RADIANT COOLING SYSTEMS OPPORTUNITIES FOR RADIANT COOLING IN NORTH AMERICAN CONSTRUCTION DALE HANSCOMB, REHAU Sales Manager Building Technology

Similar documents
Using Embedded Tube Radiant Cooling Systems to Maximize LEED Points

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Radiant Heating & Cooling for Commercial Buildings

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Radiant Cooling Nonresidential HVAC Stakeholder Meeting #2

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

Being Radiant. Planning in-slab hydronic heating and cooling. solutions for the construction industry June 2014

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff

Modular Active. Chilled. Beams

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

How to ensure Thermal Comfort in buildings with CFD

Chilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle

Chilled Beams. Getting a Warmer Reception

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Heating Installation Guide published by

Life cycle cost comparison of TABS vs. other HVAC (UK) TECHNICAL BROCHURE

HVAC 101. H V A C S y s t e m s

GARCIA GALUSKA DESOUSA Consulting Engineers

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER

Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems

ASHRAE JOURNAL ON REHEAT

Sustainable HVAC Design: Using Air Movement in Air Conditioned Buildings

Comfort and health-indoor air quality

Optimizing the use of Chilled Beams for health and comfort GUNNAR SVENSSON

Optimizing energy efficiency and occupant comfort with climate specific design of the building

EMBEDDED PIPE SYSTEMS. SURFACE HEATING AND COOLING Heat transfer coefficient COOLING CAPACITY. Max. heating-cooling-capacity

Passive building in Hot and Humid Climates

Dehumidifying with Dedicated Outdoor Air

NET ENERGY WATER LOOPS A clear path to net zero energy buildings

Architectural Engineering Senior Thesis Mechanical System Redesign

IRRAD - PHASE II RADIANT COOLING - DESIGNING FOR FLEXIBLE PARTITION OF SPACE

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Relative Humidity in Schools Jim Cummings and Chuck Withers

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

HVAC DISTRIBUTION and DELIVERY SYSTEMS

Liquid Desiccant Technology Delivers Energy Cost Reductions and Indoor Air Quality Improvements. White Paper

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

MT. AIRY MIDDLE SCHOOL CARROLL COUNTY PUBLIC SCHOOLS

Systems engineering Slide 1

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

DADANCO Technical Paper

August 15, 2013 Page 1 of 19

Radiant Heating. Systems

ASHRAE Illinois Chapter 2015 Excellence in Engineering Awards

HONORABLE MENTION: COMMERCIAL BUILDINGS, EXISTING

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2

CHAPTER 4. HVAC DELIVERY SYSTEMS

Summary Comparison of Simulation Program Features

Technical Report Three

Problems Air and Water Distribution Systems

Displacement Ventilation

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

Displacement Ventilation in Classrooms

Fundamentals of Hydronic Design

7. MECHANICAL SYSTEM DESIGN

POTENTIAL AND LIMITATIONS FOR HYDRONIC RADIANT SLABS USING WATERSIDE FREE COOLING AND DEDICATED OUTSIDE AIR SYSTEMS

RADIANT COOLING RESEARCH SCOPING STUDY

A Technical Introduction to Cool Thermal Energy Storage Commercial Applications

DESCRIPTION OF TECHNOLOGY

Engineering Guide VAV Diffusers. Please refer to the Price Engineer s HVAC Handbook for more information on VAV Diffusers.

HME09 NATURAL VENTILATION

HVAC Mandatory Provisions Part II, Page 1

Vernonia K-12 School: Thermal Comfort in Passively-Cooled Zones

Recent Advances in Energy, Environment and Economic Development

Des Places Residence Hall

Modelling Appliance Loads in Multi-Unit Residential Buildings

ω = (1) Kirby S. Chapman Ph.D.

SECTION H. Engineering Guide Radiant Products. Please refer to the Price Engineer s HVAC Handbook for more information on Radiant Heating and Cooling

Richard Hiles ClimateMaster

SPACE CONDITIONING IN RESIDENTIAL BUILDINGS

Heat loss: the Reason for Heating

Experimental study of space cooling using ceiling panels equipped with capillary mats

LOW TEMPERATURE HYDRONIC HEATING FOR COLD CLIMATES TRAVIS SMITH PRESIDENT T AND T MOUNTAIN BUILDERS INC

buildingscience.com Windows and Occupant Comfort EEBA Building Solutions 2003 Lincolnshire, IL

The Corbioli House is a single-family house situated

SESSION Michigan Energy Code (MEC) Update (3 Technical) Per SMACNA Standard (TAB, Duct Design) and ASHRAE ( ) ASHRAE Detroit Members:

Case Study of an Innovative HVAC System with Integral Dehumidifier. Florida Solar Energy Center Cocoa, Florida

Job Name Control Systems Description Date

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

4-Pipe VAV vs. Active Chilled Beams for Labs

RADIANT HEAT. Construction Automotive Industry

Appendix 13. Categories of Cooling and Heating systems

design brief This design brief provides an introduction into the design and application of DV. It addresses the following issues:

Adelaide Homes Design Guide 4 - Winter warming

EASY$ TIP SHEETS. Energy Advice Saving Yukoners Money. How hydronic heating systems work

MECHANICAL INFRASTRUCTURE ASSESSMENT FOR VICTOR VALLEY COLLEGE

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

The Unplanned Impacts On Houses By Powered Attic Ventilators

Center for the Built Environment October 2013

European Researcher, 2014, Vol.(75), 5-2

Company Acme HVAC Inc. Customer James Allen Preparer J White Address 3652 Shady LaneAnywhere, Earth Phone

Transcription:

RADIANT COOLING SYSTEMS OPPORTUNITIES FOR RADIANT COOLING IN NORTH AMERICAN CONSTRUCTION DALE HANSCOMB, REHAU Sales Manager Building Technology www.rehau.com Construction Automotive Industry

LEARNING OBJECTIVES OF THIS COURSE BY THE END OF THIS COURSE, PARTICIPANTS SHOULD BE ABLE TO: 1. Explain the basic principles of radiant cooling systems and the factors that affect the output capacities 2. Define the meaning of a hybrid HVAC system and how it can be optimized to address the concern of condensation 3. Discuss how a hybrid HVAC system using radiant cooling leads to an improved building environment 4. Describe how a hybrid HVAC system using radiant cooling can reduce initial investment costs 5. Explain how a hybrid HVAC system using radiant cooling can reduce operating costs through reduced energy consumption and maintenance 6. Demonstrate how a hybrid HVAC system using radiant cooling can affect the net present value of the investment 7. Summarize the advantages of having a radiant system from an specifier s perspective 21-Sep-15 - Page 2

PROLOGUE: RADIANT COOLING SYSTEMS CORE COMPONENTS USED IN RADIANT HEATING AND COOLING INSTALLATIONS - Crosslinked polyethylene (PEX) pipes - Distribution manifolds 21-Sep-15 - Page 3

CROSSLINKED POLYETHYLENE (PEX) PIPES INTRODUCTION History - Development work started in Germany in 1968 for the first PEX pipes - Series production began in 1972 for PEX pipes for radiant heating applications - PEX pipes are now used for multiple fluidbased applications around the globe Capabilities of PEX pipes - Toughness to withstand jobsite conditions - High pressure and thermal capabilities - High flexibility for making tight bends - Wide range of diameters and coil lengths - Proven long life with more than 40 years experience PEXa molecule 21-Sep-15 - Page 4

CROSSLINKED POLYETHYLENE (PEX) PIPES AVAILABLE SIZES - Sizes 3/8, 1/2, 5/8 and 3/4 in. are most commonly used as radiant heating and cooling pipes* within floors, walls or ceilings - Larger sizes 1, 1 1/4, 1 1/2 and 2 in. are used to supply heated or cooled fluid to distribution manifolds and other hydronic components * Note: Radiant cooling applications are most commonly designed with 5/8 or 3/4 in. diameters 21-Sep-15 - Page 5

DISTRIBUTION MANIFOLDS REQUIRED IN ALL RADIANT SYSTEMS FOR CONTROL OF DISTRIBUTION PIPING - A typical circuit of radiant pipe covers 150 to 250 ft² (14 to 23 m ² ); typical project uses many circuits of pipe - Circuits are connected to factory-assembled distribution manifolds to control flow - Examples: 21-Sep-15 - Page 6

1. PRINCIPLES OF RADIANT COOLING BASIC PHYSICAL PHENOMENA Whenever there is a temperature difference between two objects, both objects will attempt to equalize the temperature. The energy transfer required to approach equivalent temperatures occurs through radiation. Radiant energy travels from hot to cold through a space, without heating the space itself. 21-Sep-15 - Page 7

PRINCIPLES OF RADIANT COOLING BASIC PHYSICAL PHENOMENA MODES OF HEAT TRANSFER FROM OUR BODIES Conduction Direct contact - Ex: Hand on a hot plate, feet on a cool floor Evaporation Energy transfers with the vapor associated from perspiration and breathing - Ex: Moisture lost through sweating in warm conditions Convection A fluid transfers the energy (air is a fluid) - Ex: Air being heated by a warm floor becomes buoyant; warm air gently rises while cold air falls Radiation Warm objects radiate heat waves to cooler objects in line of sight - Ex: Sun heating the earth or people warmed near a bonfire; no air is involved 21-Sep-15 - Page 8

PRINCIPLES OF RADIANT COOLING BASIC PHYSICAL PHENOMENA HUMAN COMFORT - Heat emission from the human body occurs through four modes of transfer: - Conduction (~5%) - Evaporation (~20%) - Convection (~30%) - Radiation (~45%) - Our bodies radiate heat to any surface in line of sight which is cooler than our bodies surface temperature of 85 to 90 F (29 to 32 C) - Reducing surrounding surface temperatures draws more heat from our bodies via radiation - Humans feel most comfortable when they can regulate at least 45% of their heat emission through radiation Image courtesy of RPA 21-Sep-15 - Page 9

PRINCIPLES OF RADIANT COOLING OVERVIEW OF RADIANT COOLING SYSTEMS HEAT TRANSFER In a radiant heating system, warm fluid circulates through PEX pipes which are integrated in the floor structure - Heat radiates up from the warmed floor, providing a comfortable environment by warming people and objects - Warm air also rises due to natural convection A radiant cooling system works with the reverse energy transfer process, providing a comfortable environment by absorbing heat from the space - Heat transferred through the floor is removed from the space via the circulating fluid - In cooling mode, the same network of pipes is used as in the heating mode - In some applications pipes can be embedded into the ceiling or even the wall WARMED CONCRETE SLAB COOLED CONCRETE SLAB COOLED CONCRETE SLAB Floor Covering PEX Pipe Floor Covering PEX Pipe PEX Pipe Ceiling Exposure 21-Sep-15 - Page 10

PRINCIPLES OF RADIANT COOLING OVERVIEW OF RADIANT COOLING SYSTEMS INSTALLATION TYPES Thermally Activated Building System (TABS) - a.k.a. TAS, BATISO, BKT - Without insulation underneath to condition the space above and below - Heated/cooled floor and ceiling - Bi-directional Radiant Floor Cooling and Floor Heating (FC/FH) - With insulation underneath to condition the space above - Heated/cooled floor - Uni-directional 21-Sep-15 - Page 11

PRINCIPLES OF RADIANT COOLING THERMALLY ACTIVATED BUILDING SYSTEM EXAMPLE WITH EXPOSED DUCTWORK AND CEILINGS WOODBRIDGE, ONTARIO 21-Sep-15 - Page 12

PRINCIPLES OF RADIANT COOLING TEMPERATURE SET POINTS From years of adjusting thermostats, we have been conditioned to believe that air temperature alone translates to comfort, but this is not necessarily true. We have to consider: 1. Air temperature Space s air temperature, monitored by thermostat as set point temperature 2. Mean radiant temperature (MRT) Average temperature of surrounding surfaces 3. Operative room temperature Weighted average of mean radiant temperature and the conditioned space s air temperature The operative temperature is what we perceive on our skin in a room and what is most important to consider when specifying a radiant system. Higher air temperature set points during the cooling season and lower set points during the heating season are possible with radiant systems. 21-Sep-15 - Page 13

PRINCIPLES OF RADIANT COOLING TEMPERATURE SET POINTS THE EFFECTS OF MEAN RADIANT TEMPERATURE ON COMFORT Hot Pink area is the approximate comfort zone Cold Mean Radiant Temperature ( F) MRT comfort graph originally published in Architectural Forum, January 1939 21-Sep-15 - Page 14

PRINCIPLES OF RADIANT COOLING TEMPERATURE SET POINTS Spaces with 100% forced-air systems have higher mean radiant temperatures due to solar gains and office equipment - Occupant turns down the air set point, trying to counter radiant loads using cooler air - This requires more air movement, inefficiently countering MRT With an air-based system in combination with a radiant cooling system, surface temperatures are lower - This increases the heat emitted from the occupant to surrounding surfaces via radiation - Occupant feels comfortable within the space, which removes the need for a lower air temperature and/or increased air flow - Most efficiently counters heat loads 21-Sep-15 - Page 15

PRINCIPLES OF RADIANT COOLING RADIANT COOLING CAPACITIES THEORY Specific heating/cooling capacity in W/m² or Btu/(h ft 2 ) Heat transfer coefficient Average surface temperature Air temperature q& = HTC ( ) T T SURFACE AIR Cooling Heating Ceiling ~1.9 Btu/(h ft² F) Floor ~1.2 Btu/(h ft² F) Ceiling ~1.1 Btu/(h ft² F) Floor ~1.9 Btu/(h ft² F) - ~ 60% more output from ceiling cooling system vs. floor cooling system - Reverse for heating mode Heat transfer coefficient (HTC) values can be approximated based on values from DIN EN 1264 and 15377 21-Sep-15 - Page 16

FACTORS AFFECTING OUTPUT CAPACITIES RADIANT COOLING CAPACITIES PERFORMANCE OF RADIANT FLOORS AND CEILINGS For comfort, ASHRAE Standard 55 limits floor temperature range to: - Greater than 66 F (19 C) in cooling mode - Less than 84 F (29 C) in heating mode Typical capacities based on setpoints adjusted for radiant systems: T SURFACE OUTPUT Floor Heating 78-84 F 19-31 Btu/(h ft 2 ) Cooling 66-70 F 8-12 Btu/(h ft 2 ) Ceiling Heating 78-84 F 11-17 Btu/(h ft 2 ) Cooling 66-70 F 15-24 Btu/(h ft 2 ) Ceilings are not limited by the ASHRAE 55 floor limit; ceiling values are used only to show capacity comparison Obtaining a designed surface temperature from a radiant floor system depends on factors such as average fluid temperature, pipe spacing, pipe placement, floor covering, room set point temperature 21-Sep-15 - Page 17

PRINCIPLES OF RADIANT COOLING RADIANT COOLING CAPACITIES PERFORMANCE OF RADIANT FLOORS - Obtaining a designed surface temperature from a radiant floor system depends on factors such as insulation, pipe spacing, floor construction, floor covering, room set point temperature - Floor surface temperatures less than 66 F (19 C) should be avoided for comfort reasons, according to ASHRAE Standard 55 - Under optimal design conditions, floor cooling capacities of up to 16 Btu/(hr ft²) can be achieved*, with more typical capacities in the 8-12 Btu/(h ft²) range * Olesen, Bjarne. Radiant Floor Cooling Systems, ASHRAE Journal, September 2008 Compared with the same floor system in radiant heating mode: - Floor surface temperatures over 84 F (29 C) should be avoided for comfort reasons - Capacities of up to 32 Btu/(hr ft²) can be achieved under optimal design conditions 21-Sep-15 - Page 18

2. ADDRESSING CONCERN OF CONDENSATION DESIGN CONSIDERATIONS HUMIDITY AND CONDENSATION Understanding the basic principles of radiant systems starts to reveal where their many benefits can be found. Many are convinced that radiant heating systems contribute to sustainable building, but still have reservations about radiant cooling. Radiant cooling needs a slightly more sophisticated design approach compared to radiant heating due to solar gains, occupant loads and resulting moisture management issues, which for most climates of North America pose concerns for specifiers. When a surface temperature is lower than the dew point, condensation can form 21-Sep-15 - Page 19

ADDRESSING CONCERN OF CONDENSATION DESIGN CONSIDERATIONS HUMIDITY AND CONDENSATION Cooling projects located outside arid climates demonstrate that results are driven by successful design, not climate - Controls are available to avoid uncomfortable and dangerous condensation See DOE sponsored research: Radiant Cooling in US Office Buildings: Towards Eliminating the Perception of Climate- Imposed Barriers, C.Stetiu (1998): Lawrence Berkeley National Laboratory Sampling of radiant cooling projects in NA Also noteworthy, usage of radiant cooling in very cold regions - Where specifiers have chosen radiant heating, they can easily take advantage of the cooling potential in the existing PEX network - Addition of radiant cooling minimally increases the initial cost and has many advantages during operation 21-Sep-15 - Page 20

ADDRESSING CONCERN OF CONDENSATION DESIGN CONSIDERATIONS HYBRID SYSTEMS Successful radiant cooling projects center around understanding the correct balance of an air handling unit (AHU) working in conjunction with a radiant system. These are referred to as hybrid HVAC systems. Note: AHU is used to indicate any forced-air system used to condition a space (e.g., fan coil, packaged rooftop unit, DOAS). The radiant system and the AHU work together as a hybrid HVAC system, optimizing system design and performance by decoupling the following portions of the system: 1. Hydronic and air-based 2. MRT and air temperature 3. Sensible (dry) and latent (humid) cooling 21-Sep-15 - Page 21

ADDRESSING CONCERN OF CONDENSATION DESIGN CONSIDERATIONS HYBRID SYSTEMS Although hydronic conditioning systems have many benefits, they usually can not work alone in commercial applications Hybrid HVAC systems must have an air-based component for several reasons: 1. AHU is required to meet the building s fresh air requirements, staying consistent with increased building environment standards (e.g., ASHRAE 62.1, LEED) 2. Downsized forced-air components must exist to counter humidity from outside air and from occupants within a building (latent cooling) 21-Sep-15 - Page 22

ADDRESSING CONCERN OF CONDENSATION DESIGN CONSIDERATIONS HYBRID SYSTEMS The key to preventing condensation lies in a three specific areas: 1. Infiltration - First and foremost, use a tight building envelope to reduce loads associated with nonmechanical infiltration 2. Surface Temperature - Control surface temperatures by designing cooled surfaces to operate at specific supply temperatures to prevent the surface from reaching dew point, which might lead to surface condensation 3. Relative Humidity - Control the level of humidity in a building with the AHU to keep the dew point lower than the cooling slab s operating temperatures - Spaces are typically designed for about 50% maximum relative humidity during peak cooling periods 21-Sep-15 - Page 23

ADDRESSING CONCERN OF CONDENSATION DESIGN CONSIDERATIONS BUILDING CONTROL STRATEGY - Outdoor temperature sensor on the northern side of the building, not exposed to direct sunlight - Humidity and temperature sensor(s) in each zone to monitor dew points and set points - Floor temperature sensor in the upper level of the thermal mass - Supply and return fluid temperature sensors in the piping network 21-Sep-15 - Page 24

3. HYBRID HVAC SYSTEMS FOR IMPROVED BUILDING ENVIRONMENT THERMAL COMFORT Radiant cooling and heating systems are integral in creating hybrid systems that reach higher levels of thermal comfort than their 100% forced-air system counterparts. - This finding is supported in detail through a research study - Concrete Core Temperature Control Systems, 2008 by the University of Nuremberg, Germany - Study evaluates seven common and uncommon heating and cooling systems under North American conditions for a fully simulated commercial building 21-Sep-15 - Page 25

HYBRID HVAC SYSTEMS FOR IMPROVED BUILDING ENVIRONMENT CONTENT AND PURPOSE OF STUDY The study compared several types of commercial heating/cooling systems on the following attributes: - Thermal comfort (learning objective 3) - Initial investment cost (learning objective 4) - Operating costs: energy demand + maintenance costs (learning objective 5) The study considers the following conditions: - North American and local building codes and standards (e.g., ASHRAE Title 24 California Standards and Energy Code) - North American construction techniques - North American energy and investment costs including material and labor - North American climate 21-Sep-15 - Page 26

HYBRID HVAC SYSTEMS FOR IMPROVED BUILDING ENVIRONMENT BASIS OF STUDY 1,375 - Project type: Four-story poured commercial construction - Location: Sacramento, California - Outside design temperatures: 100 F / 31.5 F (0.4% / 99.6%) - Effective area: Approximately 14,500 ft² total area on four floors - Heaviness of construction: 160 lb/ft², cast-in-place construction Example of construction type simulated 21-Sep-15 - Page 27

HYBRID HVAC SYSTEMS FOR IMPROVED BUILDING ENVIRONMENT BASIS OF STUDY THE REFERENCE OFFICE ROOM The study focused on a typical occupied office Supply Air Return Air Office dimensions: Floor Area: Volume: 17.7 ft x 18.5 ft x 9.8 ft 328 ft² 3,210 ft³ PC 100 W Printer 50 W Interior loads: - Heat loss per person: 132 W - Heating load from work wquipment: 11 W/m² - Heating load from lighting: 12 W/m² PC 100 W Lighting 182.5 W TFT 42.5 W TFT 42.5 W Occupancy: Heat emission per person: 2 persons 450 Btu/h (seated, office work) Person 132 W Person 132 W Lighting 182.5 W Electrical equipment: Lighting: 3.5 Btu/(h ft²) 3.8 Btu/(h ft²) Normal office hours: Operating hours of heating and cooling systems: 7:30 am to 6:00 pm on weekdays 6:00 am to 6:00 pm on weekdays 21-Sep-15 - Page 28

HYBRID HVAC SYSTEMS FOR IMPROVED BUILDING ENVIRONMENT COMPARED SYSTEMS - OVERVIEW 100% Forced Air System (AHU) Floor Radiant System (FCH) + downsized AHU Ceiling Radiant System (CHC) + downsized AHU Thermally Activated Slab (TAS) + downsized AHU The three hybrid HVAC systems shown above include a downsized air handling unit (AHU) to decouple and optimize the space s cooling requirements. The University of Nuremberg s study compares seven systems, three of which are not very common in North America so they are excluded from this presentation. 21-Sep-15 - Page 29

HYBRID HVAC SYSTEMS FOR IMPROVED BUILDING ENVIRONMENT COMPARED SYSTEMS - OVERVIEW 100% Forced Air System (AHU) Floor Radiant System (FCH) + downsized AHU Ceiling Radiant System (CHC) + downsized AHU Thermally Activated Slab (TAS) + downsized AHU - VAV s positioned in corridor plenum feed the space with conditioned air - Fresh air supply requirements are met by the air handling unit (AHU) - Supply air is conditioned to ensure required temperature and humidity Zone Loads: 2 persons Persons at a 450 450 Btu/h BTU/h Electrical Equipment: Electrical Equipment: 3.5 BTU/(hft²) 3.5 Btu/h ft² Lighting: 3.8 BTU/(hft²) Lighting: 3.8 Btu/h ft² External Wall: Extenal Wall: U=0.16 Btu/(h ft²r) U=0.16 BTU/(hft²R) Window: U=0.46 BTU/(hft²R) Btu/(h ft²r) Frame: U=0.55 BTU/(hft²R) Btu/(h ft²r) Percentage Frame: Frame:10 U=10% % Glazing: U=0.45 BTU/(hft²R) Glazing: U=0.45 Btu/(h ft²r) g=0.26 Blinds: g=0.26 z=0.75 Blinds: z=0.75 21-Sep-15 - Page 30

HYBRID HVAC SYSTEMS FOR IMPROVED BUILDING ENVIRONMENT COMPARED SYSTEMS - OVERVIEW 100% Forced Air System (AHU) Floor Radiant System (FCH) + downsized AHU Ceiling Radiant System (CHC) + downsized AHU Thermally Activated Slab (TAS) + downsized AHU Zone Loads: Zone Loads: 2 persons Persons at 450 a 450 Btu/hBTU/h Electrical Equipment: 3.5 Btu/h ft² BTU/(hft²) Lighting: 3.8 BTU/(hft²) Lighting: 3.8 Btu/h ft² Extenal External Wall: U=0.16 U=0.16 Btu/(h ft²r) BTU/(hft²R) Window: U=0.46 U=0.46 Btu/(h ft²r) BTU/(hft²R) Frame: U=0.55 U=0.55 Btu/(h ft²r) BTU/(hft²R) Percentage Frame:10 % Percentage Frame: U=10% Glazing: U=0.45 BTU/(hft²R) Glazing: U=0.45 Btu/(h ft²r) g=0.26 Blinds: g=0.26 z=0.75 Blinds: z=0.75 21-Sep-15 - Page 31

HYBRID HVAC SYSTEMS FOR IMPROVED BUILDING ENVIRONMENT COMPARED SYSTEMS - OVERVIEW 100% Forced Air System (AHU) Floor Radiant System (FCH) + downsized AHU Ceiling Radiant System (CHC) + downsized AHU Thermally Activated Slab (TAS) + downsized AHU Zone Loads: Zone Loads: 2 persons Persons at 450 a 450 Btu/h BTU/h Electrical Equipment: 3.5 Btu/h ft² BTU/(hft²) Lighting: 3.8 BTU/(hft²) Lighting: 3.8 Btu/h ft² External Extenal Wall: U=0.16 U=0.16 Btu/(h ft²r) BTU/(hft²R) Window: U=0.46 U=0.46 Btu/(h ft²r) BTU/(hft²R) Frame: U=0.55 U=0.55 Btu/(h ft²r) BTU/(hft²R) Percentage Percentage Frame: Frame:10 U=10% % Glazing: U=0.45 BTU/(hft²R) Glazing: U=0.45 Btu/(h ft²r) g=0.26 g=0.26 Blinds: z=0.75 Blinds: z=0.75 21-Sep-15 - Page 32

HYBRID HVAC SYSTEMS FOR IMPROVED BUILDING ENVIRONMENT COMPARED SYSTEMS - OVERVIEW 100% Forced Air System (AHU) Floor Radiant System (FCH) + downsized AHU Ceiling Radiant System (CHC) + downsized AHU Thermally Activated Slab (TAS) + downsized AHU Zone Loads: 2 Persons a 450 BTU/h Electrical Equipment: 3.5 BTU/(hft²) Lighting: 3.8 BTU/(hft²) Extenal Wall: U=0.16 BTU/(hft²R) Window: U=0.46 BTU/(hft²R) Frame: U=0.55 BTU/(hft²R) Percentage Frame: 10 % Glazing: U=0.45 BTU/(hft²R) g=0.26 Blinds: z=0.75 21-Sep-15 - Page 33

HYBRID HVAC SYSTEMS FOR IMPROVED BUILDING ENVIRONMENT THERMAL COMFORT Thermal comfort has a special standing concerning productivity in a work environment. ASHRAE Standard 55 Thermal Environmental Conditions for Human Occupancy - Thermal comfort is that condition of mind which expresses satisfaction with the thermal environment. The following factors must be considered when thermal comfort is defined: - Clothing insulation - Metabolic rate - Air temperature - Air speed / draft - Humidity - Radiant temperature Creates a broad range of perceived comfort 21-Sep-15 - Page 34

HYBRID HVAC SYSTEMS FOR IMPROVED BUILDING ENVIRONMENT THERMAL COMFORT ASHRAE Standard 55 Thermal Environmental Conditions for Human Occupancy Boundaries for thermal comfort according to Standard 55 - Operative temperature: - Summer period @ 50% RH: 75-80 F - Winter period @ 30% RH: 70-77 F - Range of the floor temperature: 66-84 F - Radiant temperature asymmetry: - Warm ceiling: < 9 F - Cool ceiling: < 25 F - Warm wall: < 41 F - Cool wall: < 18 F - This is the so called comfort area, where the percentage of people who are comfortable is optimized. Less than 10% dissatisfied. 21-Sep-15 - Page 35

HYBRID HVAC SYSTEMS FOR IMPROVED BUILDING ENVIRONMENT BASIS OF STUDY DESIGN TEMPERATURES The study used: - Cooling period: 75 F - Heating period: 68 F - Minimum floor temperature: 66 F - Maximum floor temperature: 84 F 21-Sep-15 - Page 36

HYBRID HVAC SYSTEMS FOR IMPROVED BUILDING ENVIRONMENT RESULTS OF STUDY OPERATIVE ROOM TEMPERATURES DURING SIMULATED SUMMER WEEK Indoor operative temperature felt by office occupants during simulated week in summer 100.0 95.0 90.0 85.0 80.0 75.0 70.0 65.0 60.0 55.0 50.0 6:00 AM 12:00 PM 6:00 PM 6:00 AM 12:00 PM 6:00 PM 6:00 AM 12:00 PM 6:00 PM 6:00 AM 12:00 PM 6:00 PM 6:00 AM 12:00 PM 6:00 PM Operative Temperature ( F) MONDAY TUESDAY WEDNESDAY THURSDAY Monday Tuesday Wednesday Thursday FRIDAY Friday 100% FORCED AIR FLOOR SYSTEM + AHU CEILING SYSTEM + AHU TAS SYSTEM + AHU 21-Sep-15 - Page 38

HYBRID HVAC SYSTEMS FOR IMPROVED BUILDING ENVIRONMENT HEATING AND COOLING LOAD CALCULATION Heating/cooling systems are specified and designed for worst case scenario with respect to outdoor weather conditions. - What if the indoor environment is given worst case scenario conditions? Example: The interior loads were doubled on highest cooling load period - Assumed room was used for a meeting Wednesday afternoon from 12:00 pm to 6:00 pm - Assumed twice the occupancy and corresponding equipment loads (e.g., computers, projectors) 21-Sep-15 - Page 39

HYBRID HVAC SYSTEMS FOR IMPROVED BUILDING ENVIRONMENT RESULTS OF STUDY OPERATIVE ROOM TEMPERATURES DURING SIMULATED SUMMER WEEK Hybrid systems handled the doubled interior loads during Wednesday afternoon s meeting better than the 100% forced-air system 100.0 95.0 90.0 85.0 80.0 75.0 70.0 65.0 60.0 55.0 50.0 6:00 AM 12:00 PM 6:00 PM 6:00 AM 12:00 PM 6:00 PM 6:00 AM 12:00 PM 6:00 PM 6:00 AM 12:00 PM 6:00 PM 6:00 AM 12:00 PM 6:00 PM Operative Temperature ( F) MONDAY TUESDAY WEDNESDAY THURSDAY Monday Tuesday Wednesday Thursday FRIDAY Friday 100% FORCED AIR FLOOR SYSTEM + AHU CEILING SYSTEM + AHU TAS SYSTEM + AHU 21-Sep-15 - Page 40

HYBRID HVAC SYSTEMS FOR IMPROVED BUILDING ENVIRONMENT RESULTS OF STUDY THERMAL COMFORT COMPARISON FOR VARIOUS METRICS 100 Air Quality 90 Compliance to Humidity Setpoints Avoidance of Elevated Air Speed Floor Temperature Radiant Temperature Asymmetry Vertical Temperature Gradients Scaled Thermal Comfort 80 70 60 50 40 30 20 10 Compliance to Temperature Setpoints 0 AHU FCH + AHU CHC + AHU TAS + AHU 21-Sep-15 - Page 41

4. REDUCED INVESTMENT COSTS OVERVIEW A radiant cooling system has significant benefits when used in a hybrid HVAC system to increase economic efficiency for a building. The study compared the following cost components: - Initial investment costs - Operating costs including energy demand and maintenance (learning objective 5) - Net present value (NPV) (learning objective 6) 21-Sep-15 - Page 42

REDUCED INVESTMENT COSTS RESULTS OF STUDY COOLING LOAD CALCULATION FOR SIZING EQUIPMENT - Calculated using comprehensive DOE software Energy Plus - Specific cooling load of 23.6 Btu/(h ft²) for the office space - Air change rate of 7.5 (incl. 1.5 external air change) was necessary for handling 100% of the calculated cooling load - Radiant cooling systems cover part of the cooling load and allow for a significant reduction on the air handling side Type of Heating/Cooling System 100% Forced Air (AHU) Radiant Floor + AHU Radiant Ceiling + AHU Required Air Change Rate Per Hour Equivalent cfm for 327 ft 2 Office Equivalent cfm for Office Building 7.5 ACH 400 cfm 16,850 cfm 5.0 ACH 268 cfm 11,230 cfm 4.0 ACH 214 cfm 8,990 cfm TAS + AHU 4.0 ACH 214 cfm 8,990 cfm 21-Sep-15 - Page 43

REDUCED INVESTMENT COSTS RESULTS OF THE STUDY INITIAL MATERIAL INVESTMENT COSTS - Specific unit pricing for the geographic region of Sacramento, CA was considered - A survey of engineers and contractors yielded the following unit pricing Component Unit Price Unit Machine Life Service and Maintenance (%) Heat generation (gas-fired boiler incl. main manifold; pipes incl. insulation, pumps, control system, exhaust system, valves) 0.15 $/(Btu/h) 20 3.5 Cooling production (piston water set, recooling plant, pipes incl. insulation, control system, pumps, valves) 0.38 $/(Btu/h) 15 3 AHU as mixed air system incl. AC device with four thermodynamic air treatment functions, duct system with insulation, outlets, built-in parts such as fire protection valves etc., control system 0.8 $/(ft³/h) 15 3.5 Under floor heating / under floor cooling incl. connection 5 $/ft² 30 1 Sub-distribution FH/FC incl. control system, pipes incl. insulation, pumps, sub-distribution manifold, valves 4.5 $/ft² 20 1.5 Concrete core temperature control incl. connection 3.5 $/ft² 30 1 Sub-distribution concrete core temperature control incl. control system, pipes incl. insulation, pumps, sub-distribution manifolds, valves 5.5 $/ft² 20 1.5 Chilled ceiling incl. connection 25 $/ft² 20 1.5 Sub-distribution chilled ceiling incl. control system, pipes incl. insulation, pumps, sub-distribution manifolds, valves 5 $/ft² 20 1.5 21-Sep-15 - Page 44

REDUCED INVESTMENT COSTS RESULTS OF STUDY INITIAL INVESTMENT COST COMPARISON 100 Radiant Sub-distribution PEX pipes, manifolds, valves, pumps, sensors, control units, etc. Radiant System Ceiling panels, connections, insulation, installation, etc. AHU All air equipment, ducting, controls, humidification Cooling Production Chilled fluid generation, control unit, connections Scaled Initial Investment Cost 90 80 70 60 50 40 30 20 10-29% -21% -31% Heat Production Boiler, pumps, control unit, valves, etc, 0 AHU FCH + AHU CHC + AHU TAS + AHU 21-Sep-15 - Page 45

5. REDUCED OPERATING COSTS OVERVIEW Hybrid HVAC systems incorporating a radiant system can aid in reducing energy consumption - The study compared the following categories of energy demand: - Heat generation - Cooling production - Auxiliary air handling components (i.e., fans for air distribution) - Auxiliary radiant components (i.e., circulator pumps for fluid distribution) 21-Sep-15 - Page 46

REDUCED OPERATING COSTS RESULTS OF STUDY FINAL ENERGY DEMAND COMPARISON Auxiliary Radiant incl. Distribution 60,000 50,000 Auxiliary AHU incl. Distribution Cooling Production for Radiant Cooling Production for AHU Annual Energy Demand Btu/ft 2 40,000 30,000 20,000-30% -38% -40% Heat Production for Radiant 10,000 Heat Production for AHU 0 100% AHU FHC + AHU CHC + AHU TAS + AHU Final energy demand correlates directly with building owner s operating costs 21-Sep-15 - Page 47

REDUCED OPERATING COSTS RESULTS OF STUDY MAINTENANCE COST COMPARISON Radiant Sub-distribution Pumps, miscellaneous Radiant System Miscellaneous servicing AHU Filter replacement, blower fan motors, miscellaneous servicing Cooling Production Pumps, chiller maintenance Annual Maintenance Costs ($/sq ft) 3.00 2.50 2.00 1.50 1.00 0.50-34% -35% -41% Heat Production Pumps, boiler maintenance 0.00 100% AHU FCH + AHU CHC + AHU TAS + AHU 21-Sep-15 - Page 49

6. NET PRESENT VALUE CALCULATION OVERVIEW The net present value (NPV) is defined as the total present value (PV) of a time series of cash flows. - Present value is the value on a given date of a future payment or series of future payments, discounted to reflect the time value of money and other factors such as investment risk The comparison was made with the following assumptions: - The rate of interest is calculated to be 3.8% - The price increases for natural gas and for electricity are set to 4% annually - The term of investment is 15 years, the estimated life of major components of the AHU system 21-Sep-15 - Page 50

NET PRESENT VALUE CALCULATION RESULTS OF STUDY NET PRESENT VALUE WITH CONVENTIONAL ENERGY SUPPLY 150 100% AHU FCH +AHU -30% CHC +AHU -27% NPV ($/sq ft) 140 130 120 110 100 90 80 See legend on left for each system s savings at year 15 TAS +AHU -35% 70 60 50 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Years - High-cost components of an AHU are estimated to need major servicing after year 15 - This indicates that a system running for longer periods of time (e.g., 30 years) would illustrate huge advantages for the hybrid radiant systems if the NPV were extended to look at a building s life time 21-Sep-15 - Page 51

7. ADVANTAGES TO SPECIFIERS OVERVIEW The study compared the following parameters for the four systems: 1. Thermal comfort 2. Initial costs 3. Energy demand 4. Maintenance costs The comparison lead to an overall score based on the following weighted values: Category Weighted Average Thermal comfort 30% Initial costs 20% Energy demand 40% Maintenance costs 10% Total: 100% 21-Sep-15 - Page 52

ADVANTAGES TO SPECIFIERS RESULTS OF STUDY OVERALL EVALUATION Systems scored on four main parameters 100 Energy Demand 80 Maintenance Costs Intial Costs Evaluation % 60 40 Thermal Comfort 20 0 100% Forced Air FCH + AHU CHC + AHU TAS + AHU 21-Sep-15 - Page 53

ADVANTAGES TO SPECIFIERS FROM EXPERIENCE The study and also the experience from hundreds of radiant cooling projects realized throughout the world prove the advantages of these systems. Increased Thermal Comfort - Radiant cooling optimizes the surface temperatures of the occupants surroundings, providing a comfortable environment - The human body feels most comfortable when it can regulate at least 45% of its heat emission via radiation achieved through a radiant system - Comfortable cooling is provided with reduced ventilation air and little to no flow noises 21-Sep-15 - Page 54

ADVANTAGES TO SPECIFIERS FROM EXPERIENCE The study and also the experience from hundreds of radiant cooling projects realized throughout the world prove the advantages of these systems. Reduced Investment Costs - Radiant cooling can lead to a significant investment reduction in forced-air system components and ductwork - Radiant cooling systems have lower operating costs due to the superior heat transfer properties of water compared to air - A 1 in. water pipe carries same thermal energy as 10 in. x 18 in. rectangular duct - A 60 watt circulator can deliver the same energy as a 1,500 watt air distribution fan - Reduction in required maintenance of the radiant system compared to the 100% air system helps to augment operating incentives 21-Sep-15 - Page 55

ADVANTAGES TO SPECIFIERS FROM EXPERIENCE The study and also the experience from hundreds of radiant cooling projects realized throughout the world prove the advantages of these systems. Reduced Operating Costs - Radiant cooling allows a higher set-point temperature while still maintaining the same level of cooling comfort compared to a traditional AHU - Operating with moderate supply water temperatures allows the integration of renewable systems such as geothermal heat pumps at maximum efficiencies - Peak load can be reduced by thermal storage of the slab, making it possible to downsize cooling devices - Flexible zoning is possible; areas can be separately controlled and balanced - Lower energy usage may aid in LEED certification 21-Sep-15 - Page 56

ADVANTAGES TO SPECIFIERS FROM EXPERIENCE The study and also the experience from hundreds of radiant cooling projects realized throughout the world prove the advantages of these systems. Architectural Flexibility - Reduced mechanical equipment foot print yields more usable square footage - Intrusive ductwork may be reduced - Conditioning brought to space without the need for large ceiling plenum, leading to increased ceiling height, reduced building height or potential for additional levels 21-Sep-15 - Page 57

ADVANTAGES TO SPECIFIERS SUMMARY Architects, engineers and other specifiers note the following advice from experience: - Radiant cooling is suitable for most commercial, industrial and institutional applications with careful engineering design of total HVAC solution - Radiant cooling is not practical for most residential applications mainly due humidity control issues Scenario where radiant cooling is most advantageous; - Atriums with large glass exposures; counter solar gains directly with cooled floor - Areas where reduced noise from ventilation is desired - Buildings already being designed with radiant heating systems - Buildings where peak electrical rates are favorable toward thermal storage Coordination between all people involved in the building design and construction is mandatory for the success of the integration of radiant systems! - Taking an integrated design process (IDP) approach has proven successful and is advocated by ASHRAE and AIA 21-Sep-15 - Page 58

RADIANT COOLING SYSTEMS RADIANT FLOOR EXAMPLE APPLIED IN SHOWROOM LIBERAL, KANSAS - Project received award from the Radiant Professionals Alliance (RPA) - Radiant system was combined with air system to meet customer s need for: - Optimum thermal comfort - Reduced energy consumption 21-Sep-15 - Page 59

RADIANT COOLING SYSTEMS THERMALLY ACTIVATED SLAB APPLIED IN A DORMITORY TORONTO, ONTARIO 21-Sep-15 - Page 60

RADIANT COOLING SYSTEMS RADIANT CEILING EXAMPLE APPLIED IN A UNIVERSITY LIBRARY CHICAGO, ILLINOIS 21-Sep-15 - Page 61

CONCLUSION REVIEW LEARNING OBJECTIVES 1. Explain the basic principles of radiant cooling systems and the factors that affect the output capacities 2. Define the meaning of a hybrid HVAC system and how it can be optimized to address the concern of condensation 3. Discuss how a hybrid HVAC system using radiant cooling leads to improved building environment 4. Describe how a hybrid HVAC system using radiant cooling can reduce initial investment costs 5. Explain how a hybrid HVAC system using radiant cooling can reduce operating costs through reduced energy consumption and maintenance 6. Demonstrate how a hybrid HVAC system using radiant cooling can reduce the net present value of investment 7. Summarize the advantages of having a radiant system from a specifier s perspective 21-Sep-15 - Page 62

THANK YOU FOR YOUR TIME QUESTIONS? 21-Sep-15 - Page 63