Installation and Commissioning Instructions

Similar documents
Installation and Commissioning Instructions FMU3 Floor Mixing Unit with Grundfos UPM3 Pump

Technical Product Guide

50/60 Hz. ecocirc BASIC Series WET ROTOR CIRCULATORS FOR HEATING, COOLING AND SANITARY SYSTEMS. ErP 2009/125/EC

Lowara ecocirc and ecocirc PREMIUM THE NEW HIGHLY EFFICIENT CIRCULATORS WITH THE PATENTED ANTI-BLOCK-TECHNOLOGY

Manifolds Controls Pipes Accessories

Lowara ecocirc and ecocirc PREMIUM

Lowara ecocirc and ecocirc PREMIUM

Mercury Mixing Kit (Code: ME1053)

Case Study - Yardley Park Road Gerpex MLCP and Press Fit System, Underfloor Heating and Manifold Based Sanitary Systems

CALEFFI. Thermostatic regulating unit for heating systems. 166 series 01238/17 GB. replaces dp 01238/15 GB. Function

Method Statement. General Site preparation by others: Preparation for screed system by others: Preparation for plate system by others:

Systems for central heating

M07. Wunda Premium Manifold. Before you start: Check the contents THE BRAND YOU CAN TRUST

Metering systems 0548EN April 2014

Standard. thermostatic valve body without presetting

APPLICATIONS. For the accelerated circulation of hot water in heating circuits with duty point optimisation

regulux Radiator lockshield with drain-off facility Pressurisation & Water Quality Balancing & control thermostatic control engineering ADVANTAge

INSTRUCTIONS REHAU PRO-BALANCE MIXING MODULE

WARM WATER UNDERFLOOR HEATING SYSTEMS. Guidance Notes

THERMOSTATIC SINGLE-PIPE AND DOUBLE-PIPE VALVES

Thermostatic valves with radiator connection systems

CONNECTION OPTIONS FOR MANIFOLDS & CONTROL UNITS

PRIUX HOME D. High-efficiency double circulating pumps Heating Air conditioning 50 Hz OPERATING RANGE APPLICATIONS BENEFITS

thermostatic valve body with stepless precision presetting

Function series Thermo-electric actuator electric supply 230 V (ac) or 24 V (ac/dc)

Convertible radiator valve for one-pipe systems, centre distance 35 mm

Calypso exact. Thermostatic Radiator Valves With stepless precision presetting

Design-Edition. Design-Edition Thermostatic valves and lockshields, sets

E-Z Valve. Thermostatic valves with radiator connection systems For single and two-pipe heating systems

CONTROL UNIT FOR UNDERFLOOR HEATING SYSTEMS

Affordable efficiency!

V-exact II. Thermostatic Radiator Valves Thermostatic valve body with stepless precision presetting

Forced draught gas burner

Regulux. Radiator lockshield with drain-off facility. To be precise.

Regulux. Return Lockshield Radiator lockshield with consistent presetting and drain-off facility

4-way valve with thermostatic option with variable centre distance and pre-adjustment for Single pipe and Dual pipe systems.

Thermomix Underfloor Heating Control Pack

Deluge Shower Mixing Valve 10045CP

Technical Helpline. Installation Manual. WHS-M-S3-Series Manifolds. Hydronic Heating System

CALEFFI. Set point thermostatic regulating unit. 182 series 01190/18 GB. replaces dp 01190/15 GB

Synergy Grill User & Engineer Installation & Conversion Guide

Inta City Shower Mixing Valve CT20010CP

ACCREDITED. Product range Code A2L Pre-assembled set point temperature regulating unit with manifolds and box, with UPM3 Auto L pump

HIGH POWER. VICTRIX PRO 2 ErP. High power, wall-hung condensation boiler

Flush individual room control for floor heating systems

THERMOSTATIC RADIATOR VALVES FOR IRON, COPPER, POLYETHYLENE AND MULTILAYER PIPE PRODUCTION RANGE IRON PIPE CODE CONNECTION

External Module Floor Standing Condensing Oil Boiler Range ADDENDUM ATTENTION INSTALLERS - UPDATED INFORMATION!

MK 8706 / MB 8706 CONCEALED THERMOSTATIC SHOWER VALVE INSTALLATION GUIDE

TA-COMFORT-S. Prefabricated units Heating interface unit for surface heating and hot water services

TEMPRA. Wall Mounted Fan Flue System boiler. Wall mounted fanned flue boiler INSTALLATION AND USE INSTRUCTIONS. Appr. nr. B A - CE 0063 AQ 2150

Enzo Safe Touch Thermostatic Shower EZ20011CP & EZ20012CP

Calypso TRV-3. (for the Nordic countries) Thermostatic radiator valves With presetting

Multibox. Floor Heating Controller Flush individual room control for floor heating systems

Utility and Utility System Floor Standing Condensing Oil Boiler Range ADDENDUM ATTENTION INSTALLERS - UPDATED INFORMATION!

Multibox 4. Floor Heating Controller Flush individual room control for floor heating systems with supply shut-off

Product range Code HE1 Connection and energy management compact unit without anti-condensation valve

For reversed flow direction. Thermostatic Radiator Valves Thermostatic valve body with and without presetting

CASSETTE UNIT. Comfort Circle

Vortex 15/21 Utility and Outdoor Module Vortex Combi 21 and Outdoor Vortex Combi 21

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

MIX2 - MIX3 MIX2 MIX3 COMPONENTS DESCRIPTION DIMENSIONS

Forced draught gas burner

MAINTENANCE AND SERVICE GUIDE

Standard. Thermostatic Radiator Valves Thermostatic valve body without presetting

LK Electric Boiler - 4,5

GRUNDFOS DATA BOOKLET. Grundfos COMFORT. Circulator pumps. 50/60 Hz

High-efficiency circulating pumps Heating Air conditioning 50 Hz

SATK50-60 series CONTENTS. Recess Mounted Heat Interface Unit - SATK series INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE

Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16)

Powerstock Storage Tank

INSTALLATION AND MANINTENANCE INSTRUCTIONS

Euromixer Thermostatic Mixing Valves

CALEFFI. SATK wall-mounted heat interface unit Fitted for connection to DHW storage. SATK40 series 01216/14 GB

Thermostatic valve bodies

STREAMLINE OVERSINK. Fitting Instructions and User Guide _iss_05.indd 1 15/09/ :46:30

INSTALLATION AND OPERATING INSTRUCTIONS GN2. HIGH EFFICIENCY CAST IRON BOILER FOR LIQUID and/or GAS FUELS

Compact. Installation & Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER

Stainless steel range of condensing boilers. Designed to meet carbon reduction targets. Lifetime service and support. Outputs from 50kW to 660kW

Standard. Thermostatic Radiator Valves Thermostatic valve body without presetting

R557R EN January 2012

Underfloor Heating Control Pack

PRE-ASSEMBLED MANIFOLD FOR HEATING SYSTEMS WITH THERMOSTATIC MIXING

ecocirc E1 Domestic hot water / Sanitary pumps Unequalled economically! Only 8 Watt!

Closomat Lima Vita installation & user guide

The New Caroma TMV20

HERZ-DR-T-90. Radiator Control Valves with Pre-Setting Function by Means of Double Cone, Suitable for Conversion to Thermostatic Operation. H max.

Dynalux. Floor Heating Manifolds Underfl oor heating circuit manifold

Installation and Operation Instructions K36E Modular Heating Circuit - DN 25 Boiler charging set

SERVICE MANUAL. Bradford White ElectriFLEX HD (Heavy Duty) Commercial Electric Water Heater CEHD SERIES Immersion Thermostat Models

Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16)

Compact HE. High efficiency combi boiler. Installation & Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER

AVTI Multifunctional self - acting controller

TRV pack Eclipse. Thermostatic valves with radiator connection systems Thermostatic raditor valve with automatic flow control, head and lockshield

Mikrotherm. Manual Radiator Valves With presetting

Aluminium range of condensing boilers. Works every time. Designed to meet carbon reduction targets. Lifetime service and support

OPERATING MANUAL MODEL AIR 1500TM AIR DRYER

Mikrofill Ethos Condensing combination boiler

LOW SURFACE TEMPERATURE RADIATORS

Eliminator TotalGuard Installation Manual

BAXI BOSTON ALL MODELS FLOOR STANDING OPEN FLUE (OF) CENTRAL HEATING BOILERS INSTALLATION AND SERVICING INSTRUCTIONS. GAS TYPE G20 (Natural Gas)

Transcription:

Installation and Commissioning Instructions FMU Floor Mixing Unit with Lowara Ecocirc Class A Pump Pre-assembled TM Thermostatic Mixing Control Group and manifold with either lockshields or flowmeters, available from to ways Thermostatic mixing valve with remote sensor for accurate control of flow temperature Easy to use thermostatic head with temperature locking feature Flow increase valve to increase flow rate for larger manifolds / heat outputs Adjustable temperature range from o C to o C making it suitable for screed drying Lowara Ecocirc Class A pump with unique anti-block operation. ErP compliant Built-in non-return valve to aid filling during commissioning Built -in automatic air-vent Built-in temperature gauge male close coupled primary flow and return connections male manifold connections with union for fast assembly / removal Optional ball valve set for fitting to M primary connections Valve body kv range:..8 For more information please call us on 99 89 or view our website at www.emmeti.co.uk

. Construction 9 8 Fig. Primary return Primary flow mm L =. Underfloor heating manifold flow rail fitted with either flowmeters or lockshields. Underfloor heating manifold return rail designed to be fitted with electrothermic heads. Manifold mounting bracket - mm. TM mixing group mounting bracket - mm. Mixing valve body with Mx. thread for fixing the thermostatic head, supplied separately. Flow increase valve (thermostatic model only). Lowara Ecocirc -/ circulating pump 8. Thermostatic sensor phial located in pocket 9. Mixed flow temperature gauge, o C to 8 o C. Automatic air vent. Mixing valve thermostatic head with remote sensor, adjustable from o C to o C with M x. securing ring. Non-return valve. Fill and drain valves. Primary flow connection, BSP. Primary return connection, BSP For more information please call us on 99 89 or view our website at www.emmeti.co.uk

. Operation The FMU Floor Mixing Unit offers a time saving pre-assembled mixing unit and manifold. At its heart is the TM Thermostatic Mixing Control Group which has an Emmeti designed mixing valve to ensure accurate temperature control of underfloor heating. The unique design of the internal mixing valve components ensures that hot water from the heat source and return water from the underfloor circuit are mixed together in the valve body to produce a range of temperatures from o C to o C. This range of temperatures suits the whole field of underfloor heating applications, from commissioning new floor screeds to operating with very thick floor screeds in commercial applications. The illustrations below show how the mixing valve operates through its remote sensing thermostatic head: Calling for heat position Thermal to Mid-mix mechanical position actuator Satisfied position Calling for heat position Thermal to Mid-mix mechanical position actuator Satisfied position Initially the cool liquid in the remote sensing probe, allows almost all of the primary hot water from the heat source through the valve. Gradually the temperature of the probe rises as the underfloor circuits begin to warm up. Depending on the temperature setting of the thermostatic head, as the temperature of the probe rises, the shuttle starts to close off the primary hot water allowing return water to maintain the temperature set on the head, up to o C if required. Return Flow Calling for heat position Thermal to Mid-mix mechanical position actuator Satisfied position Return To pump Flow Return Flow Once the temperature set on the head has been reached at the probe, the shuttle balances the right amount of primary hot water and secondary return water to maintain this temperature. Depending on the thermostat setting, the hot water could be almost completely closed off allowing very low temperatures suitable for commissioning screed floors right down to o C if required. The thermostatic mixing valve has a flow increase valve which allows return water to flow directly into the mixed water outlet. This cools the mixed water temperature sensed by the remote phial and causes the mixing valve to open allowing more primary hot water through the mixing chamber and raises the temperature to the setting on the head. Cut-away / exploded view showing flow increase valve /mixing chamber The other part of this powerful combination is Emmeti s reliable, tried and tested underfloor heating manifold. Fitted with double regulating flowmeters or lockshields and electrothermic valves, the manifold complements the TM thermostatic mixing unit to create the perfect combination for today s generation of underfloor heating systems For more information please call us on 99 89 or view our website at www.emmeti.co.uk

. Technical Data FMU Floor Mixing Unit Primary circuit maximum temperature: 9 C Maximum pressure: bar Primary circuit max ΔP: bar Secondary control range: (thermostatic regulation) C - C Heating capacity that can be exchanged at ΔT C, ΔP available. bar : Thermostatic regulation: kw by-pass pos. Thermostatic regulation:. kw by-pass pos. Climatic regulation:. kw Mixing valve pressure drop (thermostatic regulation) Kv Pressure drops with open bypass valve (thermostatic regulation) Kvmax.8 Thermometer scale: C - 8 C Mixing unit inlet connections: BSP male Manifold outlet connections: DN x 9tpi Lowara Ecocirc circulator connections: / BSP male union Lowara Ecocirc -/ Motor design: Max. system pressure Electric connection Power consumption Electronically commutated, shaftless spherical motor design with permanent magnetic rotor bar Volt, / Hertz Models Ecocirc -: - Watt Accepted liquids Heating water VDI Water/Glycol mixtures Magnetite resistance Anti-Block Technology Accepted temperature range - C** to + C Energy efficiency EEI,, ErP ready Motor protection class IP Insulation class F Power cable length m Ecocirc Dimensions G / G / G / G / mm mm mm mm mm mm mm mm For more information please call us on 99 89 or view our website at www.emmeti.co.uk

. Installation. Installing the FMU Floor Mixing Unit The FMU Floor Mixing Unit can be installed directly on the wall or a suitable mounting board by securing its brackets with suitable fixings (depending on the kind of wall). These need to be inserted into the designated holes shown or in an Emmeti manifold cabinet suitable for mm minimum depth partitions. Where the FMU unit is to be wall-mounted, then the mounting surface should be flat and vertical. The space necessary for the FMU can be determined from the table and drawing below. Ensure that there is room for the isolating valves and fittings below the mixing unit inlet connections and leave at least mm from the lower manifold rail to the floor to prevent damage to the pipes where they enter the floor. The mounting bracket holes can be used to mark the fixing positions and the mixing unit and manifold assembly screwed to the wall/ mounting surface using suitable fixings ensuring that the assembly is level. The pump should be turned to face forwards to avoid fouling the wall/ mounting surface Where the FMU mixing unit is to be mounted in a cabinet, check the overall dimensions of the FMU Floor Mixing Unit using the table and drawing below. Type ways ways ways ways ways ways 8 ways 9 ways ways ways ways L mm mm L Minimum mm Fig. Secure the mixing unit and manifold assembly inside the cabinet. Ensure that there is room for the isolating valves and fittings below the mixing unit inlet connections and leave at least mm from the lower manifold rail to the floor to prevent damage to the pipes where they enter the floor. Emmeti cabinets have movable internal mounting rails which allow the pump to be turned sideways to minimise the depth (see Fig. Page and Fig. ) and enable the assembly to fit inside the cabinet. For more information please call us on 99 89 or view our website at www.emmeti.co.uk

the power cable. To make it easier to mount, use a mm hex key to turn the indicator on the servomotor s head from to. Re-connect the power cable when you have completed the step. To install the delivery temperature probe to the floor-mounted system, insert the probe in the probe-holder well (ref. Fig. A). Installation & Commissioning Instructions. Installation. Installing the FMU Floor Mixing Unit Minimum mm Adjust the cabinet feet with the wing screws at each side, so that there is at least mm between the lower manifold rail and the floor. See Fig.. Fig. Secure the casing to the wall with suitable fixings and fill any gaps around the case with cement mortar or other suitable filler. A cardboard protector is provided with Emmeti cabinets to prevent the mortar entering the case. Connect the flow and return pipes for the underfloor heating system circuits with a Monoblocco connector selected from the Emmeti range for the type of pipe being installed.. Installation of the thermostatic head and remote sensor for thermostatic regulation For thermostatic regulation, a thermostatic head, supplied as a separate item, code 9, must be used. Set the thermostatic head to the maximum setting then position the head on the thermostatic valve body (see Fig., item ) with the index marker facing to the front. Then attach the head to the valve body using the securing ring on the head, tightening the ring lightly: do not over tighten.. Installation of the electric box with safety thermostat or T standard control unit. The Electrical power supply Connections of a circulator of a low-temperature circuit/system must This always allows be the controlled connection by a safety of the thermostat mains power to provide supply, protection from thermostats delivery temperature and actuators values with above electrical / C. interlock terminals for the boiler and manifold pump as required by Building On the TM mixing unit install the electric box with the safety thermostat Regulations. Full instructions are provided with all four items. for the circulator s cabling or the T standard control unit for electrothermal heads. Fix them onto the wall with plugs and screws using the Please ensure that the electrical wiring of the installation and connections designated to pre-drilled and from profile electrical located system at the back components of both of them are (Fig. in B). accordance with BS, the latest edition of the IET Wiring Regulations. High limit thermostat, code: 8 Wall Mounting - Install the high limit thermostat adjacent to the FMU manifold where the thermostat phial can be trapped between the rubber mounting Pre-drilled pad in the profile support bracket and the surface of the flow manifold, fixing it to the wall with suitable fixings. Cabinet mounting - Where the FMU manifold is installed in an Emmeti manifold cabinet, install the thermostat in the enclosure Fig. B above or to the side of the manifold assembly. Make the electrical connections to the thermostat as shown in the installation leaflet. Maximum suggested thermostat setting: / C for cement slabs; for other materials refer to the maximum values as stated by the supplier, and not more than C (EN -). EWC- wiring centre, codes: U9, U9 EWC- wiring centre, codes: U9, U9 Wall mounting Install the wiring centre adjacent to the FMU manifold so that the electrical cables from the electrothermic heads can reach the wiring centre, ideally on the lower face of the centre, then fix the centre to the wall using the fixings. Cabinet mounting where the FMU manifold is installed in an Emmeti manifold cabinet, the wiring centre can be installed above or to one side of the manifold providing all electrothermic head cables can reach the centre. Make the electrical connections to the centre as shown in the installation leaflet. Take extra care to ensure that EWC- manifolds are kept away from water.. Electrical Connections The Domestic Building Services Compliance Guide recommends the use of a separate flow temperature high limit thermostat for systems connected to a high temperature water supply (i.e. more than o C) to ensure that the water temperature in an underfloor heating system does not rise above the temperature recommended for the floor. Emmeti UK offer a thermostat for this purpose, code: 8. Emmeti UK also offer EWC- and EWC- wiring centres designed specifically for the connection of electrical components in underfloor heating systems: Code U9 EWC- V 8-way wiring centre with on-off switch Code U9 EWC- V 8-way wiring centre with on-off switch Code U9 EWC- v 8-way wiring centre Code U9 EWC- v -way wiring centre. Hydraulic Connections Connect the flow and return pipes to the G male inlet connections on the mixing unit. Emmeti recommend installing a suitable isolating valve for connection to the G inlet connections: - Code 8, ¾ F x F union, pair with red and blue butterfly handles (no gaskets) - Code R, F x F union, pair with red and blue butterfly handles The use of jointing paste and hemp or similar sealing materials is not recommended as this may interfere with the correct operation of the mixing valve and manifold. For more information please call us on 99 89 or view our website at www.emmeti.co.uk

. Commissioning. Filling and Testing The FMU Mixer Control Group has a built-in non return valve to ensure that the underfloor heating circuits can be simply filled from the drain and fill valves fitted to Emmeti manifolds. To use the non-return valve the underfloor heating circuits must be filled using the drain and fill valve fitted to the upper rail only it will not work if the lower drain and fill valve is used to fill the circuits see Fig.. (The FMU manifold is shown but the Topway T manifold is filled in the same way).. Lowara Ecocirc -/ The pump is supplied with a pre-connected m long -core lead assembly ready for connection to the electrical controls system which should include a suitable switched fused isolator. Ecocirc.../ Once the pump has SERIES been connected to the electrical controls system, ensure that it is filled and vented, then operate SINGLE-PHASE the controls system to call OPERA for heat and select the desired Ecocirc pump -/ setting Ecocirc using -/8 the knob shown below in Fig.. Proportional Pressure Mode SINGLE-PHASE OPERATING CHARACTERISTI Ecocirc -/ Ecocirc -/8 Ecocirc -/ H [m] 8 Q [US gpm] EN - 8 Q [Imp gpm] H [ft] H [kpa] Ecocirc -/ Ecocirc -/ Ecocirc -/ H [m] Ec Ec Ecocirc.../ SERIES SINGLE-PHASE OPERATING TING CHARACTERISTIC Ecocirc -/ Ecocirc -/8 Ecocirc -/ Ecocirc -/8 Ecocirc -/ The control group, manifold and underfloor circuits can now be filled and commissioned in accordance with the manifold instructions. Prior to filling, a final check of all joints should be made to ensure no connections have loosened during transit (For details of the recommended commissioning procedure please refer to the Emmeti literature for the manifold). Emmeti manifolds are provided with double regulating valves supplied fitted with either lockshields or flowmeters as standard. We recommend filling each circuit separately, opening the relative valves and double regulating valves each time and closing them again when the operation is completed. Once filled the system should be pressure tested in accordance with EN. P [W] H [m] 8 Q [Imp gpm] 8 Q [US gpm]. Lowara Ecocirc -/.......Q [m /h]......8 TING CHARACTERISTICS EN - Q [l/s] H [ft] H [kpa] 98_D_CH Ecocirc -/ Ecocirc -/8 Ecocirc -/ Ecocirc -/8 Ecocirc -/ P [W] Constant Speed Mode 8 Q [US gpm] H [m] 8 Q [Imp gpm].......q [m /h]......8 Q [l/s] These performances are valid for liquids with density ρ =. Kg/dm and kinematic viscosity ν = mm /sec. Pump operates steplessly. Lines correspond to knob settings and are for reference only. HYDRAULIC PERFORMANCE TABLE (CONSTANT SPEED) P [W] EN - 98_D_CH P [W].... PUMP POWER SPEED TYPE ABSORBED l/s,,, EEI MIN MAX m /h,,, V Hz W W H = TOTAL HE Ecocirc -/,* min,,,, Ecocirc -/, Ecocirc -/, Ecocirc -/8, max,9,,, Ecocirc. -/8...,.. Q [m. /h]. Performances. according. to standards. EN -..8 * ErP Q [l/s] ready (PROPORTIONAL PRESSURE) SURE) These performances are valid for liquids with density ρ =. Kg/dm and kinematic viscosity ν = mm /sec. Pump operates steplessly. Lines correspond to knob settings and are for reference only. Operating knob PUMP POWER CURRENT SPEED HYDRAULIC PERFORMANCE TABLE with LED TYPE ABSORBED ABSORBED l/s,, EEI (CONSTANT SPEED) MIN MAX MIN MAX m/h,, PUMP POWER SPEED V Hz Q = DELIVERY W W A A H = TOTA TYPE ABSORBED l/s,,,,,,,,9,89 EEI Ecocirc -/,* MIN MAX m /h,,,,8,,,,,min,,, Ecocirc -/, V Hz W W H = TOTAL HEAD METRES COLUMN OF WATER Ecocirc -/,,9, Ecocirc -/,* Ecocirc -/8, min,,,,,, Ecocirc -/, max,8,9,8 Ecocirc -/8, Ecocirc -/, Performances according to standards EN - * ErP ready Fig. Lowara Ecocirc Ecocirc -/8 pump operating, knob max,9 "The, benchmark,for most, efficient, circulators, is EEI,.",,,,9 Ecocirc -/8, H [ft] H [kpa] 98_D_CH Performances according to standards EN - * ErP ready ecocirc-c--en_a_th For more (PROPORTIONAL information please call PRESSURE) us on SURE) 99 89 or view our website at www.emmeti.co.uk PUMP POWER CURRENT SPEED Q = DELIVERY TYPE ABSORBED ABSORBED l/s,,,,,8,,,9,8 8

. Commissioning. Lowara Ecocirc -/ The pump has two operating modes:. Proportional pressure where the pump automatically reduces its speed where lower flow is required, saving energy. Constant speed - where the pump maintains the same speed regardless of the flow. To change between the two modes, turn the knob fully anticlockwise and then back to the chosen setting (between and ) within seconds. The LED in the knob will change colour to indicate which operating mode has been selected: White constant speed Blue proportional pressure The graphs on the previous page show the seven settings available in each operating mode to enable the pump to be set to give the correct flow to meet the designed heating load. In order to remove air from the pump, an air purge function can be selected by turning the knob fully anticlockwise, waiting for at least five seconds, then turning the knob to the desired setting between and. The air purge cycle will then start and last about minutes before reverting to the chosen operating mode. The pump can also be set to standby if required by selecting the air purge cycle and then immediately turning the knob back fully anticlockwise again. The LED will give a steady light to show it is in standby mode.. Setting the Flow Increase Valve Δp [mbar] Mixing Perdite unit carico pressure gruppo drops miscelazione Fig. Kv= Kv=, Kv=,8 Kv=, Kv=, Kv=,8 Q [l/h] ΔTip = C T Boiler = C Tip = C ΔPip =, bar Capacity (W) Circulator Setting Valve Setting 8 maximum maximum - maximum maximum maximum average average average - average ΔTip = C T Boiler = C Tip = C ΔPip =, bar Capacity (W) Circulator Setting Valve Setting 9 maximum 8 maximum - maximum average average - average Fig. ΔTip temperature difference on UFH circuits TBoiler primary flow temperature Tip secondary flow temperature ΔPip underfloor circuit pressure drop 8 For more information please call us on 99 89 or view our website at www.emmeti.co.uk

. Commissioning. Setting the Flow Increase Valve Once the total flow rate of the system has been calculated: Qip = total underfloor system flow-rate = (P [W] x.8) / (ΔTip) Where P is the total calculated heat demand in Watts and ΔTip is the calculated temperature difference across the underfloor system the pressure drop for the mixing unit can be read off on the graph Fig.. The mixing unit pressure drop curves show the Flow Increase Valve settings from fully closed to fully open and allow the installer/ designer to choose a suitable flow rate and pressure drop to suit the system. Together with the calculated pressure drop of the underfloor system and manifold, the pump setting can then be chosen. The tables, Fig., show two examples of required system output against the Flow Increase Valve setting based on assumed values of underfloor flow temperature, temperature drop and pressure drop for the underfloor system for guidance. If necessary, adjust the Flow Increase Valve as follows: Excessively high temperature drop. Insufficient flow rate - gradually open the Valve until you reach the required temperature drop. Flow temperature below the required value. Gradually close the Valve until the required temperature is reached, allowing time for the system temperature to stabilise.. Double regulating lockshield adjustment The following commissioning instructions show separately the different procedures for setting up the designed flow rate using either lockshields or flowmeters.. Setting the thermostatic head Once the system has been filled and pressure tested, the individual underfloor circuits can be balanced. As part of this process the mixed flow temperature must be adjusted to the correct level for the system design. To achieve this, the thermostatic mixing valve can be set on the thermostatic head (ref. no., Fig. ), from to C as follows:. Turn the knob of the thermostatic head, to set the required underfloor flow temperature. Allow sufficient time for the temperature to stabilise, then check the setting against the temperature reading on the mixed flow temperature gauge fitted to the control group (ref. no. 9, Fig. ). Temperature setting lock The thermostatic head is provided with two setting pins, one red and the other blue. These pins are provided to lock the temperature setting as follows:. Set the required temperature as described above. Locate the black dot - see Fig. 8 - and insert one pin on each side of the dot. The head can not now be rotated. black dot setting pins black dot Emmeti have evolved a new and superior lockshield design. This allows easier, quicker and more accurate onsite setting of the correct flow. It is more accurate at maintaining the correct low flow,when set to a small aperture. This lockshield can be upgraded on site to become an integrated flowmeter and lockshield. How to balance using the lockshield: Remove the red cover. The black plastic assembly underneath has an inner sleeve, and an outer sleeve. The outer sleeve is used for isolating the valve, actuated using the impression in the top of the red cover.the inner sleeve is used to balance the circuit, increasing or decreasing the flow by using a mm Allen key, placed in the hexagon recess in the centre.the valve is supplied in the fully isolated position (flow is closed). First fully open the circuit. Turn the red cover over and using the top, turn the outer (isolating) sleeve anticlockwise, until the circuit is fully open, rotate until you feel steady resistance, then stop. Then rotate back half a turn. To verify, you will have seen the black plastic assembly rising. Then, using the mm Allen key placed in the hexagon recess, rotate the inner (balancing) sleeve clockwise. To verify you will have seen the inner sleeve falling. Rotate until you feel a strong resistance, then stop. Rotate back half a turn. The lockshield is now ready for flow setting. NOTE:Make sure you do not leave the inner (balancing) sleeve in the fully open position, back it off half a turn to be sure the o-ring is not stressed. Fig. 8 For more information please call us on 99 89 or view our website at www.emmeti.co.uk 9

. Commissioning. Double regulating lockshield adjustment Using the graphs below you can calculate the number of turns required to reach your chosen flow rate. Now start to open the inner (balancing) sleeve anticlockwise, by the number of turns you have calculated. Then stop. It is now set. Replace the red cover. To prevent tampering, you can seal the red cover into position, using wire and a lead seal, making use of the holes in fins on the red cover. Calculation methods: How to calculate the Δp pressure drop with a l/h Q water delivery capacity determined by the valve and lockshield, with, turns opening of the inner (balancing) sleeve. Method: Use the pressure drop diagram see Fig. 9 below Q = l/h Δp = mbar where Kv stands for Q theflow rate in m /h corresponding to Δp equalling bar: Kv = Q /Δp The relationship between Δp (bar) and Q (m /h) is as follows: Δp = Q / Kv Fig. 9 TA = All open. The above values refer to water temperature C. Δp = Δp one way + Δp return; = no. of turns for opening adjustment device Method: Use the Kv diagram, see Fig. below Kv =.98 Q =. m /h p =./.98 =. bar Fig. p (mbar) Kv values (lockshield), Kv,8,,, Flow rate (l/h),,, T. A. Kv=, Kv=, Kv=, Kv=, Kv=, Kv=, 8 Kv=,,,, Lockshield adjustment screw: nr. turns. Double regulating flowmeter adjustment Combined Flow regulator and flow meter Red Collar 9mm black spanner flats Range of measurement - l/min Maximum operating pressure bars Max. operating temperature 9 C Kv =. ( l/min) -. ( l/min) Kv max off scale =.9 Precision ±% fs fs= Bottom of scale Flowmeter tube Fig. Fig. Fig. How to balance the circuits using flowmeters Flowmeters have a double regulating function i.e. they not only adjust water flow but also include an isolating function which can be opened and closed without affecting the flow setting. The flowmeter has an inner combined flow regulator and flowmeter, see Fig., and an outer red collar. The red collar, (). is used for isolating the valve. The inner regulator is used to set the flow in the circuit, increasing or decreasing the flow by using the 9 mm spanner flats provided, see Fig.. The change in flow can be read in the scale on the flowmeter tube. The valve is supplied in the fully closed position. First open the isolating valve following the instructions below: Turn the red collar anticlockwise approximately three and a half turns. You will see the whole of the flowmeter rotating and rising. If the valve is over-rotated - more than three and a half turns - then the internal plastic threads can become damaged and cause leaks. If you reach the positive stop please rotate back half a turn. You are now ready to use the flow regulating function. Lower the red collar until it touches the manifold (). Then using a 9mm spanner, or your fingers, adjust the flow using the black spanner flats at the bottom of the flowmeter (). You can read the required flow in litres per minute directly from the red indicator against the scale in the clear flow meter tube. When you have set the required flow rate, raise the red collar () again, until it is engaged against the black spanner flats at the bottom of the flowmeter (), see Fig.. You can seal the red collar into position, using wire and a lead seal, using the two holes in the red collar () - Fig. or product code red circuit indicator bands. Please see our website at www.emmeti.co.uk/products/ manifold-acccessories/spares-and-upgrade-kits. Cleaning the flowmeter tube Turn the red collar () clockwise, until the isolating function is fully closed. Remove the flowmeter tube by securing the black spanner flats, then using either hand pressure or a mm ring spanner, gently unscrew the flowmeter tube anticlockwise. Clean the tube and screw it back on. Turn the red collar () anticlockwise until the isolating valve is fully open again. For more information please call us on 99 89 or view our website at www.emmeti.co.uk

. Commissioning. Double regulating flowmeter adjustment Flowmeter pressure drop vs flow rate p [mbar] Kv=,, Kv=, Kv=,, Kv=,8 Kv=,9, Kv=, Kv=,9, Kv=, TA Kv=, Flow rate (l/h) TA no. of turns for opening the flow regulator = Fully open. The above values refer to water temperature at C.; For more information please call us on 99 89 or view our website at www.emmeti.co.uk

Emmeti UK Tannery Yard Witney Street Burford Oxfordshire OX8 DW T + () 99 89 F + () 99 899 W www.emmeti.co.uk E sales@emmeti.co.uk For more information please call us on 99 89 or view our website at www.emmeti.co.uk