INSTRUCTION MANUAL MM-226D

Similar documents
! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-226(A) Series 69 Low Water Cut-Offs For Steam Boilers

INSTRUCTION MANUAL HS-229G

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-214(C) Series 61 Low Water Cut-Off OPERATION

INSTRUCTION MANUAL HS-208REVI

Series 47 and 247 Mechanical Water Feeders. Series 47-2 and Combination Mechanical Water Feeder/Low Water Cut-Off ! WARNING

! WARNING. Replacement Head Mechanism INSTRUCTION MANUAL MM-413F

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-315(C)

INSTRUCTION MANUAL MM-615E. Series FS1 High Sensitivity Liquid Flow Switch

WIRING MODEL 20 Low Water Cut-Off and Pump Control MAXIMUM PRESSURE: 20 PSI INTERNAL WIRING BLUE WHITE UPPER PROBE (FEED OFF) FEED PROBE (FEED ON) ALL

! WARNING. Before using product, read and understand instructions.

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-284. Series PSE-800 Probe Type Low Water Cut-Off for Steam Boilers

! WARNING. Series 101-A Electric Water Feeder SPECIFICATIONS INSTRUCTION MANUAL MM-307H

TrueClean ToteCleaner

INSTRUCTION MANUAL MM-601REVI. Series FS4-3 General Purpose Liquid Flow Switch

TrueClean ToteCleaner

XT Series Thermostats

User s Manual and Operating Instructions

Installation and Maintenance "L" and "LS" Series

! WARNING. Before using product, read and understand instructions.

User s Manual and Operating Instructions

! WARNING. Before using product, read and understand instructions.

MaxLite LED MICRO-T PANEL

STOP. SAFETY INFORMATION Please read and understand this entire manual before attempting to assemble, operate or install the product.

WARNING. Pro Pack Portable Spray Pack 3A1292C. Operation. Model 24F893 Maximum Working Pressure 12 psi (0.83 bar, MPa)

User s Manual and Operating Instructions

Instruction Sheet LTR - Low Water Cutoff for Hot Water Boilers

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

Clean Steam Generators

ELECTRONIC FAUCETS INSTRUCTION MANUAL. Toll Free: (800) Haul Road Wayne, NJ krowne.

SH-2000, SH-2500, AB-3000 Bimetallic Steam Traps Installation and Operation Manual SH-2000

Steam Humidifier Fan Pack Installation & Maintenance Instructions

Industrial Vacuums, Inc

WATERSHIELIJrM REVERSE OSMOSIS INSTALLA TION MANUAL ~ ~ ~ ~ ~ l ~ TO INSURE THIS PRODUCT AND THE INSTALLATION THEREOF. ~ ~ ~ ~ ~

! WARNING. Before using product, read and understand instructions.

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

DRY AIR SYSTEMS, INC Metro Boulevard Maryland Heights, Missouri (314) fax (314)

MaxLite LED High Bay Fixtures

INSTALLATION INSTRUCTIONS

Model R060 Installation - Operation Manual

PLL. Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual

SH-300, SH-900, SH-1500, SH-1600 and SH-1700 Bimetallic Steam Trap Installation and Operation Manual

AIC Series Float & Thermostatic Steam Trap Installation and Maintenance Instructions

Electric Space Heater

READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.

24 VAC SYSTEM CONTROL KIT Model: CK-91F and CK-91FG

OPERATION MANUAL Dated: 04/09/2018 Document Name: SHV _OM Page 1 of 8. Ion Technologies SHV40, 75 & 100 Sewage Ejector Pump SAFETY WARNINGS

MaxLite LED VAPOR TIGHT LINEAR FIXTURES

ST. KITTS CEILING FAN

Installation Manual Universal Single-Arm Side-of-Pole Mount UNI-SA/21.5

ICS Float and Thermostatic Steam Trap Installation and Operation Manual

Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3

FLCH4R Garage and Utility Electric Heater

SPA BLOWER OWNER'S MANUAL XXXX, XXXX, XXXX, XXXX, XXXX, XXXX fax

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

ELSTON 52 CEILING FAN

INSTALLATION AND OPERATING MANUAL

CT-7 Series Toxic Gas Transmitter Operator s Manual

Installation Instructions PP-AS20 Anti-Scale System

OPERATIONS MAINTENANCE MANUAL

Instant Hot Water Dispenser Owner s Manual

Installation Manual Universal Side-of-Pole Mount UNI-SP/01A

BLT-999W-2 Item # 60757

SC Installation, Operation & Application Guide

Operating & Safety Instructions

INSTALLATION, OPERATION AND MAINTENANCE

MAN AUTO IMPORTANT INSTRUCTIONS PLEASE READ THIS MANUAL BEFORE INSTALLING AND USING APPLIANCE

BX Series. Installation, Operation, Maintenance Instructions & Spare Parts

55-Gallon Dispenser Package

WARNING. Before using this product read and understand instructions.

Use this product according to this instruction manual. Please keep this instruction manual for future reference. MODELS: ST-H15-B & ST-H30

INSTALLATION AND OPERATING MANUAL

Model 9001EXP Alarm. NOTE TO INSTALLER: Please leave this information with the Maintenance Department. LIMITED WARRANTY

BLOWER ACCESSORY MODEL #FIB100 Español p. 17

Patent Pending invent for New Construction

User s Manual and Operating Instructions

SUTTON 52 CEILING FAN

G Series SAVE THESE INSTRUCTIONS. (Model B) Convector Heater for Hazardous Locations GENERAL! INSTALLATION

Instruction Leaflet. Read instructions before operating. Retain for future reference.

2. All connections are 24 volt AC. Verify all planned connections at TT thermostat connections, before turning on power

Humidistat-Thermostat

R Series B & T2 Model

INSTRUCTION MANUAL. Keep this manual in a safe place for future reference TEMPERATURE CONTROL STEAM TRAP LEX3N-TZ LEX3N-TZ.

User s Manual & Operating Instructions

LV-5 Direct Contact Low Voltage Detector and LV-5/K01 Kit including LV-PT Tester, Holster and Available Accessories

Installation, Operation & Service Manual

GENERATION 2 QUADRATHERM Heater

Owner s Guide. 24-inch Gas Wall Oven with Time-Of-Day Clock and Timer Canada w A/01/08

Installation Manual. Models 99168, 99169, 99170

Point-of-Use Water Heater Owner s Manual. Installation, Care & Use

QMF MAINFRAME Installation Manual

Owner s Manual PUH1500. Electric Umbrella Heater. Model Number: Model Number Part Number. Quality checked by: R00

TURBO Fiberglass Cone Fan and Grill Fan 48'' Belt Drive. Installation & Operator s Instruction Manual

TOUCHDOWN 48 CEILING FAN

OPERATION, SERVICE & PARTS MANUAL

ITEM # SAIL STREAM CEILING FAN MODEL #41695

DS 2001 REVISED Humidifier Assembly and Instruction Manual

SSF1610B-CN TRUSTED FOR OVER 100 YEARS. 16 inch (40cm) Oscillating. Stand Fan. Instruction Leaflet PLEASE READ AND SAVE THESE IMPORTANT INSTRUCTIONS

55-Gallon Dispenser Package

Transcription:

ISTRUCTIO MAUAL MM-6D 4675

OPERATIO Maximum Steam Pressure: 0 psi (1.4 kg/cm ) A F C The Series Built-in Low Water Cut-Off is furnished with a threaded barrel casting which fits right into a 1/" tapping provided by some boiler manufacturers in the side of the boiler. Selection of the particular model depends upon the insertion length into the boiler (see chart). Order the built-in which provides maximum insertion within the boiler. Electrical Ratings Mot Switch Rating (Amperes) Voltage Full Load Locked Rot Pilot Duty 10 VAC 7.4 44.4 40 VAC.7. 15 VA at 10 40 VAC OTE: MV models are rated at 4 VA @ 4 VAC to 10 VAC D CUT-OFF LEVEL B Dimensions, in. (mm) A B C D E F Insertion Model Length PT 4 1 8 (105) 1 1 8 (79) 1 4 (57) 1 (5) 4 1 8 (105) 1 4 (45) 4, 5 1 16 (0) E AA 1 8 () 1 9 1 (41) Based on desired usage, connect wires from low water cut-off to appropriate control/alarm. Diagram 1 Diagram SCEMATIC OF TWI SWITC ITERAL OPERATIO USED AS MAI LIE SWITC 0 0 0 0 0 4 0 0 4 0 0 4 ORMAL WATER LEVEL FEEDER OR ALARM OPERATIG LEVEL LOW WATER CUT-OFF OPERATIG LEVEL TO BURER SAFETY SWITC TO ALARM 0 0 0 4 EUTRAL WIRE OT WIRE OT WIRE EUTRAL WIRE Diagram Diagram 4 USED AS PILOT SWITC I SERIES WIT OLDIG COIL OF AUTOMATIC STARTER USED WIT MODEL 101 ELECTRIC WATER VALVE OR I ALARM CIRCUIT SAFETY SWITC 0 TO LIE 0 4 0 TO BURER STARTER L1 L L TO BURER SAFETY SWITC JUMPER 0 0 0 4 EUTRAL WIRE OT WIRE TO TWO WIRES OF 101A OR TO ALARM CIRCUIT IMPORTAT: Low water cut-off circuit of the series must be electrically wired in series with all other boiler limit operating controls.

ISTALLATIO TOOLS EEDED: One (1) flathead screwdriver, one (1) level indicat and one (1) pipe wrench. IMPORTAT: Follow the boiler manufacturer's instructions along with all applicable codes and dinances f piping, blow down valve and water gauge glass requirements. The center line on the casting of the Series must be installed above the lowest permissible water level determined by the boiler manufacturer. Whether the gauge glass is mounted directly into the boiler on an independent water column, the cut-off line on the control should be mounted 1/ (15mm) above the lowest visible point of the gauge glass. Using a flathead screwdriver, remove the one (1) screw that secures the switch cover. Cover Installation of the Low Water Cut-Off Turn the boiler off. Drain the water in the boiler to a level which is below the tapping on the boiler. Allow the boiler to cool to 80 F (7 C) and allow the pressure to release to 0 psi (0 bar). Determine where to install the control. The low water cut-off must be positioned at above the boiler manufacturer s minimum safe water level. Separate the mounting barrel from the control slightly by loosening the eight (8) slotted screws on the clamping ring. This allows the barrel to be turned into the tapping in the boiler without rotating the whole control. (The barrel may also be completely removed to install easily). Apply a small amount of pipe dope thread sealant to the 1/ PT and hand screw the barrel into the boiler without rotating the rest of the control. Tighten the barrel securely using a pipe wrench to about 150 ft-lbs. (00 m) tque. Rotate the control in the barrel to the finished position using a level to set the two () conduit housing screws (AA) in a hizontal position. Complete the installation by securing the control onto the barrel by tightening the eight (8) clamping ring screws to 5 ft-lbs (7 m) tque. "TOP" on the switch terminal panel MUST be in the up position. minimum safe water level O OFF Cut-off level Clamping ring and 8 screws AA OTE: To connect wires to the terminals on the water feeder, burner, low water cut-off, place the bare end of the wire under the terminal screw and tighten the screw with a flathead screwdriver.

Wiring Instructions! WARIG To prevent electrical shock, turn off the electrical power befe making electrical connections. This low water cut-off must be installed in series with all other limit and operating controls installed on the boiler. After installation, check f proper operation of all of the limit and operating controls befe leaving the site. Failure to follow this warning could cause electrical shock, an explosion and/ a fire, which could result in property damage, personal injury death. Electrical connect is movable into any one of four positions illustrated, by simply removing two black headed screws and rotating housing. OTE: This control should be wired with materials suitable f use at 75 C. Switch Operation The o. 11 switch can be identified by a black terminal panel. The switch contains two () single pole single throw switches to control the water feeder and the low water cut-off. The low water cut-off switch is between terminals marked 1 and. A second switch is located between terminals marked and 4. This can be used to operate a low water alarm a McDonnell & Miller electric water feeder. TOP LEFT BOTTOM RIGT 1 TOP Wiring Diagrams: Series Low Water Cutoff with M&M Model 101-A Electronic Water Feeders 10V Burner and 10V Feeder Using a wire nut, connect a wire from the neutral side of the power supply to one of the wires inside the feeder's junction box. (Does not make a difference which one). Connect a wire from the "hot" side of the power supply to terminal of the Series junction box. Connect the neutral side of the power supply to the burner. Connect the wire from the burner to terminal 1 of the low water cut-off. Connect a "jumper" from terminal to terminal of the low water cut-off. Connect a wire from terminal 4 of the low water cut-off to the remaining wire in the 101-A water feeder. BURER 101A 10 VAC 4V Burner and 4V Feeder Connect the "hot" wire from the boiler transfmer to terminal of the low water cut-off. Connect the "hot" side of the water feeder transfmer to terminal of the low water cut-off. Connect the neutral side of the boiler transfmer to the burner. Using a wire nut, connect the neutral side of the water feeder transfmer to the water feeder. Connect the wire from the burner to terminal 1 of the low water cut-off. Connect a wire from terminal 4 of the low water cut-off to the remaining wire in the water feeder. BURER 101A-4 4V 10 VAC 4V TRASFORMER (101-4V-48)! IMPORTAT To prevent damage to the water feeder, a McDonnell & Miller transfmer Model 101-4V-48 must be used. 4

Wiring Alternatives - Controls of Different Voltages F 10V Burner/4V Feeder setups F 4V Burner/10V Feeder setups BURER 101A-4 10 VAC 4V TRASFORMER (101-4V-48) BURER 4V 10 VAC TO AVOID DAMAGE TO 101A SOLEOID COIL, TRASFORMER 101-4V-48 MUST BE USED. 101A! IMPORTAT To prevent damage to the water feeder, a McDonnell & Miller transfmer Model 101-4V-48 must be used. Models -MV-P and -MV Millivolt Burner Circuit Controls with Water Feeder Millivolt Burner Control and Model 101-A 10V Water Feeder Wire only terminals 1 and into the millivolt circuit. Do not attach any other wiring to terminals 1 and. Install wire (A) from water feeder to 10 volt eutral wire. Install wire (B) from water feeder to terminal 4 of the low water cut-off. Install wire (C) from terminal of the low water cut-off to 10 volt ot wire. MILLIVOLT BURER CIRCUIT C B OT 10 VAC EUTRAL WIRE UTS 101A FEEDER A Millivolt Burner Control and Model 101-A 4V Water Feeder Wire only terminals 1 and into the millivolt circuit. Do not attach any other wiring to terminals 1 and. Install wire (A) from 10 volt circuit eutral wire to the transfmer input eutral terminal. Install wire (B) from burner circuit ot wire to the transfmer input ot terminal. Install wire (C) from transfmer output eutral terminal to the water feeder. Install wire (D) from the water feeder to terminal 4 on the low water cut-off. Install wire (E) from terminal on the low water cut-off to the transfmer output ot terminal. 10 VAC B A E 4V TRASFORMER (101-4V-48) MILLIVOLT BURER CIRCUIT D WIRE UTS C 101A-4! IMPORTAT To prevent damage to the water feeder, a McDonnell & Miller transfmer Model 101-4V-48 must be used. 5

Wiring Diagrams (continued): Series Low Water Cut-off with M&M Model WF--U Electronic Water Feeders The Uni-Match water feeders have a three-position slide switch which initiates a dwell period specific to the position of the switch. If the system condensate raises the boiler water level above the cut-off level during the dwell period, no additional water will be added to the boiler. Once the dwell period has passed, the feeder will be activated and water will be added to the boiler. The feeder will be deactivated when the LWCO reactivates the burner circuit. The position of the slide switch also sets the length of the dwell period, the length of time valve is open and the number of dwell/feed cycles. The control is set with the slide switch in position and can be changed in the field after installation. The chart on the right indicates the cycles and length of dwell/feed cycles f each position. M&M M&M Switch Initial Initial Dwell/Feed Position Dwell Feed Cycles M&M 60 60 Repeats until LWCO seconds seconds reactivates the burner circuit 90 90 One seconds seconds 100 100 One seconds seconds Connect a wire from the "ot" side of the power supply to the water feeder terminal, and low water cut-off terminal. Connect a wire from the neutral side of the power supply to the water feeder terminal, and to the neutral side of the burner. Connect the wire from the burner to terminal 1 of the low water cut-off. Connect a jumper from terminal to terminal of the low water cut-off. Connect a wire from terminal 4 of the low water cut-off to terminal 1 of the water feeder. WIRIG ALTERATIVES WE USIG MIXED VOLTAGES 4V Burner/10V Feeder BURER 4V TRASFORMER 10 VAC 10V Burner/10V Feeder 4V Burner/4V Feeder WF-U-10 W 1 BURER Supply Voltage SAME as Feeder 10V Burner/4V Feeder WF-U-10 WF-U-4 W 1 BURER 10 VAC 4V TRASFORMER WF-U-4V W 1 6

Replace the cover on the switch housing and, using a flathead screwdriver, tighten the one (1) screw to approximately ft lb (.6 m). Switch ousing Cover ISTALLATIO COMPLETE TESTIG Manually fill boiler until water level in the sight glass is above the control. Turn on the power to the boiler and water feeder. Activate the burner by raising the thermostat set point. Using the sight glass as a reference, slowly drain water from boiler by opening the blow down valve the boiler drain until the low water cut-off activates the water feeder. IMPORTAT: If the water feeder does not activate befe the water level reaches the bottom of the sight glass, immediately close any open drain blow down valve and check controls and piping f proper installation. Crect any problems. LWCO Level Continue to drain the boiler slowly. If the burner does not turn off befe the water level reaches the bottom of the sight glass, immediately close any open drain blow down valve. Check control f proper installation. Crect any problems. Once the burner turns off on low water, close all boiler drains blow down valves. Using the sight glass as a reference, see that the water feeder activates and fills to approximately 1/ to 1 (1-5mm) above the burner cut-off level of the low water cut-off. IMPORTAT: If the water feeder does not turn off once the water level has surpassed the halfway point of the sight glass, immediately turn off the power to the boiler and water feeder and check control f proper installation. Crect any problems. Repeat test times. Reste boiler and controls to nmal settings. 7

TROUBLESOOTIG Problem: 1. Burner does not shut off on low water. a. Cause: Float shield is loaded with mud sediment. Shield may be out of position damaged; bellows folds obstructed. Test: With water level below the control check if terminals 1 and are open. If not, remove switch and manually test if terminals 1 and can be opened. Solution: Remove the control and clean. At this time, check f a build-up of scale sediment between crugations of the bellows. b. Cause: Contacts are fused together. Test: Remove switch and operate manually to verify proper switch operation. Solution: Replace switch. Check electrical load and make sure it is within the ratings of the switch. MAITEACE SCEDULE: Blow down weekly (at least once) when the boiler is in operation. Disassemble and inspect annually. Replace the low water cut-off if it is wn, croded, if components no longer operate properly. Inspect the shield, float and bellows annually. Remove all sediment and debris. We recommend replacement when the switch no longer operates properly. If you choose to replace the switch, der the McDonnell & Miller replacement switch and follow the Repair Procedure provided. Replace the low water cut-off every 10 years. Me frequent replacement may be required when severe conditions exist such as rapid switch cycling, surging water levels, and use of water treatment chemicals.. Electric water feeder does not shut off. a. Cause: Float obstructed damaged. Build-up of scale sediment between crugations of the bellows. Shield may be out of position. Test: With water level above the control, check if terminals and 4 are open. If not, remove switch and manually test to verify terminals and 4 can be opened. Solution: Check the clearance of the shield; replace clean the bellows. b. Cause: Contacts are fused together. Test: Remove switch and operate manually to verify proper switch operation. Solution: Replace switch. Check electrical load and make sure it is within the ratings of the switch. PROCEDURE:! CAUTIO To prevent serious personal injury from steam pipe blow down, connect a drain pipe to avoid exposure to steam discharge. Failure to follow this caution could cause personal injury. Test the low water cut-off when the water level is at its nmal level and the burner is on. Slowly open the boiler drain valve and observe the water level fall in the gauge glass. Close the valve after verifying that the alarm/feeder contacts have closed and the burner shuts off. If this does not happen, immediately shut off the boiler and crect the problem. 8

COMMERCIAL WARRATY Warranty. F goods sold to commercial buyers, Seller warrants the goods sold to Buyer hereunder (with the exception of membranes, seals, gaskets, elastomer materials, coatings and other wear parts consumables all of which are not warranted except as otherwise provided in the quotation sales fm) will be (i) be built in accdance with the specifications referred to in the quotation sales fm, if such specifications are expressly made a part of this Agreement, and (ii) free from defects in material and wkmanship f a period of one (1) year from the date of installation two () years from the date of manufacture, whichever shall occur first, unless a longer period is specified in the product documentation (the Warranty ). Except as otherwise required by law, Seller shall, at its option and at no cost to Buyer, either repair replace any product which fails to confm with the Warranty provided Buyer gives written notice to Seller of any defects in material wkmanship within ten (10) days of the date when any defects non-confmance are first manifest. Under either repair replacement option, Seller shall not be obligated to remove pay f the removal of the defective product install pay f the installation of the replaced repaired product and Buyer shall be responsible f all other costs, including, but not limited to, service costs, shipping fees and expenses. Seller shall have sole discretion as to the method means of repair replacement. Buyer s failure to comply with Seller s repair replacement directions shall terminate Seller s obligations under this Warranty and render the Warranty void. Any parts repaired replaced under the Warranty are warranted only f the balance of the warranty period on the parts that were repaired replaced. Seller shall have no warranty obligations to Buyer with respect to any product parts of a product that have been: (a) repaired by third parties other than Seller without Seller s written approval; (b) subject to misuse, misapplication, neglect, alteration, accident, physical damage; (c) used in a manner contrary to Seller s instructions f installation, operation and maintenance; (d) damaged from dinary wear and tear, crosion, chemical attack; (e) damaged due to abnmal conditions, vibration, failure to properly prime, operation without flow; (f) damaged due to a defective power supply improper electrical protection; (g) damaged resulting from the use of accessy equipment not sold approved by Seller. In any case of products not manufactured by Seller, there is no warranty from Seller; however, Seller will extend to Buyer any warranty received from Seller s supplier of such products. TE FOREGOIG WARRATY IS EXCLUSIVE AD I LIEU OF AY AD ALL OTER EXPRESS OR IMPLIED WARRATIES, GUARATEES, CODITIOS OR TERMS OF WATEVER ATURE RELATIG TO TE GOODS PROVIDED EREUDER, ICLUDIG WITOUT LIMITATIO AY IMPLIED WARRATIES OF MERCATABILITY AD FITESS FOR A PARTICULAR PURPOSE, WIC ARE EREBY EXPRESSLY DISCLAIMED AD EXCLUDED. EXCEPT AS OTERWISE REQUIRED BY LAW, BUYER S EXCLUSIVE REMEDY AD SELLER S AGGREGATE LIABILITY FOR BREAC OF AY OF TE FOREGOIG WARRATIES ARE LIMITED TO REPAIRIG OR REPLACIG TE PRODUCT AD SALL I ALL CASES BE LIMITED TO TE AMOUT PAID BY TE BUYER FOR TE DEFECTIVE PRODUCT. I O EVET SALL SELLER BE LIABLE FOR AY OTER FORM OF DAMAGES, WETER DIRECT, IDIRECT, LIQUIDATED, ICIDETAL, COSEQUETIAL, PUITIVE, EXEMPLARY OR SPECIAL DAMAGES, ICLUDIG BUT OT LIMITED TO LOSS OF PROFIT, LOSS OF ATICIPATED SAVIGS OR REVEUE, LOSS OF ICOME, LOSS OF BUSIESS, LOSS OF PRODUCTIO, LOSS OF OPPORTUITY OR LOSS OF REPUTATIO. LIMITED COSUMER WARRATY Warranty. F goods sold f personal, family household purposes, Seller warrants the goods purchased hereunder (with the exception of membranes, seals, gaskets, elastomer materials, coatings and other wear parts consumables all of which are not warranted except as otherwise provided in the quotation sales fm) will be free from defects in material and wkmanship f a period of one (1) year from the date of installation two () years from the product date code, whichever shall occur first, unless a longer period is provided by law is specified in the product documentation (the Warranty ). 9

Except as otherwise required by law, Seller shall, at its option and at no cost to Buyer, either repair replace any product which fails to confm with the Warranty provided Buyer gives written notice to Seller of any defects in material wkmanship within ten (10) days of the date when any defects non-confmance are first manifest. Under either repair replacement option, Seller shall not be obligated to remove pay f the removal of the defective product install pay f the installation of the replaced repaired product and Buyer shall be responsible f all other costs, including, but not limited to, service costs, shipping fees and expenses. Seller shall have sole discretion as to the method means of repair replacement. Buyer s failure to comply with Seller s repair replacement directions shall terminate Seller s obligations under this Warranty and render this Warranty void. Any parts repaired replaced under the Warranty are warranted only f the balance of the warranty period on the parts that were repaired replaced. The Warranty is conditioned on Buyer giving written notice to Seller of any defects in material wkmanship of warranted goods within ten (10) days of the date when any defects are first manifest. Seller shall have no warranty obligations to Buyer with respect to any product parts of a product that have been: (a) repaired by third parties other than Seller without Seller s written approval; (b) subject to misuse, misapplication, neglect, alteration, accident, physical damage; (c) used in a manner contrary to Seller s instructions f installation, operation and maintenance; (d) damaged from dinary wear and tear, crosion, chemical attack; (e) damaged due to abnmal conditions, vibration, failure to properly prime, operation without flow; (f) damaged due to a defective power supply improper electrical protection; (g) damaged resulting from the use of accessy equipment not sold approved by Seller. In any case of products not manufactured by Seller, there is no warranty from Seller; however, Seller will extend to Buyer any warranty received from Seller s supplier of such products. TE FOREGOIG WARRATY IS PROVIDED I PLACE OF ALL OTER EXPRESS WARRATIES. ALL IMPLIED WARRATIES, ICLUDIG BUT OT LIMITED TO TE IMPLIED WARRATIES OF MERCATABILITY AD FITESS FOR A PARTICULAR PURPOSE, ARE LIMITED TO OE (1) YEAR FROM TE DATE OF ISTALLATIO OR TWO () YEARS FROM TE PRODUCT DATE CODE, WICEVER SALL OCCUR FIRST. EXCEPT AS OTERWISE REQUIRED BY LAW, BUYER S EXCLUSIVE REMEDY AD SELLER S AGGREGATE LIABILITY FOR BREAC OF AY OF TE FOREGOIG WARRATIES ARE LIMITED TO REPAIRIG OR REPLACIG TE PRODUCT AD SALL I ALL CASES BE LIMITED TO TE AMOUT PAID BY TE BUYER FOR TE DEFECTIVE PRODUCT. I O EVET SALL SELLER BE LIABLE FOR AY OTER FORM OF DAMAGES, WETER DIRECT, IDIRECT, LIQUIDATED, ICIDETAL, COSEQUETIAL, PUITIVE, EXEMPLARY OR SPECIAL DAMAGES, ICLUDIG BUT OT LIMITED TO LOSS OF PROFIT, LOSS OF ATICIPATED SAVIGS OR REVEUE, LOSS OF ICOME, LOSS OF BUSIESS, LOSS OF PRODUCTIO, LOSS OF OPPORTUITY OR LOSS OF REPUTATIO. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Some states do not allow the exclusion limitation of incidental consequential damages, so the above exclusions may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which may vary from state to state. To make a warranty claim, check first with the dealer from whom you purchased the product call +1-847-966-700 f the name and location of the nearest dealer providing warranty service. Xylem Inc. 800. Austin Avenue Mton Grove, Illinois 6005 Phone: (847) 966-700 Fax: (847) 965-879 www.mcdonnellmiller.com McDonnell & Miller is a trademark of Xylem Inc. one of its subsidiaries. 015 Xylem Inc. MM-6D April 015 Part o. 4675