Basic Hood Considerations The design process for a successful kitchen ventilation system starts when the engineering design HVAC team receives

Similar documents
LABEL PLEASE NOTE: ALL APPLICATIONS AND SITE PLANS MUST BE COMPLETED IN BLACK OR BLUE INK ONLY

REQUIREMENTS FOR HOOD PLANS

FOUNDATIONS OF MODERN KITCHEN VENTILATION (CKV) DESIGN HANDBOOK

Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS

Notable Changes in the Mechanical Codes

PDH & Professional Training

MSYS 4490 AC Systems

2012 International Mechanical Code Significant Changes. About the Significant Changes

2015 ICC Commercial Cooking Systems

Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

Schust Engineering, Inc. 701 North Street P.O. Box 128 Auburn, IN (260) Fax: (260)

IMC Significant Changes Summary Tier I

MODEL: JRSVH SERIES JEAN S RESTAURANT SUPPLY 426 SOUTH STAPLES CORPUS CHRISTI, TEXAS PH: (361)

EXHAUST FAN SCHEDULE

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

SECTION DUCTWORK

COMcheck Software Version Mechanical Compliance Certificate

SECTION COMMERCIAL-KITCHEN HOODS

GUIDELINES FOR HIGHRISE BUILDING CONSTRUCTION PROJECTS (MECHANICAL VENTILATION)

2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

SECTION AIR OUTLETS AND INLETS

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

Cleveland Clinic Design Standards MECHANICAL SYSTEMS DESIGN GUIDELINES HVAC AIR DISTRIBUTION PART I - GENERAL 1.1 SUMMARY

CHAPTER 5: EXHAUST SYSTEMS

Effective ventilation is necessary for the comfort

Kitchen Ventilation Hood Permit Application

Displacement Ventilation

D. Fabrication: Steel or Aluminum with baked enamel off-white finish. B. Type: Square and rectangular, adjustable pattern, multi-louvered diffuser.

COPPER INSERT INSTALLATION INSTRUCTIONS, USE AND CARE GUIDE

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

APPUZO RANGE HOOD INSTALLATION

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

Commercial Kitchen Ventilation (CKV) Design and Recent Innovations and Developments in the Industry.

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

Ventilation for New Low-Rise Residential Buildings July 20, 2015

2012 ICC Commercial Kitchen Hoods

MECHANICAL VENTILATION

for commercial kitchen ventilation

1.1 This section applies to air handling units for HVAC Systems.

SECTION AIR DUCT ACCESSORIES

2012 INTERNATIONAL FUEL GAS CODE VENTS

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

Demand-Controlled Ventilation For Commercial Kitchens

Low Wall Back Shelf Exhaust Canopy

INSTALLATION INSTRUCTIONS & USE & CARE GUIDE Air-O Ultra Series Range Hoods

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

Introduction to the Exhaust Fan Interceptor Commercial Exhaust Fans from a Service Perspective

AUTOMATIC MAKE-UP AIR DAMPER WITH TRANSFORMER READ AND SAVE THESE INSTRUCTIONS

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717)

INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

Project Name: Project Address: Installer Name: Installer Address: Date of Inspection:

ENVIRO UNIT ENGINEERING MANUAL KES SERIES

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL

SECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW...

Zoning System Design Manual

Union County Vocational - Technical Schools Scotch Plains, New Jersey

90.1 and Designing High Performance Commercial Kitchen Ventilation Systems BY DON FISHER, P.ENG., RICH SWIERCZYNA,

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

BUILDING VENTILATION GUIDE FOR LG HVAC SYSTEM INSTALLATION

City of Duluth Festival Center 04/25

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

Square Ceiling Diffusers : All extruded aluminum constructions. Opposed blade damper is adjustable from face of diffuser. Available in square and

UNIFORM MECHANICAL CODE SIGNIFICANT CHANGE COMPARISON STUDY

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

VentZone Systems VentZone Zoned IAQ with Heat Recovery Kits

Linear Floor Heaters

AIR HANDLING. B. Section Building Automation and Control System Guidelines. C. Section Air Cleaning Devices and Filters

CONTENTS. B. System Design and Performance Requirements

Inspection Checklist Mechanical Rough in

B. System Design and Performance Requirements

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

BEST PRACTICE RECOMMENDATIONS

DOCUMENT TABLE OF CONTENTS

VentZone Systems VentZone Zoned IAQ with Energy Recovery Kits

Ventilation Guidelines

SECTION DUCTWORK

Don t Turn Active Beams Into Expensive Diffusers

BUILDING VENTILATION GUIDE

User s Manual WS-68N30SS WS-68N36SS WS-68N42SS

KVF - Capture Jet canopy with Supply Air and Side-Jet Technology KVF. Capture Jet Canopy with Supply Air and Side-Jet Technology

DUCT SYSTEMS CHAPTER 6

PLAN THE INSTALLATION Planning the installation first requires selecting the most appropriate installation approach. The chart below offers suggestion

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

1 Exam Prep Florida Building Code-Mechanical Tabs and Highlights

WARNINGS: Must be followed carefully to avoid personal injury. IMPORTANT: Must be followed carefully to avoid damage or incorrect installation.

RL Series Commercial/Residential Ventilation Fan Installation Instructions Please Read And Save These Instructions.

Design Guide Improving Commercial Kitchen Ventilation System Performance

MECHANICAL EXHAUST VENTILATION SYSTEMS OPERATIONAL GUIDELINES-REVISED 2003

Chapter One Commercial Kitchen Fires

Kitchen Exhaust Air Cleaning Systems

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

Installation, Operation and Maintenance Manual

Transcription:

Design Considerations for Commercial Kitchen Ventilation By John A. Clark, P.E., Member ASHRAE Commercial kitchen ventilation (CKV) design must consider everything needed to be coordinated to form a system that will perform heat/moisture/smoke/odor/fire protection control, provide space comfort, be cost effective, and be acceptable to the local code authority. This article addresses hood selection, filter devices, replacement air systems, variable airflow systems, comfort heat/cooling, exhaust duct options, fan selections, stack outlets, sidewall outlets, utility connections, and fire protection control. Basic Hood Considerations The design process for a successful kitchen ventilation system starts when the engineering design HVAC team receives the kitchen equipment information from the kitchen designer (equipment supplier). The information package should include the equipment layout, the equipment shop drawings, the dimensions of the exhaust hoods selected and the exhaust cubic feet per minute (cfm) of the selected hoods. The design engineer should check that the hood selected will provide enough overhangs. Front overhang should be a minimum of 9 in. (229 mm); side overhang should be a minimum of 6 in. (152 mm). However, on convection ovens, the overhang should be 6 in. (152 mm) past the door opening at 90 from the oven. This often translates to an 18 in. (457 mm) front overhang. Also verify that grilling and broiler units are not at the end of the hood. These high heat and smoke-producing devices should be toward the center of the hood s length. About the Author John A. Clark, P.E., is a senior mechanical engineer at Karges-Faulconbridge, Inc. (KFI), St. Paul, Minn. 54 ASHRAE Journal ashrae.org February 2012

This article was published in ASHRAE Journal, February 2012. Copyright 2012 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org. Minimum Exhaust Flow Rate, cfm Per Linear Foot of Hood Type of Hood Light Duty Medium Duty Heavy Duty Extra-Heavy Duty Wall-Mounted Canopy, Unlisted 200 300 400 550 Listed 150 to 200 200 to 300 200 to 400 350+ Single-Island, Unlisted 400 500 600 700 Listed 250 to 300 300 to 400 300 to 600 550+ Double-Island (Per Side), Unlisted 250 300 400 550 Listed 150 to 200 200 to 300 250 to 400 500+ Eyebrow, Unlisted 250 250 Not Allowed Not Allowed Listed 150 to 250 150 to 250 Back Shelf/Proximity/Pass-Over, Unlisted 300 300 400 Not Allowed Listed 100 to 200 200 to 300 300 to 400 Not Recommended Source: 2011 ASHRAE Handbook HVAC Applications Table 1: Exhaust flow rates by cooking equipment category for unlisted and listed hood. Hood Static Pressure Loss, in. of Water Type of Grease Removal Device 150 to 250 cfm/ft 250 to 350 cfm/ft 350 to 450 cfm/ft 500+ cfm/ft Baffle Filter 0.25 to 0.50 0.50 to 0.75 0.75 to 1.00 1.00 to 1.25 Extractor 0.80 to 1.35 1.30 to 1.70 1.70 to 3.00 2.90 to 4.20 Multistage 0.55 to 1.10 1.10 to 1.70 1.70 to 2.90 2.90 to 4.00 Source: 2011 ASHRAE Handbook HVAC Applications Table 2: Exhaust static pressure loss of Type I hoods for various exhaust airflows. Note: Values based on 20 in. (508 mm) high filters and 1,500 fpm (7.62 m/s) through hood/duct collar. The HVAC designer should compare the submitted exhaust values with the minimum listed UL 710 exhaust rates for capture/ containment (Table 1). Always consider the exhaust flow recommended by the hood supplier. Then work with the equipment supplier to achieve a workable hood size and equipment layout. Most hood manufacturers also offer hood end panels. These end panels should be considered, if the hood is not next to a wall, to help minimize any effects of side drafts that disturb the rising thermal plume. Should the hood duct connection fall under a beam or a bar joist, request that the hood duct collar be shipped for on-site installation. This will allow for a straight duct connection, rather than sharp offsets. Check with the hood supplier as to how far from the normal collar location the field installed collar can be moved. Other Hood Selection Considerations The kitchen equipment designer s package often contains a Type II hood in addition to the primary Type I grease removal hood. The Type II hood collects and removes steam, condensable vapor, heat and odor. The Type II hoods have two subcategories: one removes condensate from the exhaust stream, and the other removes heat or odors. The Type II condensate unit often has a filter to cool/capture the exhaust stream moisture, as well as baffles and drainage trays to help prevent drips into the cooking food. The Type II heat unit does not have a filter. Be sure to verify if the Type II hood requires the condensate system. Typical kitchens also have dishwashers. The pass-through type and the conveyor type require a Type II hood with collection points at the inlet and the outlet of the dishwasher. The exhaust ductwork should be stainless steel below the kitchen ceiling and either stainless steel or aluminum above the ceiling. The exhaust duct should be liquid tight and pitch back toward the dishwasher. The dishwasher fan should be an aluminum unit. Connect the operation of the dishwasher exhaust fan to the dishwasher control panel. The dishwasher control panel has auxiliary contacts for this purpose. Provide a time delay relay to allow the dishwasher fan to run for a period after the dishwasher has been turned off. Filter Selection The primary purpose of a filter in the face of a hood is to prevent cooking flames from entering the exhaust duct. Also, the quantity of exhaust air keeps the filter s surface temperature not to exceed 200 F (93 C). The configuration of the filter s baffles are to facilitate condensing of the moisture and grease vapors so they can be captured by centrifugal separation as they pass through the turns and cooling surfaces. Industry reported grease extraction efficiency of filtration systems may not reflect actual performance. The filter type selected by the designer should match the expected duty of the hood (Table 2). Light and medium duty hoods can use simple baffle filters. These filters have a static pressure loss range from 0.25 to 1.25 in. w.c. (62 to 311 Pa.) This range also matches well with standard up-blast power roof ventilators (PRV) (up to 2 in. w.c. February 2012 ASHRAE Journal 55

Advertisement formerly in this space. [498 Pa]). The heavy and extra heavy hoods should consider using extractor filters that have a greater baffle length path, which allows for more condensing of the vapors before being centrifugally separated. A multistage water mist, scrubber and water bath also mechanically separates the grease. The fan static pressure requirement for the heavy and extra heavy hoods is more than 2.0 in. w.c. (498 Pa), which requires a special family of up-blast PRVs or centrifugal fans. In rare special cases, consideration can be looked at using other multistage units such as electrostatic precipitators, ultraviolet destruction devices, pleated bag, pleated, bag, and HEPA filters. All these devices are expensive to install and have high maintenance costs; therefore, a cost-effectiveness study should be done by the design team. Replacement Air Systems Replacement air is required to makeup the air being exhausted by the cooking hood(s), the dish machine and the toilet exhaust systems. The source of the replacement air is from three systems; primary heating/cooling supply air, makeup air and transfer air. Primary supply air to the kitchen area provides comfort for the working staff. This air is filtered, heated, and cooled to meet IAQ standards. The primary air can be supplied from a single source such as a rooftop unit or a main facility air-handling unit. Makeup air is outside air introduced though the primary air system. This air is filtered, heated, and cooled to help attract and keep a cooking staff. However, with the advent of variable exhaust requirements during non-cooking times a dedicated outdoor air system (DOAS) concept can be used to control the outdoor supply air to match the varying exhaust. Conditioned outdoor air from the dining area can be transferred into the kitchen area for 10% to 15% of the replacement air. This air also helps control the kitchen cooking odors from getting into the dining area. This air has been treated for occupant comfort and indoor air quality. A transfer fan system may be required to prevent cooling the cooked food, if a pass through serving window is used. Any airflow through a pass through window should be less than 75 fpm (0.38 m/s) velocity. A pressurization relationship between supply and exhaust air must be controlled to prevent cooking odors from migrating to adjacent building spaces. Avoid locating a gas water heater in a location where negative kitchen area conditions could cause a down flow of fumes from the gas water heater s stack. Variable Airflow System When there is no cooking taking place, there is reduced heat (thermal plume), no smoke, no steam, and no odor being produced. Therefore, the exhaust cfm can be reduced, which saves operational money. NFPA 96 allows the duct velocity to drop to a minimum of 500 fpm (2.54 m/s). The hood fan capacity is controlled by either optical smoke, infrared, or temperature sensors that reduce the exhaust fan speed. It is also important to reduce the replacement air in parallel with the exhaust rate to keep the facility pressure relationships constant. The 500 fpm (2.54 m/s) minimum also allows for reuse of existing grease ducts that were previously installed with higher cfm exhaust rates. Comfort Heating and Cooling The kitchen area is traditionally a hot or warm environment; therefore, cooling is the primary goal for comfort. Heating of the replacement air is required in the cooler climates; the air should be heated to a minimum of 50 F (10 C). Most building codes have adopted ASHRAE Standard 62.1 to set the outdoor air requirements for ventilation. This Standard set 15 cfm/person (7.0 L/s) for the kitchen area and 20 cfm/person (9.4 L/s) for the dining area. The energy saving trend is to reduce exhaust air, and ventilation air. The IMC 2009-2012 Section 403.3 requires 7.5 cfm/person (3.5 L/s) plus 0.18 cfm/ft 2 (0.08 L s/m 2 ) of the occupied space. 56 ASHRAE Journal February 2012

Advertisement formerly in this space.

Reasonable kitchen air-conditioning design is a balance of spot workstation heating/cooling, occupant ventilation, space pressure relationships, and exhaust replacement air capacity. The hood perimeter replacement air supply plenum has become the choice for supply air cooling and replacement air at the hood face, according to the major hood manufacturers (Photo 1, Page 54). The air is discharged through perforated face panels that blow down toward the front of the cooling line. The terminal velocity at the cooks head should be at 50 fpm (.25 m/s) to avoid any feeling of a draft. The width of the plenum and its mounting height should be considered when determining the supply air to the unit. If a DOAS unit is used the air can be heated to 50 F (10 C) and cooled to 75 F (24 C), thus saving energy. The use of four-way diffusers or two-way slot diffusers, for the general kitchen area, should not be closer than 15 ft (4.6 m) from the hood face. This distance arrangement is to avoid disturbing the hood capture of the rising thermal plume from the cooking surface. The location of the thermal controls for the heating/cooling units is traditionally in the kitchen manager s office with the thermal space sensors located in the kitchen and dining areas. This is done to maintain control by one person only. Exhaust Duct Options Type I duct construction consists of at least 16-gauge black steel or 18-gauge stainless steel. This duct must slope 0.25 in. per foot (6 mm per 0.3 m) toward the hood or an approved grease reservoir. For ducts longer than 75 ft (23 m), the slope shall be at least 1 in. per foot (25 mm per 0.3 m). Clean out doors are to be provided in the side of the duct at least every 12 ft (3.6 m) and at each change of direction. Type II duct construction consists of rigid metal ductwork in accordance with normal SMACNA Standards. Slope is not required, however, should be considered in ducts that exhaust steam or water vapor. Slope should be provided in dish and pan washer hood ducts. The air velocity for Type I ducts should not be less than 500 fpm (2.54 m/s) (variable flow and reuse of existing ducts) and should not be more than 2,500 fpm (12.7 m/s) (for reasonable noise levels). Duct hood exhaust collars are sized to provide a velocity of 1,800 fpm (9.1 m/s). If the exhaust duct rises vertically for more than two stories, consider using the factory made/insulation chimney stacks rather than duct wrap/rigid fire insulation on the welded steel exhaust stack. Chimney stacks may cost more to purchase, but the labor costs to install the insulated units are less. Advertisement formerly in this space. 58 ASHRAE Journal February 2012

Advertisement formerly in this space.

4Dh Upper Stack Held Off From Lower Stack 0.5 in. On All Sides. Bracket Upper Stack To Lower Stack 6 in. Minimum For Round Duct, Dh = D For Rectangular Duct, Dh = (H + W)/2 Reducer If Necessary To Increase Stack Velocity To Disperse Effluent Utility Set Figure 1: Rooftop centrifugal fan (utility set) with vertical discharge. If the Type I grease duct is to be power washed and the design is documented as such, negotiate with the authority having jurisdiction (AHJ) to avoid installing most of the duct access doors. If the AHJ still requires the access doors, consider installing them, but do not cut them thru the duct wall. This is done because cleaning accessibility is better with power wash units and also the access door gaskets are not liquid tight and allow moisture to leak into the insulation, which causes mold and mildew. The duct system should be pressure tested (1 in. w.c. [249 Pa] for 20 minutes) for leakage before the hood and fan are connected, as well as the exterior insulation applied. Also consult with the duct cleaning service as to where they need water and drain connections for the power wash duct cleaning. Photo 2: High velocity, vertical discharge, centrifugal roof fan with a dilution air intake. Fans The exhaust discharge from a Type I grease duct system is required to be at least 40 in. (1 m) above the roof surface with the outlet at least 10 ft (3 m) from a supply intake. The fan most often selected to meet this criterion is an upblast power roof ventilator (PRV). However, this type of fan has a volume capacity limit of about 5,000 cfm (2360 L/s) and a static pressure limit of 2 to 2.25 in. w.c. (498 to 560 Pa). A centrifugal fan has greater volume and static pressure capability. The fan can be either a utility set type or an inline type. The utility fans offer variable discharge directions that vary from horizontal to vertical. In all these fan selection cases the motor and drive is external to the fan unit. Consideration must be given for flexible duct connections, between the fan unit and the ductwork, to be fire resistant and liquid tight. All fans must be UL 762 listed for grease exhaust and temperatures to 400 F (204 C). All roof fans must be mounted on raised curbs so that duct stack access is available for cleaning. The PRV units use a hinged fan base with a safety cable to hold the unit steady. Utility set fans use an access panel in the curb. Provide a vented roof curb if the Type I grease duct is enclosed in a rated shaft. The curb vent is to relieve the heat from the shaft space. Stack Outlets The discharge of the fan system should be arranged to prevent reentry of any of the exhaust flow into the outdoor air intakes. Horizontal and vertical distance is important and is often governed by local codes. Some code authorities will allow discharge dampers arrangements such as horizontal discharge backdraft dampers from a utility set arrangement and butterfly discharge dampers on a vertical discharge inline fan stack with a windband protector. These damper arrangements are to keep weather, birds, and animals out of the grease ducts. A good vertical stack arrangement is shown in Figure 1 and Photo 2. This vertical stack discharge velocity should not exceed a 2,000 to 2,500 fpm (10 to 13 m/s) range. Any velocity above 2,500 fpm (13 m/s) creates velocity noise that may be objectionable to neighbors. If stack odor is a problem, consider introducing outdoor air from the roof area into the fan s suction duct. This added air will dilute the stack discharge. A value of 20% is a good dilution factor. Sidewall Exhaust Outlets The sidewall outlet is usually a wall louver. Provide a plenum behind the louver to reduce the exit velocity. Provide an access panel and a drain in the plenum for cleaning. Avoid louver vanes that blow down toward sidewalks 60 ASHRAE Journal ashrae.org February 2012

Advertisement formerly in this space.

where the airflow and odors are objectionable to people in the area. Utility Connections The electric connections should be installed in a flat wall panel arrangement behind the equipment. This is done to provide a space behind the equipment that is easier to keep clean. The gas solenoid must be visibly piped below the ceiling line. Some health departments require the exposed pipe to be epoxy painted to prevent rusting. Fire Protection Control NPFA Standard 96 requires the Type I grease duct to have a fire-extinguishing system that protect the cooking surfaces, filters and ducts. The system may be a wet chemical or a water spray system. The type selected must be coordinated with the hood supplier. This coordination can determine if the hood comes with the internal piping factory installed or if it needs to be field installed by a fire protection contractor. All exposed piping under the hood must be stainless steel or chrome plated, and the piping penetrations to the hood must be grease tight as per NFPA 96. The activation control also must be coordinated with the fan power controls. A control point often missed is an exhaust fan restarting to remove fire and smoke in the event of a night fire, often resulting from a worker leaving something on the range top, turning off the exhaust fan system for the night, and forgetting to turn off the range controls. The gas-fuel valve (mechanical or electrical solenoid) and or the electrical power trip for equipment located under the hood must also be coordinated with the operation of the fire protection system. In addition, the fuel and electrical trip systems require reset controls, which the designer must locate. Conclusion The coordination required for a successful CKV exhaust system requires the mechanical HVAC designer to work with kitchen equipment supplier, the fire protection contractor, the controls contractor, the duct cleaning contractor, the electrical contractor, the gas piping contractor, and the HVAC contractors to complete a composite system that works together. An operational, economical, and sustainable system should be the team s goal. Advertisement formerly in this space. 62 ASHRAE Journal February 2012