DIGITAL ALARM UNIT Model ALU-AP

Similar documents
Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

BSR Addressable Fire Detection control panel. Installation operation manual

1 measurement signal input 4-20 ma for connection to an external gas sensor 5 freely programmable alarm switching points per measuring point

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

Technical Manual. Level Alarm Unit CARLA & WIDS

WIRING DIAGRAM AND INSTRUCTIONS

Type 8001 PRIME MOVER CONTROLS INC. ALARM ANNUNCIATOR TYPE8001 FEATURES SB 8001B

OPERATING INSTRUCTIONS COP-IE, COP-I, COP-E (ANSI 50,51,50N,51N)

Installation, Operating and Maintenance Manual

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

Lubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector)

OPERATING INSTRUCTIONS COP-F (ANSI 81O/81U)

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

Watchguard WGAP864 User Manual

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

CTT8 TEMPERATURE MONITOR DEVICE

Pioneer-R16 Gas Monitor Operator s Manual

Product Manual SZ1144

Excel-EN Conventional Fire Control Panel

20 Light Remote Annunciator

MO n : 12JMC rév A

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Product Manual SZ1145

Two-Channel Gas Controller

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

MODEL 5100 VOTING LOGIC MODULE

AFMS Audible Flow Monitoring System TECHNICAL SPECIFICATION

Model 17A00 Expansion Enclosure

CLEANROOM MONITOR CR3A Network - Installation Instructions

FCR 05, FCR 07. Power factor correction controller. User and service manual

TCM-2 Thyristor Control Module DATA SHEET

ELSEMA MD2010. Application Controls automatic doors or gates when a vehicle is present. Description

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

Oxygen (O2) Single-Point Gas Detection System

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

EVO192 v3.0 Fire and Burglary What s New

M1000 Alarm Annunciator

ST Wiring diagram. Product description. Standard temperature controller. Order number

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

Carbon Monoxide Transmitter

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

EXTINGUISHING CONTROL PANEL PX2 SERIES

VA301C CONTROLLER WITH BACnet OPTION

BURGLAR ALARM PANEL BS-468

FEC400 Series. Installation Manual

Independent Zone Control (I.Z.C.)

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev.

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

PolyGard 2-channel Gas Controller MGC-03

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

Installation Manual Premier 412/816/832. Issue 10

Eclipse MC240. Double & Single Gate Controller with Eclipse Operating System (EOS) 3rd Edition. MC240 for Double and Single Gates.

M2000 Engine Controller

SALES SUPPORT DOCUMENT

QA16 Addressable System

EasyTronic III MANUAL SERVICE

Instruction Manual PCS-400-XY. Pump Controller. Y=2: 4-20 ma Y=6: 0-10 VDC X=5: 1-5 VDC. 4 Pump Control Relays 1 Alarm Relay 1 Signal Fail

M2500 Engine Controller Installation Manual

DRYTEK 1 - User Manual ELECTRICAL PANEL FOR 1 MOTOR WITH POWER FACTOR CONTROL

DIMENS. MIN TYPICAL MAX A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826) B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173)

LMS-188-4P-BMS 4 POINT DIGITAL MONITOR/ALARM WITH PROTOCOL CONVERTER OPERATING INSTRUCTIONS

Safe T Net 210. Instruction Manual Part Number Mar2010

FireNET Plus Wiring Instructions

Fire Control Panel FS4000

User Manual Doc.Ref : JA-KNX-UM. JA-KNX Jablotron KNX Interface ELAUSYS JA-KNX. KNX Interface for Jablotron alarm system.

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

Entwicklung + Fertigung + Service: Heerweg 15 D, Denkendorf Tel.: / Fax.: /

Application, Installation, Operation & Maintenance Manual

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

Dixell Installing and Operating Instructions release 7.0

Analogue Addressable Fire Panels FP1500. Manual for Installation, Configuration and Commissioning

RTD TEMPERATURE SENSING SYSTEM

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

FLOW CONTROLLER TYPE S/601

LA5579 Wireless Siren Operation Manual

3 User s settings. 3.3 Internal clock setting

Danfoss gas detection units

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

User Guide

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

REPEATER FS5200R INSTRUCTION MANUAL

Planning Elevator Relay Groups Programming Millenium for Windows Software

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

Beacon 800 Gas Monitor Operator s Manual

S304 and S305 Dust Emission Monitors. User Manual. Distributor

Instruction Manual August sitrans CU 02

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

EARTH LEAKAGE RELAY. User Manual - Issue 1.0

User Guide. HTM Nurse Call. In the event of requiring assistance, please contact your Installer/Supplier.

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

G34 AU1B (External Ultrasonic Sensor) Version 3

Model A1600 Series Annunciator

Static Pressure Control

Transcription:

DIGITAL ALARM UNIT Model ALU-AP Description Digital alarm unit ALU-AP has the following characteristics: 1. Operates in MASTER or SLAVE mode. 2. It can connect with other devices through a RS485 network with two ways: either as an independent network where there is one device set in MASTER mode and all the rest are in SLAVE mode or as a PC network where a PC has full control of the network and all the devices are set in SLAVE mode. Each device s address is adjusted from parameter Ν.70 Add. The network needs to be powered with +12 24VDC. 3. Capability of controlling the fault line for every input through parameters L1 L10 and i1 i10, see sketches 3, 4. Line control must be applied only with +24VDC power supply. 4. Without fault line control: ΝΟ or NC contact with common at 0V or +24V for adjusting each input independently, see sketch 2. 5. Internal relay with one associated auxiliary contact 250VAC 10A for setting up an external alarm circuit in case of main power failure. 6. The device can be placed on the ship s bridge. 7. The device can connect to a thermal printer for instant print of any alarm (applied only in network mode). 8. One general internal relay output 250VAC 10A for siren activation. 9. 14 digital outputs for driving relays where input alarms, fault line alarms and LED operation for monitoring can be driven into groups or separately. Maximum total load of outputs is 300mA. 10. Capability of holding the alarm in every input after RESET through parameters Η1 Η10. 11. Time delay for each input can be set from 0 100 sec. 12. Accepts alarm inputs of ±24VAC/DC. 13. Up to 98 devices can connect to a network with common RESET, TEST LAMP and alarm activation. 14. One or more devices connected to a network can become a repeater of any other device. This means that the alarms of the latter device will be forwarded to the repeater device. 15. Capability of adjusting contact 9 in TEST LAMP operation and contact 10 in RESET operation for usage of remote buttons. 16. Adjustment of LED brightness by pressing SET button. 17. Power supply: 24VAC ± 10% 50/60 Hz ή ±24VDC +30% / -10% 18. Maximum consumption: 10W 19. Internal power supply fast blow fuse: 1A 20. Internal fast blow fuse in the outputs: 315mA 21. Internal fast blow fuse in the network s communication: 315mA Operation of the device in a network The device accepts a signal through an input and the corresponding LED starts flashing while the relay (siren) of the device is activated. If the RESET button is pressed, the LED stops flashing and remains ON until the signal that caused the alarm is removed from the input. By pressing the TEST button, all LEDs light up simultaneously in order to verify good operation of the device. In MASTER mode the device displays nna, while in SLAVE mode it displays its address on the network Α 0, Α 1, etc. The RESET and the TEST buttons are common for all devices within a network. This means that they operate at the same time in all connected devices. ALARM Alarm inputs can be driven towards one output either separately or into groups. Address alarm of the MASTER device: when several devices operate in a MASTER - SLAVE network and the MASTER device does not receive any data from one or more SLAVE devices, the indication Α 1, Α 2 starts flashing, which corresponds to the address of the SLAVE device that isn t sending any data to the MASTER device. This causes the activation of the output set from the parameter No.33 AdF. Fault line alarm in MASTER and SLAVE device: the indication L 1, L 2 starts flashing, indicating the channel that is faulty while the corresponding programmable output defined by the parameter No.32 brl is activated. Repeater alarm: when a repeater loses the connection with the mother device, the indication rep starts flashing. Τhe cut line alarms and the lost-communication alarms in a SLAVE device can be driven either into separate outputs either into the same output defined by the parameters No.32 brl and No.33 AdF. Power failure setup An internal relay 250VAC 10A with one contact (terminal blocks 11, 12) is available to set up an external alarm circuit in case main power supply fails. When the device is powered on, the said auxiliary contact will open and when power failure occurs the same contact will close, therefore an external alarm circuit with a separate power supply will also close and consequently, an audible and/or visual alarm will be triggered. 1

Button s function Managing the parameters button ΕΝΤΕR SET function - enter parameter s menu - confirm a new value of a parameter cancel a new value of a parameter - change parameter within the parameter menu - alarm RESET button outside the parameter menu - change parameter within the parameter menu - TEST LAMP button outside the parameter menu By pressing [ENTER] we enter the parameters menu and the first parameter is displayed, Cod. By pressing [SET] the value of the parameter is displayed and we set number Cod = 22. By pressing [ENTER] we confirm the new value and with the [ ], [ ] we scroll between the parameters. By pressing [SET] we cancel the new value and we return to the parameter s name. Connection diagram By pressing [ENTER] again we exit the parameter menu. Connection diagram in a network (up to 98 devices) Every 50 devices a network amplifier RS485 Type RS485 Amplifier must interfere. Sketch 1 Parameters table 2

No Parameter s description min max def UOM SAn The parameter is not in use and must always have value SΑn = 0 0 1 Cod Entry code in parameter menu = 22 0 250 0 2 t 1 Time delay of alarm 1 in input 1 0 100 0 sec 11 t10 Time delay of alarm 10 in input 10 0 100 0 sec 12 ο 1 The alarm of the 1 st input can be driven into one of the 14 outputs. For ο 1 = 0, the alarm is not driven into any output. 21 ο10 The alarm of the 10 th input can be driven into one of the 14 outputs. For ο10 = 0, the alarm is not driven into any output. 22 d 1 The 1 st LED can be driven into one of the 14 outputs. For d 1 = 0, the LED is not driven into any output 31 d10 The 10 th LED can be driven into one of the 14 outputs. For d10 = 0, the LED is not driven into any output 32 brl The fault line alarm can be driven into one of the 14 outputs 33 AdF The lost communication alarm can be driven into one of the 14 outputs 34 i 1 Operation of input with NO or NC contact. With line control: i1 = 0 or 1 NO and i1 = 2 or 3 NC. Further details in sketches 3 and 4. Without line control: 0 3 0 1. If the contact is tied to +24V: i1 = 0 ΝΟ i1 = 1 ΝC 2. If the contact is tied to 0V: i1 = 2 ΝΟ i1 = 3 ΝC Further details in sketch 2. 35 43 i10 Operation of input with NO or NC contact. With line control: i10 = 0 or 1 NO and i10 = 2 or 3 NC. Further details in sketches 3 and 4. Without line control: 0 3 0 1. If the contact is tied to +24V: i10 = 0 ΝΟ i10 = 1 ΝC 2. If the contact is tied to 0V: i10 = 2 ΝΟ i10 = 3 ΝC Further details in sketch 2. 44 Η 1 For Η 1 = 1, if the input alarm persists, so does the output alarm (1 14) after the RESET For Η 1 = 0, the output alarm (1 14) disappears after the RESET 53 Η10 For Η10 = 1, if the input alarm persists, so does the output alarm (1 14) after the RESET For Η10 = 0, the output alarm (1 14) disappears after the RESET 54 L 1 Activation of line control, where for L 1 = 0, there is no line control while for L 1 = 1 there is line control. For further details see sketches 3 and 4. 63 L10 Activation of line control, where for L10 = 0, there is no line control while for L10 = 1 there is line control. For further details see sketches 3 and 4. 64 ret For ret = 0, the RESET and TEST LAMP are activated on the network, while for ret = 1, the RESET and TEST LAMP are deactivated. 0 1 1 65 dis For dis = 1, nna is displayed where for dis = 0, only a dot is displayed. 0 1 1 66 te Input 9 configuration for TEST LAMP mode, where te = 0 is for normal mode and te = 1 is for TEST LAMP mode. 67 re Input 10 configuration for RESET mode, where re = 0 is for normal mode and re = 1 is for RESET mode. 68 rep If rep = 0, the device is not a repeater of any of the devices If rep = 1 98, the device is repeater of the device with the corresponding address If rep = 99, the device is a repeater of the network s MASTER device. The MASTER device cannot become a repeater of any device in the network. 0 99 0 At the repeater, the RESET and TEST LAMP of the inputs are deactivated, whereas the time delays that are applied to the inputs are the mother s device. 69 typ MASTER or SLAVE mode, where typ = 20 is for MASTER mode and typ = 21 is for SLAVE mode 20 21 20 70 Add 1. Devices network: A device is programmed in MASTER mode and at its Add parameter we enter the number of the SLAVE devices (1 98). In the respective parameter (Add) in the SLAVE devices we enter its unique network address (1 98). For connecting the devices in a network see sketch 1. 2. PC device network: all devices are in SLAVE mode and the Add parameter has the device s unique network address (1 98). 0 98 0 3

Input configuration according to the parameters L1, L2 L10 and i1, i2 i10 Without line control where line parameters L1, L2 = 0. Sketch 2 ------------------------------------------------------------------------------------------------------------------------------------------------------------------ With line control where line parameters L1, L2 = 1. ATTENTION: Line control must be applied only with +24VDC power supply. 1 st case: Ν.Ο. contact (normally open) Sketch 3 Line fault occurs when there is: a cut line or a short circuit at 0 Volt, where a line alarm is ON a short circuit at +24VDC, where an alarm is ON but not a line alarm 2 nd case: Ν.C. contact (normally close) Sketch 4 Line fault occurs when there is: a cut line or a short circuit at 0V, where an alarm is ON but not a line alarm a short circuit at +24VDC, where a line alarm is ON Technical specifications Power supply: 24VAC ± 10% 50/60Hz or ±24VDC +30% / -10% 50/60Hz Maximum consumption: 10W Internal power supply fast blow fuse: 1A Internal fast blow fuse in the outputs: 315mA Internal fast blow fuse in the network s communication: 315mA General internal alarm relay 250VAC 10A resistive loads Internal relay with one associated auxiliary contact 250VAC 10A for setting up an external alarm circuit in case main power supply fails The device can be placed on the ship s bridge. The device can connect to a thermal printer for instant print of any alarm (applied only in network mode). Operating temperature: -15 +70 C Storage temperature: -20 +80 C The device is mounted on a panel hole with dimensions 137x137mm Connection with plug in terminal blocks ΙΡ protection rating: ΙΡ42 front side. To be installed in an enclosure which provides protection against solid foreign objects and liquids at least IP 42. Class of equipment: Class II Internal audible alarm is not included (buzzer) 4

Dimensions Internal fuses Internal power supply fast blow fuse: 1A Internal fast blow fuse in the outputs: 315mA Internal fast blow fuse in the network s communication: 315mA ATTENTION to prevent electrostatic discharges at the side slots of the device and insertion of sharp objects. ATTENTION: separate the signal cables from the power supply cables to prevent electromagnetic disorders. Signal cables must never be in the same pipe with the power supply cables. Read and keep these instructions. The device is under a two year good operation guarantee. The guarantee is valid provided the manual instructions have been applied. The device check and service must be performed by an authorized technician. The guarantee covers only the replacement or the service of the device. V1.2/25.9.2015 preserves the right to adjust its products without further notice www.kiour.com 5