S-Series. Protect your water from pathogens and disease with the UV-Guard S-Series. Protect:

Similar documents
INSTALLATION & MAINTENANCE

SLT-Series Installation and maintenance instructions

S-Series Installation and maintenance instructions

Installation & operating manual. Swimming pool water. UV disinfection device UV10+

SmartStream UV. Ultraviolet Water Disinfection System. Maximize Water Quality Without Chemicals. Watts.com

INSTALLATION AND OPERATING INSTRUCTIONS FOR RW519 RAIN WATER FILTRATION SYSTEM

Ultraviolet (UV) Water Treatment System

VMS-3. Part Number: Ultraviolet Systems VMS-3. Installation, Operation & Maintenance

Customized Drinking Water

WATER STERILIZERS TYPE: AM1; AM2; AM3; AM4; AM5; AM6; AM8; AM10; AM12; AM15

Design and manufacture process of DUV units comply with international standards for UV disinfection of potable water such as CE certificate.

UV I UNIT030W / UV I UNIT055W

1020 Industrial Drive, Orlinda, TN fax

A measured step forward

Ultraviolet Water Sterilizer Installation and Maintenance Manual

ADVANCE Ultraviolet (UV) Water Treatment System

Section 3: Ultraviolet - UV

HydroRite UVO 3. Troubleshooting Guide Residential. TSG-UVO158a. Copyright 2015 Hayward Industries Inc.

BWT ECO. Fitting and operating instructions. Ultra Violet Water Disinfection System. ECO Range: LC 8 UV LC19 UV LC36 UV LC51 UV

I N S T A L L A T I O N, O P E R A T I O N, M A I N T E N A N C E M A N U A L UVR SERIES ULTRAVIOLET WATER TREATMENT SYSTEM

Pro-MAX Ultraviolet Sterilizer

Parasitic Cysts - Cryptosporidium and Giardia, Chemicals, Heavy Metals, Dissolved Salts, Offensive Tastes and Odours, Sediment, Dirt,

254 Nanometer Germicidal UV Disinfection Systems

Instructions for Emperor Aquatics, Inc. s 16, 25, & 57 Watt Retro-Fit UV Sterilizer (for Savio s Skimmers)

PRINCIPLE MAIN APPLICATION

Spektron UV Series SHINING NEW LIGHT ON DRINKING WATER DISINFECTION

Ultraviolet Systems UV-C 50 INSTALLATION INSTRUCTIONS & PRODUCT MANUAL

Model CWA200 Owner s Manual

HF Series R_RevB

NANO TECH UV-C DISINFECTION SYSTEM

TROJANUVSWIFT SC. Drinking Water Treatment

Based in the UK, Triogen is a world leading company with over twenty years experience in the design and manufacture of specialist Ozone and UV

Professional Amalgam Non-regulated

UV disinfection. System. Type A Series. Main applications: Potable water, process water, hot water/legionellae DIN EN ISO 9001 DIN EN ISO 14001

Owner s Manual. DO NOT REMOVE FROM UNIT See back cover for vital records

WEDECO DLR A SERIES ULTRAVIOLET WATER DISINFECTION UNIT INSTALLATION OPERATION AND MAINTENANCE MANUAL MODELS DLR-A SERIES NO'S

AS-V/186K Series. Ultraviolet Disinfection Systems. Installation, Operation and Maintenance Manual

OptiVenn TM Series INDUSTRIAL UV SYSTEMS. High performance, cost-effective system for stringent Industrial applications

AEM EASY DRUM M A N U A L

BIOSHIELD COMMERCIAL VERTICAL UV STERILIZER

VIQUA is an ISO9001:2008 registered company specializing in the design, manufacture and sale of ultraviolet systems for:

ALL IN ONE SERIES HOTLINE 1300 AQUATEC INSTRUCTION MANUAL MODEL 03AS310 03AS311. DATE JULY 2017 v2.0. AQP All in One 1000 Instructions.

BALLAST REPLACEMENT. Contents WARNING INSTALLATION MANUAL

PRE INSTALLATION PROCEDURES

Radiator Connection System, Thermostatic Valve and Return Valve with Shutoff Function

Vorton 11/18/36/55 2YEAR. GUARANTEE. Hozelock Ltd. Midpoint Park, Birmingham, B76 1AB. England Tel: +44 (0)

PRO Series PRO10 PRO20 PRO30

ULTRA-VIOLET STERILIZATION

Bio-Logic. Owner s Manual. Installation, Operation & Maintenance ULTRAVIOLET WATER PURIFIERS. Ballast 120v 50/60 Hz

Getting Started Quick Reference Guide

Quadron UV Series. Sustainable UV Disinfection with Minimum Footprint

SimplyClear Pressurized Filter Product Manual

375 Marcus Boulevard Hauppauge, NY USA Fax: Extensive Product Information Available at:

PRE INSTALLATION PROCEDURES

uv and ozone for commercial pools

INSTALLATION MANUAL & OWNER S GUIDE. Stainless Steel Ultraviolet Water Purification System

WATER FILTRATION SYSTEM (USF3) OWNER S MANUAL

ALL-IN-ONE SF PF312 MAR PMAX All-In-One Instructions.indd 1 3/1/2017 9:20 AM

UV Lamp and Quartz Sleeve Replacement/Maintenance

WM-450-PT WM-900-PT Commercial Wall Mounted Reverse Osmosis

Instruction Sheet AquaMotionHot One AMH1K-1 Point of Use Hot Water Recirculation System

WEDECO Quadron UV System

Models 120v 50/60 Hz 230v 50/60Hz MIN B A MIN B A MIN B A

Ultraviolet Monitoring System. Part Numbers UV/MS-1 V3 UV/MS-2 V3. Installation And Operations Manual

Installation, Operation and Maintenance Instructions for ThermaFlex Gasketed Plate Heat Exchangers

Instructions for the 4-20mA Unit

Instruction Sheet DANGER

Ballast MIN A

Installation Manual PS-225 & PS-275

Owner s Manual MIGHTY PURE. Installation, Operation & Maintenance ULTRAVIOLET WATER PURIFIERS. Models MP16A, MP22A, MP36C & MP49C

OTO BONDER OWNER S MANUAL WITH CIRCULATING SYSTEM MACHINERY DIVISION - - L to R Unit Shown

Instructions for the 4-20mA Unit

VADA - Rain2Main Automatic Rainwater Controller

Installation & Operating Instructions

Ballast 230v 50/60Hz MIN B B MIN B B MIN B B

Operation & Installation Instructions

Ultraviolet Disinfection Systems

PRECAST CONCRETE. Never Looked So Good!

Ultraviolet Disinfection Systems

SERVICE REQUIREMENTS

OWNERS MANUAL. Operation & Installation Instructions. L12, L22, L41, L57, L79 (Standard Output) H38, H53, H95, H151 (High Output)

SUPER NOVA SERIES UV STERILIZER HIGH INTENSITY ULTRAVIOLET STERILIZATION

Ultraviolet Disinfection Unit Installation and Owners Manual

GARDENA. F 3000 Art F 6000 Art F 9000 Art F Art. 7929

INSTALLATION MANUAL & OWNER S GUIDE. Stainless Steel Ultraviolet Water Purification System

Instructions. Certifications CH Chrome SS Stainless Steel. Single Handle, Industrial Style, Pull-Down Kitchen Faucet.

Installation, Operation and Maintenance Instructions ThermaFlex Gasketed Plate Heat Exchanger OM010

Instruction Sheet DANGER

A few simple steps to ensure perfect water, every time.

SAFETY ALERT SYMBOLS SAFETY PRECAUTIONS

Easy Rooter. Operating Instructions

PRE-INSTALLATION PROCEDURE

(UV) - R830F & ) INTRODUCTION

DRINKING WATERCOOLER MANUAL. Website:

Heater Upgrade Instructions

Installation and Use Manual

OWNER S MANUAL. How to install, operate and maintain your. EcoWater Systems Automatic Sediment Filter. EcoWater Systems Poland

Water Distiller Service Manual

REGISTERED HANDBOOK. Document: ECN: Revision: C. MANUAL, O&M TrojanUVLogic TM System Systems Without Wiper AM, VM & TM Models

PURION UV plants for disinfection

Transcription:

UVG S440 MW UVG S160, S245 UVG S75, S40-76 S-Series Protect your water from pathogens and disease with the UV-Guard S-Series. The S-Series is a robust and dependable UV disinfection system able to provide recommended UV dose rates at flows of up to 737 liters per minute, from commercial business installations to hospitals, mining camps and more. Accredited by the WaterMark certification scheme, a requirement documented within The Plumbing and Drainage Code Australia, making the S-Series food grade compliant. Flow rates are calculated using complex UV dosage programs and are based on the requirements of the Austrian, German and USA NSF 55 Class A UV water disinfection standards. Free UV transmittance (UVT) testing performed on request to ensure correct system is specified*. UVG S40-62 Protect: Remote communities, employees, customers and family members from E.coli, Giardia and Cryptosporidium contained within drinking water supplies. Water treatment processes from microbial colonisation. Fish farms from disease outbreaks resulting in greater yields and a better quality product. Display fountains and ponds from algae, increase aesthetic qualities and enabling safe human contact. Pool users from bacteria and viruses, eliminate algae, reduce chlorine use by up to 90% and create a more pleasant experience. Residents from Legionella found within warm water systems. Food and beverage products from bacteria, viruses, spores, yeast and mold without any detrimental impact on product quality. Pharmaceutical products and processes where ultra-pure water is essential. Any other water user or water using process where disinfection is required!

S-Series Benefits No micro-organism is known to be immune to UV - even the chlorine resistant Giardia and Cryptosporidium Economical and efficient operation disinfecting at the point of use, no contact time required No harmful by-products chemical free, no impact on taste or colour and no corrosion problems No risk of overdosing reducing the risks associated with chemical overdosing Easy maintenance lamp can be replaced easily without interrupting water flow Proven performance and flexibility system designed according to application and project requirements Peace of mind power supplies show when lamp is in operation and audibly alerts any faults. UVG S40-62 with IP65 rated Power Box Options Lamp life run counter and alert to indicate when the lamp needs replacing Volt free contacts - for remote system status indication Industrial IP rated outdoor power boxes and indoor power supplies customized to suit your requirements Temperature management thermostat and solenoid valve linked to power box to ensure unit temperature does not increase to unsafe levels UV intensity monitoring real time monitoring to alert when design UV intensity is not being achieved Manual and automatic wiping mechanisms** ensure the quartz remains in good condition, limiting fouling and ensuring design UV intensity is continuous UVG S440 with manual wiper and IP65 rated Power Box Standard Features Systems accredited by the WaterMark certification scheme guaranteeing quality and fit for purpose High quality 316 grade stainless steel reactor ensures longevity of the system BSP threaded connections in a number of inlet/outlet location choices for ease of connection to plumbing infrastructure Heavy duty stainless steel brackets system permanently mounted securely Lamp fail alarm alerts user and prevents untreated water from being consumed Innovative high output, low pressure UV lamps target UV dose is maintained throughout lamp life Pure fused quartz sleeves allows optimum UV output from the lamp to the water Lamps parallel to water flow water disinfected from chamber entry point to exit UV intensity Monitor and Sensor

S-Series S-Series - peak flow vs UVT graph for 40 mj/cm 2 Peak Flow Rate (lpm) 220 200 180 160 140 120 100 80 60 40 20 0 35 40 45 50 55 60 65 70 75 80 85 90 95 UV Transmittance (UVT) (%) Peak Flow Rate (lpm) 650 600 550 500 450 400 350 300 250 200 150 100 50 0 35 40 45 50 55 60 65 70 75 80 85 90 95 UV Transmittance (UVT) (%) S20 S30 S40-62 S40-76 S40T S125-100 S160 S160-100 S245 S125T S75 S80 S80-100 S125 S172 S245-100 S172T S160T S245T S440 Model Flow rate per UV Dose figure*** 40mJ/cm 2 30mJ/cm 2 Connection Lamp Power (W) Dimensions (cm) UVG S20 17 lpm 23 lpm ¾ male BSP 20 32l x 6.2w UVG S30 25 lpm 34 lpm ¾, 1 male BSP 30 59l x 6.2w UVG S40-62 35 lpm 46 lpm 1 male BSP 40 97l x 6.2w UVG S40-76 45 lpm 60 lpm 1, 1½ male BSP 40 97l x 7.6w UVG S40T 69 lpm 92 lpm 2 male BSP 40 x 2 97l x 29w UVG S75 90 lpm 120 lpm 1, 1½ male BSP 80 97l x 7.6w UVG S80 86 lpm 115 lpm 2 male BSP 80 97l x 7.6w UVG S80-100 118 lpm 157 lpm 2 male BSP 80 97l x 10w UVG S125 137 lpm 183 lpm 2 male BSP 125 97l x 7.6w UVG S172 186 lpm 248 lpm 2 male BSP 172 97l x 7.6w UVG S125-100 188 lpm 250 lpm 2 male BSP 125 97l x 10w UVG S160 203 lpm 270 lpm 2 male BSP 160 128l x 7.6w UVG S160-100 271 lpm 361 lpm 2 male BSP, 3 Table E Flange 160 128l x 10w UVG S245 263 lpm 351 lpm 2 male BSP 245 128l x 7.6w UVG S125T 275 lpm 366 lpm 2 male BSP 125 x 2 97l x 29w UVG S245-100 358 lpm 478 lpm 2 male BSP 3 Table E Flange 245 128l x 10w UVG S172T 372 lpm 496 lpm 2 male BSP 172 x 2 97l x 29w UVG S160T 406 lpm 541 lpm 2 male BSP 160 x 2 128l x 29w UVG S245T 527 lpm 702 lpm 2 male BSP 245 x 2 128l x 29w UVG S440 553 lpm 737 lpm 3 Table E Flange 440 154l x 10w * UVT testing provided free of charge following a system order. **No wiper option for S20 and S30 chambers. ***Approximate flow rates calculated using UVCalc software and are based on a UV transmittance (UVT) of 85% and a UV dose at the end of lamp life.

INSTALLATION AND MAINTENANCE INSTRUCTIONS MODELS S20, S30, S40-62, S40-76, S75, S80, S125, S172, S40X2, S125X2, S172X2, S160, S160X2, S160X4, S245, S245X2, and S245X4 Stainless Steel Water Disinfection Units ATTENTION Please read this manual carefully and follow the instructions. Installation shall be carried out only by authorised technicians. Manual S Series Rev 7, 1103 Page 1

CONTENTS 1. GENERAL APPLICATIONS 2. ASSEMBLY AND INSTALLATION 2.1 Reactor Types 2.1.1 Installing the Reactor 2.1.2 Installing the View Port Quartz Thimble and UV Lamp 3. SERVICING 3.1 Servicing the Quartz Thimble 3.2 Servicing the UV Lamp 3.3 Power Supply Box 4. SPARE PARTS AND CORRESPONDING PART NUMBERS 5. WARRANTY Manual S Series Rev 7, 1103 Page 2

1. GENERAL APPLICATIONS UV disinfection is an efficient, low cost and environmentally friendly process. UV light kills pathogenic micro-organisms quickly without leaving any residues, harmful byproducts or affecting the smell or taste of the water. These units use UV lamps which emit UVC radiation at 254nm which disrupts the DNA in the micro-organisms, so they are either killed or their ability to replicate is destroyed. The kill rate depends on the UV dose received by the micro-organisms, i.e. the time that a micro-organism is exposed to a certain intensity of UV radiation (Wm 2 ). A UV dose of 400 J/m 2, (40 mj/cm 2 ) is recognized internationally as suitable dose requirement to ensure safe disinfection. The disinfection performance of a UV system is determined by the intensity of the UV light, water flow rate, the optical transmission of the water at 254nm and the geometry of the reactor. The sizing of the UV system should be based on these parameters. As there are no disinfection substances added to water by UV radiation, there are no residual effects once the water has passed through the UV Reactor. Only original spare parts should be used to ensure proper operation and performance. General Safety Instructions ELECTRIC SHOCK! Attention: Dangerous electric voltage is present inside the power supply box and chamber. These instructions must be followed closely to prevent serious personal injuries. ENSURE EYE PROTECTION IS WORN WHEN SERVICING AND INSTALLING THIS UNIT! UV-C radiation is harmful to the eyes and skin! UV lamps should be used only when properly installed in the irradiation chamber. Persons should never be exposed to UV-C radiation. Make sure this disinfection unit is only used for the intended purpose as described in the operating instructions. This disinfection unit is to be installed properly, according to these operating instructions, before use. Do not use a unit with a damaged electrical lead or plug, a unit with any faulty functions, or a unit which has been dropped or has been damaged in some way. Manual S Series Rev 7, 1103 Page 3

Make sure that the unit is unplugged when it is not being used, before fitting, or removing any parts, or before cleaning the unit. Ensure the disinfection unit is electrically isolated before carrying out any service work The unit must be depressurized before maintenance. Do not use the UV lamp outside of the UV disinfection reactor. UV lamps have been designed for permanent operation to reach their best disinfection capacity. Frequent switching on and off reduces the life of the UV lamp and may affect warranty! The UV lamps may take 2-5 minutes to reach maximum output 2. ASSEMBLY AND INSTALLATION Installation should be carried out only by qualified technicians. The Following MUST be Checked Prior to Installation: A maximum operating pressure of 1000KPa (10 bar) must not be exceeded. The maximum ambient temperature is 40 o C The maximum water temperature should be 60ºC (maximum recommended flow rates may be reduced for some units, such as UVG S75 and S80 models, at temperatures higher than 25 o C) The maximum flow rate should not exceed specified rate (see section 2.1) The Reactor must be plumbed so it remains full of water at all times while the lamp is operating. The S series units should not be installed so there are long periods with no flow. Recommended maximum period with no flow is 60 minutes. Longer periods for S80 and larger units, may damage the UV lamp due to overheating. If there are going to be long periods with no flow for these units, it is recommended a thermostat controlled solenoid valve is installed downstream of the UV unit so that if the temperature of the UV reactor gets too hot, the solenoid valve will open to return a small amount of water to the source, or dump to waste. The water flow from this action which will cool the reactor. Manual S Series Rev 7, 1103 Page 4

2.1 Reactor Types 1. The following reactor types are available in the S series. ( Table 1a & 1b ) Series Length No. Lamps in unit Diameter mm S20 245mm 1 62 S30 505mm 1 62 S40-62 895mm 1 62 S40-76 895mm 1 76 S75 895mm 1 76 S80 895mm 1 76 S125 895mm 1 76 S172 895mm 1 76 S40X2 895mm 2 62 S80X2 895mm 2 62 S125X2 895mm 2 62 S172X2 895mm 2 62 S160 1210mm 1 76 S160X2 1210mm 2 76 S160X4 1210mm 4 76 S245 1210mm 1 76 S245X2 1210mm 2 76 S245X4 1210mm 4 76 Table 1a Series Inlet/outlet Ø Min. space to service reactor at power end of chamber mm Max. flow rate l/h - Drinking water Max. flow rate l/h - Treated effluent S20 ¾ BSP Nipples 300 500 150 S30 ¾ BSP Nipples 600 2000 500 S40-62 1 BSP Nipples 1000 2,700 2000 S40-76 1½ BSP Nipples 1000 3,600 S75 1½ BSP Nipples 1000 6,700 4200 S80 2 BSP Nipples 1000 6,800 4600 S125 2 BSP Nipples 1000 10,500 7100 S172 2 BSP Nipples 1000 14,000 6500 S40X2 2 BSP Nipples 1000 7,200 4000 S80X2 2 BSP Nipples 1000 14,000 8000 S125X2 2 BSP Nipples 1000 20,000 14,000 S172X2 2 BSP Nipples 1000 26,000 (hydraulic limit) 13,000 S160 2 BSP Nipples 1300 13,700 9200 S160X2 2 BSP Nipples 1300 26,000 (hydraulic limit) 18400 S160X4 2 BSP Nipples 1300 26,000 (hydraulic limit) 26,000 (hydraulic limit) S245 2 BSP Nipples 1300 18,400 12,300 S245X2 2 BSP Nipples 1300 26,000 (hydraulic limit) 24,600 S245X4 2 BSP Nipples 1300 26,000 (hydraulic limit) 26,000 (hydraulic limit) Table 1b Before installation ensure you know which reactor type you are using. Make sure that there is enough free space to service the glassware with the reactor. ( for dimensions, see Section 2.1, Table 1a ). Otherwise it will not be possible to install the UV lamp and maintain the UV system. Manual S Series Rev 7, 1103 Page 5

Control Box Standard 10A Power Lead Outlet Inlet Power lead for UV lamp Viewing Port Mounting Brackets Sealing Nut Sealing Nut End Cap 2.1.1 Installing the Reactor The disinfection chamber comes complete with it's own wall mounting brackets (except for the S20 and the S30 units). The preferred orientation for the reactor is horizontal however vertical orientation is acceptable for all single lamp reactors. It is recommended that the outlet port is above the main body of the chamber to prevent airlocks. Multi-chamber reactors such as the S40X2, S80X2, S125X2, S172X2, S160X2, S160X4, S245X2, and S245X4 must be wall or frame mounted horizontally with flow coming in from underneath and out the top, so the water flow will expel any air. Refer to Table 1a for the distance from the sealing nut, required for servicing the unit. When mounting the chamber, consideration must be made for the weight of the system due to the stresses associated with pipe work etc. The stainless steel chamber and surrounding pipe-work must be properly earthed to prevent electrolysis/corrosion. Manual S Series Rev 7, 1103 Page 6

2.1.2.1 Installation of the Power Box The power supply box must be mounted clear of the floor as a precaution against the ingress of water. The power supply box is not designed for remote mounting. Recommended maximum distance of chamber to power supply box is two (2) metres. Depending on which version of the power supply box is ordered, there may be an audible lamp fail alarm included. This will sound in the event of a lamp failure to notify the operator to replace the UV lamp. The power supply box should be mounted so it is not exposed to rain or direct sunlight. Power supply 40048 (40088) Power supply 50162 For Power supply 50044 (50081) Power supply 40044 For For S20, 30, 40 (75 and 80) Must S125 and S160 Can be S20, 30, 40 (75 & For S20, 30 and 40 be installed under cover installed in weather 80). Can be installed in Must be installed under cover away from direct weather away from sunlight direct sunlight 2.1.2 Installation of View Port, Quartz Thimble and UV Lamp View Port:- The view port consists of an O ring seal, a pyrex window and a poly carbonate window, held in place by a brass annular screw. The pyrex window is inert and in contact with the water, while the polycarbonate window prevents any UV light from escaping. Remove the brass screw from the chamber view port Insert the view port O ring into the view port Insert the pyrex window into the view port Insert the polycarbonate window into the view port Secure all components in place by screwing the brass screw firmly into place. Manual S Series Rev 7, 1103 Page 7

Quartz Thimble:- DUE TO THE FRAGILE NATURE OF THE QUARTZ, CARE MUST BE TAKEN WHEN HANDLING AND INSTALLING THE QUARTZ THIMBLE and UV LAMP. Unscrew the sealing nut from the top of the reactor, take care to remove the orange O ring as well. Reactor / chamber Sealing nut O Ring seal Place the O ring inside the sealing nut so that it is seated in its groove on the threaded side of the nut. Sealing nut O Ring There are two types of reactors that have different methods for installing the quartz thimble. There are the reactors / chambers with a spring support for the quartz thimble. These chambers have inlet ports at the end of the chamber. Then there are the reactors chambers with static support cups for the quartz thimble. These chambers typically have side entry inlet ports or are twin series (-X2) chambers. Once you have determined which version you have, proceed according to the instructions below. In either case the quartz thimble needs to be wiped with alcohol / methylated spirits then dried clean to remove any finger marks or deposits on the quartz. Once the quartz has been cleaned, ensure it is only handled with clean cotton gloves, or rag or tissue. Ensure that no thread tape is used on the sealing nipple. The O ring provides the seal. The sealing nipple may be lubricated with silicon grease or petroleum jelly. Manual S Series Rev 7, 1103 Page 8

For chambers with Spring quartz support: To load the quartz for these units it is best to insert the open end of the quartz sleeve into the sealing nut before inserting the quartz into the chamber. Insert the open end of the quartz into the sealing nut past the O ring so it rests against the stop inside the sealing nut (Fig. 1) For Chambers with Static quartz support: To load the quartz for these units it is best to load the quartz thimble into the chamber before using the sealing nut. insert the domed end of the sealing nut and ensure it is located in its support cup at the closed end of the chamber. There should be 5-15mm sticking out the open end of the chamber and square with the end of the chamber when it is properly located. (Fig. 4) Fig 1. Then insert the domed end of the quartz, with the sealing nut attached, into the chamber through the sealing nipple. (Fig. 2) Fig. 2 Slide the quartz into the chamber and it will centre itself in the spring support Keeping firm hold of the sealing nut so it does not spring back, start screwing the sealing nut onto the chamber. Carefully screw the sealing nut until it just starts compressing the O ring seal, then another ½ to ¾ turn so it is firmly hand tight should be sufficient to ensure it is properly sealed. (Fig. 3) Fig. 4 Take the sealing nut with the O ring in place and screw it on to the chamber over the top of the open end of the quartz thimble that is protruding from the chamber. During this process the O ring should slip over the open end of the quartz thimble. It is important to ensure the O ring does not become pinched as it slips over the end of the quartz as this may break the quartz. You may look through the end of the sealing nut with a light source to check or you could check with your finger inside the sealing nut, as it is being screwed on. (Fig. 5) Fig. 5 Fig. 3 You can inspect the O ring through the sealing nut to confirm it is compressed on the quartz thimble with 2-3mm of O ring flat against the quartz. The unit should be checked against maximum water pressure to ensure it is properly sealed. Compression can be increased by turning the nut in a clockwise direction. Carefully screw the sealing nut until it just starts compressing the O ring seal, then another ½ to ¾ turn so it is firmly hand tight should be sufficient to ensure it is properly sealed. Do not over tighten with multi-grips. You can inspect the O ring through the sealing nut to confirm it is compressed on the quartz thimble with 2-3mm of O ring flat against the quartz. The unit should be checked against maximum water pressure to ensure it is properly sealed. Compression can be increased by turning the nut in a clockwise direction. Manual S Series Rev 7, 1103 Page 9

UV Lamp:- Remove the UV lamp from its protective wrapping and wipe down with a soft cloth/tissue soaked in methylated spirits. Do not touch it without protective gloves, care should be taken not to leave markings of any nature on the UV lamp, as this could have a detrimental effect on the performance of the UV lamp. Insert the UV lamp into the quartz thimble through the hole through the centre of the sealing nut. If the chamber is installed vertically, NEVER drop the lamp into the quartz thimble, as this may break the quartz thimble and the UV lamp. Always keep a firm hold of the UV lamp until it is secured to its four pin connector. Using cotton gloves or a soft cloth to hold the UV lamp, push the female 4 pin connector firmly on to the lamp pins. Locate the three holes in the end cap with the three holes on the end of the sealing nut. Screw all three screws (M3) through the holes in the end cap, into the sealing nut. Return full water pressure to the UV reactor. Insert the power lead into the outlet then turn power on. The UV lamp will ignite and come on, however it will take between 2 and 5 minutes for the lamp to reach full output. Manual S Series Rev 7, 1103 Page 10

3. SERVICING The servicing of this UV reactor should only be carried out by a qualified service technician. Failure to do so will result in the warranty being void. 3.1 Servicing the Quartz Thimble The UV unit must be switched off and hydraulically isolated and drained before servicing. Isolate the water supply to the UV reactor. Switch off main power supply to the UV disinfection reactor. Release pressure and drain water within the UV disinfection reactor. Remove the three screws that secure the end cap to the sealing nut. Slide the lamp out enough to be able to remove the four pin plug. Disconnect the four pin plug from the end of the UV lamp. Remove the UV lamp from the reactor and place in a safe place or if it is being replaced dispose of the used UV lamp according to local regulations Unscrew the sealing nut in an anti-clockwise direction and carefully remove it from reactor. Take care with chambers with spring quartz support as the spring will suddenly push the quartz out of the chamber when the sealing nut becomes disengaged from the chamber. Take care to hold on to the quartz thimble as it may come out of the reactor at the same time. Remove the sealing nut from the quartz thimble and store in a safe place. You can then remove the quartz thimble from the reactor. If the thimble is due for a clean, wipe it down with a cleansing cream or similar and then wash down with water. It may be necessary to scrape off the remnants of the old O ring with a sharp knife or razor blade. Repeat this step Manual S Series Rev 7, 1103 Page 11

until the quartz thimble is clean, then wipe down the quartz thimble with a soft cloth/ tissue that has been soaked in methylated spirits, then dry it. (take care to protect your hands with suitable gloves). Reassemble the unit as described in section 2.1.2 above. 3.2 Servicing the UV Lamp The UV unit must be switched off and hydraulically isolated and depressurized before servicing. Switch off the mains power to the UV disinfection unit. Remove the three screws that hold the end cap in place on the end of the sealing nut. The UV lamp will be attached to the lead that goes through the end cap. Slide the UV lamp out just enough so that you are able to get a firm hold on it, you will then be able to remove the four pin plug that is connected to the end of the UV lamp. Disconnect the 4 pin plug from the lamp (inserting a thin screw driver between the plug and lamp may assist). Remove the UV lamp from the reactor and place in a safe place. If it is being replaced dispose of the used UV lamp according to local regulations. Reinstall UV lamp. (see in section 2.1.2.2 above). 3.3 Power Supply Box The servicing of the power supply box should be only carried out by a qualified service technician. Manual S Series Rev 7, 1103 Page 12

4. SPARE PARTS LIST WITH CORRESPONDING PART NUMBERS Series Quartz thimble UV Lamp Quartz O Rings Sealing Nuts S20 20280 11020 31000 32100 S30 20290 11030 31000 32100 S40-62 20310 11040 31000 32100 S40-76 20310 11040 31000 32100 S75 20310 11074 31000 32100 S80 20140 11080 31010 32110 S125 20140 11125 31010 32110 S172 20140 11172 31010 32110 S40X2 20140 11040 31010 32110 S80X2 20140 11080 31010 32110 S125X2 20140 11125 31010 32110 S172X2 20140 11172 31010 32110 S160 20200 11160 31010 32110 S160X2 20200 11160 31010 32110 S160X4 20200 11160 31010 32110 S245 20200 11248 31010 32110 S245X2 20200 11248 31010 32110 S245X4 20200 11248 31010 32110 Table 2 Series View port (pyrex) Viewing port Viewing Port O Ring (polycarbonate) All S series units 32210 32200 31040 Table 3 Optional Power Supplies Power boxes with options such as UV intensity monitors will be supplied with a supplemental operating manual to cover the optional items. Manual S Series Rev 7, 1103 Page 13