PRO-WATCH NOTIFIER SECONDARY FIRE INTERFACE ARCHITECT AND ENGINEERING SPECIFICATION

Similar documents
B. After installation, the Owner shall be able to perform hardware configuration changes as desired without the services of the Integrator.

DIVISION 26 ELECTRICAL SECTION LIGHTING CONTROL SYSTEM

ACTIVE INFRARED BARRIER

- HSDK. to Integration. Honeywell Integrated Security Consultants Event, July Rev 10/07/11

SECTION SECURITY TESTING AND COMMISSIONING

WebStat Temperature Control System WITH WEB-BASED BUILDING MANAGEMENT

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS

FIRE & LIFE SAFTEY STANDARD

ONYX FirstVision Specification Interactive Firefighters Display

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

opti-visor ultra-efficient chiller plant automation Typical specification

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA 250BP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM

1.3 REFERENCE STANDARDS

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

Northwestern University Scope of BAS Contractor

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming.

MultiSite Manager. Setup Guide

Installation, Configuration and User Manual

DIVISION LOW VOLTAGE DE-ICING / SNOW MELTING SYSTEM IN EXISTING ASPHALT/CONCRETE

SECTION NURSE CALL SYSTEM

Linear Heat Detection Engineering Specifications

DONALD H. BERG, ARCHITECT

SPECIFICATIONS FOR TENDER # SUPPLY OF A FIRE ALARM SYSTEMS SERVICE AGREEMENT FOR WESTERN HEALTH

Michigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE

CRESTRON MEDIAMANAGER INTELLICLASS

HikCentral Web Client. User Manual

SECTION DIGITAL-NETWORKING LIGHTING CONTROLS ENLIGHTED LIGHT MANAGEMENT SYSTEM

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

SECTION AUTOMATIC VERTICAL CONVEYOR SYSTEM CLOSURE FIRE BARRIER

IntesisBox BACnet/IP Server - Notifier ID3000 series

UNIFIED FACILITIES GUIDE SPECIFICATIONS

DTW Master Specification Section EMCS: Start Up, Verification and Commissioning

CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated)

East Central College

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

Western Michigan University Facilities Management Engineering Division

Advanced Power Monitor (APM)

ADDENDUM NO. 1 FDVA-ITB B ITB TITLE: Bennett SVNH Nurse Call System ISSUE DATE: March 27, 2014

SECTION REGULATORY REQUIREMENTS. A. Relationship between Code, Ordinances, Standards and Contract Documents

SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM. ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM February 2017

15900 HVAC INSTRUMENTATION AND CONTROLS

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Installation Manual. ATS Remote Annunciator Catalog 5350 DANGER WARNING D

i.net Engineered system solutions for

Avigilon Control Center 5 System Integration Guide

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

Fire Smoke Damper Actuator Replacements SECTION COMMISSIONING OF HVAC

Thermo Scientific Revco UxF -80C Series Upright ULT Freezers

GARCIA GALUSKA DESOUSA Consulting Engineers

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

OJD ITB No Attachment E Duress Alarm Equipment Specifications

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA 250FBP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM

Perimeter Product Overview. Effective protection for your business

CONTENTS AUTOMATIC TRANSFER SWITCHES

SECTION Mass Notification Systems

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR SYSTEM INTEGRATION AND TESTING. ITS:CLC 1 of 13 APPR:LWB:DBP: FHWA:APPR:

LightSweep. Lighting Control System

DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC

UNIFIED FACILITIES GUIDE SPECIFICATIONS

A. The requirements of this Section and the other Division 26, 27 & 28 Sections apply to all the video surveillance system work.

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

See Part II for additional information regarding Indoor Pollutant Reduction and Control, Energy Efficiency, etc.

Home center Interface Server. Technical sheet

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

LG ELECTRONICS Air Conditioning Technologies LG Guide Specifications Controls

Bosch TCU Integration Module Administrator's Guide

RFP Addendum 2 March 31, 2016

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.

CONSTRUCTION SYSTEMS AND ASSEMBLIES

Electronic Safety and Security

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA-128FB ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM

Revitalize Building Mechanical Systems (4619)

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

HikCentral Web Client. User Manual

Advanced FireAlarm Panel 1-4Loop

SENTRY PRODUCTS, INC. 01/98 SCAN - STAND-ALONE - Sample Specification

SECTION SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT

SECTION AUTOMATIC TRANSFER SWITCHES

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

CAREL heatersteam Electric Element Steam Humidifiers

September 30, Dear Fire Suppression System Contractor/Designer:

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION ELECTRICAL SYSTEMS COMMISSIONING

Architectural and Engineering Specification for a Real-Time Locating System Flare

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.

Introduction PLAYING NICE: HVAC AND LIGHTING CONTROLS INTEGRATION. Why should I care? Background Integration VAV box Occ sensor

CARD ACCESS CONTROL SYSTEM

PRIVATE FIRE SERVICE INSTALLATION PACKET

Proliphix. Remote Management. User Guide

SECTION GENERATOR PARALLELING CONTROLS

ADDENDUM NO.1. March 4, 2013 HEAT PUMP REPLACEMENT FOR: GATE CITY ELEMENTARY SCHOOL

CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 1

Transcription:

Section 00000 SECURITY PRO-WATCH NOTIFIER SECONDARY FIRE INTERFACE ARCHITECT AND ENGINEERING SPECIFICATION PART 1 GENERAL A. The intent of this document is to specify the minimum criteria for the design, supply, installation, and commissioning of a Honeywell Pro-Watch Notifier Secondary Fire Interface 1.01 SUMMARY A. The Pro-Watch Notifier solution shall enable secondary monitoring of Notifier fire events and point status information from a Pro-Watch central command and control location through the Notifier BacNet IP gateway (BacNET-GW-3). The Pro-Watch Secondary Fire Interface is not Underwriters laboratories (UL 864) listed as a fire alarm control unit. It is designed to provide only secondary informative monitoring, and shall under no circumstance be used as a primary fire alarm monitoring solution. 1.02 REFERENCES A. Underwriters Laboratories Inc. (UL 864) B. Notifier BacNet-GW-3 manual and application engineering guide C. Pro-Watch HSDK user s manual 1.03 SYSTEM DESCRIPTION The Pro-Watch Notifier solution shall enable secondary monitoring of Notifier fire events and point status information from a Pro-Watch central command and control location through the Notifier BacNet IP gateway (BACnet-GW-3). The Pro-Watch Notifier solution shall support multi-node BACnet-GW-3 gateway configurations with more than one Notifier panel connected to the same gateway. The Pro-Watch Secondary Fire Interface is not Underwriters laboratories (UL 864) listed as a fire alarm control unit. It is designed to provide only secondary informative monitoring, and shall under no circumstance be used as a primary fire alarm monitoring solution.

1.04 SUBMITTALS A. General: Submittals shall be made in accordance with the conditions of the Contract and Submittal Procedures Section. B. Product Data: The following shall be provided: a. Technical datasheets b. A complete set of instruction manuals 1.05 QUALITY ASSURANCE 1.06 DELIVERY, STORAGE, AND HANDLING A. General: Delivery, storage, and handling of Pro-Watch Notifier Secondary Fire interface shall be in accordance with the manufacturer s recommendations. B. Ordering: The manufacturer s ordering instructions and lead-time requirements must be followed in order to avoid installation delays. C. Delivery: Pro-Watch Notifier Secondary Fire interface shall be delivered in the manufacturer s original, unopened, and undamaged electronic delivery package (soft delivery). 1.07 PROJECT CONDITIONS 1.08 SEQUENCING 1.09 SCHEDULING 1.10 MAINTENANCE A. Preventive Maintenance Agreement during Warranty: As a separate price item, the Contractor shall provide preventive maintenance during the warranty period. Maintenance shall include, but not be limited to: a. Labor and materials, at no additional cost, to repair Pro-Watch Notifier Secondary interface. b. Labor and materials, at no extra cost, to provide test and adjustments to Pro-Watch HSDK Secondary Notifier interface. c. Regular inspections. B. Service Support agreement: The Pro-Watch Notifier Secondary fire interface shall only be available to end-user with a software support agreement. A service support agreement line item shall be included for each Pro-Watch Notifier Secondary fire interface (SSAPWNOTI). The Pro-Watch Notifier Secondary Fire support agreement shall entitle the user to receive Pro-Watch Notifier Secondary Fire interface software updates and fixes for a period of one year.

1.11 TRAINING A. System Administrator and Operator training shall be conducted for a minimum of one training session, at the end user s site. B. Training shall include, but not be limited to, Pro-Watch Notifier Secondary Fire administration, provisioning, configuration, operation, and diagnostics. PART 2 PRODUCTS 2.01 SYSTEM COMPONENTS A. HSDK a. Manufacturer: Honeywell Security b. Part #: B. Notifier a. Manufacturer: Honeywell Life Safety b. Part #: BacNet-GW-3 C. Pro-Watch a. Manufacturer: Honeywell Security b. Part #: PWCE D. Pro-Watch Notifer Interface a. Manufacturer: Honeywell Security b. Part #: PWNOTI 2.02 SYSTEM OPERATION A. The Pro-Watch Notifier Secondary fire interface shall include, as a minimum, the following features/functions/specifications: Notifier BacNet/IP gateway (BacNet-GW-3) connectivity 1. Pro-Watch Notifier Secondary fire interface shall support BacNet/IP connectivity to the Notifier BacNet IP gateway (BacNet-GW-3) via standard BacNet/IP. Any and all configurations to the Notifier BacNet/IP gateway (BacNet-GW-3) shall be undertaken by a qualified Notifier dealer under and in compliance with Notifier certifications and best practices.

2. The BacNET-GW-3 Notifier gateway shall be configured in BacNET multi-state point configuration. If necessary, an additional BacNET-GW- 3 gateway shall be deployed in multi-state point configuration. 3. Configuration of the BacNet IP gateway shall be undertaken by a qualified Notifier dealer for LAN and WAN configurations including BacNet/IP remote gateway support. 4. Configuration of the BacNet IP gateway shall be undertaken by a qualified Notifier dealer to publish BacNet compliant enumerated points containing alarm and status information for each published point. 5. Configuration of the BacNet IP gateway shall be undertaken by a qualified Notifier dealer to publish one or more Notifier panels through the Notifier BacNet IP gateway. Pro-Watch Notifier Secondary fire BacNet/IP configuration tool 6. Pro-Watch Notifier Secondary fire interface shall support a maximum of one Notifier BacNet IP gateway (BacNet-GW-3) and up to 2,000 Notifier points per BacNet-GW-3 Notifier gateway 7. Pro-Watch Notifier Secondary fire interface shall include a configuration tool that enables a user to configure the Pro-Watch Notifier Secondary fire BacNet/IP client interface communications parameters including BacNet/IP Network number. The system administrator shall be responsible for assuring that the appropriate BacNet/IP ports are open and available. 8. Pro-Watch Notifier Secondary fire interface shall include a configuration tool that enables a user to monitor the BacNet/IP network status (up/down). Pro-Watch Notifier Secondary fire interface Notifier BacNet IP gateway (BacNet-GW-3) point discovery 9. Pro-Watch shall implement an authenticated graphical user interface accessible from the Pro-Watch HSDK application module interface or through web browser interface supporting java. Specifically, Internet Explorer or Firefox with Sun Java virtual machine support (including appropriate permissions). 10. Pro-Watch Notifier Secondary fire interface shall implement a BacNet/IP client capable of communicating to the Notifier BacNetIP gateway (BacNet-GW-3). 11. Pro-Watch Notifier Secondary fire interface shall implement a graphical tool to discover and add Notifier BacNet IP gateways in a LAN environment to the Pro-Watch Notifier Secondary fire interface. 12. Pro-Watch Notifier Secondary fire interface shall enable all added Notifier BacNet IP multi-state points to generate Pro-Watch events for normal, offnormal and fault.status transitions.

Pro-Watch Notifier Secondary fire interface Pro-Watch point discovery 13. Pro-Watch shall implement a graphical user interface that enables a user to add one or more Pro-Watch Notifier Secondary fire interfaces to a Pro- Watch system as a HSDK application module. 14. Pro-Watch shall implement a Pro-Watch channel for each Pro-Watch Notifier Secondary fire interface mechanism 15. Pro-Watch shall implement a panel for each Pro-Watch Notifier Secondary fire interface 16. Pro-Watch shall implement a Pro-Watch HSDK application module interface for each Pro-Watch Notifier Secondary fire interface. 17. Pro-Watch HSDK application module shall implement a mechanism to graphically import selected Notifier fire points from a Pro-Watch Notifier Secondary fire interface (obix tree) as Pro-Watch obix input points (read only). 18. Pro-Watch obix points shall support Pro-Watch standard store procedures and video integration capabilities including the Pro-Watch video manager integration tab. 19. Pro-Watch HSDK application module shall implement a mechanism to graphically subscribe/unsubscribe to the Pro-Watch Notifier Secondary fire interface (obix tree) to receive Pro-Watch Notifier fire point to normal, off-normal and fault status. 20. Pro-Watch HSDK application module shall implement a mechanism to view the Pro-Watch Notifier Secondary Fire graphical user interface from within Pro-Watch. Pro-Watch Notifier Secondary fire interface Licensing 21. Pro-Watch Notifier Secondary fire interface shall support a maximum of one Notifier BacNet IP gateway (BacNet-GW-3) and up to 2,000 Notifier points per BacNet-GW-3 gateway 22. Pro-Watch Notifier interface shall support 500 points in its base configuration expandable in 250 point increments up to a maximum of 2,000 Notifier points. PART 3 EXECUTION 3.01 PREPARATION A. Prior to installation, the Pro-Watch Notifier Secondary fire interface shall be configured and tested in accordance with the manufacturer s instructions.

3.02 INSTALLATION A. The Pro-Watch Notifier Secondary fire interface must be installed, programmed, and tested in accordance with the manufacturer s instructions. a. In order to ensure a complete, functional Pro-Watch Notifier Secondary fire interface for bidding purposes where information is not available from the Owner upon request, the worst-case condition shall be assumed. b. Interfaces shall be coordinated with the Owner s representative, where appropriate. c. All necessary backboxes, racks, connectors, supports, conduit, cable, and wire must be furnished and installed to provide a complete and reliable Pro-Watch Notifier Secondary fire interface installation. Exact location of all boxes, conduit, and wiring runs shall be presented to the Owner for approval in advance of any installation. B. Any and all configurations to the Notifier BacNet/IP gateway (BacNet-GW-3) shall be undertaken by a qualified Notifier dealer under and in compliance with Notifier certifications and best practices. 3.03 TESTING AND CERTIFICATION A. The Contractor shall demonstrate the functionality of Pro-Watch Notifier Secondary Fire Interface upon completion of installation, documenting the result of all tests and providing these results to the Owner. Pro-Watch Notifier Secondary Fire Interface shall be tested in accordance with the following: a. The Contractor shall conduct a complete inspection and test of all installed Pro-Watch Notifier Secondary Fire Interface equipment. This includes testing and verifying operation with connected equipment. b. The Contractor shall provide staff to test all devices and all operational features of the system for witness by the Owner s representative and the authority having jurisdiction. All testing must be witnessed by the Owner s representative prior to acceptance. c. The testing and certification shall take place as follows: i. Pro-Watch Notifier Secondary Fire Interface shall be tested in conjunction with the manufacturer s representative. ii. All deficiencies noted in the above test shall be corrected. iii. Test results shall be submitted to the consultant or Owner s representative. iv. The test and correction of any deficiencies shall be witnessed by the Owner s representative and noted. v. The Owner s representative shall accept the system. vi. The system shall be witnessed by the authority having jurisdiction. Any deficiencies noted during the testing must be corrected. The Pro-Watch Secondary Fire Interface is not Underwriters laboratories (UL 864) listed as a fire alarm control unit. It is

designed to provide only secondary informative monitoring. It shall under no circumstance be used in life safety applications. d. A letter of certification shall be provided to indicate that the tests have been performed, and all equipments are operational. END OF SECTION