WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS

Similar documents
DUCT SYSTEMS CHAPTER 6

HIGH-RISE RETROFIT ORDINANCES - NO and NO

DUCT SYSTEMS CHAPTER 6

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

INSTALLATION OF ACCESS FLOOR SYSTEMS IN GENERAL OFFICE AREA AND COMPUTER ROOM

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering

DUCT SYSTEMS CHAPTER 6

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

PERFORMANCE COMPLIANCE METHODS

Residential-based Care Facility R-4 Guideline

Fire Protection Coffee Break Training May 2016

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

Design & Construction Standards, Revised January

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance

SCHEDULE. Essential Safety Measures taken from Schedule 9 of the Building Regulations PART 1 BUILDING FIRE INTEGRITY

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Large Family Daycare Guideline

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)

Fire Sprinkler Plan Submittal Form

COMPLIANCE ALTERNATIVES

COMPLIANCE ALTERNATIVES

2007 CBC & CFC Residential Care Facility Requirements (24 hour care only)

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.

SECTION 915 CARBON MONOXIDE DETECTION

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

PLAN REVIEW SUBMITTAL GUIDE

SECTION : FIRE ALARM & DETECTION SYSTEMS

PERFORMANCE COMPLIANCE METHODS

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

Narrative Reports As Regulated by 780 CMR, Section 903.0

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

PERFORMANCE COMPLIANCE METHODS

Diesel Fuel System Report

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

Report on First Revisions with Statement June 2014 NFPA 101

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES

BUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

Agency for Health Care Administration

Common Building Code Misinterpretations

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

SECTION WET-PIPE SPRINKLER SYSTEMS

El Reno Fire Department Fire Alarm Plan Review Worksheet

Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com

Liberty Township Fire Department Fire Prevention Bureau. Clean Agent Fire Protection Plan Submittal Checklist

Bold items are particular to the City of Euless

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

Prescriptive Requirement for Smoke Control

DESIGN GUIDELINE SBA 5.11

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION

New Construction Fire Inspection Process

University Design Standard Fire Alarm Systems

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SECTION WATER-SOURCE UNITARY HEAT PUMPS

For additional information regarding R-3.1 residential care facilities please contact (951)

CHAPTER 5: EXHAUST SYSTEMS

BULLETIN: Subchapter 4 Retrofit Requirements for Nightclubs

Building Automation System (BAS) Design Criteria

Element Z General Design Requirements Existing Facilities Information

FIRE SERVICE FEATURES

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Smoke, Not Flame

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

CHAPTER 7 MECHANICAL VENTILATION AND SMOKE CONTROL SYSTEMS 7.1 AIR CONDITIONING & MECHANICAL VENTILATION SYSTEMS

ADMINISTRATIVE BULLETIN

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208)

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

HVAC Equipment Access Equipment Location

SMOKE CONTROL: ISSUES / APPROACHES. Smoke, Not Flame

CHINO VALLEY INDEPENDENT FIRE DISTRICT FIRE PROTECTION STANDARD

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection

Agency for Health Care Administration

FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY

Agency for Health Care Administration

Smoke Management in High-Rise Structures

Part I Extraction Process Equipment

CHAPTER 7 ALTERATIONS LEVEL

The Residences at Christina Landing Wilmington, DE

DACC Health Sciences Building Air Handler Assessment/Study

Building Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Life Safety Dampers Selection and Application Manual

MONTECITO FIRE PROTECTION DISTRICT

FIRE & LIFE SAFTEY STANDARD

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION GUIDELINE RESIDENTIAL CARE FACILITIES 2007 CBC/CFC (R-3.1)

YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

Transcription:

WHITE PLAINS SMOKE CONTROL CODE a. Application of Code. PART 1. GENERAL REQUIREMENTS The following uniform standards and procedures shall apply to the design, installation and testing of new smoke purge systems and alterations thereto. (1) New uses: Smoke Purge Systems shall be installed in the following new uses, including occupied areas and means of egress: (iii) (iv) (v) (vi) Enclosed malls and atriums. All theaters and auditoriums. All Public Assembly Uses accommodating three hundred (300) persons or more. All buildings greater than six (6) stories or seventy-five (75) feet in height. Within any building for those floors below grade that are greater than 7,500 sq. ft. in size and occupied or accessible to the public. Institutional uses for persons whose movements are limited because of illness, physical or mental handicap. (2) Existing uses: Smoke Purge Systems shall be installed in existing buildings for the uses listed in WPSCC-1a, as follows: (iii) (iv) An addition in excess of 50% of the existing building gross floor area, for which both the original building and addition shall comply. For any existing use where there is an increase in the pre-existing legal occupancy limit. Any change of an existing occupancy to a use listed under Section a(1). herein. Any major alteration (i.e., removal of all walls, ceilings, etc.) in excess of 50% of the existing building gross floor area, for those uses listed under Section a(1) herein. (3) Any modification(s) to an existing smoke purge system, including those resulting from a building (or space) alteration or addition, shall be designed so as to be fully integrated and compatible with the base building smoke purge system b. Permit Filing and Review Procedure. (1) Three (3) sets of Mechanical drawings (signed and sealed by a Licensed Professional Engineer having mechanical engineering design experience) for smoke purge systems are to be submitted to the Department of Building for review. Drawings must clearly show and identify dampers, controls and smoke purge design and be approved prior to issuance of a mechanical permit. WPSCC:1

Pt. 1 WHITE PLAINS SMOKE CONTROL CODE (2) Mechanical design engineer to be required to submit the following along with mechanical drawings: Design Engineer's Affidavit for Mechanical Work. Narrative description of system operation (describing various operational modes, and addressing all design parameters listed in Item (3.) below. c. Mechanical drawings and permit to be noted as follows: "Mechanical engineer is required to witness for verification purposes the smoke purge system test upon completion of installation and verify that the installation and operation of the system meets the intent of the mechanical design." PART 2. SMOKE PURGE SYSTEM DESIGN PARAMETERS a. Smoke purge system ducts, transfers, etc. passing through fire rated partitions shall be protected as follows: (1) One Hour rated wall or ceiling. Do not provide a fire or smoke damper at wall penetration. Sprinkler head(s) are to be installed on fire load side of wall(s),at return air transfer openings. (2) Two hour rated wall or ceiling. Provide automatic combination fire/smoke damper with manual control override. Activation - Heat link closes damper. The damper shall be UL555S classified with low (285 F) and high limit (450 F) temperature stats and open/closed status switches. Dampers maybe electrically or pneumatically operated. The damper shall be no smaller than sixteen (16) square inches. b. Conduit for Smoke Purge Control (1) Control wiring shall be run in metal conduit. (rigid or EMT). (2) Pneumatic tubing must be copper. c. Ducts through Exitways and Within Rated Ceiling Assemblies. (1) Smoke purge system supply and exhaust ducts passing through a rated exitway or within a fire-rated suspended ceiling assembly shall be wrapped with thermal fiber - two (2) hour or encased in a two (2) hour rated enclosure. (2) Trapeze hangers to be outside of thermal wrapping. WPSCC:2

WHITE PLAINS SMOKE CONTROL CODE Pt. 2 d. Smoke Purge Fans. (1) Smoke Purge System fans must provide for a minimum of six (6) air changes per hour (or greater if necessary), to obtain adequate visibility within legal means of egress within ten (10) minutes of starting smoke purge. (Adequate visibility is interpreted as clear enough to see exit signs to permit a person to safely exit the building). (2) The smoke purge fan system may be designed as either a separate fan system or as an integrated smoke purge /HVAC system, and as required by Section 4 (Building Alterations and Additions). (3) All smoke purge fans (supply and return) and controls (including air compressors) shall be connected to the building emergency generator and adequate electric power provided for same. (4) Manual override switches shall be provided at the fire alarm panel or fire command station panel to control both smoke purge supply and smoke purge exhaust fans separately. Refer to Part 3 for more information. e. Duct Work. (1) All smoke purge system ducts shall be galvanized steel with minimum thickness of 22 ga. constructed in accordance with ASHRAE and SMACNA sheetmetal ductwork construction details. Flexible ductwork is not permitted in duct systems that are part of a smoke purge system (return or exhaust ductwork). Flexible duct is permitted at supply diffuser connections and at air handling equipment for vibration isolation (maximum 3 ft. length). (2) Design and spacing of duct hangers shall be in accordance with SMACNA duct construction details but hangers to be minimum of 20 ga. steel and be of the trapeze type. (3) Where a smoke purge enters a rated shaft, utilized as a smoke exhaust riser, N.F.P.A. requirements for a vertical boot shall be followed (22 inch height, directed upward within the shaft itself), or in lieu of such boot, automatic combination fire/smoke dampers shall be provided at such core shafts. Smoke dampers shall be operated either pneumatically or electrically as previously described in paragraph 3 (A) (2.) (a). (4) All smoke purge system components (including ductwork) shall be clearly identified as such by stenciling the function and zone on the components, e.g. Smoke Purge Supply - Zone 2; Smoke Purge Exhaust - Zone 3; Smoke Damper No. 5; etc. Stenciling shall be 6" high red letters located (every 10 feet along duct). f. Smoke Purge Coverage. (1) Smoke purge systems shall be designed for a minimum of one (1) zone per floor. WPSCC:3

Pt. 2 WHITE PLAINS SMOKE CONTROL CODE g. Smoke Exhaust of Interior Stairwells. (1) All new interior exitway stairways shall be equipped with an approved automatic smoke-actuated roof scuttle vent, or other approved automatic smoke purge system located at the uppermost ceiling thereof. Such system shall activate the building fire alarm system. This provision shall not conflict with stair pressurization provisions of the State of New York codes. PART 3. SEQUENCE OF OPERATION AND CONTROL FUNCTIONS a. Sequence of Operation. (1) The activation of one (1) automatic initiation device (e.g. smoke detector) or pullstation shall cause the central fire alarm system to go into alarm activation in accordance with the sequence required for the particular existing building. (Note: If a new building or new fire alarm system contact Fire Prevention Bureau for required sequence of operation). In addition, any combination fire/smoke dampers on the floor in alarm shall close. If the low limit temperature firestat (285 F) activates the combination fire/smoke dampers shall close. (2) The simultaneous activation of any two (2) automatic initiation devices (e.g. smoke detectors) or one (1) heat detector or the activation of a single waterflow switch shall cause the central fire alarm system to go into alarm activation in accordance with the sequence of operation required for the particular existing building (Note: If a new building or new fire alarm system contact Fire Prevention Bureau for required sequence of operation). In addition, the smoke purge system shall automatically initiate and the following shall occur: Index all smoke dampers on the particular floor in alarm to an "open" position (supply and return) and index all other building smoke dampers (supply and return) to a "closed" position. Index supply air handling unit(s) air handling (unit(s) or fans) to 100% outside air and return air handling unit(s) or fans to 100% spill. The return damper (between the supply and return systems) shall be fully closed. Note: The return dampers within the air handling units that are part of a smoke purge system shall be a UL smoke damper. The smoke purge system shall override the low limit temperature sensor on the fire smoke damper if it was activated. If the high limit temperature firestat (450 F) is activated during the purge process the fire/smoke damper shall close permanently and smoke purge will be halted. WPSCC:4

WHITE PLAINS SMOKE CONTROL CODE Pt. 3 b. Control Functions: (1) Purge manual control shall be provided at the fire alarm panel or fire command station in the main lobby. This control shall consist of the following: A switch shall be provided for each floor or area that is part of the smoke purge system. The switch shall have three positions "on" "off" and "automatic". The switch when indexed to the "on" position shall: I. Index all smoke dampers on the particular floor to an open position (supply and return) and index all other building smoke dampers (supply and return) to a "closed" position. II. Index the appropriate supply air handling unit(s)or fans to 100% outside air and the appropriate return air handling unit(s) or fans to 100% spill. The return damper (between the supply and return systems) shall be fully closed. Note: The return dampers within the air handling units that are part of a smoke purge system shall be a UL smoke damper. Note: The smoke control system ductwork and components shall be designed and configured to accommodate excessive static pressure that may occur during purge cycle. (iii) The switch when indexed to the "off" position shall: I. Index all smoke dampers on the particular floor or zone to "closed" position (supply and return). II. Index the appropriate supply and return air handling units or fans to their normal mode of operation. Note: The smoke control system ductwork and components shall be designed and configured to accommodate excessive ductwork static pressure that may occur during purge cycle. (iv) The switch when indexed to the "automatic" position shall: I. Cause the smoke purge system to be controlled automatically via the fire alarm system. Alarm initiation devices shall cause the purge system to automatically activate. During non-alarm conditions the H.V.A.C. systems and fire/smoke dampers that are part of the smoke purge system can be controlled by a building management or similar control system( if one exists) as long as the fire alarm system has override priority. The control switches shall not be able to override the fire/smoke damper if the high limit temperature (450 ) is activated. WPSCC:5

Pt. 4 WHITE PLAINS SMOKE CONTROL CODE PART 4. SMOKE PURGE SYSTEM TEST (1) Upon completion of system installations, the mechanical design engineer of record shall personally conduct, and oversee, for verification purpose, a field smoke purge test (in the presence of the City of White Plains Code Enforcement Officer and Fire Prevention Bureau representative). (2) Such tests shall be conducted under both normal and emergency power conditions. (3) Any and all necessary modification and system reinforcements (such as boosters, fans, ducts, etc.) shall be provided if smoke purge tests result in unsatisfactory performance. WPSCC:6