Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5

Similar documents
FUNDERMAX GMBH FIRE TEST REPORT

UL 94 Flammability Ratings: Introduction

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.

In Search of Standard Reference Materials (SRMs) for ASTM E05 Fire Standards by. Norman Alvares & Harry Hasegawa

Report on Public Input June 2014 NFPA 101

ASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Fire Test Methods ASTM NFPA UL ISO IEC

Criteri di Preselezione in Accordo ad UL 94 e Conformità del Prodotto Finito. Matteo Paleari Senior Project Engineer

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes

DualGuard Fluoropolymer Barrier FRP Duct. Composites USA. Fluoropolymer Barrier FRP Duct. A Critical Process Systems Group Company LISTED

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Fire Performance of Translucent Systems


Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria

Public Comment No. 2-NFPA [ Section No ]

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Heat and Smoke Release of a Ceiling-Installed Speaker

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

ASTM E662 TESTING FOR COLE MOTORSPORTS/CM RACING PRODUCTS ON WINDSHIELD TEAROFFS ON ¼ GLASS VTEC # TESTED: MARCH 27, 2009

FIRE RETARDANT ARCHITECTURAL WOOD COATING FIRE SHIELD FS020 FIRE-SHIELD SEALER. FS021 FIRE-SHIELD TOP COAT Available in different gloss

Abrasion Resistance of Fluoropolymer and polyester Coatings

We Identify and S.T.O.P. Your Noise Problems

Forbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877.

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.

Fire Risk and CODE Compliance For Fabric Wrapped Acoustic Panels

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

Public Comment No. 1-NFPA [ Section No ]

Materials Testing by Gregory Havel

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

Test Report No. AJFS FF Date: OCT.17, 2018 Page 1 of 6

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation

The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

First Revision No. 6-NFPA [ Section No. 2.2 ]

RENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy

SIGMADEK, LTD. FIRE TEST REPORT

Report on First Revision June 2014 NFPA 101

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

FRANCE M & F RANKING ACCORDING TO NF F

Market-Leading Non-Metallic Enclosure Brands

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

TFI Report Classification

Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC

ZH Low Smoke 0-Halogen Flameretardant Identification Sleeves

Classification of Fire Performance of Wall and Ceiling Lining Materials


NF X : Parts 1, 2, 3, 4 & 5

(a) Flame shall not spread to the outer extremities of the sample on the 8 ft 12 ft (2440 mm 3660 mm) wall. Flashover shall not occur.

TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

Analysis Report

CMZH Low Smoke 0-Halogen Flame- Retardant Mass Transit Tag

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

CLASSIFICATION REPORT

TFI Report Classification

CLT Adhesive Tests in Support of Mass Timber Buildings

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

GUARDIAN FIRE TESTING LABORATORIES, INC.

Additional Reaction to Fire Classification Report

Safety Code Users. Fire Tests for Life SUPPLEMENT 3. Marcelo M. Hirschler FIRE PROPERTIES

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

PRESSURE-SENSITIVE TAPE CLOSURE SYSTEMS FOR USE WITH FACTORY-MADE AIR DUCTS- STANDARDS UL 181A AND UL 181B

Benefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E.

BS EN ISO : 2010

Flame Retardant Polyethylene Tubing

Pneumatic Tubing POLYTUBING O.D. 5/32"

C-01 FIRE DECKS AND BULKHEADS

Fire Testing of Foams

BS EN ISO : 2010

Fire Research and Education at the University of Maryland

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY

New European Fire Testing Classification for Construction Products

Nuclear Power Plant LSZH Cable Overview

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5

1.0 INTRODUCTION 2.0 CLASSIFICATION CRITERIA

IMO Resolution MSC 61(67): Annex 1: Part 2

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

ORDINANCE NO

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013

6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement

BS EN ISO : 2010

Technical Training International Textiles Training September 2018 Ellen Roaldi Instructor

Test Report: ICL/CR15/11/087

Test report. NanoPhos coating system EPR and EEN. Name of client: NanoPhos SA. Date: Pages: 5 Encl.: 1 Ref: BP / KTO

NFPA 285 THE BURNING QUESTION

BS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009.

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

IBC Committee Responsibility Matrix January 2017

Report Of Surface Burning Characteristics Tests On PVC Sheeting As Submitted By Jain (Americas) Inc.

EU flammability standards and ENFIRO

Transcription:

INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5 5 Tech Notes TESTING PROTOCOL Fire Retardant Gel Coats Issue Date: 4/22/2010 Document ID: TN-TS-05A 2010 Interplastic Corporation

Testing Protocol for Fire Retardant Gel Coats Background: The glass fiber reinforced composites (fiberglass) have been widely used in building, mass transit and industrial applications. Some these products are made from fire resistance raw materials. The fire resistance testing is conducted to determine flammability, surface burning characteristic and optical density of smoke generated type tests. The ASTM E84, ASTM E162, ASTM E662 and UL 94 tests are widely utilized in the industry to determine the suitability of the gel coat and resin products used in glass fiber reinforced (fiberglass) composites. The testing on the building materials are driven by the end use of the product that it is being intended for. In addition most of the code requirements are driven typically by the authority having jurisdiction (AHJ). This can be either the local code or the purchaser of the product intended for its end use. Reference: ASTM E84-10 Standard Test Method for Surface Burning Characteristics of Building Materials. ASTM E162-09 Standard Test Method for Surface Flammability of Materials Using a Radiant Heat Energy Source ASTM E662-09 Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials UL 94 The Standard for Safety of Flammability of Plastic Materials for Parts in Devices and Appliances testing Testing Criteria: 1) ASTM E84 This test method is intended to provide only comparative measurements of surface flame spread and smoke density measurements with that of select grade red oak and fiber-cement board surfaces under the specific fire exposure conditions. This test method exposes a 24-ft (7.32-m) long by 20-in. (508-mm) wide specimen to a controlled air flow and flaming fire exposure adjusted to spread the flame along the entire length of the select grade red oak specimen in 5 ½min. This test method does not provide measurement of heat transmission through the tested surface, the effect of aggravated flame spread behavior of an assembly resulting from the proximity of combustible walls and ceilings and classifying or defining a material as noncombustible, by means of a flame spread index by itself. Rating Flame Spread Smoke Index A 0 25 0-450 B 25 75 0-450 C 75-200 0-450 Issue Date: 4/22/2010 Document ID: TN-TS-05A Page 1

Testing Criteria: 2) ASTM E162 This test method provides a laboratory test procedure for measuring and comparing the surface flammability of materials when exposed to a prescribed level of radiant heat energy. It is intended for use in measurements of the surface flammability of materials exposed to fire. The test is conducted using small specimens that are representative, to the extent possible, of the material or assembly being evaluated. (Example: in terms of their thickness, layering, and any potential substrate.) The rate at which flames will travel along surfaces depends upon the physical and thermal properties of the material, product or assembly under test, the specimen mounting method and orientation, the type and level of fire or heat exposure, the availability of air, and properties of the surrounding enclosure. In this procedure, the specimens (6 inches by 18 inches) are subjected to one or more specific sets of laboratory fire test conditions. If different test conditions are substituted or the end-use conditions are changed, it is not always possible by or from this test to predict changes in the fire-test-response characteristics measured. Therefore, the results are valid only for the fire test exposure conditions described in this procedure. Test results are calculated using 1) Flame Spread Factor (Fs), 2) Temperature Rise ( C), 3) Heat Evolution Factor (Q), 4) Flaming Drippings (m:s) and 5) Test Duration (m:s) as Radiant Panel Index (Is) based on five individual test data. 3) ASTM E662 This test method provides a means for determining the specific optical density of the smoke generated by specimens of materials and assemblies under the specified exposure conditions. Values determined by this test are specific to the specimen or assembly in the form and thickness tested and are not to be considered inherent fundamental properties of the material tested. It is likely that closely repeatable or reproducible experimental results are not to be expected from tests of a given material when specimen thickness, density, or other variables are involved. The photometric scale used to measure smoke by this test method is similar to the optical density scale for human vision. However, physiological aspects associated with vision are not measured by this test method. Correlation with measurements by other test methods has not been established. At the present time no basis is provided for predicting the density of smoke generated by the materials upon exposure to heat and flame under other fire conditions. The test method is of a complex nature and the data obtained are sensitive to variations. In this procedure, the specimens are subjected to one or more specific sets of laboratory test conditions. If different test conditions are substituted or the end-use conditions are changed, it is not always possible by or from this test method to predict changes in the fire-testresponse characteristics measured. Therefore, the results are valid only for the fire test exposure conditions described in this procedure. Results are expressed in terms of specific optical density which is derived from a geometrical factor and the measured optical density or as measurement of the concentration of smoke. The results are intended for use in research and development and not as a basis for ratings for regulatory purposes. Issue Date: 4/22/2010 Document ID: TN-TS-05A Page 2

Testing Criteria: 4) UL94 V-0, V-1, V-2 FLAMMABILITY STANDARD There are 12 flame classifications specified in UL 94 that are assigned to materials based on the results of these small-scale flame tests. These classifications listed in descending order for each of the following three groupings are used to distinguish a material's burning characteristics after test specimens have been exposed to a specified test flame under controlled laboratory conditions. Six of the classifications relate to materials commonly used in manufacturing enclosures, structural parts and insulators found in consumer electronic products (5VA, 5VB, V-0, V-1, V-2, HB). Specimen: Length 125 mm (5 in) x Width 13 mm (0.5 in) x Thickness [typically 0.7 mm (1/32 in) or 1.5 mm (1/16 in) or 3.0 mm (1/8 in)]. To pass UL94 V-0 flame must be out in ten seconds, no glow beyond thirty seconds, and no burning material can fall. To pass UL94 V-1 flame must be out in thirty seconds, no glow beyond sixty seconds, and no burning material can fall. To pass UL94 V-2 flame must be out in thirty seconds, no glow beyond sixty seconds, and burning material can fall. Issue Date: 4/22/2010 Document ID: TN-TS-05A Page 3

ASTM E84 Images: The Substrate Before Testing After Testing Issue Date: 4/22/2010 Document ID: TN-TS-05A Page 4

ASTM E162 Image: ASTM E662 Image: Issue Date: 4/22/2010 Document ID: TN-TS-05A Page 5