LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division

Similar documents
LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

LGA... Gas Burner Controls. Building Technologies Division

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies Landis & Staefa Division

LOA44.252A27. Oil Burner Control. Building Technologies HVAC Products

LAE10 LFE10. Use. Series 02

Flame Safeguards LFE10. Building Technologies HVAC Products

Flame Safeguards LFE10. Building Technologies HVAC Products

Oil Burner Controls LOA3... Building Technologies HVAC Products

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies HVAC Products

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

UV Flame Supervision System

Use. Burner controls for use with forced draught gas or gas / oil burners of small to medium capacity in intermittent operation.

Use. The burner controls are certified to EN 230 and EN 298.

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

Oil Burner Controls LOA3... Building Technologies Division

C Note! LGI16... Burner Controls. Building Technologies

Oil Burner Controls LMO24... LMO44...

Oil Burner Controls LMO24... LMO44...

Burner controls. Building Technologies HVAC Products

Infrared Flame Detectors

Main Features. Functions. with automatic ignition and control functions for the heating and domestic hot water circuit

Flame detector. The QRA4.U is for use with the following types of burner control:

EUROBOX SERIES TYPES CM...N SM...N MM...N

EUROBOX SERIES TYPES CM... SM... MM...

Gas Burner Controls. Building Technologies HVAC Products

Burner Controls. Building Technologies HVAC Products

QRA4.U. Flame Detector. Siemens Building Technologies HVAC Products

Flame detector. The QRA4.U is for use with the following types of burner control:

QRC1... Blue-flame Detectors. Siemens Building Technologies HVAC Products

Flame detector. Building Technologies Division Infrastructure & Cities Sector

Infrared Flame Detectors

Burner Management System

EUROFLAT SERIES TYPES C... S... M...

QRA2... QRA10... QRA53... QRA55... Flame Detectors. Siemens Building Technologies HVAC Products

QRA10... QRA53... QRA55...

MICROFLAT SERIES TYPES C.../U T X

Building Technologies Division

QRA10... QRA53... QRA55...

LFL Series Burner Flame Safeguard Control

Burner Management System

Building Technologies

Program module for burner control LME71.000

QRA10... QRA53... QRA55...

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

Burner Management System

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR..

MMI (40-34) Gas burner safty control

QRA10... QRA53... QRA55...

RAR... Photocell Detectors. Building Technologies Division

Product Range Overview

Blue-flame Detectors

CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD. Corona Corporation

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

Basic unit with integrated air-fuel ratio control for forced draft burners

MMG Gas burner safety control

Forced draught gas burner

DKG 972. Gas Burner Safety Control. For 2-stage atmospheric gas burners

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners

Heating Element. Building Technologies HVAC Products

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

Basic unit with integrated fuel-air ratio control for forced draft burners LMV Building Technologies Division

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

BOSCH CONDENS 5000W ZSB18-2A

Operator: Save these instructions for future use!

GAS FIRED ATMOSPHERIC ELECTRONIC VERSION kw

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

Gas burner automatic safety control MMI / 811.1

SERIES 35-63J APPLICATIONS FEATURES SPECIFICATIONS AGENCY CERTIFICATIONS

CATALOGUE PRODUITS - CSA - CSI - CSM - CSS - CSS2 - P16 - P19 - P20 - P25 - UV DETECTOR

AUTOMATIC BURNER CONTROL SYSTEM SAFETY INFORMATION CONFORMITY

FIREYE M4RT1 FLAME SAFEGUARD CONTROLS DESCRIPTION

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

Operator: Save these instructions for future use!

Building Technologies Division

Operator: Save these instructions for future use!

Use. Functions. Key function. Other functions

DATASHEET. Burner control unit FDA 601x

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

50A Integrated Furnace Control

Basic Unit with integrated Fuel / Air Ratio Control for Forced Draft Burners LMV Building Technologies

CAUTION WARNING. 50T Integrated Furnace Control INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS

INSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL

UV - flame detector dual fuel burners for intermittent burner operations

Old documentation - Only for your information! Product is not available anymore!

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use!

Flame detector FD 2011 / FD 2012

Operator: Save these instructions for future use!

Forced draught gas burner

Operator: Save these instructions for future use!

G a

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

Operator: Save these instructions for future use!

Quick Reference Guide. Application. Gas Furnaces Boilers Water Heaters Commercial Cooking. Features

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

Quickheat 30 weather compensated boiler control

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

Transcription:

7 418 ISO 9001 Gas Burner Controls LGA... The LGA... are used for the startup and supervision of atmospheric gas burners of low to medium capacity, without fan assistance, in intermittent operation. The LGA... and this data sheet are intended for use by OEMs which integrate the gas burner controls in their products. Use The flame is supervised with an ionization current ionization electrode. Using the appropriate adapters, the LGA... can replace their predecessor types LFI7... and LFI5... in terms of both function and size (refer to «Ordering»). LGA41.173A27 and LGA52.171B27 can also be used on direct fired air heaters (WLE to DIN 4794). 27.06.2000 Landis & Staefa Division

Warning notes To avoid injury to persons, damage to property and the environment, the following warning notes should be observed. Do not open, interface with or modify the unit. Before performing any wiring changes in the connection area of the LGA..., completely isolate the burner control from the mains supply (all-polar disconnection) Ensure protection against electric shock hazard by providing appropriate protection for the burner control s terminals Check wiring and all safety functions Press the lockout reset button only manually, without using any tools or pointed objects Fall or shock can adversely affect the safety functions. Such units may not be put into operation even if they do not exhibit any damage Mounting notes The relevant national safety regulations must be complied with. Siting the ionization electrode The ionization current ionization electrode and the ignition electrode must be positioned such that the ignition spark cannot arc over to the ionization electrode The position and the polarity of the ignition electrode can adversely affect the magnitude of the flame signal. Reversal of polarity of the ignition transformer s connections on the primary side usually solves the problem Since the burner bars form the earthed counter-electrode, the burner must be adjusted such that the flame is hot and stable and in firm contact with the burner bars. With pulsating flames or yellow-burning flames resulting from lack of air, a very low or even no ionization current is generated so that the burner control will initiate lockout 2/10

Installation notes Only with the LGA41... Only with the LGA52... / LGA63... Electrical connection of the ionization electrode Installation and commissioning work must be carried out by qualified staff Observe the permissible length and shielding of the detector cable (refer to «Technical data») Always run the ignition cables separate from the unit and other cables while observing the greatest possible distances To isolate the burner control from the mains supply, use an all-polar switch with a contact gap of at least 3 mm Secure the earthing lug in the terminal base with a metric screw and a lockwasher or similar Switches, fuses, earthing, etc., must be in compliance with local regulations. Primary fuse max. 10 A (slow) Make absolutely certain that life conductor «L» is connected to terminal 1. Otherwise, no flame signal will be generated Connect the gas pressure monitor and other monitoring devices - whose contacts must be closed from startup to controlled shutdown - in series with «R» and «W» If the fully closed position of the main gas valve «BV2» shall be checked on startup, the closed position contact must be included in the loop between terminals 9 and 3. In addition, the connecting links between terminals 9 and 11 and 8 and 3 must be fitted During the startup sequence, terminal 6 carries voltage and may not be used as an auxiliary terminal The auxiliary contact of a gas valve for checking the fully closed position must be included in the loop between terminals 9 and 3 During the startup sequence, terminals 9 and 6 carry voltage and may not be used as auxiliary terminals Connect the load controller of two-stage burners to terminal 5 in series with «BV2» It is important that signal transmission takes place with the smallest possible losses: The cable length may not exceed 20 m The detector line may not be run together with other conductors in the same cable since line capacitance reduces the magnitude of the flame signal The insulation resistance between the ionization electrode and ground must be a minimum of 50 MΩ, even after a large number of operating hours. Prerequisite for this is not only high quality heat-resistant insulation of the electrode cable, but also of the ionization electrode itself (ceramic holder!) A soiled ionization electrode holder offers favourable conditions for surface leakage currents which reduce the magnitude of the flame signal The burner (acting as the counter-electrode) must be correctly earthed, or else no ionization current will flow Earthing the boiler alone does not suffice! In networks with unearthed neutral, use RC unit 4 668 9066 0. Live, neutral and central point conductors may not be incorrectly connected to terminals 1 and 2 of the burner control, or else no flame signal will be generated Commissioning notes Commissioning and maintenance work must be carried out by qualified staff When commissioning the plant, when doing maintenance work, or after longer off periods, perform the following safety checks: a) Burner startup with no flame signal; for that purpose, cut the connection between burner control and ionization electrode prior to burner startup and maintain this status b) Burner operation with simulated «flame failure» during operation; for that purpose, cut the connection between burner control and ionization electrode during burner operation Lockout at the end of «TSA» Repetition 3/10

Mechanical design LGA... The gas burner controls are of plug-in design, suitable for installation in any position on burners, in control cabinets or on control panels. The housing is made of impact-proof, heat-resistant plastic and accommodates: - The thermal sequencing device (ambient temperature-compensated) acting on a multiple snap action switching system - The flame signal amplifier with the flame relay, and - The lockout warning lamp and the lockout reset button (splash-proof) AGK11 plug-in base Undervoltage detection Only with the LGA63.191A27 Type summary Refer to data sheet 7201. In the event of undervoltage (below approximately AC 165 V), an electronic circuit ensures that the burner control will prevent burner startup. Undervoltage threshold: AC 178 V ±10 V «TSA»: smaller tolerance band Flame signal amplifier: higher sensitivity, for typical applications with pilot flames The type references given in the table refer to burner controls with no base and no accessories. Burner control with under- AC 220...240 V LGA41.173A27 LGA41.153B27 LGA52.150B27 LGA52.171B27 LGA52.191B27 LGA63.191A27 voltage detection AC 100...110 V --- --- LGA52.150B17 --- --- --- Connection facility for auxiliary fan ¹) --- --- x x x X Connection facility for air pressure monitor --- --- x x x X Control outputs for gas valves 2 2 2 2 2 2 Reversed polarity protection x x x x x x Ordering 1) Auxiliary fan not monitored to EN 298 Gas burner control without plug-in base Plug-in base (refer to data sheet 7201) Cable gland holder (refer to data sheet 7201) Cable holder (refer to data sheet 7201) Cable holder (refer to data sheet 7201) refer to «Type summary» AGK11 AGK65 AGK66 AGK67... Pedestal (empty housing) For increasing the height of the LGA... (62.5 mm) to that of the LFI1... or LFI5... (90 mm) Adapter for replacing LFI1... by LGA... Adapter for replacing LFI5... by LGA... AGK21 KF8828 KF8829 RC unit for the supervision of ionization currents in networks with non-earthed neutral ARC 4 668 9066 0 4/10

Technical data General unit data Environmental conditions Mains voltage AC 220 V 15 %...AC 240 V +10 % AC 100 V 15 %...AC 110 V +10 % Mains frequency 50...60 Hz ±6 % Power consumption 3 VA Input current at terminal 1 max. 5 A Terminal rating - Terminals 4 and 8 - Terminals 6, 7 and 9 - Terminals 5 and 10 Primary fuse max. 4 A max. 2 A max. 1 A max. 10 A (slow) Degree of protection IP 40 Mounting orientation optional Weight - Without plug-in base - With plug-in base approx. 180 g approx. 260 g Transport IEC 721-3-2 Climatic conditions class 2K2 Temperature range -50...+60 C Humidity < 95 % r.h. Mechanical conditions class 2M2 Operation IEC 721-3-3 Climatic conditions class 3K5 Temperature range 0...+60 C for LGA41.173A27 and LGA52.171B27: -20...+60 C Humidity < 95 % r.h. Condensation, formation of ice and ingress of water are not permitted! CE conformity According to the directives of the European Union Electromagnetic compatibility EMC 89 / 336 EEC incl. 92 / 31 EEC Directives for gas-fired appliances 90 / 396 EEC Flame rectification probe Voltage between ionization electrode and mains voltage ground Required detector current min. 2 µa Possible detector current max. approx. 100 µa Detector line length max. 20 m (separate cable) Required insulation resistance between min. 50 MΩ ionization electrode with its cable and ground Identification code to EN 298 A M C L X N A T C L X N single-stage two-stage 5/10

Function Control sequence (times in seconds) 1 ) AC 220...240 V LGA41.173A27 LGA41.153B27 LGA52.150B27 LGA52.171B27 LGA52.191B27 LGA63.191A27 AC 100...110 V --- --- LGA52.150B17 --- --- --- t1 Pre-purging with auxiliary fan 15 10 approx. 13 approx. 13 approx. 13 approx. 13 t3 Pre-ignition time 15 10 --- --- --- --- t3 Ignition time from start of «TSA» --- --- max. 5 4.5...7.5 7...10 max. 10 TSA Ignition safety time 10 5 5 4.5...7.5 7...10 10 TSAmax. Max. ignition safety time 20 10 10 20 20 20 t3n Ignition after flame establishment max. 2 max. 1 --- --- --- --- t4 Interval «BV1 BV2» approx. 13 approx. 18 approx. 18 approx. 13 approx. 23 approx. 23 ¹) All times specified are valid for AC 220 V and AC 110 V respectively For AC 240 V operation, the above times must be multiplied by 0.7 Control sequence in the event of fault Erroneous flame signal during «t1» or «t3» Lockout ²) prior to the release of gas Lockout ²) prior to ignition and the release of gas No flame on completion of «TSA» Lockout ²) Lockout ²) Flame failure during operation Repetition Repetition No air pressure signal during «t1» --- No start Air pressure failure during operation --- Shutdown ²) After lockout, the burner control can be reset after about 60...90 seconds Flame supervision with ionization electrode The conductivity and the rectifying effect of hot flame gases are used for flame supervision. For this purpose, an AC voltage is applied to the ionization electrode which projects into the flame. The current that flows in the presence of a flame (ionization current) generates the flame signal which is then fed to the input of the flame signal amplifier. The amplifier is designed such that it only responds to the DC current component of the flame signal, thus ensuring that a short-circuit between ionization electrode and ground cannot simulate a flame signal (since in that case, an AC current would flow). 6/10

Internal diagram LGA41... When the switch-on command is given, power is supplied to both the ignition transformer and the heating coil of the bimetal sequencing device. The bimetal bends and pushes contact set «c, d, e» towards «f». On completion of the pre-ignition time, the system tilts so that «e - f» closes and «f - g» opens. Contacts «c - d» still remain closed («c» resting on «d»). On flame establishment, the flame relay is energized, latching mechanically «e - f» in the position now assumed. The relay also closes contact «f» and, at the same time, opens «c - d», so that the ignition transformer and the bimetal heating element will be switched off. Then, «d» slowly returns to its starting position, also catching «g». When tilting back, «g - f» closes, so that the main gas valve «BV2» will be energized. If no flame signal is generated, the flame relay does not open «c - d», so that the bimetal will continue to be heated. The bimetal thus continues to bend until tilting it actuates contact «tz2»: Lockout. In the event of an erroneous premature flame signal, the flame relay by means of its latch - prevents «e - f» from making, which means no release of gas. «TZ», however, remains under voltage, so that the bimetal continues to bend until, eventually, lockout is initiated by «tz2». LGA41... EK L1 tz2 X Y Z a fr b tz1 c d e f g FR TZ 1 2 10 9 11 8 3 7 6 4 5 12 W R AL Z BV1 BV2 FE L N 7418i02/0200 Legend AL Fault status signal Safety limit thermostat BV... Fuel valve TZ Electro-thermal timer EK Lockout reset button (bimetal system) with contacts «tz» FE Ionization electrode W Thermal reset limit thermostat or manual FR Flame relay reset safety limit thermostat L1 Built-in lockout warning lamp Z Ignition transformer R Thermostat or pressurestat 7/10

Internal diagram LGA52... / LGA63... When the switch-on command is given, the auxiliary fan starts to run. When the air pressure monitor closes its contact, the heating coil of the bimetal sequencing device is energized and the bimetal pushes contact set «c, d, e» towards «f» (thereby opening «f - g»). On completion of the pre-purge time, «e - f» is closed so that both the gas valve «BV1» and the ignition transformer receive voltage: the safety time starts. On flame establishment, the flame relay latches mechanically «e - f», pushes «c» back at the same time and opens «fr». The ignition transformer is thus switched off and the heating coil de-energized, so that «d» can revert to its starting position. When tilting back, «g - f» closes, so that the main gas valve «BV2» receives voltage. If no flame signal is generated, the flame relay does not open «c - d», so that the bimetal will continue to be heated. The bimetal thus continues to bend until tilting it actuates contact «tz2»: Lockout In the event of an erroneous premature flame signal, the flame relay by means of its latch - prevents «e - f» from making, which means no release of gas. «TZ», however, remains under voltage, so that the bimetal continues to bend until, eventually, lockout is initiated by «tz2». LGA52... / 63... EK L1 tz2 X Y Z a b fr tz1 c d e f g FR TZ L N 1 2 10 8 7 11 9 6 4 5 12 LP W FE R AL M 1) Z BV1 BV2 7418i01/0200 Legend AL Fault status signal R Thermostat or pressurestat BV... Fuel valve Safety limit thermostat EK Lockout reset button TZ Electro-thermal timer FE Ionization electrode (bimetal system) with contacts «tz» FR Flame relay W Thermal reset limit thermostat or manual L1 Built-in lockout warning lamp reset safety limit thermostat LP Air pressure monitor Z Ignition transformer M Auxiliary fan 1) Not monitored to EN 298 8/10

Connection diagram LGA41... LGA41... FR 1 2 9 11 8 3 7 4 5 10 6 12 W FE R Z BV1 BV2 AL R/W Z BV1 BV2 t3 Control sequence A B C D t3n TSA t4 1 7 4 5 L N 7418a04/0200 FS 7418f01/0200 12 LGA52... / LGA63... LGA52... / 63... FR 1 2 6 8 9 11 7 4 5 10 12 LP R/W LP A B C D 1 11 W R M 1) Z BV1 BV2 AL FE M 9 8 9 L N 7418a05/0200 6 t1 t3 t4 6 Z TSA 7 BV1 4 BV2 5 FS 7418f02/0200 12 Legend AL Fault status signal M Auxiliary fan BV... Fuel valve R Thermostat or pressurestat FE Ionization electrode Safety limit thermostat FR Flame relay W Thermal reset limit thermostat or manual FS Flame signal reset safety limit thermostat LP Air pressure monitor Z Ignition transformer Required input signals 1) Not monitored to EN 298 Burner control s output signals A Commencement of startup sequence C Operating position B Time of flame establishment D Controlled shutdown by «R» t1 Pre-purging with auxiliary fan t3n Ignition on flame establishment t3 Pre-ignition time t4 Interval «BV1 BV2» t3 Ignition time from the start of «TSA» TSA Ignition safety time 9/10

Dimensions Dimensions in mm LGA... 62,5 5,5 25 25 9 41,5 7418m01/0200 88 91 LGA... with AGK11 plug-in base and AGK65 cable gland holder xxxxxxxxxx 47 62,5 22 AGK11 plug-in base 1 2 3 4 5 6 7 8 9 10 11 12 7418m02/0200 5,4 16,2 N 31 32 4 17 23,5 10,5 4,5 A B C 24 24 30 30 Plug-in base with screw terminals. Hatched: position of insertable cable gland holder or cable holder. «A»: holes for the fixing screws «B»: holes for cable entry «31 / 32»: auxiliary terminals «N»: neutral terminals, connected to neutral input (terminal 2) Underneath: 4 earth terminals, joining in a lug for earthing the burner Also refer to data sheet 7201. Mandatory: Earthing lug «C» and fixing screws in «A» must be connected to burner ground (using a metric screw with a lockwasher or similar). 10/10 2000 Landis & Staefa Produktion GmbH