Technical Concept. Plenum Integrated Filter Fan PIFF 3-AC PIFF 3-EC

Similar documents
Technical Concept. Ultraflex Ceiling Grid (UFR) All Types Cleanroom Ceiling Systems

Ultraflex Ceiling Grid (UFR)

TopVent Design Handbook

Comfort Ceiling Fan Coil System INDULVENT ec. Draught-free ambient air distribution with cooling capacity up to 2600 W

Cleanroom systems. Supply air ceiling and recirculated air ceiling OP. for operating rooms with low-turbulence displacement flow

DUCTIMAX 2-8 kw. Medium available static pressure ducted hydronic units. Duct unit DUCTIMAX

Cassette units Model Comfort Circle. - heating - cooling - ventilation

CASSETTE UNIT. Comfort Circle

TECHNICAL MANUAL YEFB HIGH PRESSURE DUCTED UNIT

Vacuum drying oven for non-flammable solvents

CUMULUS CUMULUS. Key figures. Construction. Function Integrated chilled beams

CHILLED BEAM CASSETTE IQ STAR LYRA

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

RoofVent Design Handbook

Resolair 62 and 66. Comfort air conditioning unit with highly efficient regenerative heat storage packages. AIR VOLUME FLOW: 1,200 4,300 m³/h

Adsolair 56/58. Comfort air conditioning unit with double plate heat exchanger and adiabatic evaporative cooling system

Puri-Drall PDK. Puri-Clean PCK. Puri-Inlet PEK. HEPA filter air outlet with pull-down outlet element

50CO. Close Control Unit. Wide range of chilled water cabinets. Compact and attractive design. EC motor for energy savings. Auto-adaptive control

Blower-YEFB-020-3R-1maxVel

Cooling and heating systems. Static cooling ceiling system SKS-5/3 for visible installation

Hoval Indoor Climate Systems TopVent TP

Krantz. Multifunction exposed ceiling AVACS. Cooling and heating systems

Homepage > Products > Decentralised ventilation systems > Vertical units > Type FSL-V-ZAB/SEK FSL-V-ZAB/SEK

Fan coil unit KL. Wall unit Ceiling unit

Clean Air Laminar Flow Ceiling CG 3 A CLEAN AIR WORLD. Draft-free, comfortable room climate. Minimal, undisruptive noise level

Technical documentation Fan coil unit

WOLF VENTILATION SYSTEM PRICE LIST

SIMPLICITY FULL MODULARITY?

Refrigerant Dryers Refrigerant Compressed Air Dryer with integrated DF Filters

Shop. Item Information. Interface I-100 For V-100/V-7x0. Send item information. Show item in shop. Add item to cart.

DATA & FACTS Clean Rooms DencoHappel Air Shower. Active Air Shower for Personnel in Clean Rooms

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

The green and friendly entrance. Comfort air curtains Model CA 2

SECTION FAN COIL UNITS

Bi2 4tubes * SLR 4T Fan coil radiator for heating and cooling at the same time. FEATURES. Cools, Dehumidifies, Heats and Filters

Efficient and comfortable air conditioning solutions for every requirement GEA Flex-Geko Comfort Edition

GEA Ultra-Denco. GEA Heat Exchangers / HVAC Systems. Close Climate Control for IT Environments. Reliability with low power consumpstion

SWIMMING POOL SWIMMING POOL DEHUMIDIFICATION

Homepage > Products > Grilles and Diffusers > Ceiling diffusers > Design ceiling swirl diffusers > Type ADD. Type ADD

Product Brochure Fan coil units Flex-Geko Comfort -Edition. Efficient and comfortable air conditioning solutions for every requirement

Dryer Systems. Breathing Air Units

Quality Heat Exchangers

Differential Pressure and Flow Meter. Media 5 Indicator 160 Ø PN 50

System architecture. Air treatment Index

We have some on stock... GEA MultiMAXX Prompt. Unit Heaters Data & Facts. GEA Heat Exchangers / HVAC Systems

Technology for life. Unit heater LH

Safety vacuum drying oven for flammable solvents

CWX 6 - CWX 8 - CWX 10 CASSETTE TYPE TERMINAL UNIT

Ceiling air diffuser INDULTHERM INDULTHERM-e

Optimal work climate with open doors. Industrial air curtains Model IndAC

Units for suspended ceilings

Laminar Flow Cabinets eco air V

KOG LN. Low Noise Chilled Water Cassettes Models 09, 12 & to 6.10kW to 5.10kW. 330 to 920 m3/h

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

Standard-Incubators. Avantgarde.Line BD BF series. Classic.Line B BD BF series. Solid.Line BD-S series

Conditioning your ambient, maximising your comfort.

Automatic balancing valves ASV-PV (new generation) DN 32-50

290 on. 286 on. Comfortable climate with pre-heated, filtered supply air. Fresh air boxes ALB WW MODEL WITH WARM WATER HEATING

Adconair 76. Comfort air conditioning unit with counterflow plate heat exchanger. AIR VOLUME FLOW: 2,600 23,600 m³/h

Compact Filter Unit Type CFU

Microbiological Safety Cabinets ENVAIR eco safe Comfort

Vacuum drying chambers. VD VDL series

HRV-IP. Ceiling Type Heat Pump Heat Recovery Unit

Series. Suspended air supply units with the air capacity up to 4100 m 3 /h in the sound- and heat-insulated casing with the water heater

energy efficient air curtains technical data and controllers

CWX 3 - CWX 5 CASSETTE TYPE TERMINAL UNIT. Cooling

Powerful and efficient trolley cleaning and sanitizing. WS 125 trolley washer. Group

Microbiological Safety Cabinets ENVAIR eco safe Comfort Plus

Cleanroom Air Showers

Air Shower TECHNICAL DATA

66 on. Central ventilation system ZLS-DV EC according to DIN Central ventilation system ZLS EXTRACT AIR FIRE PROTECTION OUTSIDE AIR

Series VUT PW EC. wool internal heat and sound-insulating layer for VUT PE/PW 350, 600, 1000 units and 50 mm for VUT PE/PW 200, 3000 units.

Cooling Strip Model SPB

SIMPLICITY OR FULL MODULARITY?

QZB "Standard" comfort fan coil

AIR CURTAINS. Air curtains with integrated control panel and remote control. Air curtains without heating, with electric heating or water heating

technical data Fan coil unit FWB small duct unit

Hi-Pres Cooling Products Catalogue

iq Star LYRA II chilled beam cassette

MAGISTER. Compact and attractive design Energy savings with EC motor and self-regulating control. Easy to install. Use. Chilled water operation

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

Air Handling Unit. REC Temovex Blue 4 NEW! Experts on indoor climate in low-energy houses

MAKING MODERN LIVING POSSIBLE. Danfoss Air Catalogue. Catalogue DANFOSS HEATING

Horizontal rotor heat recovery ventilation unit RH 5. Vertical rotor heat recovery ventilation unit RV 9

Product is subject to and complies with Regulation (UE) N.327/2011. cert. n Fan Coil Unit Cassette SkyStar Jumbo ECM. technical catalogue

Fresh air unit ALB. ALB it s simple and so easy! Air supplied through a heater and filter in a single unit.

GEA Fan Coil Units Effective and quiet. Quality in detail GEA Cassette-Geko. Product Brochure

Drying and heating chambers

AIR COMPACT. Air handling units. Ultra high performance USE RANGE DESCRIPTION

COMPACT AIR HANDLING UNIT

Type TDF-SilentAIR WITH VERY LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH FIXED AIR CONTROL BLADES

Pharmaceutical Facility Design

Air distribution for clean rooms. Clever and flexible.

CONTENT: VEX308 Decentralised ventilation VEX308

Fan Coil Unit CULTRA

PLEXUS. Marine HVAC Components for Boats and Yachts CATALOGUE

Hi-Pres Cooling Products Catalogue. Product Catalogue

Silvento concealed variant clamped-ventilator - Replaces Skalar-; Skalar-V...; Skalar-2V... - Installation directions - Please pass on to the user -

Technical Description. Laboratory Climate Test Chamber. System Weiss. Mat. No.: Type WKL 34/40

Indirect Evaporative Air Conditioning

Transcription:

Technical Concept Plenum Integrated Filter Fan PIFF 3-AC PIFF 3-EC

Technical Concept Plenum Integrated Filter Fan Product Description The Plenum Integrated Filter Fan (PIFF) is a fan filter unit with integrated return air and cooling coil. It is used to supply turbulent mixed air-flow while reducing the concentration of particles and the temperature inside of clean environments e.g. pharmaceutical laboratories and clean rooms. Depending on the coverage of the clean room ceiling, the classes 5.0 to 8.0 according to DIN EN ISO 14644-1 as well as B, C and D according to EC Guide GMP can be achieved. The PIFF is installed into the existing ceiling grid by an installation frame. Compared to standard air supply systems with centralized air handing unit, the supply & return air ducts on top of the clean room ceiling can be eliminated, which results in considerable savings of installation space and in a reduction of design expenditures. The unit is working in recirculation mode by default; if needed, supply with make up air can be engaged up to 500 m 3 /h to keep up the over-pressurization of the clean room as well as to maintain the supply with fresh air. Through the exhaust air connection used air can be removed. For an operation with 100% return air supply both supply and exhaust connections can be closed with a cap. Design and Function The PIFF consists of an outer housing 1 with make-up air connection 2 and exhaust air connection 11 together with the internal components HEPA filter cell 7 with fan motor unit 5 in a common internal housing 6 and a cooling coil 13. As an option, a prefilter 12 can be installed. The supply with fresh air and the collection of exhaust or return air is implemented by a specially designed air grill 10 which is located on top of the ceiling installation frame of the PIFF. The power 17 and network 16 connectors as well as the cooling water connections (supply 14 /return 15 ) are located at the side of the unit. The control valve for the cooling coil is to be provided for a single or a group of PIFF (by others). The fan 5 draws air from the room via the return air intake in the outlet grill and channels the air through an optional prefilter 12 to the cooling coil 13. The chilled air-flows through the HEPA filter 7 and is blown with high turbulence into the cleanroom via the outlet air grill. This design prevents a short-cut between supply air and return air. The distribution elements of the outlet air grill are arranged in a special design to ensure a homogenous air distribution to all sides. The product is protected by patent. Legend 2 3 4 5 6 7 1 8 a 10 17 18 16 13 12 11 1 Housing 2 Make-up air connection DN 160 3 Inlet nozzle 4 Motor 5 Fan motor unit 6 Internal housing 7 HEPA filter 8a/8b Particle measuring point 8b/8c Differential pressure measuring point Ceiling installation frame a Intermediate profile 10 Air grill 11 Exhaust air connection DN 160 12 Prefilter (option) 13 Cooling coil 14 Cooling return ¾ 15 Cooling water supply ¾ 16 RJ45 network connectors (EC version) 17 Power supply 18 Ground connection 1 Transport lock 20 UFR 55/70 T/P ceiling grid 21 UKD cassette ceiling grid 15 14 1 1 8c Fig. 1 PIFF module with air grill 10, ceiling installation frame and Prefilter 12 : construction 8 b 2

Plenum Integrated Filter Fan Technical Concept Technical Data Grid size mm 1 200 1 200 Housing L W H mm 1100 1100 720 Air grill cassette L W H mm 1145 1145 60 Ceiling installation frame L W H mm 1166 1166 60 Height Total mm 720 Weight Total kg 80 Motor IP20 EC-Motor AC-Motor Voltage / Phase V 200-277/ 1 230 / 1 Frequency Hz 50 / 60 50 Nominal current A 1,8-1,3 1,4 Air-flow volume m 3 /h 1500 1500 Power 1) W 280 320 2) Sound power level 1) db(a) 62 64 2) Sound pressure level 1) 25% 10% db(a) db(a) 62 5 64 2) 61 2) HEPA Filter Filter class DIN EN 1822-1 H14 Dimensions L W H mm 1000 700 10 Separation efficiency in MPPS %,5 Pressure drop Pa 126 Cooling Coil Cooling capacity kw 2,6 Media volume flow m³/ h 0,4 Water temperature In Out 14 20 Pressure loss water-side max. kpa 12,7 Air temperature In Out Pressure loss air-side at 1500 m 3 /h 1) with H14 fi lter cell 2) measured with transformer 23 18 Pa 42 Sound power level measurement according to ISO 3741, tolerances according to DIN 24166 System Installation The installation of a PIFF into the M+W Products ceiling systems is very simple. Fig. 3 shows a sample installation situation into the Ultraflex ceiling grid UFR 55/70 T/P 20 (an UFR 55/70 T/E can be used the same way). Fig. 4 shows the installation into the Ultraflex cassette ceiling 21. Installation is executed from the clean room side using a ceiling installation frame and an intermediate profile a. Installation in other ceiling systems available on the market is possible as well (for installation instructions please send an enquiry). Access to the top side of the PIFF is only necessary to connect the BUS-Systems (EC only), the power supply and the chilled water connection. Maintenance is executed from the clean room side. Therefore the air grill is removed by loosening the fixing screws. Next, the fan-motor-unit is lowered with an installation lift and there is free access to the HEPA filter. Alternatively the maintenance can be executed from the plenum side by unfastening the PIFF cover panel. 20 a 1 10 Fig. 3 Installation situation with ceiling installation frame and intermediate profile a in ceiling grid profile UFR 55/70 T/P 21 a 1 Fig. 2 PIFF module without air grill and installation frame 17 18 16 15 14 10 Fig. 2.1 Power supply 17, grounding 18, RJ45 network connectors 16, cooling water connection ( supply 14, return 15 ) Fig. 4 Installation Situation with ceiling installation frame and intermediate profile a in ceiling grid profile UKD Cassette Ceiling Grid 3

Technical Concept Plenum Integrated Filter Fan Key Features Complete, plug & play unit Provided with supply air and return air as well as make-up air and exhaust air connections Type Designation PIFF Integrated air cooling coil (without valve or thermostat, water connection 3/4 female thread) Plenum Integrated Filter Fan Motor type HEPA filter Prefilter No additional plenum necessary Connections for particle and/or differential pressure measurements at the HEPA filter Low sound power level Easy installation with ceiling installation frames and intermediate profiles for an optimal unit integration into the cleanroom ceiling system Flexible in that way that the unit can be easily relocated Filter change from above or below Easily operated and maintained Housing made of 1.5 mm aluminum, untreated Motor type: AC EC/LR EC/LF HEPA Filter H14 Optional Prefilter O Optional G4 AC-Motor EC-Motor with LON RS485-interface EC-Motor with LON FTT10A-interface standard filter class special type without filter class G4 special type Fig. 5 Typical room air velocity situation with turbulent mixed air generated by a Plenum Integrated Filter Fan (example) Fig. 6 Supply air grill with return air inlet, view from below 4

Plenum Integrated Filter Fan Technical Concept Submittal Text pcs. Plenum Integrated Filter Fan (PIFF) The PIFF is a ceiling installed, compact recirculation air unit that accomplishes the following: Mixing make-up and recirculation air in the unit s plenum HEPA filtration of the supply air Blowing the supply air into the room through the air grill Developping turbulent mixed air-flow Intake the return air through the air grill Discharging exhaust air rate Cooling the recirculated air Housing The housing is made of 1.5 mm aluminum sheet, fastened with rivets and sealed. The surface is untreated and cleaned. The servicing level is recessed to protect it from damage. The fan power supply and bus cable connections (only EC) as well as grounding are on the left. The cooling water connections are on the right. All connections are labeled. Function Normally the unit runs in recirculation mode. Through the make-up air connection up to 500 m 3 /h of make-up air can be supplied and through an additional connector exhaust air can be discharged. In a 100 percent recirculation air mode the make-up and exhaust air connections will be closed by a cap. Components Filter Fan Unit (FFU) with the dimensions 2 62 414 [mm] HEPA filter, class H14, efficiency.5 % Cooling coil, capacity approx. 2.6 kw (see technical data) Water connection ¾" female thread Connection for particle counter and / or differential pressure measurements at the HEPA filter Ceiling installation frame for M+W Products ceiling systems Technical Data Ceiling grid size.............1200 mm 1200 mm Outer dimensions............1100 mm 1100 mm Height PIFF.................720 mm Height installation frame.......60 mm Total module height..........780 mm Total Weight incl. filter.........80 kg Fan Operating Parameters........EC...........AC Air-flow volume..............1500 m 3 / h.. 1500 m 3 / h Filter pressure loss...........126 Pa..... 126 Pa Power.....................220 W...... 320 W Voltage / Phase..............200-277/ 1... 230 V / 1 Nominal current.............1,8-1,3..... 1,4 A Sound power level...........62 db(a).... 64 db(a) HEPA filter H14 Dimensions.............1000 700 10 [mm] Pressure loss............126 Pa (at v = 1500 m 3 /h) Efficiency................5 % in MPPS Optional Filter class Cooling Coil Power.....................2.6 kw Air-flow volume..............1500 m 3 /h Pressure loss air.............42 Pa Air inlet temperature..........23 Air outlet temperature.........18 Water amount...............400 l/h Pressure drop water..........12.7 kpa Water supply temperature......14 Water return temperature......20 Optional Ceiling installation adaptor for other ceiling systems Prefilter G4 according to DIN EN 77 Manufacturer Type M+W Products GmbH PIFF 5

M+W Products GmbH (Headquarters) A Company of the M+W Group Lotterbergstr. 30 704 Stuttgart, Germany Phone +4 711 8804-1742 Fax +4 711 8804-1668 products@mwgroup.net www.products.mwgroup.net M+W Products (Shanghai) Co., Ltd. A Company of the M+W Group No. 13 Beimin Road, Che dun, Songjiang Area Shanghai, 201611, P.R. China Phone +86 21 3783-8360 Fax +86 21 3783-7681 M+W U.S., Inc. A Company of the M+W Group 4710 East Elwood, Suite# Phoenix, AZ 85040, USA Phone +1 480 303-6600 Fax +1 480 303-300