Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.

Similar documents
Building Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2

Life Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved

Agency for Health Care Administration

Public. Mike Free Health. State of Alabama Department of

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6

Public Health Fax: Web Site:

3/6/2018. Design Tips For Fire and Smoke Barriers. Professional Development Hours (PDH) Certificates. Copyright Materials

Defend In Place 2012 IFC Overview of Institutional Occupancies

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

Common Building Code Misinterpretations

E25 (D) Automatic controls for general means of egress lighting

Agency for Health Care Administration

FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway. AIA Healthcare Group

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011

CHAPTER 7 ALTERATIONS LEVEL

FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

<< COMPANY LETTERHEAD >>

Agency for Health Care Administration

Are there any policies regarding outlets that contain USB ports?

Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com

Part 3 BUILDING CODE MYTHS & INTERPRETATIONS

Agency for Health Care Administration

Report on First Revisions with Statement June 2014 NFPA 101

First Revision No NFPA [ Section No ]

Agency for Health Care Administration

Life Safety Crosswalk

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS

Chapter 2: Definitions

Top (15) Life Safety Code Deficiencies and Tips for Compliance (10/01/2011 thru 02/22/2012)

Report on First Revisions with Statement June 2014 NFPA 101

FIRE/SMOKE BARRIER FUNDAMENTALS

PRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING

Fire & Life Safety Code Compliance. Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities

Emergency Planning for Institutional Facilities

Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services

Agency for Health Care Administration

Accreditation Program: Hospital

Changes to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates

City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION GUIDELINE RESIDENTIAL CARE FACILITIES 2007 CBC/CFC (R-3.1)

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

FIRE AND SAFETY PROJECT REVIEW REPORT

2000 to 2012 Hospital K-tag crosswalk matrix for hospitals 2000 Tag #

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen

YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS

Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4

The Physical Environment Portal: Module 5, LS Leadership

NFPA 101 Life Safety Code Culture change 2012

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES

AHC Meeting #7 July 12-13, Occupancy WG Report

BCBC 2012 CHANGES TO PART 3

Residential Care Facilities Requirements

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS

2007 CBC & CFC Residential Care Facility Requirements (24 hour care only)

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

Agency for Health Care Administration

Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA

Chapter Nursing Homes

Chapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work.

Agency for Health Care Administration

NFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering

Agency for Health Care Administration

January 1, 2014 Mandatory Effective Date

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

NORTH CAROLINA. Downloaded (l) For each nursing unit, or fraction thereof on each floor, the following shall be provided:

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

10/28/2015. Enjoy Your TJC Survey. Bill H. McCully CHFM SASHE. Senior Consultant MSL Healthcare Partners. MSL Healthcare Partners, 2015 PREPARATION

PERFORMANCE COMPLIANCE METHODS

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)

SAF-BCF SECOND REVISIONS WITH STATEMENTS

New Facilities. Minimum Requirements

Agency for Health Care Administration

COMPLIANCE ALTERNATIVES

COMPLIANCE ALTERNATIVES

For the Florida Building Commission And the Fire Code Advisory Council

PERFORMANCE COMPLIANCE METHODS

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

K SURVEY FOR DATE OF PLAN APPROVAL SURVEY UNDER

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1

AHC MEETING #4 PART I ROUND 1 ISSUES CODE CHANGES

Tennessee Department of Health Bureau of Health Licensure and Regulations Division of Health Care Facilities

PERFORMANCE COMPLIANCE METHODS

Barrier Management- Defending the Safety of Patients, Visitors, & Staff

Interim Amendments to Ontario s 2012 Building Code Retirement Homes. August 17, 2017

AD HOC HEALTHCARE COMMITTEE MEANS OF EGRESS WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B MOE COMMITTEE

Transcription:

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes

Comparing the Codes: NFPA 101 Life Safety Code (2000) (NFPA) International Building Code (2012) (IBC) Chicago Building Code (2012) (CBC)

Comparing the Codes: NFPA 101 Life Safety Code (2000) (NFPA) International Building Code (2012) (IBC) Chicago Building Code (2012) (CBC) In addition, don t forget: The Hospital Licensing Act (HLA) Guidelines for Design and Construction of Health Care Facilities (FGI)

Why do we need to do this?

Challenge Question: What is the REQUIRED rating for a corridor wall in NEW construction in a Hospital in the State of Illinois?

ANSWER: It Depends

Factors: Where is the facility Chicago needs to follow BOTH the Chicago Building Code (CBC)for local AND the 2000 NFPA 101 Life Safety Code (LSC) for IDPH/CMS/JCAHO or DNV. Outside Chicago MOST municipalities follow the International Building Code (IBC), PLUS you must use the 2000 NFPA 101 Life Safety Code (LSC) for IDPH/CMS/JCAHO or DNV. Beware of other local ordinances requiring other editions of NFPA or even local supplemental codes. ALWAYS use the most stringent requirement.

2000 NFPA 101: Section 18.3.6.2* for new construction (and facilities built or remodeled after March 2003) requires Corridor walls shall form a barrier to limit the transfer of smoke. Such walls shall be permitted to terminate at the ceiling where the ceiling is constructed to limit the transfer of smoke. No fire resistance rating is required for corridor walls. Section 18.3.6.3.1 Doors protecting corridor openings shall be constructed to resist the passage of smoke Door ratings for hazardous areas, stairs or other vertical openings must meet other required fire ratings.

2000 NFPA 101: For existing buildings, Section 19.3.6.2.1 requires Corridor walls shall be continuous from the floor to the underside of the floor or roof deck above, through any concealed spaces, such as those above suspended ceilings, and through interstitial structural and mechanical spaces, and they shall have a fire resistance rating of not less than ½ hour. Exception: for smoke compartments which are fully sprinklered, NFPA allows the partitions to terminate at the ceiling, similar to chapter 18. Section 19.3.6.3.1 requires that doors be substantial doors, such as those constructed of 1 ¾ (4.4-cm) thick, solid-bonded core wood or of construction that resists fire for not less than 20 minutes and shall be constructed to resist JENSEN the & HALSTEAD passage LTD. of smoke

International Building Code: Table 1018.1 Allows zero (0) fire rating of corridor walls in fully sprinklered buildings. Section 407.3 requires Corridor walls shall be constructed as smoke partitions in accordance with section 710. Section 710 allows the partition to terminate at the underside of the ceiling above where the ceiling membrane is constructed to limit the passage of smoke. Section 407.3.1 does not require the corridor doors to be rated except for those in a wall required to be rated by section 509.4.

Chicago Building Code: Section (13-80-030) (a) Requires that corridor walls be one (1) hour fire rated that the doors to only have a 20 Minute Fire Rating in a minimum 18 gage steel frame.

Chicago Building Code: Challenge Question: What is the exception for the one (1) hour fire rated corridor requirement in the Chicago Building code?

Chicago Building Code: The same section allows the partition to stop at the ceiling if the building is fully sprinklered INCLUDING THE CEILING SPACES.

Challenge Question: What is the difference between a SMOKE PARTITION and a SMOKE BARRIER?

Simple Answer: A Smoke Partition is an Assembly of Components that limits the passage of smoke. A Smoke Barrier is a rated partition that separates the building into compartments.

2000 NFPA 101: Smoke Partition NFPA uses the term barrier to limit the passage of smoke These types of partitions (such as corridor partitions) are allowed to stop at the ceiling. Section A18.3.6.2 An architectural, exposed, suspended-grid acoustical tile ceiling with penetrating items such as sprinkler piping and sprinklers; ducted HVAC supply and return-air diffusers; speakers; and recessed lighting fixtures is capable of limiting the transfer of smoke. Be careful which partitions that you stop at the ceilings. The HLA and FGI have requirements for sound transmission into patient rooms and other areas.

2000 NFPA 101: Smoke Barrier Where Required 18.3.7: To divide every story used by inpatients for sleeping or treatment into not less than two smoke compartments To divide every story having an occupant load of 50 or more persons, regardless of use, into not less than two smoke compartments. (Look at 18.3.7.1 Exceptions for items specific to NFPA) To limit the size of each smoke compartment required above into an area not exceeding 22,500 square feet. Limit the travel distance from any point to reach a door in the required smoke barrier to a distance not exceeding 200 feet.

2000 NFPA 101: For Smoke Barriers: Section 18.3.7.3 requires the smoke barrier to be constructed in accordance with section 8.3 and to have a fire resistance rating of not less than 1 hour. Section 18.7.5 requires that the doors in the smoke barrier be of 1 ¾ thick, solid-bonded wood core doors, or shall be of construction that resists fire for not less than 20 minutes Section 8.3.2 Smoke barriers required by this code shall be continuous from an outside wall to an outside wall, from a floor to a floor, or from a smoke barrier to a smoke barrier or a combination thereof. Such barriers shall be continuous through all concealed spaces, such as those found above a ceiling, including interstitial spaces.

IBC: Smoke Partition Essentially as discussed earlier for Corridor partitions Just limit the passage of smoke per section 710. Smoke Barrier The requirements in 407.5 mirror those in NFPA, WITHOUT the exceptions.

Chicago Building Code: Every sleeping floor shall be divided into at least two smoke sections by a one (1) hour fire rated smoke stop partition. Doors shall be C Label (45 Minutes). IN ADDITION - every institutional unit over two stories in height, every floor over 12,000 square feet which contains bed rooms or wards shall be divided into two areas by a 3-hour fire-resistive separation

Challenge Questions: Are Smoke Dampers required in Smoke Barriers where ductwork penetrates the barrier? Are Fire dampers required in these partitions since they are also required to be fire rated?

ANSWER: It Depends

Factors: Where is the facility? Is the smoke barrier ALSO being used as a Fire Wall with a rating of two (2) hours or greater?

Chicago Building Code: The City has NO requirement for smoke dampers. FIRE DAMPERS are required at the required threehour barriers (or any other partition with a fire resistance rating of two (2) hours or more).

2000 NFPA 101: Section 18.3.7.3, Exception No. 2* Allows smoke dampers to be omitted in fully ducted HVAC systems. If the Barrier is also a rated building separation, horizontal exit or other type of partition requiring a fire rating of two (2) hours or greater, a FIRE DAMPER must be installed.

BUT!!!

International Building Code: The International building code does NOT have an exception to delete smoke dampers except at Critical Exhaust Ducts. Therefore, smoke dampers must be used in most locations outside of Chicago. Combination Smoke/Fire dampers must be used at partitions with a fire rating of two (2) hours or greater.

Fire Barrier Locations: Mixed Use separations All codes Fire compartment size restrictions in IBC and CBC due to a factor of construction type and building height. Horizontal Exits

Challenge Question: What is a Horizontal Exit?

ANSWER: A horizontal exit is a fire barrier that is used when the distance to another legal exit (stair or access to the exterior) is too great to meet code.

Components of a Horizontal Exit: It is a minimum Two (2) hour fire rated partition that spans from outside wall to outside wall to separate the building into fire compartments. The adjacent horizontal separations (floors below and above) also need to maintain the Two (2) hour rating. For Healthcare, horizontal exits can account for up to 2/3 of the total exiting. It is important to read ALL of section 7.2.4 for ALL requirements. VERY IMPORTANT A fire alarm pull station must be within five (5) feet of the horizontal exit doors.

Delayed Egress Locks: Used to help limit movement into or out of areas that must still be used as a means of egress. Obstetric Units Pediatric Units Secondary exits through restricted areas such as surgical suites ICU s Geriatric units Sometimes Psychiatric units

Delayed Egress Locks: Allows the door(s) to remain locked for 15 seconds after someone tries to exit the door. Outside of Chicago, the authority having Jurisdiction can allow an increase of up to 30 seconds. DON T FORGET to apply to ALL AHJ s involved. Section 7.2.1.6.1 has all of the requirements for NFPA For IBC, see section 1008.1.9.7 For CBC, see (13-160-269) All three Codes require that the building be fully sprinklered, and that the locks drop out upon activation of the fire alarm. Don t forget to make sure that you have emergency lighting at the door so that the signage can be read.

Challenge Question: How many Delayed Egress Locks can you have in the path of Egress?

ANSWER: NFPA and IBC allow only ONE (1) delayed egress lock in the path of travel to the public way.

Psychiatric Units: Can be locked down, and have multiple locks in the path of egress. Staff MUST have keys or keycards on them at all times! And be trained for fire situations.

Electronic Locks: Be Careful with electric strikes on Fire Rated Doors, especially Stair Doors. It is acceptable to use FAIL SECURE on room doors (as long as ALL staff have keys) and occupants can gain access to the means of egress without a key or keycard. On stair doors, and rated cross corridor doors, use with caution. If you need access to all floors during an emergency situation, the strikes will be set for FAIL SAFE. This will DISABLE the latching function of the rated door creating a hazard. It is usually best to use magnetic locks or electric locksets in these locations.

Suites: Purpose: Allows for open areas, not every room is required to have a smoke tight, latching door, or even have a door. Can help alleviate a dead end condition. Can be used in an area where access to two exits is not desirable or feasible Can allow operations to store carts and items in the Passageway (BEWARE of what is being stored so that it is not considered open storage).

Suites: Requirements: All codes limit size of suites for patient sleeping rooms to 5,ooo square feet. NFPA and IBC allow non-patient sleeping areas to be 10,000 square feet. SEPARATION OF SUITES: NFPA Not specifically called out in the 2000 version. The interpretation from NFPA is to have a partition that limits the passage of smoke. IBC 407.4.3.2 Smoke partition complying with 710 CBC One (1) hour construction with solid wood doors.

Suites: Question: Can a suite exit into another suite?

Suites: Answer: It Depends

Suites: IBC allows one of the exits in a two exit suite to pass through another complying suite. CBC does not address one way or the other. NFPA does not specifically allow it but it also doesn t prohibit it. The official interpretation from NFPA is to look at the 2006 code which they state Clarifies the intent of the 2000 Code BUT

Suites: Beware, IDPH and CMS do not officially accept this interpretation. IDPH interpretation: Any suite must comply with the travel distance rules for suites (50 or 100 ) to a corridor door, to a door directly to the outside at the level of exit discharge, and/or in some cases an exit from the most remote point in a suite. Once this item is met, a second path, where required may pass through an adjoining suite. Verify specific conditions with IDPH PRIOR to implementing.

Suites:

Taming the Health Care Building Codes David Dastur AIA, NCARB, Senior Principal Jensen & Halstead, Ltd 358 west Ontario Street Chicago, Illinois 60654 312-664-7557 ddastur@jensenandhalstead.com