HFT) requirements for the sensors, logic solvers and final elements that make up each safety function. Lessons Learned in Practice Systematic Integrity Not Well Understood The long history of major accident events shows that many users have failed to understand and apply the requirements for managing quality or systematic integrity. The conclusions from many reports include these recurring systematic failures: Lack of appreciation of organisational roles, responsibilities and interfaces Poor safety culture and a lack of leadership in safety Inadequate attention paid to personnel competencies and in particular management competencies Equipment poorly maintained Alarms and automatic shutdown systems not working properly Inadequate control of modifications to critical systems Safeguards bypassed or not even commissioned Lack of documentation for safety systems Minimum Acceptable Fault Tolerance Impracticable The hardware fault tolerance required by IEC 61511 has been too onerous to achieve in practice. Most users have found it difficult to comply with the standard. The methods of assessing the HFT requirements are complicated and difficult to use. To minimise the HFT requirement to a practicable level users need to obtain extensive evidence about the suitability of the devices being used. Users also need to ensure that the majority of failures are to a safe state or that dangerous failures are promptly detected and repaired. Actuated valves are commonly used as final elements in safety functions, but the dominant failure mode of actuated valves is dangerous. The most common failures cause the valves to stick or jam in a dangerous state. 6 th Safety Control Systems Conference Melbourne 2016 6

In the existing IEC 61511 standard a risk reduction factor of 1,000 or more (SIL 3) requires at least three block valves in series as final elements unless continuous automatic diagnostic functions can be implemented. Continuous automatic diagnostic functions are not usually practicable in the process sector. In many cases it is impracticable to install three valves in series. Noncompliance is widespread. The most common practice is to use only two valves in series, either in a double block or a double block and bleed arrangement. Installing a third block valve not only increases the cost; it also increases the risk of spurious trip and loss of production. The Changes in the New Edition The new edition of IEC 61511 will include: New requirements for systematic capability New requirements for formal functional safety management systems New requirements for formal procedures to manage competence New security risk assessments, relating to deliberate malicious interference More detailed requirements about planning for verification Clarification of requirements for risk reduction is spread across multiple SIFs New annexes with detailed guidance Simplified requirements for hardware fault tolerance Requirements for better substantiation of the failure rate data and of uncertainties in the data Revised software development requirements Additional requirements for bypasses Formal review by operations and maintenance of the hazard and risk assessments Independent assessment of modifications to systems before implementation. 6 th Safety Control Systems Conference Melbourne 2016 7

Systematic Capability The concept of systematic capability was introduced in the 2010 edition of IEC 61508. Systematic capability is essentially a measure of the effectiveness of quality management techniques applied to components. Requirements for systematic capability are included in the new edition of IEC 61511. Functional Safety Management Systems The purpose of a functional safety management system is to achieve systematic integrity. Functional safety management has been poorly understood and largely ignored throughout the process sector, particularly by the end users or plant owners. Any supplier with responsibility for one or more phases in the lifecycle must now demonstrate a functional safety management system as well as a quality management system. The requirement for having a functional safety management system applies just as much to end users and owners as it does to designers and suppliers. The operation and maintenance of a safety instrumented system must be managed under a formal system of functional safety procedures. Competency More emphasis has been put on competency requirements for all parties involved in designing, developing, implementing, operating and maintaining SIS. The wording in the standard has been changed from describing factors that should be addressed when considering competence to factors that shall be addressed. A new sub-clause has been added requiring formal procedures to manage competence and requiring periodic assessments of competence of individuals with respect to their responsibilities. There are competency requirements for those in charge too: Managers and leaders need to have adequate knowledge, ability and experience relating to the activities for which they are accountable. Security Risk Assessment In the section of the standard dealing with process hazard and risk assessment, a new sub-clause has been added requiring a security risk assessment. This relates to security of the systems from deliberate malicious interference, as distinct to the risk assessment of materials, process and equipment. Requirements resulting from the security assessment need to be included into the safety requirements specification. 6 th Safety Control Systems Conference Melbourne 2016 8

Verification A new sub-clause has been added with more detailed requirements about what should be covered in planning when verification is to include testing. A new sub-clause has been added specifically requiring verification that nonsafety functions that are integrated with safety function do not interfere with the safety functions. Lack of separation between safety functions and non-safety functions has been a widespread problem which compromises safety integrity. Multiple SIFs A new sub-clause clarifies that if risk reduction is spread across multiple SIFs within the same SIS, then the safety integrity achieved must meet the overall risk reduction requirement taking into account dependencies. Risk Reduction > 10 000 The requirements for achieving four or more orders of magnitude reduction in risk are specified in much more detail. In IEC 61511-3 there is a new Annex J that provides very detailed guidance on the evaluation of dependencies between multiple safety systems or functions. This annex is particularly relevant to where high levels of risk reduction are achieved by splitting risk reduction across multiple systems. Hardware Fault Tolerance The requirements for HFT have been simplified and aligned with the method Route 2 H that was introduced in the 2010 edition of IEC 61508. The level of hardware fault tolerance required has been reduced on the basis that the reliability data used when quantifying the effect of random failures shall be credible, traceable, documented, justified and shall be based on field feedback from similar devices used in a similar operating environment. SIL 3 can now be claimed with only two block valves in series (fault tolerance of one). The new IEC 61511 edition stops short of specifically requiring the 90% confidence level required by IEC 61508 Route 2 H, but it does require an equivalent demonstration of confidence in the data. Suitability of Components IEC 61511 still allows a choice: components must either comply with IEC 61508, or else a substantial volume of evidence of prior use must be available to show that the components are suitable for the intended service. For compliance to IEC 61508 the systematic capability of components and subsystems must be demonstrated. That means that the quality control must be appropriate for the level of SIL claimed. 6 th Safety Control Systems Conference Melbourne 2016 9

New sub-clauses have been inserted into the section on Quantification of random failure requiring better substantiation of the failure rate data and of uncertainties in the data. The calculated probability of failure will need to consider faults that might never be detected, and failures that might be caused by periodic testing. Application Program Software Development The clause on application program has been completely re-written, though there are no obvious or significant changes in requirements. The term application program replaces the term software which was previously used. The new clause is shorter. The application program development lifecycle is now integrated into the overall safety lifecycle. In the earlier edition it was described separately. Control of Bypasses in Operation History has shown us that the application of bypasses and overrides has contributed to the cause of many disasters. A new sub-clause has been added requiring additional risk management where SIS devices are bypassed in continuous operation. A new sub-clause requires all bypasses to be authorised and logged. A new sub-clause requires spare parts to be identified and made available to minimise bypass duration. Operations and Maintenance Review of HRA Assumptions There has often been a lack of communication between the designers and those responsible for operation and maintenance. A new sub-clause requires those responsible for operations and maintenance to review the assumptions made in hazard and risk assessment. SIS Modification A new sub-clause emphasises the need to update documentation affected by a modification. A new sub-clause requires independent assessment of the functional safety before any modification is implemented. Annexes IEC 61511 parts 2 and 3 include many annexes that provide guidance on implementing the standard. Extensive changes, deletions and additions have been made in the annexes for the new edition. 6 th Safety Control Systems Conference Melbourne 2016 10

Summary The changes in the new edition are primarily aimed at improving systematic safety integrity. The objective is to prevent the recurring systematic failures that have been evident for many years throughout the process sector. These failures are all preventable. The requirements for hardware fault tolerance have been reduced, but the failure rate data used in calculations must be more reliable. The quality and suitability of components must be demonstrated. The guidance and support material has been enhanced in the standard to assist safety and design engineers, safety assessors, and operators. Over the past 20 years the standard has been applied widely and shown to be practicable. The changes make the standard simpler and should improve the level of compliance that can be readily achieved. Regulators now expect a reasonable level of compliance to the standard. Due diligence in fulfilling our duty of care requires us to be able to demonstrate compliance with IEC 61511. Owners, end users and EPC/EPCM contractors will need to improve and to formalise the way they execute engineering activities in order to comply with the standard requirements. For more information on functional safety visit: http://www.iesystems.com.au/publications/ 6 th Safety Control Systems Conference Melbourne 2016 11