Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Similar documents
Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Performance of CO2 Cycles with a Two-Stage Compressor

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Purdue e-pubs. Purdue University

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Performance Measurement of R32 Vapor Injection Heat Pump System

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Low GWP Refrigerants for Air Conditioning Applications

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Performance Analysis of a Miniature-Scale Vapor Compression System for Electronics Cooling: Bread Board Setup

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Study of R161 Refrigerant for Residential Airconditioning

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Air-Cooled Heat Exchanger Performance for R410A

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Design Optimization of Variable Geometry Microchannel Heat Exchangers

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

Steady and Cyclic Performance Testing of Packaged R-410A Units

Sub-Critical Operation of the CO2 Expander/ Compressor

Dae-Hyun Jin. 8/2018-Present Assistant Professor of Mechanical Engineering, Taylor University, USA

Performance Characteristic and Optimization of a Simultaneous Heating and Cooling Multi Heat Pump

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

Mini Vapour Cycle System For High Density Electronic Cooling Applications

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

Designated vs Non-designated Areas for Condenser Subcooling

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

Dynamic Simulation of Liquid Chillers

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

System Modeling of Gas Engine Driven Heat Pump

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Experimental Study of Two-phase Seperators for Vapor Compression Systems in Household Appliances

Evaluation of a Virtual Refrigerant Charge Sensor

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Effect of Inclination Angle on the Air-Side Performance of Aluminum Parallel Flow Heat Exchangers Under Wet Conditions

Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers

R32 Compressor for Air conditioning and Refrigeration applications in China

Experimental Study on the Performance of Twisted Capillary Tube

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Purdue e-pubs. Purdue University. Ian H. Bell Purdue University. Eckhard A. Groll Purdue University

Investigation of Port Level Refrigerant Flow Mal-distribution in Microchannel Heat Exchanger

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Thermal Performance of a Loop Thermosyphon

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube Heat Exchanger Rin Yun University of Maryland Yunho Hwang University of Maryland Reinhard Radermacher University of Maryland Rebeka Zecirovic Technische Universität Berlin Follow this and additional works at: http://docs.lib.purdue.edu/iracc Yun, Rin; Hwang, Yunho; Radermacher, Reinhard; and Zecirovic, Rebeka, "Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Fin-and-Tube Heat Exchanger" (2006). International Refrigeration and Air Conditioning Conference. Paper 752. http://docs.lib.purdue.edu/iracc/752 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

R108, Page 1 Comparison of Performance of a Residential Air-Conditioning System Using Microchannel and Fin-and-Tube Heat Exchanger Rin Yun, Yunho Hwang*, Reinhard Radermacher Center for Environmental Energy Engineering, Department of Mechanical Engineering, University of Maryland, 3163 Glee Martin Hall Bldg., College Park, MD, USA *: Corresponding Author: Tel: 301-405-5247, Fax: 301-405-2025, Postcode: 20742 E-mail: yhhwang@eng.umd.edu Rebeka Zecirovic Technische Universität Berlin, Institut für Energietechnik, Maschinen- und Energieanlagentechnik, Ernst-Reuter-Platz 1, Berlin, Germany E-mail: r.zeci@web.de ABSTRACT In this study the seasonal performance of a residential air conditioning system having either a fin-and-tube condenser or a microchannel condenser is experimentally investigated. Microchannel heat exchangers offer a higher volumetric heat exchange capacity and a reduced refrigerant charge amount. However, the operating characteristics and the seasonal energy efficiency ratio (SEER) of the residential air conditioning system using a microchannel condenser have not been well known. For this investigation, a commercially available 7 kw capacity residential air conditioning system having a fin-and-tube condenser served as the base system. After testing the base unit with the fin-and-tube condenser, the condenser was replaced by a microchannel heat exchanger with the same face area under identical test conditions. The test results show that the system with a microchannel heat exchanger has a reduced refrigerant charge amount of 10%, the coefficient of performance increased by 6% to 10%, and the SEER increased by 7% as compared with those of the base system. Moreover, the condensing pressure of the system is decreased by 100 kpa and the pressure drop across the condenser is decreased by 84%. The microchannel heat exchanger enhances the SEER of the residential air conditioning system by providing better heat transfers at reduced pressure drops. 1. INTRODUCTION To improve the system performance of air conditioners and to develop environmentally safe air-conditioning systems, research for each component of air conditioning systems has been extensively conducted. For heat exchangers, compactness and higher volumetric heat transfer capacity are required. The microchannel heat exchanger has a great potential for condensers or evaporators in these respects. Due to a higher air-side heat transfer performance of microchannel heat exchangers, the volume of the heat exchanger can be significantly reduced at the same cooling or heating capacity. This high air-side heat transfer performance is attributed to the small hydraulic channel diameter, the characteristics of air flow over flat channel-and-fin geometry, and the reduced contact resistance between fin and tube. With the decrease of the heat exchanger volume, the refrigerant charge amount can be decreased as well. Furthermore, it has a merit for recycling process. For typical fin-and-tube heat exchangers, tubes and fins have different materials. However, fins and tubes of microchannel heat exchangers are both made of the same material, aluminum. Therefore, it has a much higher recycling potential. Since the microchannel heat exchanger technology has been developed recently, its research is limited. Kim and Groll (2003) compared the performance of a heat pump having a fin-and-tube condenser with that having a microchannel condenser. They replaced the fin-and-tube condenser by a microchannel heat exchanger without changing other components of system including the expansion device. The microchannel condenser has about 23% smaller face area and 32% smaller internal volume than those of the fin-and-tube condenser. Among their test results, a vertically oriented microchannel condenser with 20 fpi fin density shows 2.7% lower cooling capacity and 3.2% lower compressor power. However, the same microchannel heat exchanger slanted 15 o from the vertical has 4.3%

R108, Page 2 higher cooling capacity and 1% lower compressor power consumption. Their COPs are 1.0 and 4.8% higher than the baseline, respectively. Kim and Bullard (2002) investigated the performance of a window room air conditioner with a microchannel condenser. They replaced the fin-and-tube heat exchanger with a microchannel heat exchanger having 50% smaller volume than the original fin-and-tube condenser, and the charge amount was 35% smaller than that of the baseline fin-and-tube condenser system. For the microchannel condenser system, the degrees of subcooling and superheating were controlled to the same values of the baseline fin-and-tube condenser system. They obtained almost the same COP, but the compressor power of the microchannel condenser system is 2% less than that of the baseline system. Cho et al. (1999) evaluated the system performance of the package air-conditioner having a microchannel condenser. They reported that the same cooling capacity was obtained with the smaller microchannel condenser having 82% face area of the fin-and-tube condenser. In addition, the charge amount of the refrigerant is decreased by 35% and 45% when the fin pitch decreased from 3.0 mm to 2.5 and 2.0 mm, respectively. Jeong et al. (2004) investigated the performance of three microchannel condensers having different air-side heat transfer areas but the same face area, which is 78% of the fin-and-tube condenser, by adjusting tube and fin pitches. With increase of the heat transfer area by 73.9%, 84.2%, and 88.5% from that of fin-and-tube heat exchanger, the cooling capacities and COPs approached to that of the fin-and-tube condenser system. Bea and Han (1996) experimentally studied the potential application of the microchannel condenser to the residential air conditioner. They suggested that the microchannel heat exchanger can reduce the condenser volume by 40% at the same condenser heat transfer rate compared to that of the fin-and-tube condenser, and the charge amount can be reduced to by 22%. They also investigated the effect of the different number of pass of the microchannel heat exchanger on the system performance. When the pass of microchannel condenser was changed from 4 to 6, the cooling capacity was increased by 4%, and the compressor power was decreased by 0.9%. As summarized, most of previous studies focused on reducing the condenser size at a lower or similar COP as compared to that of fin-and-tube condenser system rather than enhancing system performances, such as the COP and SEER. As achieving higher SEERs became an important issue, the current study investigated the performance enhancement while using the same face area microchannel condenser with that of fin-and-tube condenser. Moreover, its steady state and cyclic operating characteristics was investigated. 2. EXPERIMENTAL SETUP 2.1 Test Set-up and Test Unit All tests were conducted in an outdoor chamber and an indoor loop as shown in Fig. 1. Outdoor test unit of the air conditioner was installed inside the outdoor chamber, and the indoor unit was installed in the indoor loop. Details of the indoor loop are illustrated in Fig. 2. Air flow rate was measured by using the 0.127 m diameter nozzle. The test unit used in this study is a residential air conditioner having a rated cooling capacity of 6.25 kw and R22 as its working fluid. The unit is composed of the basic cycle components, a rotary compressor, a condenser, a short tube orifice, and an evaporator as shown in Fig. 1. Table 1 shows the specification of the fin-and-tube and microchannel heat exchanger. They have the same number of rows, face area, and finned length. The total number of tubes of the fin-and-tube heat exchanger is 18, and 71 for the microchannel heat exchanger. The fin-and-tube heat exchanger has a single refrigerant circuit. The microchannel heat exchanger is divided in two parallel tube groups, 48 tubes and 23 tubes. Table 1 Specification of Test Heat Exchangers Fin-and-tube heat exchanger Microchannel heat exchanger Fin shape Plate Fin Louvered fin Number of rows 1 1 fpi 18 17 Tubes per row 28 71 Face area 0.56 m² 0.56 m² Finned length 850.9 mm 850.9 mm

R108, Page 3 Figure 1 Schematic of Test Set-Up Figure 2 Details of Indoor Loop 2.2 Instrumentations and Test Procedures Fig. 1 indicates the measurement points of the experiments. The refrigerant pressures were measured by using pressure transducers in 3.5 MPa and 1.8 MPa full scales. They have an accuracy of ± 0.11% of full scale. Five instream T-type thermocouples with an accuracy of ± 0.2 o C were installed at the same places with the pressure transducers. To measure a differential pressure drop of refrigerant across the condenser a differential pressure transducer was installed. It has a measuring range of 0 to 1.0 MPa and an accuracy of ± 0.2% of full scale. Thermocouples were attached on the U-bend surfaces of the fin-and-tube condenser and on the microchannel tubes close to the headers of the microchannel condenser to observe the refrigerant phase transition in condensers. To measure the average air-side temperatures, nine thermocouples were evenly placed on a grid at the inlet and outlet of

R108, Page 4 the evaporator as shown in Fig. 2. The inlet and outlet humidity ratio of the evaporator were measured by using two chilled mirror dew-point sensors with an accuracy of ± 0.2 o C. Two watt transducers were used to measure the power consumptions of the compressor and the outdoor unit fan. The accuracy of watt transducers is ± 0.5% of full scale. Indoor unit fan power was independently measured before system tests. All data were logged and written to a file by the PC. Scanning time for each data point was 5 seconds. The baseline tests were first conducted by using the original product provided from the manufacturer without any system modification. After the baseline test, the condenser of the original product was replaced by the microchannel heat exchanger without changing other components of the system. These tests were conducted at ARI test A, B, C, and D conditions as shown in Table 2 (ARI, 1989). Except test D, other tests are steady-state tests. Test D is a cyclic test, in which the unit shall cycle with the compressor on for 6 minutes and off for 24 minutes. Baseline system tests and microchannel system tests were conducted with a constant indoor air volumetric flow rate of 0.25 m 3 /s. Table 2 Test Conditions Indoor unit Outdoor unit Cooling Test Condition Air entering Air entering DB ( F/ C) WB ( F/ C) DB ( F/ C) WB ( F/ C) Test A in steady state 80/26.7 67/19.4 95/35 75/23.9 Test B in steady state 80/26.7 67/19.4 82/27.8 65/18.3 Test C in steady state (dry coil) 80/26.7 57/13.9 82/27.8 65/18.3 Test D in cyclic (dry coil) 80/26.7 57/13.9 82/27.8 65/18.3 2.3 Data reduction Air-side cooling capacity was calculated by eq. (1). In eq. (1), the heat loss from the air in duct to ambient was considered. Energy balance between refrigerant-side and air-side was checked at every test by using eq. (2). The cooling capacity of refrigerant side was calculated by eq. (3). The refrigerant inlet enthalpy of the evaporator was assumed to be the same as that of condenser outlet. Energy balance of all tests was within 6%. Q a = Q lat + Q sens + Q loss = m wδhlv + m ac p ( Tin Tout ) + UAduct ( Ta Tamb ) (1) Q a Q r Energy balance = 100 Q a (2) Q = m h h ) (3) r r ( eva, out eva, in The coefficient of performance (COP) was calculated by eq. (4), and the uncertainty of COP of present tests was found to be ± 4%. The calculation of the seasonal energy efficiency ratio (SEER) followed the calculation methods for single-speed compressor and single-speed condenser fan unit as shown in eqs. (5), (6), and (7). (ARI, 1989) The results of test C and D shall be used to calculate a degradation coefficient of C D. COPc = W C D fan, id + W Q c, a fan, od + W 1 EERcyc, dry / EERss, = 1 CLF dry compressor (4) (5) PLF ( 0.5) = 1 0. 5 C D (6) SEER = PLF ( 0.5) EER (7)

R108, Page 5 3. RESULTS AND DISCUSSION 3.1 Charge Optimization The comparison of the performances of both systems has to be done at optimum refrigerant charge conditions. The optimum charge was determined by comparing the COP and the degree of superheating and subcooling of the system by changing the charge amount under test A condition. Fig. 3 shows the variations of COP with refrigerant charge amount. Fig. 4 shows the degree of superheating and subcooling of the system. It was observed that the superheating decreases and the subcooling increases with increase of charge amount as expected. In case of the baseline system, the maximum COP was found at around 1.5 kg of charge amount. However, the superheating is less than 1.0 o C at that refrigerant charge. Although the COP at 1.35 kg charge is less than the COP at 1.5 kg refrigerant charge by 1%, the optimum charge was decided to 1.35 kg for system stability since the superheating of 5 o C was found at that charge amount. For the microchannel condenser system, the optimum charge was decided to 1.21 kg. The maximum COP and the superheating of 6.8 o C were found at that charge amount. The optimum refrigerant charge amount of the microchannel condenser system is reduced by 10% due to the smaller internal volume of the new condenser. The internal volume of the microchannel is less than 49% that of the fin-andtube condenser. COP 3.3 3.2 3.1 COP Baseline 3.0 COP MCHX System 2.9 2.8 2.7 2.6 2.5 1.0 1.1 1.2 1.3 1.4 1.5 1.6 Charge amount [kg] Figure 3 COP vs. Refrigerant Charge Amount Temperature [ºC] 16 14 12 10 8 6 4 2 0 1.0 1.1 1.2 1.3 1.4 1.5 1.6 Charge [kg] Subcooling-Baseline Subcooling-MCHX Superheat-Baseline Superheat-MCHX Figure 4 Degree of Superheating and Subcooling vs. Refrigerant Charge Amount 3.2 System Operating Characteristics Fig. 5 shows the surface temperatures of the microchannel condenser during system operation. The thermocouples are grouped and named as I, II, III and IV. The temperatures of group I show the state of refrigerant is superheated vapor. During the refrigerant flow through the upper part of 48 tubes, condensation of refrigerant occurs. Thermocouple groups II and III show constant temperatures during this condensation. Around the condenser outlet part, the refrigerant can be found to be subcooled (group IV). Fig. 6 shows cycle characteristics of the systems with a fin-and-tube condenser and a microchannel condenser. The big difference between two systems is the lower condensing pressure of the microchannel condenser system than that of the baseline system. Also, a decrease of the enthalpy difference between the suction and discharge of the compression process for the microchannel condenser system can be observed. Details of pressure variations and temperature variations for both systems are shown in Fig. 7 and Fig. 8, respectively. The condensing pressure of the microchannel condenser system is 6.3% lower than that of the baseline system for the condition test A. This decrease of the condensing pressure can be explained by the increase of the heat transfer capacity in the microchannel condenser. On the other hand, the average evaporation pressure is about the same for both systems within 1.4% variation for the condition test A. As a result, the pressure ratio between the condensing and evaporating pressures for the microchannel condenser system is 4.5% less than that of the baseline system, which contributes to the reduction in the compressor power. Table 3 shows the comparison of the compressor power consumption between baseline system and microchannel condenser system. The compressor power consumption decreased by 6.8% for conditions test A and test B, and by 8.2% for test C. It is also observed that the compressor discharge temperature of the microchannel condenser system is 4.8% lower than that of the fin-and-tube system as shown in Fig. 8.

R108, Page 6 65 60 Temperature [ C] 55 50 45 I II 2 40 1 IV 4 3 35 II I 6 5 30 8 7 10 9 25 12III IV 11 14 13 20 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Condenser Inlet Condenser Thermocouples Condenser Outlet III Figure 5 Average Surface Temperatures of Microchannel Condenser Figure 6 Cycles in P-h Diagram Pressure [kpa] 2500 2000 1500 1000 500 0 Con in Cond out Restrictor out Location Test A-Baseline Test B-Baseline Test A-MCHX Test B-MCHX Evap in Figure 7 Comparison of Cycle Pressures Evap out Temperature [ C] 100 90 80 70 60 50 40 30 20 10 0 Cond in 1 2 3 4 5 6 7 8 9 10 11 12 13 Thermocouple Location MCHX Baseline Con out Res. out Evap in Evap out Suction Figure 8 Comparison of Cycle Temperatures Table 3 Compressor Power consumption Test conditions Fin-and-tube condenser Microchannel condenser Change (%) Test A 2,036 1,898-6.8 Test B 1,806 1,683-6.8 Test C 1,776 1,630-8.2 Table 4 shows the comparison of the refrigerant pressure drop across the condenser between the baseline and the microchannel condenser system. For all tests, the pressure drop of the microchannel condenser is 84% lower than that of the fin-and-tube condenser. This lower pressure drop of the microchannel condenser can be explained by two reasons. One is the increase of the refrigerant flow cross sectional area of microchannel condenser by 48/23 parallel tubes than that of the fin-and-tube condenser. The other is shorter refrigerant distance of the microchannel heat exchanger than that of the fin-and-tube condenser. Table 4 Refrigerant-Side Pressure Drop Across The Condenser Test Fin-and-tube condenser (kpa) Microchannel condenser (kpa) Change (%) A 130.1 20.5-84 B 148.7 23.6-84 C/D 142.3 24.5-83

R108, Page 7 3.3 COP and SEER Fig. 9 shows the cooling capacities and COPs of each test for both systems. The COPs of the microchannel condenser system are higher than those of the baseline system for all tests. The COP of the microchannel condenser system is 9.5%, 6.1% and 8.7% higher than that of the baseline system for conditions test A, test B and test C, respectively. As compared to the COP change, the change of the cooling capacity between the baseline and the microchannel condenser system is smaller, and for test B the cooling capacity of both systems is almost same. Therefore, the increase of COP for the microchannel condenser system can be attributed to the decrease of the compressor power consumption rather than the increase of the cooling capacity. Fig. 10 shows the variations of the cooling capacity and compressor power consumption during the cyclic tests for test D. The system was turned on for 6 minutes and then off for 24 minutes. The cooling capacity of the microchannel condenser system much quickly approached to its steady state cooling capacity than that of the baseline system. On the other hand, the compressor power consumption of the microchannel condenser system is less than that of the baseline system. It means that the increase in the condenser heat transfer capacity is beneficial to the cooling capacity during the cyclic conditions. The calculated SEER of the baseline system and the microchannel condenser system is 10.4 and 11.2 Btu/kW-h, respectively. This means that the SEER of the microchannel condenser system is 7.7% higher than that of the baseline system. 6.33 6.51 6.89 6.86 Capacity [kw] COP [-] 3.10 2.83 3.63 3.42 5.71 5.74 3.13 2.88 Cap A COP A Cap B COP B Cap C COP C Conv HX MCHX Fig. 9 Comparison of Steady State Performance Fig. 10 Comparison of Cyclic Performance 4. CONCLUSIONS The seasonal performance of an air conditioning system having a microchannel condenser was experimentally evaluated, and was compared with that having a fin-and-tube condenser system. The tested microchannel condenser has the same face area as that of the fin-and-tube condenser, but its internal refrigerant flow volume is 49% smaller than that of the baseline condenser. Due to its smaller internal volume, the optimum refrigerant charge amount of the microchannel condenser system is 10% lower than that of the baseline system. The refrigerant pressure drop across the microchannel condenser is 84% lower than that of the fin-and-tube condenser due to the increase in the cross sectional area of the refrigerant flow and the shorter refrigerant flow distance. The steady state COP of the microchannel condenser system is increased by 6 to 10% as compared with that of the baseline system. This is attributed to the decrease in the compressor power consumption rather than the increase in the cooling capacity. Decrease of the power consumption for the microchannel condenser system is caused by the lower pressure ratio between the condensing and evaporation pressure, which is caused by the increased condenser heat capacity. In the cyclic operation, the cooling capacity of the microchannel condenser system is higher and its compressor power is lower than those of the baseline system. These benefits in the cycle operation are originated from the increased condenser heat capacity. When both the steady state and cyclic performances are considered, it was found that the SEER of the microchannel condenser system having the same frontal area is 7.7% higher than that of the baseline system.

R108, Page 8 NOMENCLATURE A area 2 ( m ) W power ( kw ) C D degradation coefficient WB wet bulb temperature o ( C ) CLF cooling load factor COP coefficient of performance subscript C p specific heat ( kj / kgk ) a air DB dry bulb temperature ( C ) amb ambient fpi number of fins per inch c cooling h enthalpy ( kj / kg ) cyc cyclic eva evaporator Δ h lv specific enthalpy of vaporization ( kj / kg ) id indoor MCHX microchannel heat exchanger in inlet m mass flow rate ( kg / s ) lat latent Q capacity ( kw ) out outlet od outdoor PLF part load factor r refrigerant SEER seasonal energy efficiency ratio ( Btu / kwh) sens sensible T temperature ( K ) ss steady state U overall heat transfer coefficient ( W / m K ) w water REFERENCES ARI, 1989, ARI Standard 210/240-89, Unitary Air-Conditioning and Air-Source Heat Pump Equipment, Arlington, Va., Air-Conditioning and Refrigeration Institute. Bae, T.S. and Han, C.S., 1996, A Feasibility Study on Room Air Conditioner with Parallel Flow Condenser, Proceedings of the SAREK 1996 Summer Annual Conference, pp. 402 407. Cho, J.P., Choi, Y.H., Kim, N.H., and Kim, J.H., 1999, Performance Evaluation of PF-condenser Adopted to Package Air-Conditioner, Proceedings of the SAREK 1999 Winter Annual Conference, pp. 46 51. Jeong, J.H., Chang, K.S., Kim, H., Kil, S.H., and Kim, H.K., 2004, Performance Assessment of Aluminum Parallel Flow Condenser Applied to Residential Air-Conditioner, Proceedings of the SAREK 2004 Winter Annual Conference, pp. 636 641. Kim, J.H. and Groll, E.A., 2003, Performance Comparison of A Unitary Split System Using Microchannel and Fin- Tube Outdoor Coils, ASHRAE Transactions, Vol. 109, part 2, pp. 219 229. Kim, M.H. and Bullard, C.W., 2002, Performance Evaluation of a Window Room Air Conditioner with Microchannel Condensers, Journal of Energy Resources Technology, Vol. 124, pp. 47 55. Subramaniam V. and Garimella S., 2005, Design of Air-Cooled R-410A Microchannel Condensers, ASHRAE Transactions, Vol. 111, part 1, pp. 471 486. ACKNOWLEDGEMENT This work was jointly supported by the Modine Manufacturing Company, the Center for Environmental Energy Engineering (CEEE) at the University of Maryland, and the Korea Research Foundation Grant (No. M01-2005-000-10005-0).