PINETOP FIRE DEPARTMENT TIMBER MESA FIRE AND MEDICAL DISTRICT

Similar documents
Drexel Heights Fire District 2012 International Fire Code Amendments

FIRE APPARATUS ACCESS AND WATER SUPPLY GUIDELINE

FIRE SERVICE FEATURES

FIRE PREVENTION CODE

Item Referenced and Amendments Building 1 Building 2 Analysis, Review and Remarks. Page 1 of 15

TABLE OF CONTENTS ADOPTED FIRE CODES... 3 AFPD SERVICE AREA... 3 SITE AND DEVELOPMENT SUBMITTAL REQUIREMENTS... 4 PLAN REVIEW FEES...

2015 Recommended Building Code with Amendments. The Executive Committee of the Central Iowa Code Consortium does ordain as follows:

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

This guide is intended to provide assistance in the application of the fire code in all areas served by Tualatin Valley Fire & Rescue.

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2000 EDITION SECTIONS

ORDINANCE NO NOW, THEREFORE, BE IT ENACTED BY THE CITY COUNCIL OF THE CITY OF FAIRBANKS, ALASKA, as follows:

Glenwood Springs Fire Protection District Amendments to the 2009 International Fire Code

Fire & Life Safety Requirements For Fire Department Access and Water Supplies

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

4/13/2015. Everything a firefighter wants to tell a design professional or building code official, in one hour.

Site Plans. Fire Code Requirements

CAMP VERDE FIRE DISTRICT

FIRE PROTECTION SYSTEMS

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT

VACAVILLE FIRE PROTECTION DISTRICT 420 Vine Street Vacaville, California (707)

ICC CODE CORNER 2015 International Fire Code

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER FIRE CODE

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

Elk Creek Fire Protection District

North Las Vegas Fire Code Amendments

Amendment A International Fire Code

Fire Sprinkler System Design and Installation Requirements

FIRE APPARATUS ACCESS

FIRE PREVENTION CODE. conditions hazardous to life and property from fire, hazardous materials, or explosion.

*HB0217* H.B. 217 H.B STATE FIRE CODE ACT AMENDMENTS. LEGISLATIVE GENERAL COUNSEL 6 Approved for Filing: C.R. Gilbert :11 PM 6

HAWAII ADMINISTRATIVE RULES TITLE 12 DEPARTMENT OF LABOR AND INDUSTRIAL RELATIONS SUBTITLE 7 BOARDS CHAPTER 45.1 STATE FIRE COUNCIL STATE FIRE CODE

SECRETARY S CERTIFICATE

Mobile Fire Rescue Department Bureau of Fire Prevention

2009 INTERNATIONAL FIRE CODE AMENDMENTS

ORDINANCE NUMBER

FIRE PREVENTION AND PROTECTION*

1301: Fire protection systems.

EXHIBIT A STEAMBOAT SPRINGS FIRE PREVENTION SERVICES ADMINISTRATIVE POLICY & PROCEDURE MANUAL

ORDINANCE NO

Construction and Development Guide

MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE FIRE LANES

EXHIBIT A STEAMBOAT SPRINGS FIRE PREVENTION SERVICES ADMINISTRATIVE POLICY & PROCEDURE MANUAL

780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS

ADMINISTRATIVE ORDER # CERTIFICATES OF USE AND OCCUPANCY FOR EXISTING BUILDINGS

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

ARTICLE 5.02 FIRE CODE

TAMARAC FIRE RESCUE DEPARTMENT FIRE PREVENTION BUREAU 6000 North Hiatus Road Tamarac, Florida Telephone: (954) , Fax: (954)

ORDINANCE NO

Fire Prevention Bureau INFORMATION PACKAGE

ORDINANCE AN ORDINANCE AMENDING THE HENDERSONVILLE MUNICIPAL CODE, TITLE 7, CHAPTER 2, FIRE CODE

TETON COUNTY FIRE PROTECTION RESOLUTION FOR NEW SUBDIVISIONS 2008 Edition. Chapter I General Provisions

FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES

1301: Fire protection systems. (A) Section 901 General

Chapter 2: Identification, water and access

HAWAII ADMINISTRATIVE RULES TITLE 12 DEPARTMENT OF LABOR AND INDUSTRIAL RELATIONS SUBTITLE 7 BOARDS CHAPTER 45.1 STATE FIRE COUNCIL STATE FIRE CODE

CITY OF CHESAPEAKE PUBLIC FACILITIES MANUAL CHAPTER XIII FIRE PROTECTION

ORDINANCE NO WHEREAS, the WSBCC has recently adopted new editions of several of such International codes; and

C I T Y O F B A N N I N G BANNING FIRE SERVICES 3900 W. WILSON STREET (951) PHONE (951) FAX

Oklahoma. 265: Incorporated national codes and standards The following national codes and standards are incorporated by reference:

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2012 EDITION

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

ORDINANCE No A

Recommended Amendments to the 2012 International Fire Code

ORDINANCE NUMBER

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

Fire Department Access and Water Supply

Pismo Beach, CA Municipal Code. Chapter 8.08 FIRE PREVENTION REGULATIONS

Title 14 Fire Code. (Ord. 2426, Amended, 06/22/2009; Ord. 2407, Amended, 08/11/2008; Ord. 2266, Add, 02/28/2005)

Recommended Amendments to the 2003 International Fire Code North Central Texas Council of Governments region

Defend In Place 2012 IFC Overview of Institutional Occupancies

Florida Building Code 2010

APPENDIX A International Building Code Amendments

FIRE PROTECTION SYSTEMS

FIRE CODE. Coal City Fire District International Fire Code Update. 35 S. DeWitt Place Coal City, IL

Iowa (2) Delete section and insert in lieu thereof the following new section:

COMMUNITY RISK REDUCTION BUREAU MANUAL TABLE OF CONTENTS EFFECTIVE: APRIL 1, 2016 AUTHORIZED: R. Pearce

AUTOMATIC FIRE SPRINKLER SYSTEMS

Business Fire Inspection. City of Guadalupe

ERRATA TO THE 2000 INTERNATIONAL FIRE CODE. Fourth Printing, January 2002 Updated March 29, 2002

FIRE CODE APPLICATION GUIDE FOR DEVELOPMENT IN UNINCORPORATED MULTNOMAH COUNTY

Fire Suppression Introduction Contact Information

To expedite the plan review and inspection processes, please refer to the information below.

ORDINANCE NO WHEREAS, the WSBCC has recently adopted new editions of several of such International codes; and

Construction and Development Guide

Denver Fire Department Fire Prevention Division

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

OUTLINE FOR FIRE PREVENTION ACTIVITY

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

CITY OF SNOHOMISH Snohomish, Washington ORDINANCE 2192

FIRE PROTECTION SYSTEMS

BUILDING/FIRE CODE REFERENCES 2006 EDITION

TABLE OF CONTENTS. Part I Administrative... 1 CHAPTER 1 SCOPE AND ADMINISTRATION... 1

Wausau Fire Department Inspection Violation Code Listing (Modified) All Applicable Records

Richardson Fire Department 136 N. Greenville Avenue, Richardson, TX Telephone: Fax:

January 1, 2014 Mandatory Effective Date

Recommended Amendments to the 2012 International Fire Code North Central Texas Council of Governments region

Transcription:

Amendments for 2015 IFC CHAPTER 1 SCOPE AND ADMINISTRATION Section 101.2.1 Appendices. All appendices to be adopted Section 113.2 Schedule of permit fees. Is AMENDED to read: A fee for each permit shall be paid, as required, in accordance with the schedule as established by the Pinetop Fire District/Timber Mesa Fire and Medical District fee schedule. CHAPTER 2 DEFINITIONS Driveway. Is ADDED to read: Driveway. A vehicular ingress and egress route that serves no more than five buildings or structures, not including accessory structures, or no more than five residential dwelling units. Institutional Group I-1. The first sentence is AMENDED to read: Institutional Group I-1 occupancy shall include buildings, structures or parts thereof for more than 10 persons, excluding staff, who reside on a 24-hour basis in a supervised environment and receive custodial care. [1]

Institutional Group I-1, Six to Sixteen persons receiving custodial care. Is AMENDED to read: Six to ten persons receiving care. A facility such as above, housing not fewer than six and not more than 10 persons receiving such care, shall be classified as Group R-4. Residential Group R-3. AMENDED to read: Residential occupancies where the occupants are primarily permanent in nature and not classified as Group R-l, R-2, R-4 or I, including: Boarding houses (transient or non-transient) with 10 or fewer occupants, Buildings that do not contain more than two dwelling units, Care facilities that provide accommodations for five or fewer persons receiving care, congregate living facilities (transient or non-transient) with 10 or fewer occupants. Residential Group R-4. The first sentence is AMENDED to read: Residential Group R-4 shall include buildings, structures or portions thereof for more than five but not more than 10 persons, excluding staff, who reside on a 24-hours basis in a supervised residential environment and receive custodial care. CHAPTER 3 GENERAL REQUIREMENTS Section 311.5 Placards. Is AMENDED to read: When determined by the fire or building code official, any vacant or abandoned buildings or structures determined to be unsafe pursuant to Section 110 of this code relating to structural or interior hazards shall be marked as required by Sections 311.5.1 through 311.5.5. [2]

CHAPTER 5 FIRE SERVICE FEATURES Section 507.5.4 Obstruction. Is AMENDED by ADDING a third sentence: Unobstructed access to fire hydrants shall be maintained at all times. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. Vehicles shall not be placed, parked, or kept within 15 feet (4,572 mm) from the center of a fire hydrant, pursuant to A.R.S. 28-873 A(4). CHAPTER 9 FIRE PROTECTION SYSTEMS Section 901.2 Construction Documents. Is AMENDED by ADDING a second paragraph: Automatic fire protection system hydraulic calculations shall be based upon 90 percent of the available water supply as determined by the local water purveyor or flow test information. Section 901.4.6 Pump and riser room size. Is AMENDED to read: Fire pump and automatic sprinkler system riser rooms shall be located in a dedicated room and have a door directly accessible from the exterior of the building in new construction. New automatic sprinkler systems that are installed in existing buildings are to have the riser room located within 100 feet of a door leading to the exterior of the building. The room shall be designed with adequate space for all equipment necessary for the installation, as defined by the manufacturer, with sufficient working space around the stationary equipment. Clearances [3]

around the equipment to elements of permanent construction, including other installed equipment and appliances, shall be sufficient to allow inspection, service, repair or replacement without removing such elements of permanent construction or disabling the function of a required fire-resistance-rated assembly. Fire pump and automatic sprinkler system riser rooms shall be provided with a door(s) and an unobstructed passageway large enough to allow for removal of the largest piece of equipment. Section 901.6.2 Records. Is AMENDED to read: Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years. All individuals or businesses performing inspections, tests or maintenance required by the referenced standards shall forward itemized reports of such work to the fire code official within 30 days of activity performed. Section 903 - AUTOMATIC FIRE SPRINKLER SYSTEMS Section 903.2.1.1 Group A-1 is AMENDED to read: 1. The fire area exceeds 5,000 square feet (464.5152 m 2 ). 2. The fire area has an occupant load of 150 or more. Section 903.2.1.2 Group A-2 is AMENDED to read: 1. The fire area exceeds 3,000 square feet (287.7091 m 2 ). [4]

Section 903.2.1.3 Group A-3 is AMENDED to read: 1. The fire area exceeds 5,000 square feet (464.5152 m 2 ). 2. The fire area has an occupant load of 150 or more. Section 903.2.1.4 Group A-4 is AMENDED to read: 1. The fire area exceeds 5,000 square feet (464.5152 m 2 ). 2. The fire area has an occupant load of 150 or more. Section 903.2.1.6 Assembly occupancies on roofs is AMENDED to read: Where an occupied roof has an assembly occupancy with an occupant load exceeding 50 for a group A-2 and 150 for other Group A occupancies, all floors between the occupied roof and the exit level of discharge shall be equipped with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. Section 903.2.3 Group E. Is AMENDED to read: 1. Throughout all Group E fire areas greater than in area. Section 903.2.4 Group F-1. Is AMENDED to read: 1. A Group F-1 fire area exceeds 5,000 square feet (464.5152 m 2 ). 2. A Group F-1 fire area is located more than two stories above grade plane. 3. The combined area of all Group F-1 fire areas on all floors, including any mezzanines, exceeds 10,000 square feet (929.0304 m 2 ). [5]

Section 903.2.4.1. Is AMENDED to read: An automatic sprinkler system shall provided throughout all Group F-1 occupancy fire areas that contain commercial woodworking operations in excess of 1,500 square feet in area (139.3546 m 2 ) that generate combustible waste or use finely divided combustible materials. Section 903.2.7 Group M. Is AMENDED to read: 1. A Group M fire area exceeds 5,000 square feet (464.5152 m 2 ). 2. A Group M fire area is located more than two stories above grade plane. 3. The combined area of all Group M fire areas on all floors, including any mezzanines, exceeds 10,000 square feet (929.0304 m 2 ). 4. A Group M occupancy used for the display and sale of upholstered furniture or mattresses exceeds 2,500 square feet (232.2576 m 2 ). Section 903.2.8 Group R. Is AMENDED to read: An automatic sprinkler system shall be installed in accordance with Section 903.3 shall be provided throughout all buildings with a Group R-l, R-2, or R-4 fire area. Section 903.2.8.2 AND Section 903.2.8.3 are COMBINED and AMENDED to read: Section 903.2.8.2 Group R-3 or R-4 (Condition 1 or 2) congregate residencies. An automatic sprinkler system shall be installed throughout all new Group R-3 or R-4 congregate residencies in accordance with Section 903.1.2 or 903.1.3 with 10 or fewer residents. Existing Group R-3 or R-4 congregate residencies shall be retrofitted with an automatic sprinkler system in accordance with Section 903.1.2 or 903.1.3 within 24 months of discovery or annexation into Pinetop Fire District/Timber Mesa Fire and Medical District boundaries. [6]

Section 903.2.9 Group S-1. Is AMENDED to read: 1. A Group S-1 fire area exceeds 5,000 square feet (464.5152 m 2 ). 2. A Group S-1 fire area is located more than two stories above grade plane. 3. The combined area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 10,000 square feet (929.0304 m 2 ). 4. A Group S-1 fire area is used for the storage of commercial motor vehicle where the fire area exceeds 2,500 square feet (232.2576 m 2 ). Section 903.2.9.1 Repair Garages. Is AMENDED to read: 1. Buildings having two or more stories above grade plane, including basements, with a fire area containing a repair garage exceeding 5,000 square feet (464.5152 m 2 ). 2. Buildings not more than one story above grade plane, with a fire area containing a repair garage exceeding 5,000 square feet (464.5152 m 2 ). 3. A Group S-1 fire area used for the repair of commercial motor vehicles where the fire area exceeds 2,500 square feet (232.2576 m 2 ). Section 903.2.9.2 is AMENDED to read: Buildings and structures where the area for storage of tires exceeds 10,000 cubic feet (283.1685 m 3 ) shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. Section 903.2.10 Group S-2. Is AMENDED to read: 1. Where the fire area of an enclosed parking garage exceeds 5,000 square feet (464.5152 m 2 ). Exception: Is DELETED entirely [7]

Section 903.2.10.1. Is AMENDED to read. An automatic sprinkler system shall be provided throughout buildings used for storage of commercial motor vehicle where the fire area exceeds 2,500 square feet (232.2576 m 2 ). Section 903.2.13 Group B. Is ADDED to read: Group B. An automatic sprinkler system shall be installed throughout all new Group B Occupancies where the fire area exceeds 3,000 square feet (278.7091 m 2 ). Section 903.2.14 Mixed Occupancies Structures. Is ADDED to read: All new buildings or structures which have the potential to be designated as a mixed occupancy shall have an automatic sprinkler system installed throughout. Existing buildings or structures, where a change of occupancy occurs, separation requirements shall comply with Table 508.4 of the International Building Code 2015, and Section 1103.5.4 of this code. Section 903.4.2.1 Water-flow notification devices. Is ADDED to read: Water-flow notification devices. An approved audible/visual notification appliance shall be installed in a normally occupied interior area of each building or each individual tenant space at the time of a tenant improvement. ADA restrooms within the same area shall have a visual notification appliance located within the room. Such sprinkler water flow notification devices shall be activated by the water flow of a single sprinkler of the smallest size installed in the system. This section will be retroactive as deemed necessary by the fire code or building official. [8]

SECTION 905 - STANDPIPE SYSTEMS Section 905.8 Dry standpipes. Is AMENDED to read: When required by the fire code official, dry standpipes shall be installed when fire apparatus access roads do not meet the requirements as outlined in Appendix D. Section 912 - FIRE DEPARTMENT CONNECTIONS Section 912.2 Locations. Is AMENDED to read: With respect to hydrants, driveways, buildings and landscaping, fire department connections shall be located that, the fire apparatus and hose connected to supply the system will not obstruct access to the buildings for other fire apparatus. The location of fire department connections shall be approved by the fire chief, or their designated fire code official. CHAPTER 11 CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS SECTION 1103 - FIRE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS Section 1103.5.4 Fire area increase. Is ADDED to read: Fire area Increase. An automatic sprinkler system shall be provided throughout existing buildings or residential occupancies where the square footage of the new fire area is greater than 25 percent of the total fire area of the existing structure and the required fire-flow for the total fire area (new & existing) is not equal to the fire-flow required by Appendix B of this code. [9]

CHAPTER 53 COMPRESSED GASES SECTION 5307 - CARBON DIOXIDE (C02) SYSTEMS USED IN BEVERAGE DISPENSING APPLICATIONS Section 5307.5 Required protection. Is AMENDED to read: Where carbon dioxide storage tanks, cylinders, piping and equipment are located indoors, rooms or areas containing carbon dioxide storage tanks, cylinders, piping and fittings and other areas where a leak of carbon dioxide can collect shall retroactively be provided with ventilation in accordance of Section 5307.5.1 and an emergency alarm system in accordance with Section 5307.5.2. Outside storage shall only require an emergency alarm in accordance with Section 5307.5.2. APPENDIX D FIRE APPARATUS ACCESS ROADS SECTION D103 - MINIMUM SPECIFICATIONS Section D103.1.1 Driveways. Is ADDED to read: Driveways. Driveways exceeding 150 feet (45,720mm) in length providing access to single family dwelling units shall provide a minimum unobstructed width of 14 feet (4,267mm) and a minimum unobstructed height of 13 feet 6 inches (4,511mm). Driveways in excess of 150 feet (45,720mm) in length shall provide turnarounds. Driveways in excess of 200 feet (6,0960mm) in length and less than 20 feet (6,096mm) shall provide turnouts in addition to turnarounds. Driveway turnout shall be an all-weather road surface at least 10 feet (3,048mm) wide and 30 [10]

feet (9,144mm) long. Driveway turnouts shall be located as required by the fire code official. Driveway turnarounds shall have an inside turning radius of not less than 30 feet (9,144mm) and an outside turning radius of not less than 45 feet (13,716mm). Driveways that connect with a road or roads at more than one point may be considered as having a turnaround if all changes of direction meet the radius requirements for driveway turnarounds. A driveway shall not serve in excess of five residential dwelling units. Section D103.5 Fire apparatus access road gates. Is AMENDED to read: 1. Where a single gate is provided, the gate width shall be not less than 20 feet (6,096mm) when serving two or more directions. Where a fire apparatus road consists of a divided roadway, the gate shall not be less than 12 feet (3658 mm) when serving a single direction. 4. Emergency gates shall be equipped with a means of opening the gate by fire department personnel for emergency access. All electric gates shall be equipped with a key switch compatible with the fire district s existing system. tion D103.5 Fire apparatus access road gates. Item 9 Is ADDED to read: 9. Existing electric gates shall be retrofitted with Knox key switch opening equipment in accordance with this section upon discovery or annexation into Pinetop Fire or Timber Mesa Fire and Medical District s boundaries. Compliance with this section shall be completed in a time schedule approved by the fire code official. [11]

Section D103.6 Signs. Is AMENDED to read: Where required by the fire code official, fire apparatus access roads shall be marked with permanent NO PARKING - FIRE LANE signs complying with Pinetop Fire District/Town of Pinetop Lakeside or Timber Mesa Fire and Medical District/City of Show Low ordinances and or standards. Signs shall have a minimum dimension of 12 inches (30Smm) wide by 18 inches (4S7mm) high and have red letters on white reflective background. Signs shall be posted on one or both sides of the fire apparatus access road as required by Section D103.6.1 through D103.6.2. Section D103.6.2 Roads more than 26 feet in width. Is amended by adding a second paragraph: Where parking lanes are provided, they shall have a minimum dimension of 8 feet (2,438mm) in width, measured from the back of a wedge or rolled curb, or from the face of a vertical curb. [12]