THE INSTITUTE OF REFRIGERATION

Similar documents
Energy Efficiency Through Waste Heat Recovery. Heat Recovery Centrifugal Chillers and Templifier Water Heaters

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

MINTRAC MEAT INDUSTRY ENVIRONMENT CONFERENCE WASTE HEAT RECOVERY FROM RENDERING PLANTS PRESENTED BY DEREK HENDERSON

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems

Applications of Thermodynamics: Heat Pumps and Refrigerators

EN aquatech.piovan.com

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

HVAC Fundamentals & Refrigeration Cycle

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

Energy consumption storage facilities examined in ICE-E

ENERGY SAVER. Technology Report. Industrial refrigeration and chilled glycol and water applications. savepower.nsw.gov.au

Transcritical CO2 Bottle Cooler Development

Performance Optimization of the Evaporative Condenser Design

LECTURE-17. Multi-Stage Vapour Compression Refrigeration. 1. Introduction

Parilla Thermal Storage Project Case Study. May Page 1 of 11

HVAC Water chiller selection and optimisation of operation

BASE LEVEL AUDIT REQUIREMENTS REFRIGERATION SYSTEMS 1. SITE DATA COLLECTION. Business Name. Site physical address (Street, Suburb, City)

R07. Answer any FIVE Questions All Questions carry equal marks *****

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

A Technical Introduction to Cool Thermal Energy Storage Commercial Applications

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

Chapter 2.3: Steam System

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

THE BIG FIVE NATURAL REFRIGERANTS IN DIFFERENT INDUSTRIAL APPLICATIONS. MAYEKAWA EUROPE S.A.,Leuvensesteenweg 605, 1930 Zaventem, Belgium

Sustainable Techniques in Refrigerated Space

Adsorption Chillers Energysmart Green Cooling

Climate control precision in Hi-tech environments Jupiter and Mercury Close Control Units

MECHANICAL SCIENCE Module 2 Heat Exchangers

Carnot. 2. (a) Discuss the advantages of the dense air refrigeration system over an open air refrigeration system?

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Small Commercial Business Energy Audits. Recognizing and addressing the special requirements of the small business market segment.

H EDRICK ASSOCIATES OF GRAND RAPIDS West Michigan s Factory Representative

Customers. The core of our innovation. Feeding&Conveying Drying Dosing Temperature Control Refrigeration. Granulation

Single Screw Ammonia Heat Pumps. Harness Your Heat... Don t Reject It

GEOTHERMAL DESIGN GUIDE

Featuring Ozone-safe HFC134a. Hitachi Centrifugal Chillers NEW. GXG-S Series GSG-S Series. Debut

An Efficient Cold Store Facility

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

Technical Note. EHPA Quality Label Model Range Definition Version

Performance of an Improved Household Refrigerator/Freezer

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

July 2012 was a significant date for the HVAC and Refrigeration industry as it saw the introduction of the Carbon Tax and the HFC Levy.

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

INSERT NEW PHOTO HERE

Information Guide Maintenance and Refrigerant Regulations. Issue 35

Daikin Blueprint: Delivering Hot Water with a Chiller

DTI Kenneth Bank Madsen Global Application Expert Food Retail

CO2 TRANSCRITICAL BOOSTER SYSTEMS

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Appendix A. Glossary of Common Terms

The impact of water treatment on refrigeration system energy efficiency

Partial Load Performance Of Refrigeration System

Pack Calculation Pro. Users guide. Version Morten Juel Skovrup

your comfort. our world. Altherma Flex Type Renewable heat pump system for every environment

Effective temperature, relative humidity and air velocity combinations to provide most effective chilling

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Brazed Plate Heat Exchanger for CO Applications

Save energy with oil-free water-cooled compressors. Energy recovery solutions (ER )

Energy consumption in properties

Mitsubishi Electric Guide to Chiller Technologies. Information Guide 58

System Design, Commissioning, Operation

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

Chapter 1 Preface & General

THERMAL ICE STORAGE: Application & Design Guide

Refrigerant Glide and Effect on Performances Declaration

"ETI-Z, GART-ZE/ZEI" Centrifugal Chillers using Low-GWP Refrigerants for Full Capacity Range

HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS

Featuring Ozone-safe HFC134a. Hitachi Centrifugal Chillers. NEW GXG-S Series GSG-S Series Debut

Chapter 4 Compressors Overview & System Annual Power Consumption

Efficiency of Application the Condensing Heat Utilizers in the Existing Boiler's Unit in Heat Power Station

Innovation and improvements in batch centrifugal designs.

ParaWeld Plate Heat Exchangers

Efficient Steam System Design

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

High-efficiency Turbo Chiller (NART Series)

Commercial CO 2 Refrigeration Systems

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

Environmentally friendly refrigeration systems for industrial use

Screw Compressors ESN Fixed Speed & VS 250 Variable Speed

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

Reducing the Carbon Footprint of Existing Domestic Heating: A Non-Disruptive Approach

Heat Pump Water Heaters

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Process Simulation and Optimization of Cryogenic Operations Using Multi-Stream Brazed Aluminum Exchangers

Improving Cold Chain Competitiveness with Danfoss Energy Efficiency Solutions.

LOW RECIRCULATION RATE EVAPORATORS

Eco Compact Series GAS HEAT PUMP

A new solution to detect wet steam and measure the dryness fraction

OPERATING MANUAL Enertronic Control System 2

Tuthill Process Pumps Products Marketing Report Report # 3 (Rev. 04/09/06) MEAT PACKING MARKET. Meat Processing Applications

CHAPTER 8 EVAPORATION. The basic factors that affect the rate of evaporation are the:

Suction Accumulators. Introduction. Suction Accumulators

Transcription:

THE INSTITUTE OF REFRIGERATION Optimisation of Refrigeration and Heat Pump Designs for Meat Processing Plants By F J. BOWATER, MA. (CANTAB), C. ENG., M.I..MECH.E., M.I..Nuc.E., M.I.Mare.E. M.Inst.R. FJB Systems Engineering & Management s (Session 1988-1989) To be presented before the Institute of Refrigeration at The Institute of Marine Engineers, 76 Mark Lane, London, E.C.3, on Thursday, 5th January 1989. 1. Introduction Most meat processing plants are designed and constructed in a piecemeal manner by the various specialists who cover their particular discipline. Consequently it is usual for a refrigeration specialist to calculate the refrigeration loads of the plant and design a refrigeration system as economically as possible to meet the plant requirements. Likewise, when it comes to the requirements of other services, such as hot water and steam, other specialists are used to determine the requirements and they, in turn, economise the design of their side of the plant. Most large meat processing plants incorporate their own byproducts department associated with the drying of waste material and further processing into tallow and stock feed. This process therefore generates a large amount of waste heat as the water is evaporated. Again, specialist contractors are used to determine the most suitable plant for the needs of the meat works. The purpose of this Paper is to integrate these three particular technologies and to analyse the most suitable overall plant to optimise its total energy requirements, bearing in mind that there is considerable waste heat available from the refrigeration plant and the by-products sector, while there is a large, relatively low temperature, heat requirement necessary to produce the hot water. It is particularly important to employ specialists in the design of meat processing works and the management of them as without this overall analysis it would be impossible for the individual equipment designers to arrive at a suitable optimum configuration. Furthermore, specialists designing heat pumps have no way of selling their systems into such plants without a specialist in the Industry tabulating the heat pump s requirements and integrating it into the other specialist services of the plant. Inevitably the heat pump designer does not know the overall heat balance of the plant and, particularly in Europe, the quality of the meat works management is so low that there would be no way of the management providing the supplier with any accurate information. Consequently, the opportunity of making a sale and economising on energy is lost. This Paper attempts to fill this gap. 2. The Heat Balance Bearing in mind that all meat processing plants require refrigeration and hot water and have waste heat, these specific aspects can be summarised as follows: 2.1 Refrigeration The refrigeration requirements for any meat works are divided between the following sections within the plant. (i) Air Conditioning This is required for the maintenance of processing areas at a temperature of no higher than 10 0 C and refers particularly to the boning operation. The required refrigeration saturated suction temperature in the engine room is approximately 0 0 C. (ii) Meal Chilling Any modern meat works requires the carcasses to be chilled following the dressing operation at an air temperature of at least -1 0 C which requires a refrigeration saturated suction temperature of at least 10 0 C. (iii) Freezing Most meat works require a capability to either freeze carcasses or freeze boneless meat produced in the boning room, as well as offals. Freezing can be carried out either over 24 hrs or over 48 Proc. Inst. R. 1988-1989. 1-6

hrs and will require air temperatures respectively of -35 0 C and -25 0 C with corresponding refrigeration saturated suction temperatures of -43 0 C and -32 0 C. (iv) Cold Storage Plants that produce frozen products must always have a requirement for cold storage at a temperature of no higher than -18 0 C, which will require a refrigeration saturated suction temperature of approximately -25 0 C. The above requirements can be summarised as shown in Table 1. The requirements as set out in Table 1 will be analysed to determine the most economic system design. 2.2 Heat Requirements Heat is required basically for two main services within a meat works - the production of hot water and the evaporation of water out of the product in the by-product section. Hot water is usually required in three services as follows. Exact temperatures vary from plant to plant. The water temperatures for a typical abattoir are shown in Table 2. The by-products department requires steam at 6.5 bar for the evaporation process. 2.3 By-Products Plant Waste Heat In the process of evaporating water from the by-products, the water is driven off at a temperature of 100 0 C and atmospheric pressure. This relatively high temperature heat is sufficient to make a contribution to the hot water requirement of the plant. 2.4 Refrigeration Waste Heat Large amounts of low temperature waste heat approaching 35 0 C are released by the refrigeration plant and this waste heat is very rarely used. The main purpose of this Paper is to analyse whether there is an economic case for its use. 3. Typical Plants for Consideration For the purpose of this Paper and in order to arrive at a TABLE 1 Air temperature (1) Air conditioning 10 0 C 5 0 C requirements (2) Chilling -1 0 C -10 0 C (3) Cold storage -18 0 C -25 0 C requirement (4) Carcass freezing -25 0 C -32 0 C and 48 hour carton freeze (5) 24 hour carton -35 0 C -43 0 C freeze TABLE 2 Max saturated suct. temp * Sterilizing 82 0 C * Wash down 65 0 C * Basins, showers and carcass wash 43 0 C practical answer to the question of how waste heat can be utilised, three typical plant sizes will be taken into account as follows, and analysed accordingly. 3.1 Small European Plant Capacity: 200 cattle/day 1500 pigs/day 1000 sheep/day Most of these plants and particularly those in the UK are unlikely to have a by-products department, the waste material being sold in unprocessed form to specialized centralized by-products processors. 3.2 Medium Sized Overseas Plant Capacity: 550 cattle/day 1500 pigs/day 6000 sheep/day There will be very few occasions where such a plant did not have a by-products department which would require steam and which would, in turn, be producing large quantities of waste heat. 3.3 Large Southern Hemisphere Plant (Typical New Zealand Plant) Capacity: 750 cattle/day 150 pigs/day 20,000 sheep/day All such plants would have a by-products facility producing large quantities of waste heat. The small pig throughput is typical to provide local pork requirements while the beef and sheep are for export. 4. Refrigeration Design Bearing in mind the variables which exist on a meat works site associated with waste heat, its utilisation, hot water heating and refrigeration, the part of the plant which is fixed with regard to its basic design is nevertheless the refrigeration plant. This is simply because the basic refrigeration load exists for each part of the system, as described above, and the engineer must optimise the plant to meet these refrigeration loads, keeping capital costs to the minimum and at the same time producing the most economic plant with respect to the consumption of electricity. There is no option, as there is in the case of the by-products process, for refrigeration to be contracted out to third parties. As explained above, most meat plants, particularly large units, would theoretically have five separate refrigeration sections covering air conditioning, chilling, carcass freezing, carton freezing, and cold storage. It is usual in practice for the five separate suctions to be found uneconomic on capital cost, although highly efficient on electricity usage, and as a result the plant is usually simplified into three suctions as shown in Table 3. The reason for these three evaporating temperatures usually being chosen is that the air conditioning and cold storage loads are small in relation to the other services required and therefore the inefficiencies so caused by combination are minimal. Proc. Inst. R. 1988-1989. 2-6

TABLE 3 * -10 0 C Sat. suct. temperature Air conditioning and meat chilling * -32 0 C Sat. suct. temperature Carcass freezing, 48 hour carton freezing and cold storage * -43 0 C Sat. suct. temperatue 24 hour carton freezing With regard to the -43 0 C saturation suction temperatures, this is increasingly becoming less common as with more emphasis in the last 10 years being placed on energy saving most plants freeze cartons over a 48 hr period, rather than 24 hrs. There are two fundamentally different principles that can be used for the design of refrigeration plant. (a) Packaged Systems. The plants are self contained and can be located close to the load requirement. Refrigerant 22 or 502 are commonly employed in such systems so that single stage compressors can be used. (b) Centralised Engine Room Concept. Pumped recirculation compressor/condenser plant is housed in a centralised location to keep expensive lines and line losses to a minimum. The use of R22 or R717 based on two stage systems for low temperatures results in low electricity consumption. The concentration of all waste condenser heat in one location allows economies for hot water production. Figure 1 gives a summary of typical electrical consumption figures for the above systems and refrigerants. It soon becomes obvious that the only sensible solutions for large meat processing plants is a choice between either pumped R717 or R22 systems. Thus most refrigeration requirements on a large meat works is for large refrigeration loads at 2 saturated suction temperatures, i.e. -10 0 C and -32 0 C. The usual practice is to design a two stage plant with booster compressors operating at the low pressure, discharging into an intercooler which, in turn, is then serviced by the second stage compressors. The intercooler in turn is used to provide refrigeration to the -10 0 C services. With the introduction of screw compressors, there is a case for eliminating the two stage operation and working the -32 0 C on a single stage basis. This system is perfectly acceptable and in fact provides the optimum solution to reduce capital cost keeping running costs at an acceptable level, but only if sub-cooled liquid is fed to the low stage vessel via the high stage suction. The two alternatives are shown in Figs 2 and 3 and it can be seen that the single stage option will significantly reduce capital cost. With regard to the electricity consumption, Fig. 4 shows that the two stage system working with sub-cooled liquid has only a very marginal increase in electricity consumption. We would conclude, therefore, that the refrigeration plant design for most typical meat works operations should be based on Fig. 3, utilising single stage plant with sub cooled liquid feed using screw compressors, servicing two saturated suction temperatures of -10 0 C and -32 0 C. Having reached this conclusion, we list in Table 4 the refrigeration requirements for the three typical plant types shown above, together with the condenser waste heat rejection rate, all Compressor Power Consumption per kw Refrig Capacity (PkW/kWR) 1.3 1.2 1.1 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 TYPICAL ELECTRICITY CONSUMPTION RESULTS FROM DIFFERENT REFRIGERATION SYSTEMS R22 Condensing at +35 C R717 Condensing at +30 C R502 Condensing at +35 C R502 Condensing at +30 C 2 Stage Compression +5 0-10 -20-30 -40-45 COMPRESSOR SATURATED SUCTION TEMPERATURE ( C) Fig. 1. Typical electricity consumption results from different refrigeration systems -10 C -32 C Boosters Compressors feed Fig. 2. Typical two stage configuration Condensers feed taken as an average over a typical 24 hr period. The remainder of this Paper will conclude as to whether the waste heat produced from the condenser plant can be satisfactorily used to cut down on the total energy requirements of the plant. Proc. Inst. R. 1988-1989. 3-6

5. Hot Water Requirements From extensive experience in the management and design of meat works, the three plants under consideration, we know, will require approximate quantities of hot water as shown in Table 5. The quantities convert into an overall 24 hour hot water heating requirement as shown in Table 6. The heat requirements associated with the 43 0 C water supply, due to its relatively low temperature, could be met quite adequately by the refrigeration plant condenser waste heat provided that a suitable heat pump was provided to transfer heat from the refrigeration condensers into the cold water supply. 6. By-Product Waste Heat Availability From our experience in the management and operation of meat processing plants, we give in Table 7 the approximate values of waste heat rejection at a temperature of 100 0 C which would be available from the by-products plant against each of the three types of meat works under consideration. 7. Refrigeration Waste Heat Availability Versus Hot Water Requirements Table 8 summarises the heat balance, it can be seen that the small European plant, having no by-products department, has no option under normal circumstances, to produce all its hot water, other than by burning fossil fuels in a steam or hot water boiler. It is the writer s contention however that the waste heat from the refrigeration plant can be suitably upgraded by a heat pump and it can be seen that the condenser waste heat available is some four times the 43 0 C water requirement. A typical Small European Plant has been operating successfully in this way with a heat pump for a number of years. Turning now to the medium and large sized plants normally seen overseas, it can be seen that the waste heat from the byproducts department is in no way sufficient to generate all the hot water requirements of the works and again the condenser waste heat could be used via a heat pump to produce all the works 43 0 C water, there being again some twice as much waste heat available compared with the heat required. 8. Heat Pump Potential Figure 5 shows a typical arrangement for a heat pump working on R 12 and pumping the heat from the refrigeration condenser TABLE 4 Refrigeration requirements for three plant types Small plant 522kW 77kW 670kW 57,900 (148 TR) (22TR) (191TR) Medium plant 1319kW 1248kW 2785kW 240,600 (375 TR) (355 TR) (792 TR) Large plant 1143kW 4131Kw 5626kW 486,100 (325 TR) (1175 TR) (1600 TR) Note: ( ) denotes Tons Refrigerattion kw -10 0 C -32 0 C Condenser Waste heat ref load ref load waste heat kj x 1000 per day TABLE 5 Cubic metres / 24 hours High Suction Compressor -10 C Condensers feed Sub cooled liquid feed Fig. 3. Single stage with sub-cooling Screw Compressors -32 C 82 0 C 65 0 C 43 0 C Small plant 108 115 162 Medium plant 456 972 1367 Large plant 737 1572 2211 TABLE 6 Hot water heating requirements for three plant types kj x 1000 / 24 hours 0.55kW/kW 82 0 C 65 0 C 43 0 C Total 0.50 pkw/kw 0.49 pkw/kw Small plant 29,000 22,600 17,000 68,600 Medium plant 122,300 191,400 143,200 456,900 Large plant 197,600 309,600 231,600 738,800 TABLE 7 Single stage without sub cooled liquid Single stage with sub cooled liquid 1 2 3 Two stage with sub cooled liquid Fig. 4. Power consumption figures comparing single stage with two stage plant (saturated suction temperature -32 0 C) kj x 1000 / 24 hours Small plant 0* Medium plant 62,500 Large plant 98,500 * No Rendering Proc. Inst. R. 1988-1989. 4-6

TABLE 8 Waste heat versus hot water requirements kj x 1000 / 24 hours Hot water By-product Hot water 43 0 C Condenser Maximum requirement waste heat remaining heat Water heat waste heat heat pump requirement requirement output Small plant 68,600 nil 68,600 17,000 57,900 67,600 Medium plant 456,900 62,000 394,900 143,200 240,600 280,700 Large plant 738,800 98,500 640,300 231,600 486,100 567,100 18 C Water Sub Cooler Heat Exchanger 43 C Water Heat Pump Compressors 50 C Condensing TABLE 9 Daily costs & savings in water heating Daily Heat pump Conventional Possible 43 0 C electricity cost energy water cost saving (kj x 1000) Small plant 17,000 26.01 40.29 14.28 Medium plant 143,200 219.10 339.28 120.28 Large plant 231,600 354.35 548.89 194.54 Refrigeration Plant Hot Gas Line Heat Exchanger Shell & Tube Condenser 20 C Evaporation Condensed to Refrigeration Plant Fig. 5. Typical arrangemennt for a heat pump working on R12 source to a temperature of 50 0 C from which the 43 0 C hot water requirement can be met. The heat pump is of a simple design but uses sub-cooling from the incoming cold water supply and on the basis of using an evaporator temperature of 20 0 C and a condensing temperature of 50 0 C, and the effective sub cooling, the coefficient of performance of the heat pump can theoretically rise to 7 or above. Under practical conditions and as far as this Paper s calculations are concerned, a COP of 6 will be assumed as more practical. From the above assessment of hot water heating requirements it has been shown that condenser waste heat can be turned to 43 0 C water in all of the three plants analysed. Average conditions have been taken over a full day s production and as in practice there are large variations in refrigeration loads and hot water requirements, it will be necessary to install hot water tanks to act as storage buffers to even out the daily requirements. In large meat works it has been common for many years to have such tanks to use the by-products waste heat. Additional tanks may be required depending on the particular plant/heat balance. On the basis of electricity charges of 5p/kW hour and a coefficient of performance for the heat pump of 6, then the electricity cost for generating 43 0 C water will be approximately 0.231 pence per 1000 kj heat recovered. However, because the condenser heat available is so much in excess of the heat required, the heat pump would be programmed to run only when maximum demand was low, i.e. the electricity charge to the heat pump would be an energy charge only at 3.3 pence per kw per hour. This will give a cost of 0.153 pence per 1000 kj. Using a conventional boiler with an efficiency of 80% and fuel oil at 39,600 kj per kg at a cost of 75/tonne, the cost of heat water by fuel oil will be 0.237 pence per 1000 kj. Table 9 shows the daily costs for the production of 43 0 C water using the refrigeration waste heat and heat pump compared with generating the same hot water using a conventional boiler for the three plants in question, based on the above figures. It can be seen that operating for over 250 days/year will show a fuel cost saving of approximately 3570 per annum for small UK type plants, up to approximately 48,635 per annum for large overseas operations. It is the writer s opinion that compact heat pump plant situated in the actual engine room location, drawing heat from the refrigeration condenser plant, could be purchased and installed at a cost not greatly in excess of these yearly savings figures and thus could be paid off within two years of installation. For the large application to produce the full 230 million kj per day, two small packaged 1275 cubic metre per hour screw compressors would easily meet the hot water load at 43 0 C as shown in Table 9. Another way of attempting to optimize the heat pump possibilities is to run the pump over as extended a period as possible and to use the full electricity tariff at 0.231 pence per 1000 kj of heat recovered. By working the pump continously it would then be possible to heat all hot water to 43 0 C before heating further by conventional means the higher temperature quantities. By proceeding in this way the 43 0 C water quantities to be heated by the pump would be as follows: Small plant 40,400 kj x 1000/day Medium plant 292,800 kj x 1000/day Large plant 473,500 kj x 1000/day Proc. Inst. R. 1988-1989. 5-6

TABLE 10 Daily costs & savings in water heating Daily Heat pump Conventional Possible 43 0 C electricity cost energy water cost saving (kj x 1000) Small plant 40,300 50.40 95.51 45.11 Medium plant 280,700 351.01 665.26 314.25 Large plant 473,400 591.99 1121.95 529.96 Comparing this figures with Table 8, double the amount of water could be serviced by the heat pump but at the full electricity tariff. Table 8 also indicated that there is sufficient heat available to do this from the heat pump. Working in this way savings, as shown in Table 10, should be possilbe, resulting in the small plant saving some 11,250/year while the large plant should save up to 132,500/year. There is a real demand for a packaged heat pump unit to meet the above requirements and the refrigeration manufacturers should be looking to come up with a suitalble automatic economic unit. 9. Conclusion In designing the optimum refrigeration plant for most modern meat works, it is best to rationalise the refrigeration suctions to two pressures at an evaporation temperature of -10 0 C and -32 0 C. This arrangement gives good electricity consumption while allowing capital costs to be kept to a minimum using single stage screw compressors. The -32 0 C suction must use sub cooled liquid. The refrigerant should be R717 or R22 with pumped circulation. Single stage packaged plants are too energy inefficient. Further economies can be achieved by utilising the meat works by-products department to generate high temperature sterilising and wash down water by installing a by-products waste heat recovery plant. This arrangement will allow lower temperature hot water to be generated efficiently by a heat pump arrangement working between the refrigeration condenser waste heat source and a special hot water heat exchanger. Such a system could save a large meat works some 49,000 per annum in energy costs, allowing the heat pump capital cost to be recovered within two years. The alternative arrangement is to heat all hot water to 43 0 C which would mean continous heat pump operation and the use of a full electrical tariff charge. However, using typical electrical tariff charge rates saving and working in this way could save up to 133,000/year. The arrangement to be used would depend upon local tariff arrangements and specific works requirements. Heat pump design specialists should concentrate on systems to operate at higher temperatures as if an economic system can be achieved, hot wash down water at 65 0 C could also be generated in this fashion with additional savings. The heat pump condensation temperature would then have to rise from 50 0 C to 72 0 C. Exact economies depend very much upon the present fluctuations in fuel prices. A further saving by using such heat pump systems arises from the lowering of the refrigeration plant condensing pressure or cutting back on condenser capital cost, the former producing significant additional savings to the plant energy account. No allowance in the above savings has been made for this additional benefit. Proc. Inst. R. 1988-1989. 6-6