Over/Undersizing in TRACE 700

Similar documents
Supply air temperature reset

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Chilled beams. TRACE 700 incorporates two chilled beam strategies: passive and active.

Adding More Fan Power Can Be a Good Thing

TRACE 700. Slide 1. Hello, my name is Nick Cavitt and I m a marketing engineer in the C.D.S. group at TRANE.

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

Single Zone System. One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

Hello, my name is Audra Benzschawel and I m a marketing engineer in the C.D.S. Slide 1 TRACE 700

VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Coil Unit with Enhanced Humidity Control

High-Performance VAV Systems

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

When Duct Sealing Kills HVAC Equipment and Efficiency

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013

HVAC DISTRIBUTION and DELIVERY SYSTEMS

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK

Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

Chapter 6 ALL-AIR HVAC SYSTEMS 6.1 CONTEXT

A/C Cooling Load calculation and measurement

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

90% Design Submittal Mechnical Equipment Calculations Parking Garage CDRL

ApacheHVAC User Guide Part F: Loads Analysis and Reporting Tools

Don t Turn Active Beams Into Expensive Diffusers

ASHRAE Standard 62 Ventilation Report Technical Assignment #1. Calvert Memorial Hospital Prince Frederick, MD

Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

Air Conditioning Clinic

7. MECHANICAL SYSTEM DESIGN

Verasys System Operation Overview Technical Bulletin

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

Fundamentals of Psychrometrics. By James L. Murphy, Colorado Building Environments Sales Engineer

Designing Energy Efficient Outdoor Air Systems

Summary Comparison of Simulation Program Features

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

Dedicated Closed Circuit Hydrostatic Fan Drive Control

Executive Summary. OA/person (cfm/p) Private and open offices, Classrooms, Building as designed

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

Reviewing HVAC Designs for Compliance with ACCA Manual S

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

Air Conditioning Clinic

MANUAL J/S Summary One summary sheet for each system

Redesign of Bennett Hall HVAC System

Air System Sizing Summary for AHU/CU-1 Project Name: Wilton Manors Fire Station#16 06/26/2016 Prepared by: L.N.I.

Ambient (ºF) Temperature Rise Above

TOTAL SYSTEM EFFICIENCY: CONDENSING BOILER SYSTEM MYTH BUSTING. David Grassl PE Mechanical Engineer Principal

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

Mechanical Analysis Energy Savings Graph 1 Built-up Roof Graph 2 Green Roof

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

DADANCO Technical Paper

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

Trane Engineers Newsletter Live

APC APPLICATION NOTE #109

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

b.) Technical Information:

Technical Investigation, Part Three Elizabeth C. Krauss Mechanical Option September 18, 2013

Benefits Offered by Passive Dehumidification Wheel Speed Control

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, August 2015

December 6, 2018 Optimizing Solutions through Superior Dehumidification Technology SM

Trane CDQ Desiccant Dehumidification

Technical Assignment 1

Chilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Hello, my name is Sarah Hilden and I am a Marketing Engineer in the C.D.S. group at Trane.

Direct and indirect evaporative cooling

RT-OA TM Rooftop Outdoor-Air (DOAS)

Terminal. Las Vegas, NV. Technical

2 Existing Mechanical System

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Agenda and Objectives

HVAC Optimization with Cold Air Distribution

An HVAC Audit of the Canberra Institute of Technology

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

HVAC Myths and Realities Trane Engineers Newsletter Live Series

Dehumidifying with Dedicated Outdoor Air

PhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi

Mold/Moisture Control Case Study

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

COMMERCIAL HVAC PACKAGED EQUIPMENT. Rooftop Units Level 1: Constant Volume

Application of Air Source Variable Refrigerant Flow in Cold Climates

Zoned Rooftop Systems. Light commercial packaged rooftop systems from Trane

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

Pharmaceutical Facility Design

CONSTRUCTION AND ENERGY COSTS FOR RADIANT VS. VAV SYSTEMS

Closing the Gap: Getting Full Performance from Residential Central Air Conditioners. Task 4 - Develop New Climate-Sensitive Air Conditioner

Energy Use in Refrigeration Systems

4. OVERVIEW OF MECHANICAL SYSTEM

Capt. Tim s s Duct Design Mythbusters. The bitterness of poor quality is remembered long after the sweetness of low price is forgotten!

MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

Challenges and Methods of Estimating a Conceptual HVAC Design

Technical Report Three

Transcription:

Over/Undersizing in TRACE 700 Over/undersizing, which appears on the Checksums and Airflow Loads reports, typically occurs with constant volume system types, especially Single Zone (SZ), Fan Coil (FC), Variable Temperature Constant Volume (VTCV), and Multizone (MZ) systems. The following airside system and rooms will be used to illustrate what over/undersizing is and how it is calculated in TRACE 700. Exhaust Return Air Ventilation ACU Supply Air - 1 Supply Air - 2 Room 2 The sensible heat equation (see below) will be used to calculate the sensible loads, airflows, and sensible over/undersizing. Qs = DSHP x CFM x ( Tr Ts ) Qs is the sensible load in the space calculated based on the input walls, windows, internal loads, etc. A positive value indicates heat gains, a negative value indicates heat losses. DSHP is the density specific heat product (1.085 at sea level), we will use 1.1 for simplification purposes. DSHP is calculated for each weather location based on the altitude of the location and can be found on the Title Page report. CFM is the supply airflow. This can either be input on the Airflows tab of Create Rooms or calculated by TRACE using the sensible heat equation. Tr is the room set point temperature entered on the Rooms tab of Create Rooms. We will assume 75F for cooling and 70F for heating. Ts is supply air dry bulb (SADB) and it is input on the Temperatures tab of Create Airside Systems or calculated by TRACE using the sensible heat equation. If only the sensible over/undersizing is considered, then the over/undersing would be equal to the difference between Qs and DSHP x CFM x (Tr-Ts). Over/undersizing = DSHP x CFM x (Tr Ts) Qs For cooling design reports: a positive value (+) denotes overcooling (or oversizing of the cooling coil) a negative value (-) denotes undercooling (or undersizing of the cooling coil) For heating design reports: a positive value (+) denotes underheating (or undersizing of the heating coil) a negative value (-) denotes overheating (or oversizing of the heating coil)

Five scenarios will be used to calculate over/undersizing, explain why it occurs, and how to minimize it. Scenario 1 Over/undersizing on heating for a constant volume system with heating supply air dry bulb and airflow specified by user. (input by user) Heating Ts = 105F (input by user) Over/undersizing = 1.1 x 500 x (70 105) (-5,500) = -13,750 Btu This would indicate overheating of 13,750 Btu s, since the space would need 143 cfm at a SADB of 105F to properly condition the space. To minimize the overheating, remove the heating supply air dry bulb and/or the supply airflow and allow the program to calculate the value(s). Scenario 2 Over/undersizing on cooling for a constant volume system with cooling supply air dry bulb* and airflow specified by user. (input by user) Cooling Ts = 50F (input by user) In this scenario, the over/undersizing on cooling would be Over/undersizing = 1.1 x 500 x (75 50) 11,000 = 2,750 Btu This would indicate overcooling of 2,750 Btu s, since the space would need 400 cfm at a SADB of 50F to properly condition the space. Note: If the system selected has the ability to reheat at the terminal device, then this is the amount of reheat that would be done at cooling design. To minimize the overcooling, remove the cooling supply air dry bulb and/or the supply airflow and allow the program to calculate the value(s). Scenario 3 Over/undersizing on heating for a constant volume system with cooling supply air dry bulb* entered by user or calculated by TRACE and the heating supply air dry bulb specified by user. Heating Ts = 100F (input by user) Since constant volume systems supply the same airflow for both heating and cooling conditions, TRACE calculates the design cooling and heating airflows separately then selects the larger of the two airflows as the system s design supply airflow. This same supply airflow is then used for heating design and for cooling design. 11,000 = 1.1 x CFM x (75-55) -5,500 = 1.1 x CFM x (70-100) CFM = 167 cfm Over/undersizing = [1.1 x 500 x (70 100) (-5,500)] = -11,000 Btu This would indicate overheating of 11,000 Btu s, since the space would need 167 cfm at a SADB of 100F to properly condition the space. Typically, rooms do not need as much airflow for heating as for cooling, therefore oversizing occurs because there is too much airflow for the design heating load. The program tries to reduce the design supply air dry bulb for heating, but cannot reduce it below the Minimum Heating Supply Air Dry Bulb

Temperature or the Room Design Heating Dry Bulb Temperature. To minimize the overheating, remove the heating supply air dry bulb and allow the program to calculate the value(s). Scenario 4 Over/undersizing on heating for a variable volume system with cooling supply air dry bulb* entered by user or calculated by TRACE and the heating supply air dry bulb specified by user. Heating Ts = 100F (input by user) VAV min stop = 50% of cooling supply airflow (entered on Airflows tab of Create Rooms) The cooling supply cfm would be calculated using the sensible heat equation. The heating supply cfm would be calculated using the cooling supply cfm and the minimum stop 11,000 = 1.1 x CFM x (75-55) CFM = 500 x 50% CFM = 250 cfm Over/undersizing = 1.1 x 250 x (70 100) (-5,500) = -2,750 Btu This would indicate overheating of 2,750 Btu s, since the space would need 167 cfm at a SADB of 100F to properly condition the space. Any time a heating supply air dry bulb is entered for a variable volume system, oversizing or undersizing of the coil should be expected. To minimize the overheating, remove the heating supply air dry bulb and allow the program to calculate the value. Scenario 5 Over/undersizing on heating for a constant volume system with cooling supply air dry bulb* entered by user or calculated by TRACE. Heating Qs = -8,250 Btu (calculated by TRACE based on heat losses) The heating supply air dry bulb will typically be calculated from the sensible heat losses and the supply cfm calculated during the cooling calculations. 11,000 = 1.1 x CFM x (75 55) -8,250 = 1.1 x 500 x ( 70 Ts) Heating Ts = 85F (calculated by TRACE) Room 2 Heating Qs = -2,750 Btu (calculated by TRACE based on heat losses) Heating Ts = 85F (calcualted by TRACE based on worst case room assigned to system) 11,000 = 1.1 x CFM x (75-55) Over/undersizing = 1.1 x 500 x (70 85) (-2,750) = -5,500 Btu This would indicate overheating of 5,500 Btu s, since the space would need 167 cfm at a SADB of 85F to properly condition the space.

Constant volume systems supply the same airflow for both heating and cooling conditions. TRACE calculates the design cooling and heating airflows separately then selects the larger of the two airflows as the system s design supply airflow. This same supply airflow is used for heating design and for cooling design. When multiple spaces are conditioned by the same coil, a single supply air dry bulb is calculated. This often will cause one room to set the heating supply air dry bulb and other rooms to be overheated. Rooms that have very different thermal properties (internal Vs external rooms) will see large amounts of overheating, as is shown in scenario 5. Scenario 6 Over/undersizing on cooling for a variable volume system. - East Facing Cooling Qs = 11,000 Btu (Maximum sensible load calculated by TRACE based on heat gains at time of space peak - 9am for this example) Cooling Qs = 5,000 Btu (Sensible load calculated by TRACE based on heat gains at time of system (cooling coil) peak - 3pm for this example) VAV min stop = 50% of cooling supply airflow (entered on Airflows tab of Create Rooms) The cooling supply cfm would be calculated using the sensible heat equation and the loads at the time of space peak 9am for this east facing office. The minimum supply cfm would be calculated using the cooling supply cfm and the minimum stop. Minimum CFM supplied to space: 11,000 = 1.1 x CFM x (75-55) CFM = 500 x 50% CFM = 250 cfm When sizing the cooling coil, oversizing would appear in this example based on the minimum airflow requirements Over/undersizing = 1.1 x 250 x (75 55) (5,000) = 500 Btu This would indicate overcooling of 500 Btu s, since the space would need 227 cfm, but the minimum stop on the VAV box is 250 cfm. Any time the minimum airflow is more than what is required to condition the space, oversizing of the coil should be expected. Scenario 7 Over/undersizing on cooling for a system with cooling supply air dry bulb specified by user and a ventilation rate greater than the supply airflow need to condition the space. Ventilation CFM = 600 cfm (input by user) Cooling Ts = 55F (input by user) Required supply airflow to condition the space 11,000 = 1.1 x CFM x (75 55) CFM = 500 Since the user input ventilation rate is larger than the airflow required to cool the space, TRACE will use the ventilation rate as the supply airflow for the space. In this scenario, the over/undersizing on cooling would be Over/undersizing = 1.1 x 600 x (75 55) 11,000 = 2,200 Btu This would indicate overcooling of 2,200 Btu s, since the space would need 500 cfm at a SADB of 55F to properly condition the space. Note: If the system selected has the ability to reheat at the terminal device, then this is the amount of reheat that would be done at cooling design. To minimize the overcooling, remove the cooling supply air dry and allow the program to calculate the value.

Summary Points / Additional Items: 1. For cooling design reports: a positive value (+) denotes overcooling (or oversizing of the cooling coil) a negative value (-) denotes undercooling (or undersizing of the cooling coil) For heating design reports: a positive value (+) denotes underheating (or undersizing of the heating coil) a negative value (-) denotes overheating (or oversizing of the heating coil) 2. Over/undersing is an actual load on the coil, it cannot simply be ignored. 3. There are many other situations that can cause Over/undersizing. These situations are all caused by a space being either over or under-conditioned due to the system selected, user inputs, or both. Additional questions about Over/undersizing should be directed to the C.D.S. Support Center at 608-787-3926 or cdshelp@trane.com. * Inputting the leaving cooling coil temperature will cause the situations to occur as inputting the supply air dry bulb. The relationship between the two inputs is shown below: Supply Air Dry Bulb = Leaving Cooling Coil Temperature + Duct Heat Gain + Fan Heat Gain (draw thru fan configurations only)